ToggleTechnical Design Proposal for the 40-Foot 5MWh/2.5MW Containerized Energy Storage System
Document Title: Technical Design Proposal for the 40-Foot 5MWh/2.5MW Containerized Energy Storage System
Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.
Brand: KITOZER
Version: V1.0
Date: August 2026
—
Table of Contents
- Company Profile
- Project Overview
- User Requirements Analysis
- Overall Design Description
- Product Configuration List
- Detailed Technical Parameters of Each System
- Core Advantages of the Solution
- Technical Q&A
- Project Construction Schedule
- Construction Organization Plan
- After-Sales Service System
- Personnel Training Plan
- Typical Engineering Cases
- SEO Optimization System & Website Backend Configuration
- Contact Information
—
1. Company Profile
Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise specializing in data center infrastructure, intelligent enclosure systems, and new-energy energy storage system R&D and manufacturing. Our core brand is KITOZER.
With over two decades of industry expertise, the company has developed advanced technologies in green, energy-efficient data center infrastructure and energy storage system integration. We deliver tailor-made solutions for diverse application scenarios and hold multiple product patents and industry qualifications. Our client base spans government agencies, industrial enterprises, telecommunications operators, and energy sector customers across China and international markets.
Main Products: Our comprehensive product portfolio includes modular cold-aisle containment systems, indoor integrated cabinets, outdoor intelligent enclosures, shielded rooms, containerized data centers, and containerized energy storage systems — covering the full spectrum of enclosure products and system integration solutions.
Manufacturing Capability: As a manufacturer, we offer flexible custom production with a complete service chain from solution design, manufacturing, and installation & commissioning to after-sales operation and maintenance. We uphold a commitment to quality as our core, distinctive design as our hallmark, and responsive after-sales support as our guarantee. Our project delivery model ensures on-time delivery and rapid service response.
Product Philosophy: The company adheres to the principles of “Safety, Efficiency, Innovation, and Pragmatism.” Leveraging years of accumulated technical expertise in enclosure structures, power distribution integration, environmental monitoring, and intelligent control, we have launched standardized and customizable containerized energy storage systems widely deployed in commercial and industrial (C&I) applications including peak-valley arbitrage, demand management, backup power, and renewable energy storage integration.
—
2. Project Overview
2.1 Project Background
Driven by carbon peak/neutrality goals and electricity market deregulation reforms, commercial and industrial users are facing multiple challenges: widening peak-valley electricity price differentials, high demand charges, and growing requirements for power supply reliability. Containerized energy storage systems have emerged as the mainstream form of user-side storage due to their factory prefabrication, rapid deployment, mobility and reusability, and proven safety and reliability.
This project addresses the user’s requirement for a 5MWh capacity / 2.5MW power application by employing a 40-foot standard high-cube container for high-density integration. The system integrates battery, power conversion, power distribution, monitoring, fire protection, and thermal management into a single, turnkey energy storage solution — meeting both cost-reduction/efficiency goals and power supply security objectives.
2.2 Construction Objectives
- Rated capacity of 5MWh, rated power of 2.5MW, supporting 2 hours of full-power discharge
- Establish a five-level safety protection architecture (cell → module → rack → system → enclosure), combining intrinsic safety with active protection
- Support multiple operating modes: grid-connected peak-valley arbitrage, demand management, reactive power compensation, and off-grid backup
- Factory prefabrication and integration for plug-and-play on-site deployment, significantly shortening construction lead time
- Dual remote + local monitoring for unattended operation with convenient O&M
2.3 Design Basis and Standards
| Standard No. | Standard Name |
| — | — |
| GB 51048 | Design Standard for Electrochemical Energy Storage Power Stations |
| GB/T 36276 | Lithium-ion Batteries for Electric Energy Storage |
| GB/T 34120 | Technical Requirements for Power Conversion System of Energy Storage |
| GB/T 42288 | Technical Requirements for Lithium-ion Battery Energy Storage Systems |
| GB 50054 | Code for Design of Low Voltage Electrical Installations |
| GB 50057 | Code for Design of Protection of Structures against Lightning |
| GB/T 1413 | Series 1 Freight Containers — Classification, Dimensions and Ratings |
—
3. User Requirements Analysis
3.1 Basic Functional Requirements
- Grid-connected charge/discharge supporting constant power, constant current, and constant voltage modes
- Rapid switching to off-grid mode during grid outage to supply critical loads
- Automatic load peak tracking and maximum demand smoothing to reduce basic electricity charges
- Four-quadrant operation with reactive power output capability for power factor correction
- Dual local touchscreen and remote cloud monitoring and management
3.2 Performance Specification Requirements
| Parameter | Requirement |
| — | — |
| System DC voltage level | 1500V (reduces line losses, improves efficiency) |
| PCS overall efficiency | ≥98.5% |
| System round-trip efficiency | ≥88% |
| Grid current THD | ≤3% |
| Battery cycle life | ≥6000 cycles (1C, 25°C, 80% SOH) |
| Grid/off-grid switching time | ≤20ms |
3.3 Safety Protection Requirements
- Multi-level electrical protection: fuses, circuit breakers, surge protection, insulation monitoring
- Multi-level battery protection: over-voltage, under-voltage, over-current, over-temperature, short-circuit protection
- Dedicated fire suppression system: early detection + clean agent extinguishing
- Enclosure protection rating: IP65 for all-weather outdoor operation
- Complete grounding and lightning protection system
3.4 Operation & Maintenance Management Requirements
- Real-time monitoring of all equipment operating status with graded fault alarms
- Automatic statistics of charge/discharge energy and electricity cost savings with operational reporting
- Remote parameter configuration, firmware upgrade, and fault diagnosis capability
- Multi-level user privilege management with auditable operation logs
3.5 Environmental Adaptability Requirements
| Parameter | Requirement |
| — | — |
| Ambient operating temperature | -20°C to +45°C |
| Corrosion protection | C4 grade (suitable for coastal and industrial zones) |
| Seismic resistance | Intensity 8 |
| Wind resistance | Grade 12 |
| Protection | Dust-proof, rain-proof, salt-spray resistant |
—
4. Overall Design Description
4.1 Design Principles
| Principle | Description |
| — | — |
| Safety First | Multi-layer protection from cell to enclosure, comprehensive coverage of electrical, fire, and structural safety |
| Reliability Priority | Core components from proven brands with design margins on critical parameters |
| High Efficiency | 1500V high-voltage architecture + high-efficiency PCS + intelligent thermal management for minimal energy loss |
| Intelligent & Advanced | EMS intelligent dispatch with multi-mode automatic switching and cloud-based O&M support |
| Economical & Practical | Optimized space utilization, reduced initial investment and lifecycle cost |
| Scalable | Supports multi-unit parallel expansion; can integrate PV and EV chargers to build microgrids |
4.2 System Architecture
The system adopts a three-layer architecture:
- Equipment Layer: Battery modules, PCS, power distribution cabinets, fire protection, thermal management, and sensors as underlying devices
- Control Layer: BMS, PCS controller, fire alarm controller, thermal management controller, and environmental data acquisition unit
- Management Layer: EMS energy management system, local touchscreen HMI, and remote cloud platform
External interfaces connect the system to the utility grid through the grid-connection point and to the user’s monitoring system via communication interfaces.
4.3 Container Internal Layout
The 40-foot standard high-cube container is divided into two fire-separated zones: the battery compartment and the electrical compartment.
Battery Compartment: Occupying approximately 70% of the interior space, it houses 12 battery racks arranged in double rows, each containing 30 modules, for a total of 360 modules. The compartment is equipped with air ducts, fire suppression nozzles, temperature/smoke detectors, and water immersion sensors.
Electrical Compartment: Located at the end of the container, it integrates the DC busbar cabinet, PCS, AC distribution cabinet, EMS control cabinet, fire alarm host, and auxiliary power distribution unit.
The container end features Class-A fire-rated double doors. Side walls are fitted with emergency escape windows and ventilation louvers. The floor base is equipped with waterproof cable glands for cable entry.
4.4 Technology Route Selection
| Subsystem | Selected Technology | Key Advantages |
| — | — | — |
| Battery | Lithium iron phosphate (LFP) cells, 1500V DC system | High safety, long cycle life, superior cost-effectiveness |
| Power Conversion | Centralized 2.5MW PCS, three-level topology | High efficiency, mature control, easy maintenance |
| Thermal Management | Industrial precision air conditioning + balanced airflow duct cooling | Cell temperature differential ≤5°C, high reliability, no leakage risk |
| Fire Suppression | Triple detection (smoke + heat + combustible gas) + perfluorohexanone (Novec 1230) piped extinguishing system | Clean, residue-free, specifically suited for lithium battery fires |
4.5 Operating Modes
| Mode | Description |
| — | — |
| Peak-Valley Arbitrage | Charge during off-peak hours, discharge during peak hours with automatic tariff schedule execution |
| Demand Management | Real-time load tracking, automatic discharge to shave peaks when threshold exceeded |
| Backup Power | Automatic transfer to off-grid mode upon grid failure, constant voltage/frequency supply |
| Reactive Power Compensation | STATCOM mode for power factor improvement |
| Demand Response | Receives grid dispatch commands for peak shaving and frequency regulation |
| Manual Maintenance | Step-by-step manual operation during inspection and commissioning |
—
5. Product Configuration List
5.1 Battery Energy Storage DC System
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | LFP energy storage battery module | 51.2V/280Ah, 16S1P, 14.336kWh | pcs | 360 | 30 in series/rack, 12 racks total |
| 2 | Rack-level battery cluster management unit (BCU) | 30-series management, voltage/current/temperature acquisition, active balancing | set | 12 | 1 per rack |
| 3 | Battery array management system (BAMS) | 12-cluster management, SOC/SOH estimation, coordinated with EMS/fire protection | set | 1 | System-level BMS |
| 4 | Vertical battery mounting rack | Cold-rolled steel, powder-coated, 10 tiers, insulated support, load capacity ≥3.5 tons | set | 12 | Double-row arrangement |
| 5 | DC cluster-level fuse | 1500V DC, 315A, high breaking capacity | pcs | 12 | 1 on positive terminal of each cluster |
| 6 | DC manual isolating switch | 1500V DC, 400A, with visible disconnection point | pcs | 12 | For maintenance isolation |
| 7 | DC busbar cabinet | 12-in 1-out, main circuit breaker, insulation monitoring, voltage/current acquisition | set | 1 | DC main busbar |
5.2 Power Conversion System & AC/DC Distribution System
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Centralized energy storage PCS | 2.5MW, DC 1000~1700V, AC 400V, grid-connected/off-grid dual mode | set | 1 | Three-level topology |
| 2 | AC main incoming circuit breaker | 4P, 4000A, intelligent trip unit, shunt trip + auxiliary contacts | pcs | 1 | AC main protection |
| 3 | Grid-connected AC contactor | AC 400V, 4000A, with auxiliary contacts | pcs | 1 | Grid-connection interlock |
| 4 | AC surge protective device | 3P+N, Type 1 lightning protection, 100kA | set | 1 | Lightning surge protection |
| 5 | Bi-directional smart energy meter | Three-phase four-wire, 0.5S class, RS485 communication | pcs | 1 | Charge/discharge metering |
| 6 | Auxiliary distribution transformer | 10kVA, 400V/220V, single-phase isolation | pcs | 1 | Auxiliary equipment power |
| 7 | Miniature circuit breakers | 1P/2P, 10A/16A/32A, C-curve | pcs | 20 | Branch circuit protection |
5.3 Energy Management & Environmental Monitoring System
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Energy storage EMS controller | Industrial embedded, charge/discharge scheduling, multi-system coordination | set | 1 | System brain |
| 2 | Industrial touchscreen HMI | 15-inch, capacitive touch, flush-mount | pcs | 1 | Local human-machine interface |
| 3 | Environmental monitoring acquisition unit | Multi-signal input, RS485 communication, DC 24V | pcs | 1 | Environmental data aggregation |
| 4 | Temperature/humidity sensors | -20~80°C, 0~100%RH, RS485 | pcs | 6 | 4 in battery compartment, 2 in electrical compartment |
| 5 | Water immersion sensors | Electrode type, digital output, IP67 | pcs | 4 | Four corners of compartment floor |
| 6 | Door magnetic switches | Magnetic induction, digital output | pcs | 2 | 1 per door |
| 7 | 4G remote communication module | Full-network compatible, external antenna | set | 1 | Cloud connectivity |
| 8 | Industrial Ethernet switch | 8-port gigabit, DIN-rail mount, DC 24V | pcs | 1 | Internal network |
5.4 Energy Storage Dedicated Fire Suppression System
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Perfluorohexanone (Novec 1230) piped extinguishing system | 50kg per cylinder, piped network + nozzle full coverage | set | 2 | Battery compartment zoned suppression |
| 2 | Fire alarm controller | Addressable loop type, multi-zone, relay outputs | pcs | 1 | Fire protection master control |
| 3 | Photoelectric smoke detectors | DC 24V, addressable type | pcs | 12 | Evenly distributed on compartment ceiling |
| 4 | Heat detectors | Fixed temperature 70°C, addressable type | pcs | 12 | Paired with smoke detectors |
| 5 | Combustible gas detectors | Detects H₂/CO, RS485 + digital output | pcs | 6 | Battery compartment floor area |
| 6 | Audible-visual alarm | DC 24V, ≥110dB | pcs | 2 | 1 inside, 1 outside container |
| 7 | Emergency start/stop buttons | With protective cover, manual trigger | pcs | 2 | Both sides outside container |
| 8 | Mechanical pressure relief vents | Opens at 0.1MPa, 300×300mm | pcs | 2 | Balances compartment pressure |
5.5 Thermal Management & Ventilation System
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Industrial precision air conditioner | Cooling capacity 12kW, heating/cooling combined, RS485 communication | pcs | 4 | 2 in battery compartment, 2 in electrical compartment |
| 2 | Axial exhaust fans | Airflow 5000m³/h, static pressure 150Pa, IP54 | pcs | 4 | Emergency ventilation |
| 3 | Intake louvers | Aluminum alloy, insect mesh + dust filter media | pcs | 4 | Side wall air intake |
| 4 | Motorized fire dampers | 70°C fusible link closure, fire alarm interlock | pcs | 4 | Ventilation circuit isolation |
| 5 | Airflow distribution ducting | Galvanized steel, custom design, adjustable air outlets | set | 2 | Battery compartment temperature equalization |
| 6 | Auxiliary electric heaters | 2kW, PTC type, dual over-temperature protection | pcs | 4 | Low-temperature heating |
5.6 40-Foot Container Enclosure System
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | 40-foot standard high-cube container | External 12192×2438×2896mm, rock-wool insulation, IP65 | pcs | 1 | Primary load-bearing structure |
| 2 | Class-A fire-rated double door | 1800×2100mm, door closer + escape lock + observation window | set | 1 | End main entrance |
| 3 | Emergency escape windows | 600×800mm, tempered glass, breakable from inside | pcs | 2 | Symmetrical on side walls |
| 4 | Anti-slip load-bearing floor | 3mm checkered steel plate, anti-corrosion, uniformly distributed load ≥10kN/m² | set | 1 | Equipment support |
| 5 | Outdoor weather-resistant anti-corrosion coating | Epoxy zinc-rich primer + polyurethane topcoat, salt spray ≥1000h | set | 1 | C4 grade corrosion protection |
| 6 | Safety warning and signage system | Nameplates, warnings, circuit labels, operating instructions | set | 1 | O&M identification |
5.7 Cables, Conduits & Auxiliary Materials
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Intra-cluster power cables | 120mm² silicone rubber cable, 1500V DC | m | 600 | Module interconnection |
| 2 | DC main cables | 240mm² flame-retardant armored, 1500V DC | m | 200 | Cluster to busbar cabinet/PCS |
| 3 | AC grid-connection cables | 4×240+1×120mm², 0.6/1kV flame-retardant | m | 100 | PCS to grid-connection point |
| 4 | Communication shielded cables | RVSP 2×1.5mm², twisted pair shielded | m | 800 | Signal communication |
| 5 | Auxiliary power cables | RVV 3×2.5, 2×1.5mm² | m | 500 | Auxiliary equipment power |
| 6 | Hot-dip galvanized conduit | DN20/25/50, with fittings | m | 400 | Cable protection |
| 7 | Waterproof cable glands | PG9/16/21/42, metal, IP67 | pcs | 80 | Container cable entry sealing |
| 8 | Copper cable lugs | OT/UT type, 1.5~240mm², tin-plated | pcs | 600 | Cable termination |
| 9 | Busbar connection assembly | T2 copper, tin-plated, with insulating supports | set | 1 | Main circuit busbar |
5.8 Mounting, Fixing & Grounding Accessories
| No. | Equipment | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Fixing bolt kits | M8~M16, galvanized expansion + hex socket | set | 300 | Equipment mounting |
| 2 | Flame-retardant nylon cable ties | 4×200/8×300/10×400, weather-resistant black | pack | 20 | Cable bundling |
| 3 | Insulation protection materials | Electrical tape, heat-shrink tubing, insulating barriers | batch | 2 | Insulation protection |
| 4 | Equipment identification plates | Acrylic, engraved name and number | pcs | 100 | O&M identification |
| 5 | Main grounding flat bar | 40×4mm, hot-dip galvanized | m | 50 | Ring grounding busbar |
| 6 | Protective grounding cables | BVR 16/6mm², yellow-green | m | 200 | Equipment equipotential grounding |
| 7 | LED interior lighting | 20W panel light, door-activated switch | set | 4 | Compartment lighting |
| 8 | Maintenance power outlets | 10A 5-hole waterproof, AC 220V | pcs | 4 | Temporary power for maintenance |
—
6. Detailed Technical Parameters of Each System
6.1 Battery Energy Storage DC System
6.1.1 Lithium Iron Phosphate Energy Storage Battery Module
Cell Parameters:
| Parameter | Specification |
| — | — |
| Cathode material | Lithium iron phosphate (olivine structure), thermal stability ≥700°C |
| Anode material | Synthetic graphite, high lithium intercalation capacity, stable cycling |
| Separator | PP/PE composite microporous membrane, 130°C shutdown protection |
| Electrolyte | Carbonate system + flame-retardant additives |
| Cell nominal voltage | 3.2V |
| Cell rated capacity | 280Ah |
| Cell energy density | ≥165Wh/kg |
| Cycle life | ≥6000 cycles (1C charge/discharge, 25°C, 80% residual capacity) |
Module Electrical Parameters:
| Parameter | Specification |
| — | — |
| Series/parallel configuration | 16S1P |
| Nominal voltage | 51.2V |
| Rated capacity | 280Ah |
| Rated energy | 14.336kWh |
| Operating voltage range | 43.2V ~ 57.6V |
| Max continuous charge/discharge current | 1C (280A) |
| Peak discharge current | 1.5C / 30s |
| DC internal resistance | ≤8mΩ |
| Insulation resistance | ≥100MΩ (at DC 1000V) |
Mechanical & Environmental:
| Parameter | Specification |
| — | — |
| Enclosure | Cold-rolled steel plate, powder-coated, IP20 |
| Dimensions | Approx. 700×450×180mm |
| Weight | Approx. 110kg |
| Operating temperature | Charging: -10°C~55°C; Discharging: -20°C~60°C |
| Storage temperature | -40°C~60°C |
| Altitude | ≤2000m (derated above this altitude) |
Safety Features:
- Passes nail penetration, crush, overcharge, short-circuit, and hot-box safety tests
- Built-in voltage and temperature acquisition wiring harness with real-time BMS monitoring
- Flame-retardant enclosure and structural design to delay thermal propagation
6.1.2 Battery Cluster Management Unit (BCU)
| Parameter | Specification |
| — | — |
| Series management capacity | Max 32 series (30 series in this configuration) |
| Voltage acquisition accuracy | ±5mV |
| Temperature acquisition | 16 NTC channels, accuracy ±0.5°C |
| Current acquisition | Hall sensor, range ±500A, accuracy ±0.5% FS |
| Insulation monitoring | 0~10MΩ, accuracy ±10% |
| SOC estimation | Coulomb counting + OCV correction, steady-state accuracy ≤±3% |
| Balancing function | Active balancing, balancing current ≥5A |
| Protection logic | Three-level protection: alarm → current limiting → shutdown |
| Communication interfaces | 2× CAN, 1× RS485 |
| Power supply | DC 9~36V wide range, power consumption ≤10W |
| Operating temperature | -40°C~85°C |
| Mounting | DIN-rail, mounted at top of battery rack |
6.1.3 Battery Array Management System (BAMS)
| Parameter | Specification |
| — | — |
| Cluster management capacity | Max 24 clusters (12 clusters in this configuration) |
| Core functions | Full-system data aggregation, system-level SOC/SOH estimation, charge/discharge power control, graded fault handling, thermal runaway early warning, coordinated fire protection and thermal management |
| Protection functions | System over/under-voltage, total over-current, insulation fault, excessive temperature differential |
| Communication interfaces | CAN, RS485, Ethernet; supports Modbus, IEC 104 protocols |
| Data storage | Local storage ≥1 year of operational and fault records |
| Power supply | DC 24V±10%, power consumption ≤30W |
| Operating temperature | -20°C~70°C |
| Mounting | Rack-mount, integrated in control cabinet |
| MTBF | ≥100,000 hours |
6.1.4 Vertical Battery Mounting Rack
| Parameter | Specification |
| — | — |
| Material | Q235 high-quality structural steel, integrally welded + bolted |
| Structure | 10 tiers, 3 modules per tier, 30 modules per rack |
| Load capacity | ≥3500kg per rack, safety factor ≥1.5 |
| Insulation | High-strength insulated base plate on each tier, module-to-rack insulation ≥100MΩ |
| Anti-fall | Limit stop bars and hold-down clamps on each tier |
| Cable routing | Segregated power/signal cable troughs with fixing points |
| Surface treatment | Pickling + phosphating + electrostatic powder coating, C4 corrosion protection |
| Dimensions | Approx. 750×800×2200mm (W×D×H) |
6.1.5 DC Cluster-Level Fuse
| Parameter | Specification |
| — | — |
| Rated voltage | 1500V DC |
| Rated current | 315A |
| Breaking capacity | ≥50kA |
| Characteristic | gPV general-purpose photovoltaic fuse characteristic |
| Base material | High-temperature flame-retardant, V0 grade |
| Connection | Bolted compression |
| Operating temperature | -40°C~125°C |
| Standards | GB/T 13539, IEC 60269 |
| Function | Cluster-level short-circuit protection, isolates faulty cluster to prevent propagation |
6.1.6 DC Manual Isolating Switch
| Parameter | Specification |
| — | — |
| Rated voltage | 1500V DC |
| Rated current | 400A |
| Poles | 1P |
| Breaking capacity | Capable of load-breaking |
| Operation | Manual handle, visible disconnection point, lockable |
| Mechanical life | ≥10,000 operations |
| Protection rating | IP20 (inside cabinet) |
| Function | Maintenance isolation for personnel safety |
6.1.7 DC Busbar Cabinet
| Parameter | Specification |
| — | — |
| Rated voltage | 1500V DC |
| Circuits | 12 inputs, 1 output |
| Main circuit breaker | 4000A DC molded-case, overload and short-circuit protection |
| Insulation monitoring | Continuous online monitoring of ground insulation resistance, alarm on anomaly |
| Instrumentation | High-precision voltage and current sensors, power and energy calculation |
| Surge protection | Built-in Type 2 DC surge protective device |
| Enclosure | Cold-rolled steel 2.0mm, electrostatic powder coating, IP20 |
| Display | Cabinet door touchscreen showing voltage, current, insulation, and branch status |
| Accessories | Lighting, maintenance outlet, terminal blocks |
| Dimensions | Approx. 800×600×2200mm (W×D×H) |
| Mounting | Floor-standing, fixed installation |
—
6.2 Power Conversion System & AC/DC Distribution System
6.2.1 Centralized Energy Storage PCS
Main Circuit Parameters:
| Parameter | Specification |
| — | — |
| Rated power | 2.5MW |
| DC side | Voltage 1000~1700V, max current 1670A |
| AC side | Voltage 400V±15%, frequency 50Hz±0.5Hz, current 3608A |
| Power factor | -0.95~+0.95 continuously adjustable |
| Current THD | ≤3% (at rated power) |
Performance Specifications:
| Parameter | Specification |
| — | — |
| Maximum efficiency | ≥98.5% |
| European efficiency | ≥98.0% |
| Dynamic response | ≤10ms |
| Grid/off-grid switching | ≤20ms |
| Noise | ≤75dB @ 1m |
Functional Features:
- Grid-connected mode: Constant power, constant current, constant voltage charging, reactive power compensation, primary frequency regulation, low voltage ride-through
- Off-grid mode: V/f control, unbalanced load capability, non-linear load support
- Black start: Independent voltage establishment without grid
- Anti-islanding protection: Active + passive detection with rapid grid disconnection
- Protection functions: DC over/under-voltage, reverse polarity, insulation fault; AC over/under-voltage, over/under-frequency, short-circuit, ground fault; equipment over-temperature, overload, and fan fault protection
Control & Communication:
| Parameter | Specification |
| — | — |
| Topology | Three-level NPC topology |
| Control | DSP + FPGA all-digital control |
| Interfaces | RS485, CAN, Ethernet, fiber optic |
| Protocols | Modbus, IEC 61850, etc. |
| HMI | 10-inch color touchscreen for local parameter setting and status monitoring |
Mechanical & Environmental:
| Parameter | Specification |
| — | — |
| Cooling | Forced air cooling with intelligent variable-speed fans |
| Structure | Cabinet modular design, pluggable power units |
| Protection rating | IP20 |
| Operating temperature | -20°C~50°C |
| Storage temperature | -40°C~70°C |
| Humidity | 5%~95% non-condensing |
| Dimensions | Approx. 1200×1000×2200mm |
| Weight | Approx. 2500kg |
| Certification standards | GB/T 34120, GB/T 19964, IEC 62116 — meets grid-connection requirements |
6.2.2 AC Main Incoming Circuit Breaker
| Parameter | Specification |
| — | — |
| Type | Air circuit breaker (ACB) |
| Rated voltage | AC 400V |
| Rated current | 4000A |
| Poles | 4P |
| Breaking capacity | Rated short-circuit breaking capacity ≥65kA |
| Trip unit | Intelligent electronic trip unit: long delay + short delay + instantaneous + ground fault |
| Accessories | Shunt trip coil, auxiliary contacts, alarm contacts |
| Operation | Motor-operated stored-energy closing, manual opening, remote opening capability |
| Mounting | Fixed type |
| Standards | GB 14048.2, IEC 60947-2 |
6.2.3 Grid-Connected AC Contactor
| Parameter | Specification |
| — | — |
| Rated voltage | AC 400V |
| Rated current | 4000A |
| Poles | 3P |
| Coil voltage | AC 220V |
| Auxiliary contacts | 4 NO + 4 NC |
| Mechanical life | ≥1,000,000 operations |
| Electrical life | ≥100,000 operations |
| Function | Grid-connection circuit switching, coordinated with anti-islanding protection |
6.2.4 AC Surge Protective Device
| Parameter | Specification |
| — | — |
| Type | Type 1 power SPD |
| Voltage | AC 380/400V |
| Poles | 3P+N |
| Nominal discharge current (In) | 100kA (8/20μs) |
| Max discharge current (Imax) | 200kA |
| Voltage protection level (Up) | ≤2.5kV |
| Response time | ≤25ns |
| Failure indication | Red/green window indicator with remote signaling contact |
| Disconnection | Thermal + overcurrent trip, automatic disconnection on fault |
| Mounting | DIN-rail |
| Standards | GB 18802.1, IEC 61643-11 |
6.2.5 Bi-Directional Smart Energy Meter
| Parameter | Specification |
| — | — |
| Type | Three-phase four-wire multifunction energy meter |
| Accuracy | Active energy: Class 0.5S; Reactive energy: Class 2 |
| Rated voltage | 3×220/380V |
| Rated current | 1.5(6)A, with current transformers |
| Frequency | 50Hz |
| Metering functions | Forward/reverse active energy, four-quadrant reactive energy, demand, multi-tariff time-of-use metering |
| Measurement | Voltage, current, power, power factor, frequency, harmonics |
| Communication | RS485 interface, supports DL/T645 and Modbus protocols |
| Display | LCD cyclic display |
| Pulse output | Active/reactive energy pulses for verification |
| Power supply | AC 85~265V wide range |
| Power consumption | ≤2W |
| Mounting | DIN-rail |
6.2.6 Auxiliary Distribution Transformer
| Parameter | Specification |
| — | — |
| Capacity | 10kVA |
| Phases | Single-phase |
| Input | AC 400V |
| Output | AC 220V |
| Insulation class | Class F |
| Efficiency | ≥95% |
| Cooling | Natural air cooling |
| Protection rating | IP20 |
| Windings | All-copper windings |
| Function | Provides isolated power to auxiliary equipment, improves anti-interference capability |
6.2.7 Auxiliary Circuit Miniature Circuit Breakers
| Parameter | Specification |
| — | — |
| Type | Miniature circuit breaker (MCB) |
| Voltage | AC 230/400V |
| Current ratings | 10A, 16A, 32A |
| Poles | 1P, 2P |
| Trip characteristic | C-curve |
| Breaking capacity | 6kA |
| Mechanical life | ≥20,000 operations |
| Mounting | DIN-rail |
| Standards | GB 10963, IEC 60898 |
| Application | Branch circuit protection for thermal management, fire protection, monitoring, lighting, and outlets |
—
6.3 Energy Management & Environmental Monitoring System
6.3.1 Energy Storage EMS Controller
Hardware Platform:
| Parameter | Specification |
| — | — |
| Processor | Industrial-grade ARM multi-core, clock frequency ≥1.5GHz |
| Memory | DDR4 ≥2GB |
| Storage | eMMC ≥32GB, SD card expansion supported |
| Power supply | DC 24V±15%, power consumption ≤20W |
| Operating temperature | -40°C~85°C |
| Mounting | DIN-rail / rack-mount |
| MTBF | ≥100,000 hours |
Interface Configuration:
| Interface | Specification |
| — | — |
| Ethernet | 4× Gigabit ports |
| Serial ports | 4× RS485/232 (configurable) |
| Digital inputs | 8× DI, dry contacts |
| Relay outputs | 4× DO |
| 4G | Built-in full-network cellular module |
| GPS/BeiDou | Optional time synchronization and positioning |
Core Functions:
| Function | Description |
| — | — |
| Data acquisition & monitoring | Unified collection of all data from BMS, PCS, energy meter, thermal management, fire protection, and environmental sensors; real-time display and historical storage |
| Charge/discharge scheduling | Built-in peak-valley arbitrage, demand management, backup power, and demand response strategies with automatic scheduled execution; custom strategy programming supported |
| Multi-system coordination | Coordinates BMS power limiting, PCS power output, thermal management start/stop, and fire protection interlock |
| Alarm management | Three-level alarms (advisory, major, critical); multiple notification channels including local audible-visual, SMS, APP, and email; full alarm history traceability |
| Statistical analysis | Automatic daily/monthly/annual reporting; charge/discharge energy, electricity cost savings, depth of discharge, and cycle count statistics |
| Access control | Multi-level privileges for administrator, operator, and guest; operation log recording |
| Remote O&M | Remote parameter configuration, firmware upgrade, and fault diagnosis |
Software & Protocols:
| Item | Specification |
| — | — |
| Operating system | Embedded Linux |
| Northbound protocols | MQTT, HTTP, Modbus TCP, IEC 104 |
| Southbound protocols | Modbus RTU, CAN, proprietary protocols |
6.3.2 Industrial Touchscreen HMI
| Parameter | Specification |
| — | — |
| Screen size | 15 inches |
| Type | TFT true-color capacitive touch |
| Resolution | 1024×768 |
| Color depth | 16.7 million colors |
| Brightness | 300 cd/m² |
| Processor | Industrial-grade ARM |
| Memory | 512MB DDR3 + 512MB Flash |
| Interfaces | 2× RS485, 1× Ethernet, 1× USB |
| Power supply | DC 24V, power consumption ≤15W |
| Operating temperature | -20°C~70°C |
| Protection rating | Front panel IP65 |
| Mounting | Flush-mount in cabinet door |
| Functions | Local status display, parameter setting, manual control, fault inquiry |
6.3.3 Environmental Monitoring Acquisition Unit
| Parameter | Specification |
| — | — |
| Processor | 32-bit ARM |
| Analog inputs | 8× 4-20mA / 0-10V, 12-bit ADC |
| Digital inputs | 16× DI |
| Relay outputs | 8× DO |
| Communication | 2× RS485, 1× Ethernet |
| Protocol | Modbus RTU/TCP |
| Power supply | DC 24V, power consumption ≤10W |
| Operating temperature | -40°C~85°C |
| Mounting | DIN-rail |
| Function | Aggregates temperature, humidity, water immersion, door status and other environmental signals for upload to EMS |
6.3.4 In-Cabinet Temperature/Humidity Sensors
| Parameter | Specification |
| — | — |
| Temperature range | -20°C~+80°C |
| Temperature accuracy | ±0.5°C @ 25°C |
| Humidity range | 0%~100% RH |
| Humidity accuracy | ±3% RH @ 25°C |
| Output | RS485 digital, Modbus protocol |
| Power supply | DC 12~24V |
| Power consumption | ≤1W |
| Response time | Temperature ≤10s; Humidity ≤15s |
| Enclosure | ABS, IP30 |
| Mounting | Wall-mount / ceiling-mount |