Technical Design Proposal for a 40ft High-Cube Containerized Liquid-Cooled Data Center

(8 × 30kW High-Density Liquid-Cooled Racks / 240kW Total Heat Load)

—

Cover Page

Item Details
— —
Solution Title Technical Design Proposal for a 40ft High-Cube Containerized Liquid-Cooled Data Center
Configuration 8 × 30kW High-Density Liquid-Cooled Racks · 240kW Total Heat Load · CDU Indirect Liquid Cooling Architecture
Produced By Guangzhou Lain Intelligent System Development Co., Ltd.
Brand KITOZER
Version V1.0
Date August 2026

—

Table of Contents

  1. Company Profile
  2. Project Overview
  3. User Requirements Analysis
  4. Design Basis and Design Principles
  5. Overall System Architecture
  6. Detailed Configuration List
  7. Technical Specifications of Each System
  • 7.1 Container Enclosure and Compartment Infrastructure
  • 7.2 IT Racks and Liquid Cooling Terminal Systems
  • 7.3 CDU Coolant Distribution Unit System
  • 7.4 Primary/Secondary Side Liquid Cooling Piping System
  • 7.5 Cooling Medium and Water Treatment System
  • 7.6 Power Supply and Distribution System
  • 7.7 Environment Monitoring and Intelligent Control System
  • 7.8 Fire Protection and Safety System
  • 7.9 Auxiliary Support System
  1. Key Solution Advantages
  2. Technical Q&A
  3. Construction Schedule Plan
  4. Construction Organization Plan
  5. After-Sales Service System
  6. Operation and Maintenance Training Plan
  7. Typical Engineering Case Studies
  8. SEO Keyword System and Optimization Tags
  9. Website Publishing Configuration
  10. Contact Information

—

1. Company Profile

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise in China specializing in the R&D, manufacturing, and integration of data center infrastructure. Under our proprietary brand KITOZER, we have accumulated over two decades of industry expertise, mastering core technologies in high-efficiency cooling, intelligent monitoring, and electromagnetic shielding. We deliver full lifecycle services spanning solution design, custom manufacturing, installation and commissioning, and after-sales maintenance.

Our core product portfolio covers the full spectrum of data center equipment, including containerized computer rooms, micro-module cold-aisle containment, integrated cabinets, outdoor enclosures, shielded computer rooms, and intelligent shielding cabinets, widely deployed across data centers, telecommunication base stations, healthcare and scientific research, industrial control, and government/education sectors. Leveraging our flexible customization factory and professional engineering team, KITOZER tailors bespoke computer room solutions for diverse computing densities, deployment environments, and operational requirements. We offer free comparison of multiple design proposals to ensure optimal fit and cost efficiency for every project.

In quality management, our company has established a comprehensive end-to-end quality assurance system. Core components are sourced from first-tier brands, and every unit undergoes multiple rounds of power-on, dielectric withstand, thermal cycling, and leak detection testing prior to shipment. Third-party inspection agencies provide full-process quality oversight, ensuring stable delivery lead times. For after-sales support, we provide 7×24-hour professional online assistance, rapid response to customer issues, and dedicated account management throughout the full project lifecycle to guarantee reliable post-delivery operation.

—

2. Project Overview

With the rapid growth of AI large-model training, high-performance computing (HPC), and edge computing workloads, power density per server rack has surged from the traditional 5–10kW to 20–50kW. Conventional air-cooling can no longer meet high-density heat dissipation requirements and suffers from high energy consumption, excessive noise, and prolonged deployment cycles.

This proposal addresses high-density computing scenarios using a 40ft high-cube standard container as the deployment platform, integrating an indirect liquid cooling heat dissipation system. The configuration comprises eight 30kW high-density liquid-cooled racks, achieving a total cooling load of 240kW. At the heart of the thermal architecture is a CDU (Coolant Distribution Unit) serving as the heat exchange node, interfacing with external chiller plants or dry coolers as the heat rejection source to deliver stable, efficient liquid cooling for the servers.

The solution adopts a factory-prefabricated model: all systems inside the container — including racks, piping, CDU, power distribution, monitoring, and fire suppression — are fully pre-installed and tested at the factory. On-site work is limited to connecting utilities and the external cooling source, enabling rapid deployment. Construction lead time is reduced by over 80% compared to traditional computer room builds. This solution is ideally suited for edge computing nodes, temporary compute expansion, outdoor emergency data centers, and AI training clusters.

Default Scope of Work Boundary: The client is responsible for supplying and integrating the outdoor cooling source (chillers, cooling towers, dry coolers, etc.). KITOZER provides the complete internal liquid cooling infrastructure and system integration within the container. The interface point is the primary-side quick-connect coupling mounted on the exterior wall of the container.

—

3. User Requirements Analysis

3.1 Cooling Performance Requirements

  • Rated heat dissipation capacity of 30kW per rack, with a total thermal load of 240kW, meeting the cooling demands of high-power CPU/GPU servers.
  • Secondary-side supply water temperature stably controlled at 15–20°C; return water temperature ≤28°C; server chip temperatures maintained within designated thresholds.
  • Cooling system designed with redundancy — a single component failure must not compromise overall cooling, ensuring business continuity.

3.2 Deployment and Delivery Requirements

  • Standard container form factor enabling direct outdoor deployment without dedicated computer room construction.
  • Factory pre-fabrication and integration with rapid on-site interface; overall delivery cycle ≤45 days.
  • Cradle-liftable and relocatable design supporting elastic business adjustments and remote-site deployment.

3.3 Reliability and Safety Requirements

  • Core equipment adopts N+1 redundant architecture for year-round uninterrupted operation.
  • Comprehensive electrical safety, fire suppression, leak detection, and lightning protection grounding systems.
  • Multiple alarm and protection mechanisms with automatic safeguards for over-temperature, over-pressure, low liquid level, and power failure scenarios.

3.4 Intelligent Operations and Maintenance Requirements

  • Real-time acquisition and monitoring of all system parameters with dual local + remote management modes.
  • Automatic fault localization and alarm with linkage control capabilities.
  • Historical data logging and traceability to reduce manual O&M workload.

3.5 Compliance and Adaptability Requirements

  • Compliance with national data center design, electrical, fire protection, and environmental standards.
  • Reserved expansion interfaces supporting future upgrades in rack count and cooling capacity.
  • Compatibility with mainstream server cold-plate interfaces, supporting different brands of liquid-cooled servers.

—

4. Design Basis and Design Principles

4.1 Design Basis

This proposal strictly adheres to current national and industry standards and specifications, including but not limited to:

Standard Code Standard Name
— —
GB 50174-2017 Code for Design of Data Centers
GB 50016-2014 (2018 Edition) Code for Fire Protection Design of Buildings
GB 50054-2011 Code for Design of Low-Voltage Electrical Installations
GB 50343-2012 Technical Code for Protection of Building Electronic Information System Against Lightning
GB 50116-2013 Code for Design of Automatic Fire Alarm System
GB 50370-2005 Code for Design of Gas Fire Extinguishing Systems
YD/T 3299-2017 Technical Requirements for Liquid Cooling of Telecommunication Data Centers
GB/T 2887-2011 General Specification for Computer Site
GB/T 36340-2018 General Specification for Anti-Static Raised Access Floor

4.2 Design Principles

  • Safety and Reliability: System stability is the foremost priority. Critical components feature redundant design with multiple safety protections, meeting 7×24-hour continuous operation requirements.
  • High Efficiency and Energy Saving: The liquid-cooled high-efficiency heat exchange architecture reduces cooling energy consumption, achieving PUE as low as 1.1, in line with green data center development trends.
  • Rapid Deployment: Factory prefabrication and integrated delivery substantially reduce on-site construction time for rapid commissioning.
  • Intelligent Operations: Full-dimension environment monitoring, automated control, and remote management minimize manual intervention and enhance O&M efficiency.
  • Flexible Expansion: Modular design with reserved expansion interfaces supports smooth upgrades in cooling capacity, power distribution, and rack count.
  • Economic Practicality: While meeting performance and reliability targets, the solution is optimized to control both initial capital investment and ongoing operational costs.

—

5. Overall System Architecture

This containerized liquid-cooled data center adopts an indirect liquid cooling architecture comprising primary-side cooling source + CDU heat exchange + secondary-side rack liquid cooling. The complete system integrates nine major subsystems:

System Function
— —
Container Enclosure System Equipment carrier and protection structure providing insulation, waterproofing, fire resistance, and load-bearing foundation
IT Rack System Server mounting infrastructure integrating liquid cooling manifolds, quick-connect couplings, and PDUs
CDU Coolant Distribution System Core liquid cooling component facilitating heat exchange between primary and secondary sides, controlling secondary-side water temperature and flow
Piping System Primary/secondary supply and return piping connecting the cooling source, CDU, and racks for coolant circulation
Water Treatment System Coolant preparation, softened water replenishment, chemical dosing for corrosion/scale inhibition, and water quality monitoring
Power Supply and Distribution System Main distribution, UPS backup power, rack power distribution, and auxiliary power supply
Environment Monitoring System Temperature/pressure/flow liquid monitoring, leak detection, access control, video surveillance, and centralized management
Fire Protection and Safety System Gas suppression, fire detection, lightning protection grounding, and access control security
Auxiliary Support System Cold-aisle containment, lighting, maintenance spares, and signage

Spatial Layout: Along the length of the container, eight liquid-cooled racks are arranged in a single row on one side. The CDU units, power distribution cabinets, UPS, fire suppression cylinders, and auxiliary equipment are positioned on the opposite side, with a central maintenance aisle between them. The layout is compact and well-organized, providing adequate operational space and thermal management clearance.

—

6. Detailed Configuration List

6.1 Container Enclosure and Compartment Infrastructure

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 40ft High-Cube Container External 12192×2438×2896mm; Q235B steel; 50mm Class A rockwool insulation; IP55 protection; anti-corrosion coating Set 1 Reinforced load-bearing structure
2 Internal Load-Bearing Base No.12 channel steel welded frame + 3mm checkered steel plate; uniform load ≥1000kg/m² Set 1 Reinforced under rack & CDU areas
3 Anti-Static Access Floor 600×600mm all-steel; resistance 10⁶–10⁹Ω; uniform load ≥1000kg/m² No. 80 Includes supports, stringers, spares
4 LED Lighting System 40W flat panel; illuminance ≥300lux; incl. emergency lighting Set 8 Including 2 emergency lights
5 Class A Fire Door 900×2100mm fire-rated steel door; with door closer and emergency exit lock Set 1 Single-leaf, with observation window
6 Residual Pressure Ventilation Device Mechanical type; differential pressure 5–20Pa adjustable; with dust filter pcs 2 1 supply / 1 exhaust
7 Equipotential Bonding Copper Bar 40×4mm copper busbar around container perimeter with grounding terminals Set 1 Ground resistance ≤1Ω

6.2 IT Racks and Liquid Cooling Terminal Systems

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Liquid-Cooled Server Rack 600×1200×2000mm; 42U; static load ≥1500kg; front/rear perforated doors Set 8 19-inch standard mounting
2 Liquid Cooling Quick-Connect Coupling DN20; 316 stainless steel; self-sealing; male/female set; 1.6MPa Set 16 1 supply + 1 return per rack
3 Rack Branch Manifold 1-in/1-out; with manual regulating valve, temp/pressure ports; 304 stainless steel Set 8 Rear rack mounting
4 Rack Blanking Panel Set 1U/2U/4U all-steel; matte black; snap-in Set 8 Complete per rack
5 Metering PDU 380V input; 24×C13 + 8×C19 outlets; with metering & comms; 0U vertical Set 8 1 per rack
6 Cold Plate Adapter Accessory Kit Thermal pads, seals, mounting clips Batch 1 Matched for 8 racks of servers

6.3 CDU Coolant Distribution Unit System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Primary CDU Rated cooling capacity 240kW; plate heat exchanger; VFD pump set; PLC control Set 1 1+1 redundant
2 Standby CDU Identical parameters to primary CDU Set 1 Automatic failover
3 Built-in Circulating Pump Centrifugal VFD; 30m³/h; 25m head; 304 SS pump body Set 4 1 active + 1 standby per CDU
4 Plate Heat Exchanger 316L plates; heat transfer area ≥18m²; pressure rating 1.6MPa Set 2 1 per CDU
5 Diaphragm Expansion Tank 100L; constant-pressure make-up; butyl rubber diaphragm Set 2 1 per CDU
6 Y-Type Precision Strainer DN50; 316 SS; 100μm mesh pcs 4 1 primary + 1 secondary per CDU
7 Electric Proportional Control Valve DN50; temp-regulated; 4–20mA control Set 2 Primary-side supply regulation
8 Sensor Detection Kit Temperature, pressure, flow, level sensors (complete) Set 2 1 per CDU
9 Integrated Control Cabinet 7-inch touchscreen; PLC control; MODBUS communication Set 2 1 per CDU
10 Vibration Isolation Base Channel steel + rubber dampers; noise/vibration reduction Set 2 1 per CDU

6.4 Primary/Secondary Side Liquid Cooling Piping System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Primary Side Supply Header 304 SS seamless pipe; DN80; wall 3mm m 30 Cooling source interface to CDU
2 Primary Side Return Header 304 SS seamless pipe; DN80; wall 3mm m 30 CDU to cooling source interface
3 Secondary Side Supply Header 304 SS seamless pipe; DN100; wall 3mm m 25 Rack row overhead
4 Secondary Side Return Header 304 SS seamless pipe; DN100; wall 3mm m 25 Rack row underfloor
5 Rack Supply Branch Pipe 304 SS pipe; DN20; wall 2mm pcs 8 Header to manifold
6 Rack Return Branch Pipe 304 SS pipe; DN20; wall 2mm pcs 8 Manifold to header
7 Main Line Manual Ball Valve DN80; 304 SS; flanged; 1.6MPa pcs 6 Main valves + CDU inlet valves
8 Secondary Side Main Valve DN100; 304 SS; flanged pcs 4 2 supply + 2 return
9 Branch Line Manual Ball Valve DN20; 304 SS; female threaded pcs 16 1 supply + 1 return per rack
10 CDU Flexible Bellows DN80; 304 SS; flanged; vibration compensating pcs 4 1 primary + 1 secondary per CDU
11 Rack Flexible Connection Hose DN20; 304 SS braided; compression fitting pcs 16 1 supply + 1 return per rack
12 Pipe Fixing Support Hot-dipped galvanized channel + 304 SS pipe clamps Set 60 Spaced at 1.5m intervals
13 Pipe Insulation Layer Class B1 rubber-plastic; 20mm thick; aluminum foil wrap m³ 1.2 Full piping coverage
14 External Cooling Source Quick Interface DN80; 316 SS self-sealing; flanged Set 2 1 supply + 1 return set

6.5 Cooling Medium and Water Treatment System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Propylene Glycol Coolant 50% concentration; freezing point -25°C; anti-corrosion formula t 2.5 Total system volume
2 Automatic Water Softener Capacity 2m³/h; cation exchange resin; automatic regeneration Set 1 Make-up water softening
3 Precision Make-up Water Filter 5μm; 304 SS housing; PP melt-blown cartridge Set 1 Make-up water filtration
4 Corrosion/Scale Inhibitor Dosing System Metering pump + 100L chemical tank; automatic timed dosing Set 1 Anti-corrosion anti-scaling
5 Automatic Make-up Pump Diaphragm type; 1m³/h; 20m head Set 1 Automatic constant-pressure make-up
6 Water Quality Sensor Conductivity + pH combined; with temperature compensation Set 2 1 primary + 1 secondary side

6.6 Power Supply and Distribution System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Main Incoming Distribution Cabinet 380V 3-phase; 250A main breaker; branch breakers; surge protection; energy metering Set 1 Container main distribution
2 Online UPS Power Supply 20kVA; 3-phase in / single-phase out; double-conversion online Set 1 Monitoring & control power
3 Lead-Acid Battery Bank 12V/100Ah; valve-regulated sealed AGM pcs 16 15 min backup
4 Standard Battery Cabinet Fits 16 batteries; steel, powder-coated Set 1 —
5 Rack Power Supply Circuit YJV 3×6+1×4 cable + 32A breaker Circuit 8 Dedicated per rack
6 CDU Power Supply Circuit YJV 3×16+1×10 cable + 63A breaker Circuit 2 Dedicated per CDU
7 Auxiliary Power Supply Circuit BV 2.5mm² cable + 16A breaker Circuit 4 Lighting, sockets, etc.

6.7 Environment Monitoring and Intelligent Control System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Environment Monitoring Host Embedded industrial host; multi-protocol; Ethernet + 4G Set 1 Centralized monitoring management
2 Temperature Sensor PT100/NTC; accuracy ±0.1°C; RS485 output pcs 24 Piping, racks, compartment
3 Pressure Sensor 0–1.6MPa; accuracy ±0.25%FS; 4–20mA pcs 8 Main header supply/return
4 Electromagnetic Flow Meter DN100; accuracy ±0.5%; RS485 output pcs 2 Secondary side main loop
5 Level Sensor Capacitive type; high/low level alarm pcs 2 CDU expansion tanks
6 Locatable Leak Detection Cable Sensing accuracy ±1m; follows piping routing m 50 Along pipe run base
7 Access Control System Single-door controller; card + PIN; electromagnetic lock Set 1 Compartment door control
8 IR Dome Camera 2MP; night vision; PoE powered pcs 4 Full compartment coverage
9 Local Touchscreen Display 10-inch industrial touchscreen; local operation Set 1 Inside compartment
10 Audible & Visual Alarm DC24V; alarm linkage trigger pcs 2 1 inside + 1 outside
11 Signal Cables and Accessories Shielded cable, network cable, terminals, conduit Batch 1 Complete system wiring

6.8 Fire Protection and Safety System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Cabinet Type FM200 (HFC-227ea) Fire Suppression Unit 100L; pipeline-free / clean agent Set 2 Dual-zone protection
2 Photoelectric Smoke Detector 3C certified; DC24V pcs 6 Evenly distributed in compartment
3 Fixed-Temperature Heat Detector Fixed temp 70°C; 3C certified pcs 6 Linked with smoke detectors
4 Emergency Start/Stop Button With protective cover; manual discharge control pcs 2 1 inside + 1 outside
5 Discharge Indicator Light DC24V; fire suppression release indication pcs 1 Mounted outside door
6 Emergency Lighting Rechargeable; ≥90 min runtime on power loss Set 2 Fire emergency use

6.9 Auxiliary Support System

No. Equipment Name Specifications Unit Qty Remarks
— — — — — —
1 Cold Aisle Containment System Ceiling skylights + acrylic end doors; fire-linked Set 1 Encloses 8-rack row
2 Spare Quick-Connect Coupling DN20; 316 SS; male/female set Set 4 O&M spares
3 Dedicated Installation Tool Kit Leak detector, wrenches, instruments, consumables Set 1 On-site maintenance
4 System Identification Signage Pipe flow direction, equipment ID, safety warnings Set 1 Standardized labeling

—

7. Technical Specifications of Each System

7.1 Container Enclosure and Compartment Infrastructure

7.1.1 40ft High-Cube Container

Parameter Specification
— —
External Dimensions L12192mm × W2438mm × H2896mm
Internal Clear Dimensions L≈12032mm × W≈2280mm × H≈2680mm
Body Material Side/end panels: Q235B carbon structural steel, 2.0mm thickness; roof panel: 2.5mm; floor: 3mm checkered steel plate; bottom frame: No.12 channel steel welded; corner castings: standard ISO steel castings
Surface Treatment Full shot blasting to Sa2.5; epoxy zinc-rich primer + epoxy micaceous iron intermediate coat + acrylic polyurethane topcoat; total film thickness ≥120μm; corrosion resistance grade C4; outdoor service life ≥15 years
Insulation Structure Walls, roof, and floor filled with 50mm Class A fire-rated rockwool; density ≥120kg/m³; thermal conductivity ≤0.040W/(m·K); fire performance compliant with GB8624-2012 Class A; inner surface lined with 0.5mm galvanized steel sheet
Protection Rating Overall IP55 per GB4208-2017; door gaps and cable/pipe penetrations sealed with continuous EPDM rubber gaskets — no gaps, effective ingress protection against rain and dust
Load-Bearing Capacity Floor uniform load ≥1000kg/m²; local reinforcement in rack areas with point load ≥1500kg; CDU equipment area load ≥2000kg/m²
Wind & Seismic Resistance Withstands Category 12 typhoon (wind speed 32.7m/s) per GB50009; seismic intensity 8 degrees per GB50011
Fire Resistance Rating Wall fire resistance ≥2 hours, meeting Class A fire protection requirements
Pre-Engineered Openings Reserved penetrations for primary-side coolant supply/return, main power, low-voltage communications, and ventilation — all fitted with waterproof sealing glands

7.1.2 Internal Load-Bearing Base

  • Structure: No.12 hot-rolled channel steel welded grid framework; grid spacing 600mm × 600mm; covered with 3mm checkered steel plate.
  • Surface Treatment: Full hot-dip galvanizing; zinc coating ≥85μm.
  • Installation: Bolted to container floor; levelness deviation ≤2mm/m².
  • Load Capacity: Uniform load ≥1000kg/m²; concentrated load ≥5000kg/point.

7.1.3 Anti-Static Access Floor

  • Dimensions: 600mm × 600mm × 35mm; all-steel borderless construction.
  • System Resistance: 10⁶–10⁹Ω, compliant with GB/T 36340-2018 anti-static requirements.
  • Load Performance: Uniform load ≥1000kg/m²; concentrated load ≥300kg; ultimate load ≥900kg.
  • Surface Material: High-wear PVC anti-static surface, 1.5mm thickness; fire rating Class B1.
  • Support System: Galvanized steel pedestals, 300mm height, ±20mm adjustable; galvanized steel stringers for stable support.
  • Accessories: Includes pedestals, stringers, screws, perforated (vented) tiles, and cable-access tiles; 5% spare tiles supplied.

7.1.4 LED Lighting System

  • Fixture Type: LED flat panel cleanroom light, 40W.
  • Optical Performance: Color temperature 6500K cool white; CRI Ra≥80; illuminance ≥300 lux; uniformity ≥0.7.
  • Installation: Ceiling-mounted, evenly spaced along the aisle.
  • Emergency Lighting: 2 twin-head emergency luminaires, 3W per head; built-in Ni-Cd battery; auto-illumination on power failure; ≥90 minutes runtime; compliant with GB17945.

7.1.5 Steel Class A Fire Door

  • Dimensions: 900mm (W) × 2100mm (H), single-leaf.
  • Fire Resistance: 1.5 hours, compliant with GB12955-2008 Class A fire door standard; 3C certified.
  • Door Leaf Construction: Cold-rolled steel shell; filled with Class A perlite core, 50mm thick.
  • Hardware: Fire-rated hinges, door closer, emergency exit lock, smoke seals, and tempered glass observation window.
  • Surface Finish: Electrostatic powder coating, matte grey.

7.1.6 Residual Pressure Ventilation Device

  • Specification: 300mm × 300mm rectangular mechanical residual pressure valve.
  • Adjustment Range: Opening differential pressure 5–20Pa, continuously adjustable.
  • Function: Balances internal/external air pressure, prevents container deformation from negative pressure, and blocks external dust ingress.
  • Filter Configuration: G4-class primary dust filter, washable and replaceable.
  • Material: Galvanized steel body; aluminum alloy blades.

7.1.7 Equipotential Bonding System

  • Main Grounding Busbar: 40mm × 4mm copper busbar installed continuously along container perimeter.
  • Grounding Terminals: Independent grounding terminal reserved for every rack, device, cable tray, and pipeline.
  • Ground Resistance: System ground resistance ≤1Ω, compliant with GB50169.
  • Connection Method: Multi-strand yellow/green grounding cable with bolted connections for reliable contact.

7.2 IT Racks and Liquid Cooling Terminal Systems

7.2.1 Liquid-Cooled Server Rack

Parameter Specification
— —
Dimensions W600mm × D1200mm × H2000mm; 42U standard mounting space
Body Material SPCC high-quality cold-rolled steel; mounting rails 2.0mm; side panels 1.5mm; front/rear doors 1.2mm
Load Capacity Static load ≥1500kg; dynamic load ≥1000kg
Ventilation Design Front/rear perforated doors; opening ratio ≥70%; supports hybrid air + liquid cooling fallback
Internal Configuration 19-inch adjustable mounting rails; 4 pairs of cable managers; bottom liquid cooling pipe fixing brackets; top power/data cable troughs
Grounding System Independent rack grounding terminal with internal equipment grounding bus
Surface Finish Degreased, phosphated, electrostatic powder coated; matte black; film thickness 60–80μm; adhesion Class 1
Accessories Leveling casters, support feet, door locks, keys

7.2.2 Liquid Cooling Quick-Connect Coupling

Parameter Specification
— —
Specification DN20 (3/4 inch); male + female set
Body Material 316L stainless steel
Seal Material Nitrile rubber (NBR); compatible with propylene glycol coolant
Working Pressure Rated 1.6MPa; burst pressure ≥6.4MPa
Working Temperature -20°C to 120°C
Connection Type Compression fitting type, suitable for φ20 stainless steel tube
Core Features Integrated one-way self-sealing valve — automatic sealing on disconnection, leak-free; insertion/withdrawal force ≤50N; operating life ≥10,000 cycles
Applicable Standard GB/T 3765-2008 (Technical conditions for compression-type tube fittings)

7.2.3 Rack Branch Manifold

  • Specification: 1-in/1-out; DN20 ports.
  • Material: 304 stainless steel, integrally formed without welds.
  • Configuration: Supply side with manual flow regulating valve, graduated scale, adjustment range 0–100%; return side with reserved ports for PT100 temperature sensor and pressure gauge.
  • Installation: Wall-mounted at rear of rack with stainless steel mounting bracket.
  • Pressure Drop: ≤0.05MPa at rated flow.

7.2.4 Metering PDU

Parameter Specification
— —
Input 380V 3-phase 5-wire; 32A rated; IEC309 industrial connector
Output Outlets 24×C13 (10A) + 8×C19 (16A)
Metering Accuracy Voltage ±0.5%; current ±0.5%; power ±1%; energy ±1%
Display LCD display of real-time 3-phase voltage, current, active power, energy, temperature
Protection Independent breaker per circuit; overload & short-circuit protection; surge protection module, discharge capacity 10kA (8/20μs)
Communication RS485 interface; MODBUS-RTU protocol; integrates with environment monitoring system
Installation 0U vertical mount, rear rack mounting
Working Environment Temperature -10°C to 60°C; humidity 5%–95% non-condensing

7.3 CDU Coolant Distribution Unit System

7.3.1 CDU Complete Unit Parameters

Parameter Specification
— —
Model KITOZER-CDU-240
Rated Cooling Capacity 240kW (at primary side 12°C supply / 18°C return; secondary side 22°C supply / 15°C return)
Primary Side Rated flow 41.2m³/h; working pressure 1.6MPa; connection DN80 flanged
Secondary Side Rated flow 30m³/h; working pressure 1.0MPa; connection DN100 flanged
Power Supply 380V 3-phase 5-wire 50Hz; total power ≤7.5kW
Control PLC fully automatic control; 7-inch touchscreen HMI
Dimensions W1200mm × D800mm × H1800mm
Protection Rating IP31 (indoor installation)
Noise Level ≤65dB(A) @1m distance
Materials Powder-coated steel frame; 304/316 stainless steel wetted parts

7.3.2 Plate Heat Exchanger

Parameter Specification
— —
Type Gasketed (serviceable) plate heat exchanger
Plate Material 316L stainless steel, 0.5mm thickness
Seal Gaskets Nitrile rubber (NBR); compatible with propylene glycol coolant; adhesive-bonded type
Heat Transfer Area ≥18m²
Heat Transfer Coefficient ≥3000W/(m²·K)
Pressure Rating Design pressure 1.6MPa; hydrostatic test pressure 2.4MPa
Working Temperature -20°C to 150°C
Flow Channel Design Counter-current configuration for high thermal efficiency; wide-channel design resistant to clogging
Applicable Standard GB16409-1996 (Plate heat exchangers – Technical conditions)

7.3.3 Variable Frequency Circulating Pump

Parameter Specification
— —
Type Horizontal inline centrifugal pump
Quantity 2 per CDU (1 active + 1 standby, automatic failover)
Performance Rated flow 30m³/h; rated head 25m; rated power 4kW
Pump Materials 304 stainless steel pump body and impeller; silicon carbide (SiC-SiC) mechanical seal
Motor Three-phase asynchronous motor; IP55 protection; Class F insulation; bearing design life ≥50,000 hours
Variable Frequency Control Industrial VFD; 0–50Hz stepless speed regulation; automatic flow adjustment based on secondary-side return temperature; energy-saving operation
Start Method Soft start; starting current ≤ rated current; no hydraulic shock
Sealing Performance Leak-free mechanical seal, compatible with coolant media

7.3.4 Diaphragm Expansion Tank

  • Nominal Volume: 100L.
  • Type: Diaphragm type; butyl rubber diaphragm; complete air/liquid separation.
  • Working Pressure: Maximum 1.0MPa.
  • Pre-Charge Pressure: Factory pre-charged to 0.3MPa; field adjustable per system requirements.
  • Working Temperature: -10°C to 90°C.
  • Tank Material: Carbon steel body; internal epoxy anti-corrosion coating.
  • Connection: DN25 male threaded port.
  • Function: Absorbs coolant thermal expansion/contraction volume changes; maintains system pressure stability; compensates for minor system leakage.

7.3.5 Y-Type Precision Strainer

Parameter Specification
— —
Specification DN50; flanged connection
Body Material 304 stainless steel
Screen Material 316 stainless steel woven mesh
Filtration Accuracy 100μm
Pressure Rating 1.6MPa
Working Temperature ≤120°C
Blowdown Function DN15 drain valve at bottom for periodic blowdown
Quantity 1 on primary + 1 on secondary side per CDU (2 total per CDU)

7.3.6 Electric Proportional Control Valve

  • Specification: DN50; flanged connection.
  • Body Material: 304 stainless steel.
  • Trim Material: 304 stainless steel.
  • Seal Material: PTFE (polytetrafluoroethylene).
  • Actuator: Electric modulating actuator with 4–20mA control signal; stroke time ≤30s.
  • Flow Characteristics: Equal percentage; adjustable ratio 50:1.
  • Working Pressure: 1.6MPa.
  • Function: Modulates primary-side supply flow based on secondary-side return temperature to precisely regulate cooling capacity delivery.

—

[Note: The remaining sections — including the Primary/Secondary Side Piping System detailed specifications, Cooling Medium & Water Treatment Details, Power Supply & Distribution System Details, Environment Monitoring & Intelligent Control Details, Fire Protection & Safety System Details, Auxiliary Support System Details, Key Solution Advantages, Technical Q&A, Construction Schedule, Construction Organization Plan, After-Sales Service System, O&M Training Plan, Typical Engineering Case Studies, SEO Keyword System, Website Publishing Configuration, and Contact Information — are covered in subsequent chapters of this document.]

—