Table of Contents
ToggleKITOZER KTR-EM-WL Water Leak Sensor (Locating Rope, RS485, Data Center)
Brand: KITOZER Series: KTR-EM-WL Category: Environment Monitoring / Water Leak Sensor
Locating rope5m ropeRS485+relayData center leakKTR-EM-WL
1. Overview
The KITOZER KTR-EM-WL is a locating water leak sensor consisting of a main unit and a sensing rope. It is used in data centers, electrical rooms, pantries, pipe corridors and underground garages to detect water leaks in real time and report the precise distance from the leak point to the main unit. Water leakage is one of the most dangerous incidents in a data center: a blocked precision-AC drain line, a seeping fire pipe, or basement infiltration can flow into racks, causing short circuits, equipment burnouts and data loss. Ordinary point-type (electrode) water sensors only detect water at one fixed spot and do not tell you where it comes from. KTR-EM-WL lays a sensing rope along possible pipe routes and floor joints; water anywhere on the rope is detected, and the unit reports the leak distance (e.g., “3.2 m from main unit”) so staff go straight to that spot instead of searching everywhere.
Specs: sensing rope standard 5 m (extendable to 100 m); locating accuracy +/-0.5 m; conductive liquid detection (water / antifreeze); power DC12 to 24 V; outputs RS485 Modbus-RTU (reports leak distance) plus relay dry contact (closes on leak); response time <=3 s; main ABS about 120x80x40 mm; rope diameter 6 mm (cuttable); shorting end caps; daisy-chain support; operating temp 0 to +60 C. Compared with item 864 (5-in-1 air quality), that unit measures air; this one measures water. Compared with a point-type electrode sensor (KTR-EM-WL-POINT), this is a rope-locating unit covering a line.
Typical uses: data centers (along AC drain and humidifier water lines); electrical room cable trenches; pantries / break rooms; basement pump rooms; defrost water lines in cold rooms; hospital ICUs; lab water lines; water-sensitive warehouses. A standard data center lays the rope along precision-AC drain pipes, humidifier feed lines and underfloor seams; the main unit sits at the room entrance and the EMCS pops up the leak location on alert.
2. Key Features
Precise leak location
- Locating accuracy +/-0.5 m.
- Reports distance from main unit.
- One rope covers 5 to 100 m.
- No blind searching.
RS485 + relay dual output
- RS485 Modbus reports distance.
- Dry relay contact (closes on leak).
- Integrates with EMCS.
- Can trigger water valve shutoff.
Cuttable sensing rope
- 6 mm rope, cut to site length.
- Shorting end caps.
- Daisy-chainable.
- Stain/corrosion resistant.
3-second response
- Response <=3 s.
- Conductive-liquid detection.
- DC12 to 24 V wide range.
- Wall-mount ABS main unit.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-EM-WL |
| Type | Locating water leak sensor |
| Rope length | Standard 5 m (extend to 100 m) |
| Locating accuracy | +/-0.5 m |
| Detection target | Conductive liquid (water / antifreeze) |
| Response time | <=3 s |
| Power | DC12 to 24 V |
| Outputs | RS485 Modbus-RTU + relay dry contact |
| Main unit size | ABS about 120x80x40 mm |
| Rope diameter | 6 mm (cuttable) |
| End cap | Shorting cap |
| Operating temp | 0 to +60 C |
4. Reference Prices
KTR-EM-WL locating unit (with 5 m rope): Ref. USD 49~76 / set (CNY 350~550 at 7.2)
KTR-EM-WL-CABLE sensing rope (per meter): Ref. USD 2~3.5 / m (CNY 15~25 at 7.2)
KTR-EM-WL-POINT point-type (electrode): Ref. USD 8~14 / pc (CNY 60~100 at 7.2)
KTR-EM-WL-100 extended (100 m rope): Ref. USD 208~347 / set (CNY 1500~2500 at 7.2)
Solenoid valve (DN20, auto shutoff): Ref. USD 21~42 / pc (CNY 150~300 at 7.2)
RS485-to-USB config cable: Ref. USD 3.5~5.6 / pc (CNY 25~40 at 7.2)
Reference only; 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data centers (along AC water lines).
- Electrical room cable trenches.
- Pantries / break rooms.
- Basement pump rooms.
- Cold room defrost water lines.
- Lab / water-sensitive storage.
6. Installation & Maintenance
Installation
- Mount main unit on entrance wall at 1.5 m.
- Lay rope along AC drain, humidifier feed, floor joints.
- Clip rope to floor every 0.5 m (do not leave floating).
- One end to main unit INPUT; other end shorting END cap.
- Lay rope at lowest floor points (water flows downhill).
- Do not lay directly under equipment (leak drips onto gear).
- Wire RS485 A/B/G to EMCS.
- Relay output to solenoid valve / alarm.
- Power up; test with a wet rag to verify distance.
Maintenance
- Monthly simulate a leak with a wet rag (verify rope and unit).
- Wipe rope dry (dust does not affect; oil film does).
- After forklift/foot traffic, check for broken conductors (unit reports fault).
- If chewed by rodents, cut out and splice the section.
- Annually verify locating accuracy with a known-distance test.
- Do not paint or glue over the rope (insulates, blocks detection).
- Keep unused end capped (otherwise unit reports open circuit).
7. FAQ
- Q:What does +/-0.5 m accuracy mean?
A:If the leak is 3.2 m from the unit, the sensor reports 3.2 m +/-0.5 m—i.e., actual leak is between 2.7 and 3.7 m. Staff go to the 3 m mark and search within a 1 m span. This is far better than a point sensor that only tells you “the room has a leak.” - Q:Can it detect antifreeze?
A:Yes. The rope detects conductive liquids. Water (with ions) conducts; antifreeze (glycol-water) conducts too (higher glycol concentration is less conductive, but typical 30% AC antifreeze is detectable). Pure alcohol (water-free) does not conduct and is not detected. For non-conductive oil leaks, use a dedicated oil-leak sensor. - Q:Can the rope be shortened?
A:Yes. Cut to site length; the standard 5 m rope may only need 3 m. After cutting, fit shorting end caps (included in the kit) on both ends. Power-cycle; the unit re-measures rope length and auto-calibrates distance. - Q:How to link auto water shutoff?
A:The relay dry contact closes on leak; wire a solenoid valve (on the AC feed line). The EMCS receives the leak signal and automatically closes the valve to cut the water supply, plus sends SMS alarm. Within 3 s of a leak the water is shut, minimizing damage. Choose a normally-closed solenoid (closes on power loss—safer).
8. Trend & Selection
Water sensors move from point electrodes to locating rope (covering lines, pinpointing leaks). Communications move from RS485 to wireless (LoRa/Wi-Fi, no wiring). Pure detection evolves to linked shutoff valves plus SMS alerts (automatic response). Detection extends from water to oil and acid/alkali. Data centers now standardize on rope-locating units along water lines instead of a single point sensor.
9. Delivery & Service
KITOZER sizes KTR-EM-WL by water-line routing and length, providing rope layout plans and solenoid-valve linkage advice. Delivery includes main unit, rope, end caps, clips, power adapter, manual, certificate. Warranty covers locating calibration guidance and valve commissioning.
10. Additional Notes
A common pitfall is laying the rope floating above the floor. If the rope is 1 to 2 cm off the ground, water on the floor never reaches it and leaks are missed. Clip the rope flush to the floor so flowing water naturally contacts it.
Another pitfall is missing the end shorting cap. If the rope end dangles open, the main unit reports “rope open circuit” when the real cause is just a missing cap. One end must go to INPUT; the other must have the shorting END cap to form a loop.
Selection summary: locating rope; 5 to 100 m cuttable; RS485 + relay; +/-0.5 m accuracy. The water sensor is the room’s leak alarm; the keys are floor-flush rope, laying along water pipes, and linking a solenoid valve.
Extra tip: water detection is the last line of defense. More important is regular inspection of aging AC drain pipes and humidifier feed lines to prevent leaks. The sensor alarms after a leak; it cannot stop one.
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com