Table of Contents
ToggleProduct Overview
The KITOZER SIS-12 is a 10kV solid-insulated metal-enclosed switchgear in which all live parts are encapsulated in epoxy resin rather than SF6 gas. This design eliminates the environmental concern of SF6 leakage while retaining the compact footprint of gas-insulated switchgear. The vacuum circuit breaker, busbar, and disconnector are cast as a single solid-insulated pole unit, leaving only the operating mechanism and cable termination accessible in air. SIS-12 is aimed at environmentally sensitive projects, indoor substations, and installations where SF6 handling and annual gas monitoring are undesirable.
The alumina-filled epoxy housing provides excellent dielectric strength and partial discharge suppression, with a measured partial discharge below 5pC at 1.1 times rated voltage. Because there is no gas tank, there is no gas pressure gauge, no density monitor, and no future gas recovery obligation. The front door houses the protection relay, control switches, and status indicators, while the rear cable compartment accommodates up to three single-core XLPE cables per phase. The modular bays allow incoming, outgoing, metering, and bus-tie panels to be arranged in any order to fit the switchroom.
Technical Specifications
Rated voltage 12kV, rated current 630A to 1250A, frequency 50Hz, rated short-time withstand current 25kA for 4 seconds, rated peak withstand 63kA, lightning impulse withstand 75kV. Epoxy encapsulation material is alumina-filled epoxy with partial discharge below 5pC at 1.1Um. Vacuum interrupter rated breaking current 25kA.
Earthing switch making capacity 25kA peak. IP65 encapsulated pole, IP4X cabinet. Panel width 325mm per feeder bay, depth 850mm, height 1600mm. Operating mechanism is spring type, manual or motorized. No SF6 gas is used anywhere in the unit. Auxiliary supply 110V DC or 220V AC, shunt trip and undervoltage release included. Optional Modbus TCP communication allows remote monitoring of breaker position, fault events, and cable temperature.
Typical Applications
SIS-12 is selected for 10kV distribution in green building projects, indoor shopping center substations, hospital and university switchrooms, and projects seeking SF6-free medium voltage equipment. It is also suitable for warm, humid environments where condensation tracking on air-insulated busbars is a concern, and for roof-top or corridor-mounted secondary substations where ventilation is limited.
The modular bays allow incoming, outgoing, metering, and bus-tie panels to be assembled in any order to fit the switchroom layout. In hospitals, the SF6-free design aligns with green building certifications such as LEED and BREEAM. In coastal industrial plants, the sealed epoxy housing prevents salt fog from degrading the live parts. In data center switchrooms, the narrow 325mm bay width allows more panels to fit in a given floor area.
Key Advantages
Solid encapsulation removes the gas density gauge, gas refill procedures, and future end-of-life gas recovery obligations associated with SF6 switchgear. The epoxy pole is immune to dust, salt fog, and condensation, and its partial discharge level remains below 5pC throughout the service life.
At 325mm per bay, the panel is roughly half the width of conventional air-insulated switchgear, freeing valuable floor area. The vacuum interrupter is embedded inside the epoxy, preventing accidental finger contact during maintenance. KITOZER performs a 100 percent partial discharge test on every encapsulated pole before it leaves the factory. Exchangeable pole units allow a failed pole to be swapped in the field without replacing the whole panel.
Installation and Maintenance
Install the SIS-12 bays side by side on a flat concrete plinth and bolt the flanges together. Because there is no gas compartment, no gas pressure check is needed during routine visits. Inspect the cable termination annually, tighten the control wiring screws every two years, and test the spring mechanism manually at least once a year.
The vacuum interrupter contact wear can be checked with a travel indicator on the operating shaft; when the travel reaches the red zone, replace the pole unit. KITOZER supplies exchangeable pole units so that a failed pole can be swapped in the field without replacing the whole panel. Keep a spare pole unit on site for critical feeders. Clean the epoxy surface with a dry cloth once a year; do not use solvents that could damage the housing.
Price
From $4,900/bay. Contact +86 13922289957 for SF6-free switchgear quotation.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com