KITOZER KTR-TH-RS485 Temperature & Humidity Sensor (RS485 Modbus, LCD)

KITOZER KTR-TH-RS485 Temperature & Humidity Sensor (RS485 Modbus, LCD)

Brand: KITOZER Series: KTR-TH-RS485 Category: Environmental Monitoring / T&H Sensor

RS485Modbus-RTU+/-0.3 CLCDKTR-TH-RS485

1. Overview

The KITOZER KTR-TH-RS485 is a wall-mount temperature and humidity sensor with an LCD and RS485 interface. It samples real-time T and RH in server rooms, warehouses and cold-chain workshops, and uploads them via Modbus-RTU to an environmental monitor or DCIM system. Over-temperature causes servers to throttle and AC faults; high humidity causes condensation and short circuits, low humidity causes static. KTR-TH-RS485 watches these two parameters around the clock and alarms on limits.

Key specs: temperature -40 to +80 C, accuracy +/-0.3 C at 25 C; humidity 0~100% RH, accuracy +/-2% RH at 20~80%; RS485, Modbus-RTU, baud 4800~115200 (default 9600); DC12~24 V, <=0.5 W; LCD shows T and RH together; built-in probe (optional 1 m external); ABS flame-retardant case; wall 86-box base; -20 to +60 C operating.

Typical use: a 42U room has three KTR-TH-RS485 units at the cold-aisle inlet, hot-aisle outlet, and rack mid-height, daisy-chained on one RS485 bus to the DCIM host (Modbus addresses 1~3). The host shows three curves on a web UI; set upper temp 28 C, lower 18 C, upper RH 60%, lower 40%; out-of-range triggers SMS alarms.

2. Key Features

+/-0.3 C high accuracy

  • Temp accuracy +/-0.3 C.
  • RH accuracy +/-2%.
  • Industrial Sensirion probe.
  • Suits precision rooms and cold chain.

RS485 Modbus-RTU

  • Standard Modbus-RTU.
  • 9600~115200 auto baud.
  • Daisy-chain bus, up to 32 units.
  • 1200 m range.

LCD on-screen

  • T and RH on one screen.
  • Read on-site without the host.
  • Backlight optional.
  • Address and baud settable by keys.

Wall 86-box mount

  • Standard 86-box base.
  • Four screws.
  • ABS flame-retardant.
  • DC12~24 V wide range.

3. Specifications

Item Value
Model KTR-TH-RS485
Measured Temperature + relative humidity
Temp range -40 to +80 C
Temp accuracy +/-0.3 C (25 C)
Humidity range 0~100% RH
Humidity accuracy +/-2% RH (20~80% RH)
Interface RS485 (Modbus-RTU)
Baud rate 4800~115200 (default 9600)
Power DC12~24V
Power consumption <=0.5 W
Display LCD (T&H on one screen)
Probe Built-in (optional 1 m external)
Mounting Wall 86-box base
Case ABS flame-retardant
Operating temp -20 to +60 C

4. Reference Price

KTR-TH-RS485 T&H sensor (LCD): RMB 120~180 / unit (about USD 17~25)

KTR-TH-RS485-P external probe (1 m): RMB 150~220 / unit (about USD 21~31)

KTR-TH-4G cloud version: RMB 280~380 / unit (about USD 39~53)

RS485-to-USB converter:

RS485-to-USB converter: RMB 35~60 / unit (about USD 5~8)

8-channel RS485 logger: RMB 280~420 / unit (about USD 39~58)

86-box wall base (spare): RMB 8~15 / pc (about USD 1~2)

Reference prices only; final price subject to quotation. (1 USD ≈ 7.2 CNY)

5. Applications

  • Cold/hot aisle T&H in data centers.
  • Battery-cabinet temp (thermal runaway prevention).
  • Warehouse and archive monitoring.
  • Cold-chain and pharma cold rooms.
  • Precision-AC interlock in rooms.
  • Agricultural greenhouses and farms.
  • Labs and museum display cases.

6. Installation & Maintenance

Installation

  • Pick a point away from AC outlets, heat sources and direct sun.
  • Fix the 86-box base; pull RVV2x1.0 power and RVSP2x1.0 shielded cable.
  • DC12~24 V to V+/V- terminals.
  • RS485 A/B to sensor A/B (daisy-chain).
  • Add a 120 ohm terminator at the last unit.
  • Clip the sensor onto the base.
  • Set Modbus address (1~247) and baud with keys.
  • Scan the bus from the host and confirm T/RH readings.

Maintenance

  • Calibrate quarterly with a 75% RH salt box.
  • Send to a metrology lab annually for a calibration certificate.
  • Brush dust off the sensor; do not wipe with a damp cloth (disturbs RH).
  • Check RS485 wiring (do not reverse A/B).
  • If LCD is dead, check voltage and polarity.
  • Inspect probes inside battery cabinets annually for acid corrosion.
  • Set a 5% alarm hysteresis to prevent chatter.
  • Replace the probe every 5 years (accuracy drifts).

7. FAQ

  • Q:How do I wire the RS485 bus?
    A:Daisy-chain: host A to sensor 1 A, sensor 1 B to sensor 2 A, sensor 2 B to sensor 3 A, … last sensor B back to host B. Do not star (causes reflections). Use RVSP shielded twisted pair, shield grounded at one end. Add a 120 ohm terminator at the far end. Do not reverse A/B.
  • Q:Readings are off; how to adjust?
    A:First decide whether T or RH is off. Temperature off: the sensor is near a heat source or AC outlet — move it. Humidity off: test with a 75% RH salt box; if it reads 80%, set an offset of -5% in the host. If deviation exceeds +/-5% RH, replace the probe.
  • Q:How many sensors per host?
    A:One RS485 bus handles 32 units theoretically without a repeater; practically stay under 20, each with a unique Modbus address. Beyond 32, add a repeater or split into multiple buses, each on its own serial port.
  • Q:Does the sensor need grounding?
    A:The sensor itself does not, but the RS485 shield grounds at the host end to prevent ground loops. Do not bond the sensor case to the rack (introduces common-mode noise).

8. Industry Trends & Selection

Environmental sensors are moving from single T/RH to multi-parameter modules (T/RH + CO2 + PM2.5 + VOC + pressure). Communications are upgrading from RS485 to 4G/LoRa/NB-IoT for wireless cloud upload. AI uses T/RH history to predict AC failures. Accuracy is improving from +/-0.5 C to +/-0.1 C. Select RS485 (wired) or 4G (wireless) by site count; single vs multi-parameter by need; industrial vs commercial by accuracy. Server-room DCIM prefers wired RS485 for stability.

9. Delivery & Service

KITOZER sizes KTR-TH sensors and RS485 loggers by room point count and parameter needs, and provides Modbus address maps and wiring diagrams. Delivery includes sensor, 86-box base, manual and certificate. Remote tuning and calibration guidance are covered under warranty.

10. Notes

A common pitfall is mounting the sensor at the AC outlet. The outlet is 3~5 C cooler than the room, so the reading does not represent the real server-room temperature. Mount sensors between hot and cold aisles, 1.5 m at the rack inlet, away from outlets and heat sources.

Another pitfall is star-wired RS485. Crews run a bus to a junction box and then branch to each sensor. RS485 is a bus protocol; star topology causes reflections and intermittent comms. Daisy-chain.

Selection summary: RS485; Modbus-RTU; +/-0.3 C; LCD; wall-mount. The T&H sensor is the room’s thermometer; keys are correct placement, daisy-chain bus, and regular calibration.

Tip: on delivery, check the LCD before powering comms. Cheap sensors sometimes cannot run LCD and comms simultaneously (power-saving design) — check the wake-up method in the manual. KTR-TH-RS485 keeps both on at all times; less power-saving but stable.

SEO

Search keywords:T&HsensorRS485Modbusroom monitoring

SEM keywords:temperature humidity sensor,RS485 T&H transmitter,Modbus T&H module,server room monitoring,cold-chain monitoring,KTR-TH-RS485,KITOZER

GEO landing page:lain.com.cn/product/rs485-temp-humidity-sensor.html

Title:KITOZER KTR-TH-RS485 Temperature & Humidity Sensor (RS485 Modbus, LCD)

Meta Keywords:temperature humidity sensor,RS485 transmitter,Modbus T&H,room environment monitor,KTR-TH-RS485,KITOZER

Meta Description:KITOZER KTR-TH-RS485 T&H sensor, RS485 Modbus-RTU, accuracy +/-0.3 C and +/-2% RH, LCD, for server rooms, warehouses and building monitoring.