The KITOZER tinned copper grounding bar is the central bonding point in a data center or switchgear room, collecting grounding conductors from racks, cabinets, SPD, and steel structure and bonding them to the site earth electrode. Tinning prevents oxidation in humid environments and ensures long term low resistance.
Technical Specifications
Copper bar 40 mm by 5 mm, tin plated. Rating 400 A continuous. Threaded studs M8 and M10 on 25 mm pitch. Length 500 mm standard. Insulated support brackets included. Contact resistance under 0.003 ohm. Operating -20 to 80 degrees C.
Applications
Typical uses include data center grounding network, switchgear room bonding, lightning protection equipotential bonding, and telecom shelter ground distribution.
Key Advantages
Tinned surface resists oxidation. Multiple studs accept many conductors. Insulated brackets isolate from steel. Low contact resistance ensures bonding. Five-year warranty.
Installation And Maintenance
Mount the bar on insulated brackets on the wall. Connect each rack ground conductor with crimped lugs. Bond the bar to the earth electrode with 95 mm2 copper. Measure earth resistance annually, target under 1 ohm.