Toggle30kW Rated Cooling Capacity Cold Plate Liquid Cooling Rack System — Technical Design Proposal
Project No.: LAIN-YL-2026-001
Design Firm: Guangzhou Lain Intelligent System Development Co., Ltd.
Brand: KITOZER
Version: V1.0
—
Table of Contents
- Company Profile
- Project Overview
- User Requirements Analysis
- Overall System Design Description
- Detailed Technical Specifications of System Products
- Project Configuration & Quotation List
- Core Solution Advantages
- Technical FAQ
- Construction Schedule Plan
- Construction Organization Plan
- After-Sales Service System
- Operation & Maintenance Training Program
- Representative Project Case Studies
- SEO Keyword System & Optimization Tags
- Website Backend Publishing Configuration
- Contact Information
—
Chapter 1 — Company Profile
Founded in 2002 and headquartered in Panyu District, Guangzhou, Guangzhou Lain Intelligent System Development Co., Ltd. is a national high-tech enterprise specializing in the R&D, manufacturing, and sales of data center infrastructure, intelligent computer rooms, liquid cooling thermal management systems, and electromagnetic shielding equipment. With over two decades of deep industry expertise, the company has built its proprietary core brand KITOZER, with a product portfolio spanning micro-module cold-aisle containment, integrated cabinets, outdoor enclosures, shielded rooms, shielded racks, containerized data centers, and liquid-cooled data center systems — covering the full spectrum of data center equipment and engineering services.
As a professional manufacturer and supplier, KITOZER delivers custom solutions and turnkey projects for government, financial, telecommunications, internet, education, healthcare, and industrial manufacturing sectors worldwide — from solution design, product customization, and manufacturing through to engineering implementation and lifecycle O&M support — all under one roof as a one-stop integrated solution provider.
The company operates a modern production base with a dedicated R&D team, holding core competencies in high-efficiency heat dissipation, electromagnetic shielding, intelligent environmental monitoring, and green energy conservation. We hold dozens of product patents and software copyrights and are certified under ISO9001 (Quality Management System), ISO14001 (Environmental Management System), and OHSAS18001 (Occupational Health & Safety Management System). Leveraging over 20 years of industry experience and technical accumulation, we tailor exclusive solutions to individual client requirements, providing multiple differentiated design proposals free of charge — precisely matching site conditions and business needs.
Guided by the product philosophy of “Efficient, Green, Innovative, Safe, and Convenient,” the company drives growth through technological innovation, continuously launching green data center products and solutions suited to next-generation computing demands. In the liquid cooling data center domain, KITOZER has independently developed both cold plate and immersion liquid cooling technologies, built on years of HVAC and structural design experience, capable of meeting ultra-high-density cooling demands from 10kW to over 100kW per rack — enabling data centers to achieve low PUE, high reliability, and easy maintenance in their green upgrade journey.
The company has established a full-process quality control system — from incoming raw materials to finished product dispatch, every stage is inspected. Key components are sourced from tier-one industry brands, with third-party testing agencies providing end-to-end quality assurance, ensuring every product meets national and industry standards. A 7×24 hour professional technical service system responds rapidly to customer issues, with a dedicated project manager assigned to every project for full-cycle support — from pre-sales solution design through post-sales maintenance — earning widespread recognition from enterprises and clients at home and abroad, including the USA, Europe, Southeast Asia, the Middle East, and Africa.
—
Chapter 2 — Project Overview
2.1 Project Background
With the rapid advancement of the digital economy, the proliferation of artificial intelligence, big data, cloud computing, and high-performance computing has driven continuous increases in data center server compute density. Per-rack power density has climbed rapidly from a traditional 3–5kW to 10kW, 20kW, and beyond 30kW. Conventional air-cooling is increasingly challenged by insufficient heat dissipation capacity, persistently high energy consumption, noise pollution, and poor space utilization — making it difficult to meet the cooling demands of ultra-high-density computing.
Liquid cooling technology — with its superior heat transfer efficiency, lower energy consumption, and better noise control — has become the core cooling solution for next-generation high-density data centers. Among the available approaches, cold plate liquid cooling is compatible with standard server architectures, offers low retrofit complexity and high reliability, and is currently one of the mainstream technical routes for high-density heat dissipation.
Against this backdrop, the present project addresses the client’s high-density computing room construction needs by adopting a mature and reliable cold plate liquid cooling architecture. The system comprises 205 cold plate liquid cooling cabinets with 30kW rated heat dissipation capacity, complemented by a computer-room-side cold source system, primary piping network, power supply & distribution system, and intelligent monitoring system — delivering a safe, reliable, energy-efficient, and intelligently operated cold plate liquid cooling data center solution that supports the client’s business-driven compute infrastructure requirements.
2.2 Project Overview
| Item | Description |
| — | — |
| Project Name | 30kW Cold Plate Liquid Cooling Cabinet System Construction Project |
| Construction Entity | Guangzhou Lain Intelligent System Development Co., Ltd. |
| Technical Route | Rack-level CDU secondary-side isolated cold plate liquid cooling system |
| Cabinet Quantity | 205 units of 42U standard cold plate liquid cooling cabinets |
| Rated Cooling Capacity per Cabinet | 30kW (peak 35kW) |
| Total Cooling Load | 6,150kW |
| Cold Source Configuration | Closed evaporative cooling tower + high-temperature screw chiller for supplemental cooling |
| System Architecture | Primary/secondary side fully isolated, N+1 redundant design |
| Design Targets | Annual comprehensive PUE ≤ 1.2; system availability ≥ 99.99%; meets Class A data center reliability requirements |
2.3 Project Construction Objectives
Heat Dissipation Capacity Objective — Each cabinet achieves a rated cooling capacity of 30kW with a peak capacity of 35kW. Core heat-generating components such as server CPUs maintain stable operating temperatures within design limits, satisfying full-load operation requirements for high-density computing equipment.
Energy Efficiency Objective — Maximize utilization of natural cold sources, extend free-cooling hours, and adopt variable-frequency control to precisely match cooling output with IT load. Annual comprehensive PUE ≤ 1.2, significantly reducing cooling system energy consumption and operational costs.
Reliability Objective — Core equipment adopts N+1 redundancy; piping and connectors feature multi-layer sealing designs; comprehensive leak detection and safety protection systems are deployed. System availability ≥ 99.99%, meeting Class A data center reliability requirements.
Intelligence Objective — Full-system real-time operational status monitoring, automatic fault alarm, intelligent device linkage control, and support for integration with the client’s existing DCIM/BMS monitoring platform for unified O&M management — reducing operational complexity and labor costs.
Scalability Objective — Modular system architecture with expansion margin reserved across cold source, piping, power distribution, and monitoring subsystems. Supports future increases in cabinet count and per-cabinet power density, accommodating the client’s long-term business growth.
Safety & Compliance Objective — System design strictly adheres to national safety specifications, with multiple protection measures across electrical safety, pressure safety, leak prevention, and fire safety. All components comply with applicable safety certification requirements.
—
Chapter 3 — User Requirements Analysis
3.1 Core Heat Dissipation Requirements
- Per-cabinet rated cooling capacity no less than 30kW, satisfying full-load heat dissipation for dual-socket high-TDP CPU servers, with ≥15% design margin to accommodate load fluctuations and extreme operating conditions.
- Secondary-side supply liquid temperature stably controlled within 35°C; return liquid temperature not exceeding 45°C, keeping server chip operating temperatures in the optimal range for enhanced stability and extended equipment service life.
- Working fluid: 25% concentration ethylene glycol-water solution with dedicated corrosion inhibitors and scale inhibitors — safe, environmentally friendly, non-corrosive to piping, heat exchangers, cold plates, and all system wetted materials.
- Fully isolated primary/secondary architecture: primary-side cooling water never contacts server cold plates, preventing contamination and fouling from the primary side from affecting the secondary side — protecting critical IT equipment.
3.2 Cabinet Structural Requirements
- Standard 42U cabinet, compliant with 19-inch standard mounting specifications, compatible with existing standard rack-mount servers without major structural modification.
- Static load rating ≥ 1,500kg, satisfying the load requirements of high-density servers and liquid cooling components; structural strength per national standards.
- Front and rear doors adopt high open-area perforated mesh design to support limited auxiliary air-cooling requirements while facilitating equipment maintenance; three-point locking anti-theft door latches ensure equipment security.
- Cabinet top and base pre-drilled with ample liquid piping and cable entry openings, complete with sealing assemblies and fire-stop components — meeting computer room fire protection, dustproof, and rodent-proof requirements.
- Fully implemented grounding system with dedicated grounding copper busbar, satisfying computer room equipotential bonding requirements for electrical safety.
- Internal space reserved for liquid cooling piping, CDU equipment, and monitoring components with designated mounting points — rational layout enabling convenient installation and maintenance.
3.3 Power Supply & Distribution Requirements
- Each cabinet equipped with dual-circuit intelligent PDU for redundant power supply, satisfying dual-power server reliability requirements — single-circuit failure does not affect equipment operation.
- PDU supports full electrical parameter monitoring (current, voltage, power, energy, power factor), remote on/off control, overload protection, and comprehensive alarm functions.
- Dedicated grounding busbar inside each cabinet; all equipment reliably grounded with grounding resistance per computer room specifications.
- Cable entry via sealed cable glands with protection rating ≥ IP65, meeting dust and moisture resistance requirements.
- Power distribution system reserves expansion capacity for future equipment additions and power upgrades.
3.4 Monitoring & Safety Requirements
- Each cabinet configured with an independent locating leak detection system with leak position accuracy ≤ 10cm; immediate audible/visual alarm upon leak occurrence with linkage to close relevant valves.
- Temperature, pressure, and flow sensors at critical system nodes for real-time monitoring of supply/return liquid temperature, pressure, and flow; automatic alarm on abnormal conditions.
- Local touchscreen display per cabinet for on-site viewing of operating parameters, fault information, and operation control; supports remote data upload to the DCIM/BMS platform.
- Multi-level alarm mechanism supporting audible/visual alarm, SMS alert, and system pop-up notification; all fault information traceable and queryable.
- Centralized automatic control system at the cold station, enabling fully automatic linkage control of cold source equipment, pumps, and valves — unattended operation with automatic cooling output regulation based on load.
3.5 Reliability & Maintenance Requirements
- Critical circulation pumps and cold source equipment adopt N+1 redundancy; standby equipment automatically activates on primary unit failure without system disruption.
- All piping connectors use reliable sealed designs; server-side connections use self-sealing quick couplings enabling hot-swap maintenance without coolant leakage.
- System features automatic venting, automatic pressure stabilization, and automatic water make-up — reducing manual O&M workload and simplifying operational procedures.
- Modular equipment design allows online maintenance and replacement of key components without system shutdown, ensuring business continuity.
- Filters designed for online replacement — blocked filter elements can be swapped without system downtime.
- System designed for easy routine inspection and maintenance; high standardization of consumable parts, ample spare parts supply, and low maintenance cost.
3.6 Construction & Delivery Requirements
- Overall project duration ≤ 90 days, covering equipment manufacturing, on-site installation, system commissioning, trial operation, and acceptance/delivery.
- Construction strictly follows national and industry specifications, ensuring construction quality and safety with civilized, safe work practices.
- Full technical documentation delivered upon handover: operation manuals, maintenance manuals, as-built drawings, and related deliverables.
- Professional operator and maintenance training provided to enable the client’s O&M team to independently operate and perform routine maintenance.
- Comprehensive after-sales service and warranty: ≥ 2 years full-system warranty; ≥ 3 years warranty on core components.
—
Chapter 4 — Overall System Design Description
4.1 Design Basis
This proposal strictly complies with the following national, industry standards and specifications:
| Standard No. | Standard Name |
| — | — |
| GB 50174-2017 | Code for Design of Data Centers |
| GB 50462-2016 | Code for Construction and Acceptance of Data Center Infrastructure |
| GB/T 2887-2011 | General Specification for Computer Field |
| T/CCSA 317-2021 | Technical Specification for Liquid-Cooled Data Centers |
| YD/T 3984-2021 | Technical Requirements for Data Center Liquid-Cooled Server Systems |
| GB/T 39661-2020 | Technical Requirements and Test Methods for Cold Plate Liquid Cooling of Servers |
| GB 50316-2000 (2008 Edition) | Code for Design of Industrial Metallic Piping |
| GB 50054-2011 | Code for Design of Low-Voltage Electrical Installations |
| GB 50057-2010 | Code for Design Protection of Structures Against Lightning |
| GB 40879-2021 | Minimum Allowable Values of Energy Efficiency and Energy Efficiency Grades for Data Centers |
| — | Client-provided computer room site conditions and business requirements documentation |
4.2 Design Principles
4.2.1 Reliability First
System reliability is the highest priority. All core equipment and critical paths adopt redundant designs with mature, proven technical routes and high-quality components — ensuring long-term stable operation from architecture, component, and control perspectives, meeting Class A data center availability requirements. All critical components undergo rigorous reliability testing to guarantee stable performance under all operating conditions.
4.2.2 High Efficiency & Energy Conservation
High-efficiency liquid cooling technology substantially improves heat exchange efficiency, maximizes natural cold source utilization, extends free-cooling hours, and reduces mechanical refrigeration runtime. Variable-frequency control technology achieves precise matching between cooling output and IT load, maximizing system energy efficiency and reducing annual operating costs — supporting low-carbon, green data center operation.
4.2.3 Safety & Compliance
System design strictly adheres to national safety specifications with multiple protection layers across electrical safety, pressure safety, leak prevention, and fire safety. All electrical components meet CCC certification requirements; pressure components comply with pressure vessel codes; leak detection provides full coverage — safeguarding personnel and equipment alike.
4.2.4 Intelligent Operation & Maintenance
Full-digital monitoring architecture delivers comprehensive system awareness, intelligent analysis, and automated control. Local and remote two-tier monitoring systems support automatic fault diagnosis and alarming, reducing manual O&M burden while improving fault response speed and resolution efficiency — lowering operational complexity and labor costs.
4.2.5 Scalability
Modular system architecture with expansion margins reserved across cold source, piping, distribution, and monitoring subsystems. Standardized interfaces and protocols ensure seamless integration of new equipment into the existing system, accommodating long-term business growth.
4.2.6 Economic Applicability
System configuration is optimized to control construction cost while satisfying performance and reliability requirements. High-efficiency, energy-saving design reduces long-term operating costs, balancing initial investment against total lifecycle cost for optimal whole-life economics.
4.3 Overall System Architecture
The 30kW cold plate liquid cooling cabinet system adopts a two-stage isolated liquid cooling architecture structured in five functional layers from cold source to terminal heat dissipation. The architecture is clear, with independent layer functionality for simplified O&M management and fault isolation.
4.3.1 Cold Source Layer
Comprising closed evaporative cooling towers, high-temperature screw chillers, primary-side circulation pump sets, and header/collector assemblies — responsible for producing primary-side cooling water as the system’s cold source backbone. Supports evaporative cooling mode, dry cooling mode, and mechanical refrigeration supplemental mode, automatically switching based on outdoor ambient temperature to maximize natural cold source utilization and minimize energy consumption.
4.3.2 Main Piping Layer
Comprising the computer room’s main supply/return piping, row-level piping, valve assemblies, and insulation — responsible for delivering primary-side cooling water from the cold station to each cabinet’s CDU and returning heated water to the cold source for heat rejection. The main piping uses a loop design, ensuring uniform supply pressure and temperature across all cabinets.
4.3.3 Cabinet Heat Exchange Distribution Layer
Comprising the rack-level CDU (Coolant Distribution Unit) and manifold assemblies installed in each cabinet, achieving primary/secondary coolant isolation and heat exchange. The CDU integrates a plate heat exchanger, circulation pump, filter, expansion tank, sensors, and control unit — managing secondary-side coolant circulation, filtration, pressure stabilization, and flow regulation to deliver stable, clean coolant to server cold plates.
4.3.4 Terminal Heat Dissipation Layer
Comprising server CPU cold plates, thermal interface material (TIM), branch flex hoses, and quick couplings — in direct contact with server heat-generating components. Heat is carried away by coolant flow for precision cooling. Cold plates utilize micro-channel structures delivering high heat transfer efficiency and low flow resistance, compatible with mainstream server CPU specifications.
4.3.5 Monitoring & Management Layer
Comprising field sensors, cabinet-local control units, cold station PLC control systems, and DCIM integration platform — enabling full-system data acquisition, analysis, control, and alarm. Supports both local and remote O&M management, and can interface with the client’s existing BMS/DCIM platform for unified management.
4.4 Design Operating Conditions
4.4.1 Outdoor Design Conditions
| Parameter | Value |
| — | — |
| Summer outdoor design dry-bulb temperature | 35°C |
| Summer outdoor design wet-bulb temperature | 28°C |
| Winter outdoor design dry-bulb temperature | 5°C |
| Annual average temperature | 22°C |
4.4.2 System Design Conditions
| Parameter | Value |
| — | — |
| Primary-side supply liquid temperature | 30°C |
| Primary-side return liquid temperature | 38°C |
| Primary-side supply/return temperature differential | 8°C |
| Secondary-side supply liquid temperature | 35°C |
| Secondary-side return liquid temperature | 45°C |
| Secondary-side supply/return temperature differential | 10°C |
| System design working pressure | 1.0MPa |
| System test pressure | 1.5MPa |
| Rated cooling capacity per cabinet | 30kW |
| Peak cooling capacity per cabinet | 35kW |
4.5 Coolant Selection
Both primary and secondary sides of this system use 25% concentration ethylene glycol-water solution as the working fluid, offering the following characteristics:
| Property | Description |
| — | — |
| Anti-freeze Performance | Freezing point approximately −15°C, enabling safe system operation in low-temperature winter environments, preventing pipe and equipment freeze damage. |
| Corrosion Protection | Dedicated corrosion inhibitors protect carbon steel, stainless steel, copper, aluminum, and other system wetted materials — extending system service life. |
| Scale Inhibition | Dedicated scale inhibitors suppress calcium/magnesium scaling, maintaining stable heat exchange efficiency across piping and heat exchangers. |
| Safety & Environmental | Ethylene glycol-water solution is chemically stable, non-toxic, harmless, and environmentally friendly; easy to clean up in the event of leakage. |
| Heat Transfer Performance | Excellent thermal conductivity and specific heat capacity, delivering high-efficiency heat exchange. |
—
Chapter 5 — Detailed Technical Specifications of System Products
5.1 Cabinet Structural System
5.1.1 42U Cold Plate Liquid Cooling Dedicated Cabinet
This cabinet is part of the KITOZER series, purpose-designed for cold plate liquid cooling scenarios. It features a high-strength cold-rolled steel frame integrating liquid cooling piping interfaces, power distribution interfaces, and monitoring components — compatible with standard 19-inch server mounting while balancing structural strength, thermal adaptability, and serviceability.
Structural & Dimensional Parameters
| Parameter | Specification |
| — | — |
| Cabinet Height | 2000mm (42U standard height) |
| Cabinet Width | 600mm (standard 19-inch mounting width) |
| Cabinet Depth | 1200mm (deep-cabinet design for liquid piping and server depth) |
| Usable Internal U-positions | 42U, clearly marked, accuracy ±0.1U |
| Square-hole rail center distance | 465mm (standard 19-inch mounting) |
| Front/Rear door opening angle | ≥ 130° |
| Side door dimensions | Full cabinet height, tool-free detachable design |
| Mounting depth adjustment | Front/rear rails adjustable travel ≥ 100mm |
Material & Finish Parameters
| Parameter | Specification |
| — | — |
| Main frame material | High-quality cold-rolled steel sheet, thickness ≥ 2.0mm |
| Door panel material | High-quality cold-rolled steel sheet, thickness ≥ 1.5mm |
| Square-hole rail material | High-strength galvanized steel, thickness ≥ 2.0mm, No. 12 steel standard |
| Surface finish | Electrostatic powder coating, epoxy polyester powder |
| Coating thickness | 60–80μm |
| Surface hardness | ≥ 2H |
| Adhesion rating | Class 0 (per GB/T 9286-1998) |
| Salt spray resistance | ≥ 48 hours without corrosion (per GB/T 10125-2012) |
| Standard color | RAL7035 light gray (custom colors available) |
| Mesh opening rate | ≥ 65% front/rear doors — balance of ventilation and protection |
Load-Bearing Parameters
| Parameter | Specification |
| — | — |
| Static load capacity | ≥ 1,500kg (uniformly distributed) |
| Dynamic load capacity | ≥ 1,000kg |
| Cabinet top load capacity | ≥ 200kg |
| Base load capacity | ≥ 1,800kg |
| Per-rail (column) load capacity | ≥ 500kg |
| Leveling foot adjustment range | ±25mm |
Structural Configuration
| Component | Description |
| — | — |
| Front door | Single-leaf perforated mesh door, three-point anti-theft lock |
| Rear door | Double-leaf perforated mesh door, three-point anti-theft lock, dual-side maintenance access |
| Side doors | Closed solid side panels (both sides), quick-release latches, tool-free removal |
| Top panel | One-piece top, pre-drilled with 2× DN50 liquid piping openings, 4× cable entry holes, with rubber gaskets and fire-stop assemblies |
| Base panel | Split-design base with liquid piping and cable openings, anti-slip shock-absorbing pads |
| Mounting rails | 4× galvanized square-hole rails (front/rear), depth adjustable |
| Cable management | Vertical cable managers on both sides with cable tie-down clips |
| Piping supports | Dedicated liquid cooling pipe mounting brackets at cabinet rear for manifold and branch line fixation |
| Grounding kit | 3×30mm grounding copper busbar with grounding bolts and stranded copper wire |
| Leveling base | M16 heavy-duty leveling feet with anti-slip shock pads |
Protection & Compatibility Parameters
| Parameter | Specification |
| — | — |
| Protection rating | IP41 (complete cabinet) |
| EMC compliance | Per GB/T 17626 series |
| Installation compatibility | All standard 19-inch rack-mount equipment |
| Cabinet baying compatibility | Seamless multi-cabinet baying with joining brackets |
| Seismic performance | Per GB 50260-2013, designed for Seismic Intensity 8 |
| Fire performance | All materials meet B1 flame-retardant rating |
5.1.2 Cabinet Load-Bearing Leveling Base
Heavy-duty leveling base purpose-designed for liquid cooling cabinets, enhancing overall load capacity and stability while enabling precise on-site leveling.
| Parameter | Specification |
| — | — |
| Material | Q235 carbon steel welded construction, powder-coated anti-corrosion finish |
| Dimensions | 600mm × 1200mm, fully matching cabinet footprint |
| Structural profile | No. 10 channel steel main frame, 5mm steel plate base |
| Leveling feet | M16 heavy-duty galvanized feet (4 units) |
| Adjustment range | ±25mm |
| Static load capacity per base | ≥ 2,000kg |
| Surface treatment | Electrostatic powder coating, anti-rust anti-corrosion |
| Mounting method | Bolted connection to cabinet base |
| Grounding design | Grounding terminal provided for equipotential bonding |
| Anti-slip design | Rubber anti-slip pads under feet for slip resistance and vibration damping |
5.1.3 Cabinet Grounding Assembly
Dedicated cabinet grounding system meeting computer room equipotential bonding requirements and ensuring electrical safety.
| Parameter | Specification |
| — | — |
| Grounding busbar material | T2 copper, tin-plated surface |
| Busbar specification | 30mm × 3mm, length 1900mm |
| Conductivity | ≥ 98% IACS |
| Grounding wire | 6mm² multi-strand yellow/green bicolor copper core, length 2m |
| Grounding bolts | M8 stainless steel with flat and spring washers |
| Terminal connections | Copper lug crimp connection |
| Mounting position | Vertically on rear rails of cabinet |
| Grounding resistance | ≤ 1Ω |
| Corrosion resistance | Tin plating thickness ≥ 5μm, long-term oxidation-free |
5.2 Liquid Cooling Core Heat Exchange Units
5.2.1 Rack-Level Coolant Distribution Unit (CDU)
The KITOZER series rack-mount CDU is the core heat exchange device of the cold plate liquid cooling system. Installed at the cabinet base, it achieves primary/secondary coolant isolation and heat exchange. This CDU delivers 35kW rated cooling capacity, perfectly matched to the 30kW liquid cooling cabinet, with a compact 3U rack-mount design offering high integration and comprehensive functionality.
Basic Performance Parameters
| Parameter | Specification |
| — | — |
| Rated cooling capacity | 35kW (at primary supply 30°C / secondary return 45°C) |
| Applicable heat load range | 10–35kW |
| Heat exchange efficiency | ≥ 95% |
| Rated working pressure | 1.0MPa |
| Test pressure | 1.5MPa |
| Design service life | ≥ 15 years |
| Mounting form | 19-inch standard rack-mount |
| Mounting height | 3U |
| Mounting position | Bottom U-position of cabinet |
Plate Heat Exchanger Parameters
| Parameter | Specification |
| — | — |
| Heat exchanger type | Brazed plate heat exchanger |
| Plate material | 316L food-grade stainless steel |
| Brazing material | Pure copper |
| Plate quantity | 40 plates |
| Heat exchange area | ≥ 2.5m² |
| Heat transfer coefficient | ≥ 3,000 W/(m²·K) |
| Max working pressure | 1.6MPa |
| Max working temperature | 120°C |
| Connection size | Primary DN20 female thread, secondary DN20 female thread |
| Pressure drop | Primary ≤ 50kPa, secondary ≤ 60kPa |
| Media compatibility | Ethylene glycol-water solution, pure water, and common coolants |
| Sealing form | Fully brazed, gasket-free — zero leak risk |
Secondary-Side Circulation Pump Parameters
| Parameter | Specification |
| — | — |
| Pump type | Magnetic drive centrifugal pump, shaft-seal-free, zero-leakage design |
| Quantity | 1 unit (redundant dual-pump option available) |
| Rated flow | 8m³/h |
| Rated head | 12m |
| Rated power | 0.37kW |
| Supply voltage | 220V AC, 50Hz |
| Insulation class | Class F |
| Protection rating | IP55 |
| Pump housing material | 304 stainless steel |
| Impeller material | Engineering plastic PPS |
| Bearing material | Silicon carbide, wear- and corrosion-resistant |
| Sealing form | Static seal only, no dynamic seal points — leakage completely eliminated |
| Control mode | 0–10V variable frequency speed control, automatic flow adjustment by load |
| Noise level | ≤ 55dB(A) |
| Design life | ≥ 50,000 hours |
Precision Filter Parameters
| Parameter | Specification |
| — | — |
| Filter type | Y-type precision filter |
| Installation position | Secondary-side supply line |
| Filtration rating | 5μm |
| Housing material | 304 stainless steel |
| Filter element material | Polypropylene melt-blown cartridge |
| Connection size | DN20 female thread |
| Rated pressure | 1.6MPa |
| Working temperature | 0–80°C |
| Differential pressure indicator | Standard equipment — automatic warning at filter blockage |
| Replacement method | Bypass valve included, online cartridge replacement without shutdown |
Pressure Stabilization Expansion Tank Parameters
| Parameter | Specification |
| — | — |
| Tank type | Diaphragm expansion tank |
| Nominal volume | 12L |
| Pre-charge pressure | 0.2MPa (factory preset, field adjustable) |
| Max working pressure | 1.0MPa |
| Working temperature | −10°C to 90°C |
| Tank material | Carbon steel Q235-B, powder-coated anti-corrosion |
| Diaphragm material | EPDM (ethylene-propylene-diene monomer), coolant-resistant |
| Connection size | G1/2 female thread |
| Function | Compensates coolant thermal expansion/contraction, stabilizes system pressure |
Valve Assembly Parameters
| Component | Specification |
| — | — |
| Primary supply/return ball valves | 2 units, 304 stainless steel, DN20, with position indicator |
| Secondary supply/return ball valves | 2 units, 304 stainless steel, DN20, with position indicator |
| Automatic air vent | 1 unit, 304 stainless steel, G1/2 connection, automatic air purge |
| Safety valve | 1 unit, opening pressure 0.8MPa, overpressure automatic relief |
| Drain valve | 1 unit, 304 stainless steel ball valve, DN15, for routine blowdown |
| Check valve | 1 unit, secondary return end, prevents reverse flow |
| Valve seal material | PTFE (polytetrafluoroethylene), temperature- and corrosion-resistant |
| Valve cycle life | ≥ 10,000 open/close cycles without leakage |
Sensor Configuration Parameters
| Component | Specification |
| — | — |
| Secondary supply temperature sensor | PT100 platinum RTD, Class A accuracy, 304 stainless steel housing |
| Secondary return temperature sensor | PT100 platinum RTD, Class A accuracy, 304 stainless steel housing |
| Secondary supply pressure sensor | Range 0–1.0MPa, accuracy ±0.2% FS, 4–20mA output |
| Secondary return pressure sensor | Range 0–1.0MPa, accuracy ±0.2% FS, 4–20mA output |
| Flow sensor | Turbine-type, range 0.5–10m³/h, accuracy ±1% |
| Leak sensor | Locating leak detection cable at CDU base, immediate alarm on leak |
Control Unit Parameters
| Parameter | Specification |
| — | — |
| Controller | ARM architecture embedded industrial-grade controller |
| Display | 4.3-inch color touchscreen, resolution 480×272 |
| Display content | Supply/return temperature, pressure, flow, operating status, fault information |
| Control functions | Variable-frequency pump control, automatic temperature regulation, automatic fault alarm, valve linkage control |
| Communication interfaces | RS485 (Modbus-RTU protocol), Ethernet (TCP/IP protocol) |
| Alarm modes | Local audible/visual alarm, remote system alarm |
| Data storage | ≥ 30 days historical data logging |
| Supply voltage | 220V AC, 50Hz |
| Operating temperature | 0–50°C |
| Storage temperature | −20°C to 70°C |
| Immunity | Compliant with EMC industrial-grade standards |
Physical & Material Parameters
| Parameter | Specification |
| — | — |
| External dimensions | 482.6mm (W) × 132mm (H) × 600mm (D) |
| Unit weight | Approx. 45kg |
| Frame material | 1.5mm cold-rolled steel, electrostatic powder coating |
| Internal piping material | 304 stainless steel |
| Surface color | RAL7035 light gray |
| Mounting method | Standard rack-mount, with L-type mounting brackets |
| Protection rating | IP31 |
5.2.2 CPU Dedicated Liquid Cooling Cold Plate
The KITOZER series micro-channel liquid cooling cold plate is purpose-designed for server CPU heat dissipation. Featuring a red copper base with precision micro-channel manufacturing, it delivers high heat exchange efficiency and low flow resistance, compatible with mainstream x86 architecture CPU socket specifications.