1. Cover / Document Information

– Document Title: 30㎡×3m Class B Electromagnetic Shielding Computer Room Technical Design Solution

– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Date: August 2026

– Version: V1.0

– Project Type: New construction of a Class B electromagnetic shielding computer room

– Scope: Shielding enclosure, shielding doors and windows, ventilation waveguides, power filtering, signal filtering, grounding and equipotential bonding, interior decoration, fire protection and access control

2. Table of Contents Structure

1. Company Introduction

2. Project Overview

3. User Requirement Analysis

4. Overall Design Description

5. Detailed System Design and Product Technical Parameters

6. Project Quotation and Configuration List

7. Core Solution Advantages

8. Technical Q&A

9. Construction Schedule Plan

10. Construction Organization Plan

11. After-Sales Service System

12. Operation and Maintenance Training Plan

13. Typical Project Cases

14. SEO Optimization System and Website Backend Configuration

15. Contact Information

3. Company Introduction

3.1 Company Development Overview

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. has been deeply engaged in the computer room construction and intelligent protection field for more than two decades. The company is a professional total computer room solution service provider integrating R&D, production, sales, engineering implementation and after-sales service. Since its establishment, the company has focused on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has gradually grown into a source manufacturer with core competitiveness in the domestic computer room construction field.

After more than twenty years of industry accumulation and technical expertise, the company has built a large-scale production and manufacturing base, equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and a professional shielding performance testing laboratory, with an annual production capacity of hundreds of sets of various shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields, and has gained wide market recognition for its stable product performance and reliable engineering quality.

3.2 Core Business System

The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:

– Computer room EPC general contracting service: one-stop computer room construction services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering new construction and renovation of electromagnetic shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;

– Core computer room equipment R&D and production: independently produces KITOZER brand series products, including various electromagnetic shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization according to customer requirements;

– Computer room environmental monitoring system: provides full-element environmental monitoring solutions for computer room temperature and humidity, water leakage, access control, video, fire protection, UPS, power distribution, etc., realizing intelligent and unattended operation and maintenance;

– Shielding and security protection products: provides electromagnetic shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military, scientific research and other fields.

3.3 Brand and Qualification Honors

The company’s core brand KITOZER (Pioneer) focuses on the computer room equipment and shielding product field, positioned as an “efficient, green, innovative and safe” computer room solution provider. Products have passed multiple authoritative tests and comply with national and industry standards.

The company always attaches importance to technological R&D and intellectual property accumulation, holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and has established a sound quality management system. All products and projects strictly follow the ISO9001 quality management standard.

3.4 Core Competitive Advantages

1. Source production, controllable quality: the company owns its production base and professional processing equipment; core products are independently produced with full-process quality control from raw material procurement to finished product delivery, ensuring stable and reliable product performance while eliminating intermediate links to provide customers with more cost-effective solutions;

2. Customized design, matching needs: tailor-made exclusive computer room solutions can be provided according to the customer’s site conditions, shielding level requirements, equipment configuration, budget range and other actual conditions, with three different design solutions provided free of charge for selection;

3. Professional team, rich experience: a professional technical team composed of electromagnetic shielding engineers, electromechanical engineers, decoration engineers and project managers, with core members having more than ten years of industry experience;

4. Quality after-sales, full guarantee: a 7×24 professional online service system, with dedicated personnel following up each project from early coordination, construction management to later operation and maintenance.

4. Project Background and Objectives

4.1 Project Construction Background

With the rapid development of information technology, various electronic information devices are increasingly widely used, and electromagnetic information leakage and electromagnetic interference issues have attracted more and more attention. For scenarios involving confidential information processing and precision electronic equipment operation, ordinary computer rooms cannot meet electromagnetic protection requirements, and risks such as information leakage and equipment malfunction caused by electromagnetic interference may occur. Therefore, building a professional electromagnetic shielding computer room has become a necessary security protection measure.

This project addresses the customer’s actual usage needs by building a Class B confidential-standard electromagnetic shielding computer room. Through a six-sided shielding enclosure and supporting filtering and grounding systems, a closed electromagnetic protection space is constructed, which can not only prevent electromagnetic signals of internal confidential equipment from leaking outward, but also block external complex electromagnetic environment interference on internal equipment, ensuring information security and stable equipment operation.

4.2 Project Basic Overview

This project is a newly constructed electromagnetic shielding computer room project. The indoor net area of the computer room is about 30㎡, the indoor net height is 3.0m, and the computer room is designed in a conventional rectangular shape (reference dimensions: length 6m × width 5m × height 3m). The construction content includes the complete system set of shielding main structure, shielding doors and windows, ventilation waveguides, power filtering, signal filtering, grounding and equipotential bonding, interior decoration, fire protection and security, which can meet Class B electromagnetic shielding performance requirements after completion while providing a standardized computer room operating environment.

4.3 Core Construction Objectives

– Electromagnetic protection objective: the overall shielding performance of the computer room reaches the Class B confidential shielding standard, meeting the corresponding shielding effectiveness indicators in the full frequency band of 14kHz~40GHz, effectively suppressing electromagnetic leakage and external electromagnetic interference;

– Environment adaptation objective: the internal environment of the computer room meets electronic equipment operation requirements, with illumination, temperature and humidity, cleanliness, anti-static and other indicators complying with national computer room design specifications, providing a stable and reliable operating space for equipment;

– Complete function objective: complete power distribution, signal transmission, fire protection and access control systems are provided to meet all functional needs of daily computer room use, and all wall-penetrating pipelines are treated with standardized shielding without damaging the overall shielding performance;

– Safe and reliable objective: the overall structure is safe and stable, with fire protection, grounding, electrical safety and other indicators complying with national specifications; the system operates stably with a long service life and convenient maintenance;

– Standardized acceptance objective: the project construction complies with relevant process standards, and after completion can pass third-party authoritative shielding effectiveness testing, with complete engineering documentation and operation and maintenance instructions delivered.

5. User Requirement Analysis

5.1 Core Requirements for Electromagnetic Shielding Function

– The computer room needs to achieve full-space electromagnetic shielding; the six sides of walls, floor and ceiling must all have continuous shielding performance without electromagnetic leakage breakpoints;

– Shielding effectiveness must reach the Class B standard to meet the protection requirements of confidential information equipment use;

– All pipelines entering and exiting the shielding room (power, signal, air conditioning, fire protection, etc.) must be treated with corresponding shielding and filtering processing without damaging the overall shielding effectiveness;

– Movable parts such as shielding doors and observation windows must have shielding performance consistent with the enclosure, maintaining stable shielding effect after repeated opening and closing.

5.2 Computer Room Environment Performance Requirements

– The illumination inside the computer room is uniform, with average illumination not lower than 300lx, meeting the lighting needs of daily operation and maintenance and equipment operation;

– The floor has anti-static performance, with system resistance complying with anti-static computer room specifications to avoid static damage to electronic equipment;

– Wall and ceiling decoration materials have fireproof, dustproof and moisture-proof performance, complying with computer room cleanliness and fire safety requirements;

– Standard ventilation and air conditioning access conditions are provided to ensure the internal temperature and humidity of the computer room can be controlled within the suitable range for equipment operation.

5.3 Power Distribution and Signal Transmission Requirements

– Three-phase 380V power incoming line is adopted, with lighting circuits, equipment circuits and maintenance standby circuits separately arranged inside the computer room for safe and reliable power distribution;

– Gigabit network signal access is supported, with internal and external networks physically independent to ensure network transmission speed and information security;

– Telephone, surveillance video, USB peripheral and other signal interfaces are reserved to meet daily office and security needs;

– Power sockets are evenly arranged on the walls to meet equipment power supply and temporary power needs, with all power distribution circuits treated with filtering.

5.4 Safety Protection System Requirements

– Gas fire extinguishing system with smoke detectors and heat detectors is provided, enabling rapid response to extinguish fires without residue that could damage electronic equipment;

– Access control system is installed at the computer room entrance for personnel access permission management and entry/exit information recording;

– A complete equipotential grounding system is established, with the shielding enclosure and internal equipment reliably grounded, and grounding resistance meeting specification requirements to ensure electrical safety and shielding performance;

– Emergency lighting system is provided, which automatically turns on after power failure to ensure personnel evacuation and emergency operation needs.

5.5 Construction and Delivery Specification Requirements

– Construction process minimizes damage to the original building structure, with good on-site finished product protection and a clean construction site;

– Strictly operate according to national construction specifications and process standards to ensure the quality of welding, sealing, installation and other processes;

– The construction period is reasonable; on the premise of ensuring quality, the project progress is accelerated to deliver on schedule;

– Complete engineering documentation, product manuals, test reports, operation and maintenance manuals and other documents are delivered upon completion, along with operation training.

6. Design Principles and Applicable Standards

6.1 Applicable Standards and Specifications

This solution strictly follows current national laws, regulations, design specifications and industry standards for design, mainly including but not limited to:

– 《Electromagnetic Shielding Room Engineering Technical Specification》GB/T 50719-2011

– 《Electromagnetic Leakage Emission Protection Requirements for Confidential Information Equipment Use Sites》BMB3-1999

– 《Electromagnetic Shielding Room Shielding Effectiveness Test Method》BMB23-2019

– 《Electronic Information System Computer Room Design Specification》GB 50174-2017

– 《Code for Design of Building Fire Protection》GB 50016

– 《Code for Electrical Design of Civil Buildings》GB 51348-2019

6.2 Overall Design Principles

1. Safety and reliability principle: shielding performance and structural safety are put first; all materials and equipment are qualified products complying with standards; construction processes strictly follow specification requirements to ensure long-term stable shielding effectiveness, safe and solid structure, and fully compliant electrical and fire safety indicators;

2. Advanced technology principle: mature and advanced electromagnetic shielding technology and computer room construction processes are adopted, taking into account both current needs and future development; the system has certain scalability to adapt to subsequent equipment upgrades and function expansion, extending the computer room service life;

3. Economical and practical principle: on the premise of meeting performance requirements, the solution design is optimized, materials and equipment are reasonably selected, construction costs are controlled, over-configuration waste is avoided, and subsequent operation and maintenance costs are reduced to achieve a high cost-performance construction objective;

4. Standardization principle: the overall design and construction follow national and industry standards, with standardized product interfaces, construction processes and acceptance procedures, ensuring consistent and testable engineering quality and facilitating subsequent maintenance and renovation;

5. Humanization principle: the convenience of daily computer room use and operation and maintenance is fully considered, with reasonable layout of doors, windows, sockets, switches, inspection openings and other facilities; the interior decoration is simple and beautiful, and the environment is comfortable to improve the user experience.

6.3 Shielding Level Selection Description

At present, domestic electromagnetic shielding rooms are mainly divided into three levels: A, B and C, with different levels corresponding to different shielding effectiveness requirements and applicable scenarios:

– C level: suitable for scenarios with general confidentiality requirements, with relatively low shielding effectiveness requirements;

– B level: suitable for confidential-level confidential information equipment use scenarios, with moderate shielding effectiveness requirements; it is currently the most widely used level in government, scientific research, enterprise R&D and other fields;

– A level: suitable for top-secret level and other high confidentiality requirement scenarios, with extremely high shielding effectiveness requirements and higher construction costs.

Combined with this project’s usage needs and the configuration standards of conventional confidential computer rooms, this solution adopts the Class B electromagnetic shielding level, which can meet the electromagnetic protection needs of most confidential office, R&D testing, data processing and other scenarios, with balanced performance and cost and high practicality.

6.4 Overall Computer Room Architecture Design

This shielding computer room adopts a welded six-sided fully enclosed shielding enclosure as the main structure, with cold-rolled steel plates as shielding panels and hot-dip galvanized square steel as supporting keels, forming a continuous shielding cavity through full welding technology. On this basis, eight major systems are equipped to jointly constitute a complete shielding computer room:

– Shielding enclosure system: six-sided shielding steel plates (floor, walls, ceiling) and keel frame, the core carrier of shielding performance;

– Shielding door and window system: shielding doors for personnel entrances and shielding observation windows for observation, meeting access and observation needs;

– Ventilation waveguide system: honeycomb ventilation waveguide windows and various pipeline waveguides, solving shielding problems of ventilation, air conditioning and pipeline wall penetration;

– Power filtering system: power filters at all levels, filtering incoming and outgoing power circuits to prevent electromagnetic signal leakage along power lines;

– Signal filtering system: various signal filters and optical fiber waveguides, ensuring normal signal transmission while blocking electromagnetic leakage;

– Grounding and equipotential system: grounding copper bars and down conductors, realizing equipotential connection between the shielding enclosure and internal equipment, ensuring shielding effect and electrical safety;

– Interior decoration system: anti-static raised floor, color steel panel walls, aluminum perforated panel ceiling, optimizing the internal environment of the computer room to meet usage needs;

– Fire protection and security system: gas fire extinguishing, fire detection and access control systems, ensuring safe computer room operation.

All systems work together to ensure the continuity and reliability of the overall electromagnetic shielding performance while meeting the various functional usage needs of the computer room.

7. System Architecture and Working Principle

7.1 Overall System Architecture

The Class B electromagnetic shielding computer room is composed of one shielding main structure and eight supporting subsystems. The shielding enclosure is a welded six-sided fully enclosed cavity formed by cold-rolled steel plates and hot-dip galvanized square steel keels. All subsystems cooperate around the enclosure to form a complete electromagnetic protection space:

– Shielding enclosure system: six-sided shielding steel plates and keel frame — the core carrier of shielding performance;

– Shielding door and window system: personnel shielding door and observation window;

– Ventilation waveguide system: honeycomb ventilation waveguide windows and pipeline waveguides;

– Power filtering system: three-phase main filter and single-phase branch filters;

– Signal filtering system: network, telephone, video, USB filters and optical fiber waveguides;

– Grounding and equipotential system: closed equipotential copper bar loop and down conductors;

– Interior decoration system: anti-static raised floor, color steel panel walls, aluminum perforated panel ceiling;

– Fire protection and security system: gas fire extinguishing, fire detection and access control.

7.2 Working Principle

The shielding enclosure uses the highly conductive steel shell to reflect and absorb external electromagnetic waves, while internal electromagnetic signals are confined inside the cavity. All wall-penetrating pipelines (power, signal, air conditioning, fire protection) are the main leakage paths, so each path is treated with a corresponding filter or cutoff waveguide: power lines are filtered by EMI filters, signal lines by signal filters, optical fibers pass through metal waveguides (optical fiber is non-conductive and does not conduct electromagnetic signals), and ventilation uses honeycomb waveguides whose cutoff frequency characteristic attenuates electromagnetic waves below the cutoff frequency while allowing air to pass. The equipotential grounding system provides a low-impedance path for induced charges, eliminating potential differences and further improving shielding effectiveness.

8. Detailed Technical Design

8.1 Shielding Enclosure Main System

#### 8.1.1 System Design Description

The shielding enclosure is the core structure of the entire shielding computer room. This solution adopts a welded steel shielding enclosure composed of shielding steel plates and supporting keels. During construction, a hot-dip galvanized square steel keel frame is first erected inside the building structure, then 2mm cold-rolled steel plates are fully welded onto the keels. All plate splicing gaps adopt continuous full welding, supplemented by beryllium copper conductive gaskets and conductive sealant for sealing reinforcement, ensuring the entire enclosure is electrically continuous with no electromagnetic leakage points.

The enclosure covers the floor, four walls and ceiling, forming a six-sided fully enclosed shielding space. An installation gap is reserved between the enclosure and the original building structure to avoid structural deformation affecting shielding performance. The overall structure has sufficient strength and rigidity to bear its own weight and subsequent decoration and equipment installation loads, without deformation or cracking in long-term use.

#### 8.1.2 Shielding Main Steel Plate Technical Parameters

Parameter Value
Product Cold-rolled shielding steel plate for electromagnetic shielding rooms
Material Q235B high-quality carbon structural steel cold-rolled plate
Nominal thickness 2.0mm (tolerance ±0.12mm)
Standard sheet size 1250mm (W) × 2500mm (L), custom cutting available
Tensile strength 375MPa ~ 500MPa
Yield strength ≥235MPa
Elongation after fracture ≥26%
Surface conductivity Surface resistivity ≤0.1Ω/□
Shielding effectiveness ≥100dB (10kHz ~ 40GHz test band)
Surface treatment Epoxy zinc-rich anti-rust primer, dry film ≥40μm; weld areas ground and repainted after on-site welding
Fire rating Non-combustible, Class A per GB 8624-2012
Weight ~49kg/sheet (1250×2500×2mm)
Installation Welded to keel frame, continuous full welding, weld height ≥3mm, no pores/no false welds/no breakpoints

#### 8.1.3 Shielding Support Keel Technical Parameters

– Specification: 50mm × 50mm × 3mm (wall thickness) hot-dip galvanized square steel, Q235B;

– Galvanized layer: ≥85μm, anti-rust life ≥20 years indoors;

– Bending capacity: concentrated load ≥5kN at 1m span;

– Layout: wall keels vertical spacing 600mm, horizontal reinforcement keels 1200mm; ceiling main keels 1000mm, secondary keels 600mm; floor keels 600mm with reinforcement;

– Connection: welded between keels; frame fixed to building structure with expansion bolts; connections rust-treated.

#### 8.1.4 Beryllium Copper Conductive Gasket Technical Parameters

– Material: beryllium bronze alloy (QBe2), beryllium content 1.8% ~ 2.0%;

– Size: 10mm (W) × 2mm (T), custom length;

– Conductivity: ≥22% IACS; hardness HV 350 ~ 400; elastic limit ≥700MPa;

– Contact resistance: ≤5mΩ/contact point;

– Shielding contribution: improves gap shielding effectiveness by 30dB+;

– Durability: no obvious contact resistance increase after ≥10000 insertions;

– Installation: conductive adhesive + rivet fixing, continuously laid at steel plate splicing gaps and shielding door frames.

#### 8.1.5 Two-Component Conductive Sealant Technical Parameters

– Type: silver-copper filled shielding-grade conductive sealant, two-component room-temperature curing;

– Volume resistivity: ≤0.01Ω·cm; shielding effectiveness ≥60dB (10kHz ~ 10GHz);

– Curing: initial cure 2h, full cure 24h at room temperature;

– Adhesive strength: shear strength ≥8MPa on steel; elongation ≥150%;

– Aging: ≥10 years service life indoors; RoHS compliant.

#### 8.1.6 Welding and Anti-Rust Auxiliary Materials

– CO₂ welding wire: ER50-6, 1.0mm, tensile strength ≥500MPa;

– Epoxy zinc-rich primer: zinc content ≥80% (dry film), salt spray ≥500h;

– Auto putty: unsaturated polyester resin type, good sanding performance for smoothing weld areas.

8.2 Shielding Door and Window System

#### 8.2.1 System Design Description

Shielding doors and windows are the movable parts of the shielding computer room and also the weak link of shielding performance, so professional electromagnetic shielding door and window products must be adopted. This solution configures 1 manual side-hung electromagnetic shielding door as the main personnel entrance and 1 shielding observation window for internal/external observation. Both adopt full-perimeter beryllium copper gasket sealing structures, ensuring shielding effectiveness consistent with the enclosure while providing good operating feel and durability.

#### 8.2.2 Manual Side-Hung Electromagnetic Shielding Door

Parameter Value
Clear opening 1000mm (W) × 2100mm (H)
Door leaf thickness ~80mm, welded steel structure with section steel frame, 2mm cold-rolled steel plates on both sides
Shielding effectiveness Class B, ≥60dB~100dB (14kHz ~ 40GHz)
Sealing Multiple rows of beryllium copper conductive gaskets around full perimeter, multi-point elastic contact
Locking Double-point compression locking mechanism with dedicated shielding lock
Hinges Heavy stainless steel hinges ×3 per door, load-bearing, no sagging
Service life ≥50000 open/close cycles
Accessories Door frame, door leaf, lock, hinges, door closer, grounding wire

#### 8.2.3 Shielding Door Hardware Kit

– Hydraulic door closer: aluminum alloy housing, 60kg ~ 120kg load range, two-stage adjustable closing speed, ≥500,000 cycles;

– Stainless steel handle lock: 304 stainless steel, copper lock core, 3 keys, with upper/lower linkage locking;

– Heavy hinges: 304 stainless steel cast, single-pair load ≥80kg, opening angle ≥110°, three-dimensional adjustment.

#### 8.2.4 Shielding Observation Window

– Visible size: 600mm (W) × 800mm (H), overall thickness ~40mm;

– Structure: double-layer tempered glass with metal shielding mesh in between, metal frame encapsulation;

– Mesh: 80-mesh braided copper mesh; light transmittance ≥70%;

– Shielding effectiveness: Class B, matching wall shielding performance;

– Frame: cold-rolled steel plate, electrostatic powder coating, conductive gaskets around perimeter.

8.3 Ventilation and Air Conditioning Waveguide System

#### 8.3.1 System Design Description

The shielding computer room is an enclosed space, so ventilation and air conditioning pipeline wall penetration must be solved without damaging shielding performance. This solution uses honeycomb ventilation waveguide windows for ventilation and cutoff waveguides for air conditioning and fire protection pipelines, utilizing the waveguide’s high-pass characteristic to allow air and pipelines to pass while attenuating electromagnetic signals below the cutoff frequency. Configuration: 4 units of 300×300mm ventilation waveguide windows (2 supply + 2 exhaust) with fresh air system; 1 set of air conditioning pipeline combined waveguide; 1 fire smoke exhaust waveguide window.

#### 8.3.2 Honeycomb Ventilation Waveguide Window

Parameter Value
External size 300mm × 300mm (flange)
Ventilation area ≥0.06㎡
Honeycomb core hexagonal cells, 3mm side length, 100mm waveguide depth
Cutoff frequency ≥18GHz
Shielding effectiveness Class B, ≥60dB~100dB (10kHz ~ 40GHz)
Air resistance ≤10Pa (at 2m/s wind speed)
Material tin-plated cold-rolled steel honeycomb core, sprayed steel flange

#### 8.3.3 Air Conditioning Pipeline Combined Waveguide

– Composition: φ50mm waveguides ×2 (copper pipes), φ32mm ×1 (drain pipe), φ20mm ×1 (control wire), integrated on one flange;

– Material: seamless steel tube, 300mm length, cutoff frequency ≥10GHz, shielding ≥60dB;

– Sealing: conductive sealant sealing at both ends after pipeline penetration.

#### 8.3.4 Fire Smoke Exhaust Waveguide Window

– Size: 400mm × 400mm flange; honeycomb waveguide core + motorized air valve integrated;

– Shielding: ≥60dB (Class B); valve DC24V, normally closed, auto-opens on fire signal; IP54.

8.4 Power Filtering and Indoor Power Distribution System

#### 8.4.1 System Design Description

Power lines are an important path for electromagnetic signal leakage, so all power lines entering the shielding computer room must pass through power filters. This solution adopts a three-level filtering architecture: 1 three-phase high-performance power filter for the main incoming line, and single-phase power filters for lighting, standby and maintenance circuits respectively. Indoor distribution uses surface-mounted distribution boxes with branch circuits, leakage/overload/short-circuit protection; lighting uses shielded LED flat panel lights; shielded power sockets are installed on walls. All distribution lines are laid in galvanized steel conduits with grounding.

#### 8.4.2 Three-Phase Main Power Filter

Parameter Value
Rated voltage 380V AC three-phase four-wire (3L+N+PE)
Rated current 100A
Withstand voltage 2000V AC line-line / 1500V AC line-ground, 1min
Insulation resistance ≥100MΩ (DC 500V)
Insertion loss (common mode) 10kHz ≥30dB; 100kHz ≥60dB; 1MHz~1GHz ≥80dB; 1GHz~10GHz ≥60dB
Insertion loss (differential mode) 10kHz ≥20dB; 100kHz ≥40dB; 1MHz~100MHz ≥60dB
Housing galvanized cold-rolled steel, sprayed, housing shielding ≥60dB
Leakage current ≤0.5mA/phase
MTBF ≥100000h

#### 8.4.3 Single-Phase Power Filter

– Rated: 220V AC / 32A; insertion loss 10kHz ≥25dB, 100kHz ≥50dB, 1MHz~1GHz ≥70dB;

– Circuit: multi-stage LC, common + differential mode full-band filtering;

– Quantity: 3 units for lighting, equipment standby and maintenance socket circuits.

#### 8.4.4 Indoor Lighting Distribution Box

– Surface-mounted, 8 circuits, cold-rolled steel box 1.2mm, IP30;

– Main switch 32A 2P MCB ×1; branch 16A 1P MCB ×6; RCD 30mA ×1; SPD class II ×1.

#### 8.4.5 Shielded LED Flat Panel Light

– 600×600mm, 40W, 220V AC, luminous flux ≥3200lm, CCT 6500K, Ra≥80;

– Illuminance ≥300lx at 3m mounting height; life ≥50000h; metal shielded housing with built-in filter;

– Quantity: 6 units evenly arranged.

#### 8.4.6 Emergency Lighting

– LED, 5W, Li-ion battery ≥2000mAh, emergency duration ≥90min, switchover ≤0.5s;

– Quantity: 2 sets, wall-mounted at entrance and corners.

#### 8.4.7 Shielded Power Socket

– 86-type five-hole, 10A 250V, metal shielded panel with shielding ground terminal, copper nickel-plated contacts;

– Quantity: 8 units evenly arranged on walls.

#### 8.4.8 Distribution Auxiliary Materials

– Galvanized conduit DN20/DN25; low-smoke halogen-free wire WDZ-BYJ (2.5mm² lighting / 4mm² socket circuits); tinned copper terminals, flame-retardant nylon cable ties, metal wire clips.

8.5 Signal Transmission Filtering System

#### 8.5.1 System Design Description

Like power lines, signal lines are important electromagnetic leakage channels, so all signal lines entering and exiting the shielding computer room must pass through corresponding signal filters or cutoff waveguides. This solution configures filtering equipment for common signals such as network, telephone, video and USB. Optical fiber signals use waveguide wall penetration, utilizing the non-conductive property of optical fiber combined with metal waveguides for shielding. All signal filtering equipment is installed inside the shielding room with reliably grounded housings. Lines are laid with shielded cables in galvanized steel conduits.

#### 8.5.2 Gigabit Network Signal Filter

– 8-port RJ45, 10/100/1000Mbps adaptive, IEEE 802.3ab compliant;

– Insertion loss ≤1dB, return loss ≥20dB, crosstalk suppression ≥40dB, shielding ≥60dB (10kHz ~ 1GHz);

– Passive design, no external power; metal shielded housing;

– Quantity: 2 units (internal and external networks, physically independent).

#### 8.5.3 Optical Fiber Wall-Penetration Waveguide

– φ32mm, length 300mm, seamless steel tube, cutoff frequency ≥12GHz, shielding ≥60dB;

– Flanged both ends with sealing gaskets and conductive sealant;

– Quantity: 2 units; supports single-mode/multi-mode fiber bundles.

#### 8.5.4 Telephone Signal Filter

– 4-port RJ11, analog/PBX telephone lines, bandwidth 0~4MHz, insertion loss ≤0.5dB, shielding ≥60dB (10kHz ~ 100MHz);

– Quantity: 1 unit.

#### 8.5.5 Coaxial Video Filter

– 4-port BNC, analog/HD coaxial video, bandwidth 0~100MHz, insertion loss ≤1dB, 75Ω, shielding ≥60dB (10kHz ~ 100MHz);

– Quantity: 1 unit.

#### 8.5.6 USB Signal Filter

– 4-port USB2.0 Type-A, up to 480Mbps, insertion loss ≤1dB, shielding ≥50dB (10kHz ~ 500MHz), bus powered;

– Quantity: 1 unit.

8.6 Grounding and Equipotential System

#### 8.6.1 System Design Description

The grounding system is an important system for ensuring shielding effectiveness and electrical safety. This solution adopts equipotential grounding design: a closed loop of equipotential grounding copper bar is laid along the bottom of the interior walls; the shielding enclosure, metal keels, doors and windows, filter housings, distribution boxes, equipment enclosures and all other metal components are reliably connected to the copper bar, forming a unified equipotential system. The copper bar is connected to the building’s combined grounding electrode through down conductors, requiring grounding resistance ≤1Ω. A grounding resistance test box is provided for periodic testing.

#### 8.6.2 Equipotential Grounding Copper Bar

– T2 copper, purity ≥99.95%, 30mm × 3mm, conductivity ≥97% IACS, full tin-plated ≥5μm;

– Laid closed-loop along inner wall bottom on insulated supports, 150mm above floor, total ~28m;

– Connection: thermowelding or copper bolt compression between bars.

#### 8.6.3 Grounding Down Conductor

– BVR-50mm² stranded copper, PVC insulation (yellow-green), conductor resistance ≤0.387Ω/km, current capacity ≥190A, length 20m.

#### 8.6.4 Copper Grounding Terminals

– M10 tinned H62 brass terminals with nuts/washers, contact resistance ≤0.5mΩ, quantity 10 (enclosure/keel grounding);

– M6 tinned brass terminals, quantity 20 (equipment grounding reserved).

#### 8.6.5 Grounding Resistance Test Box

– ABS housing, IP54, M6 copper terminals, surface-mounted flush; provides grounding test interface for periodic resistance checks.

8.7 Interior Decoration Supporting System

#### 8.7.1 System Design Description

Interior decoration optimizes the internal environment to meet dustproof, anti-static, fireproof and aesthetic requirements while concealing pipelines and the shielding enclosure. The floor adopts all-steel anti-static raised floor, walls adopt rock-wool color steel panels, and the ceiling adopts micro-perforated aluminum panel suspended ceiling.

#### 8.7.2 All-Steel Anti-Static Raised Floor

– 600×600×35mm, HPL surface layer, system resistance 1.0×10⁶ ~ 1.0×10⁹Ω;

– Uniform load ≥1000kg/㎡, concentrated load ≥300kg, ultimate load ≥10000N; Class A fire rating;

– Installation height 150~300mm adjustable (200mm standard); area 30㎡.

#### 8.7.3 Floor Adjustable Supports

– Galvanized steel, height adjustment 150~300mm, single support capacity ≥20kN, M24 screw, 100×100mm base; ~84 sets.

#### 8.7.4 Wall Decoration Color Steel Panel

– 50mm thick rock-wool core double-sided baked color steel panel, 0.5mm panels, core density ≥80kg/m³;

– Class A fire rating, sound insulation ≥30dB, compressive strength ≥150kPa;

– Area: 66㎡ (four walls).

#### 8.7.5 Micro-Perforated Aluminum Panel Ceiling

– 600×600×0.8mm, perforation rate ≥15% (2mm holes) with sound-absorbing cotton backing;

– Class A fire rating, electrostatic powder coating matte white; ceiling height 200mm below original ceiling, net height ~2.8m; area 30㎡.

#### 8.7.6 Ceiling Light Steel Keel

– U-type galvanized steel keels: main UC50×15×1.0mm, secondary UC50×19×0.5mm, zinc coating ≥80g/㎡.

#### 8.7.7 Stainless Steel Skirting

– 304 stainless steel, 100mm high, 0.8mm thick, brushed matte finish, clip installation, ~22m.

8.8 Fire Protection and Security Adaptation System

#### 8.8.1 System Design Description

The shielding computer room is an important equipment site requiring a gas fire extinguishing system to avoid water damage to equipment. This solution configures a non-piped cabinet-type heptafluoropropane fire extinguishing device with smoke and heat detectors for automatic fire detection and extinguishing. A shielded access control system manages personnel entry/exit permissions. All fire protection and security lines are shielded and filtered at wall penetration points.

#### 8.8.2 Cabinet-Type Heptafluoropropane Fire Extinguishing Device

Parameter Value
Agent Heptafluoropropane (HFC-227ea)
Cylinder 70L, charge pressure 2.5MPa
Extinguishing concentration 8% ~ 10%, discharge time ≤10s
Start modes Auto, electric manual, mechanical emergency
Protected volume ≤70m³ per unit (adjustable for this ~90m³ room)
Standard GB 50370-2005; quantity: 1 set

#### 8.8.3 Shielded Smoke Detector

– Photoelectric scattering type, DC24V, monitor current ≤2mA / alarm ≤10mA, Class I sensitivity, shielded housing with filtered signal line; quantity 3.

#### 8.8.4 Shielded Heat Detector

– Fixed-temperature (68℃) thermistor type, DC24V, shielded metal housing with filtered signal circuit; quantity 2.

#### 8.8.5 Emergency Start/Stop Button

– IP65, DC24V, with protective cover, wall-mounted outside the door; quantity 1.

#### 8.8.6 Sound and Light Alarm

– DC24V, alarm volume ≥100dB, flash ~1Hz, high-brightness LED, IP65, mounted above the outside of the door; quantity 1.

#### 8.8.7 Shielded Fingerprint Access Control

– Fingerprint + password + card, ≥1000 fingerprints, recognition ≤1s, DC12V, metal shielded housing with dedicated signal filter; accessories include power supply, electric lock, exit button, cards; quantity 1 set.

9. Recommended Configuration and Preliminary Budget

9.1 Quotation Basis

This list is prepared for a 30㎡ (3m net height) Class B electromagnetic shielding computer room, covering the complete material and equipment set of the shielding main structure, doors and windows, ventilation waveguides, power filtering, signal filtering, grounding, decoration, fire protection and security systems. Quantities include 5% construction loss and are calculated per standard construction processes. The list covers material and equipment costs only, excluding construction installation, transportation, third-party testing and taxes, which can be calculated separately for a complete quotation. If site dimensions, shielding level or configuration requirements change, the list content and quantities can be adjusted accordingly.

9.2 Itemized Configuration List

I. Shielding Enclosure Main System

No. Product Specification Unit Qty Note
1 Shielding cold-rolled steel plate δ=2mm, Q235B, epoxy zinc-rich primer ㎡ 132 Six sides: floor 30 + walls 66 + ceiling 30 + loss
2 Shielding support keel 50×50×3mm hot-dip galvanized square steel m 260 Wall vertical/horizontal, ceiling main/secondary, floor reinforcement
3 Beryllium copper conductive gasket 10×2mm, QBe2 m 160 Full coverage at plate gaps, door/window frames
4 Two-component conductive sealant Silver-copper filled, shielding grade kg 25 Sealing welds, holes, corners
5 Welding anti-rust auxiliaries CO₂ wire, primer, putty etc. set 1 Shell welding, leveling, rust treatment

II. Shielding Door and Window System

No. Product Specification Unit Qty Note
1 Manual side-hung shielding door 1000×2100mm, Class B, double-point lock set 1 With frame, leaf, full gasket set
2 Shielding door hardware kit 304 stainless hinges, lock, closer set 1 For shielding door
3 Shielding observation window 800×600mm, metal mesh, Class B set 1 Door body or side wall

III. Ventilation and Air Conditioning Waveguide System

No. Product Specification Unit Qty Note
1 Honeycomb ventilation waveguide window 300×300mm, Class B, tin-plated core pc 4 2 supply + 2 exhaust, with fresh air system
2 AC pipeline combined waveguide φ50/φ32/φ20 integrated flange set 1 Copper pipes, drain, control wire
3 Fire smoke exhaust waveguide window 400×400mm, motorized valve, Class B pc 1 Fire smoke exhaust linkage

IV. Power Filtering and Indoor Distribution System

No. Product Specification Unit Qty Note
1 Three-phase main power filter 380V/100A, Class B high performance unit 1 Main incoming line filtering
2 Single-phase power filter 220V/32A, high performance unit 3 Lighting, standby, maintenance circuits
3 Indoor lighting distribution box Surface-mounted 8-circuit, RCD+SPD unit 1 Indoor distribution master
4 Shielded LED flat panel light 600×600mm, 40W set 6 Evenly arranged
5 Emergency light LED, ≥90min duration set 2 Auto-on on power failure
6 Shielded power socket 86-type 5-hole, 10A, metal shield pc 8 Evenly on walls
7 Distribution auxiliaries Galvanized conduit, halogen-free wire, terminals set 1 Full indoor wiring

V. Signal Transmission Filtering System

No. Product Specification Unit Qty Note
1 Gigabit network signal filter RJ45, 8-port, 1000Mbps unit 2 Internal/external network
2 Optical fiber wall-penetration waveguide φ32mm, 300mm, flanged pc 2 Single/multi-mode fiber
3 Telephone signal filter RJ11, 4-port unit 1 Telephone line filtering
4 Coaxial video filter BNC, 4-port, 75Ω unit 1 Surveillance video filtering
5 USB signal filter USB2.0, 4-port unit 1 Peripheral data filtering

VI. Grounding and Equipotential System

No. Product Specification Unit Qty Note
1 Equipotential grounding copper bar 30×3mm, T2 tinned copper m 28 Closed loop along inner walls
2 Grounding down conductor BVR-50mm² stranded copper m 20 To building ground electrode
3 Copper grounding terminal M10, tinned brass pc 10 Enclosure/keel grounding
4 Equipment grounding terminal M6, tinned brass pc 20 Equipment grounding reserved
5 Grounding resistance test box Standard test interface pc 1 Periodic resistance checks

VII. Interior Decoration Supporting System

No. Product Specification Unit Qty Note
1 All-steel anti-static raised floor 600×600×35mm, HPL surface ㎡ 30 Floor decoration, under-floor cabling
2 Floor adjustable support 150-300mm, galvanized steel set 84 With beams, screws
3 Wall decoration color steel panel 50mm rock-wool core, double-sided baked ㎡ 66 Interior of shielding walls
4 Micro-perforated aluminum ceiling 600×600×0.8mm, perforated acoustic ㎡ 30 Ceiling decoration
5 Ceiling light steel keel Main/secondary keel full set ㎡ 30 For ceiling installation
6 Stainless steel skirting 100mm, 304 brushed m 22 Wall-floor finishing

VIII. Fire Protection and Security Adaptation System

No. Product Specification Unit Qty Note
1 Cabinet-type heptafluoropropane device 70L, 2.5MPa, non-piped set 1 Gas fire extinguishing
2 Shielded smoke detector Photoelectric, DC24V pc 3 Smoke detection
3 Shielded heat detector Fixed 68℃, DC24V pc 2 Temperature detection
4 Emergency start/stop button IP65, with protective cover pc 1 Manual control outside door
5 Sound and light alarm DC24V, ≥100dB pc 1 Alarm indication outside door
6 Shielded fingerprint access control Fingerprint+password+card, filtered set 1 Entry/exit permission management

IX. Testing and Engineering Auxiliary Materials

No. Product Specification Unit Qty Note
1 Third-party shielding effectiveness test Full-band per BMB23 standard item 1 Test report after completion
2 Miscellaneous engineering auxiliaries Expansion bolts, sealant, ties, protection film set 1 Construction supporting materials

9.3 Cost Summary

This project is a customized engineering project; the total cost needs to be calculated based on the final confirmed configuration solution, construction difficulty, transportation distance and other factors. The core cost components include: shielding main structure material cost, equipment purchase cost, decoration material cost, construction and installation cost, transportation cost, testing and acceptance cost, tax and after-sales service cost. If upgrading to Class A shielding standard, or adding constant temperature and humidity air conditioning, UPS uninterruptible power supply, environmental monitoring system and other supporting equipment, supplementary configuration and quotation can be provided separately. All reference prices quoted in this solution are in RMB (CNY) only, based on reference material and equipment pricing.

10. Technical Specifications

10.1 Overall Shielding Performance

Item Specification
Shielding level Class B (confidential grade)
Frequency band 14kHz ~ 40GHz full band
Shielding effectiveness ≥60dB ~ 100dB across the band (third-party tested per BMB23-2019)
Room net size ~30㎡ (6m × 5m), net height 3.0m
Structure type Welded six-sided fully enclosed steel enclosure

10.2 Key System Specification Summary

System Key Parameters
Shielding enclosure 2mm Q235B cold-rolled steel, 50×50×3mm galvanized keels, continuous full welding, weld height ≥3mm
Shielding door 1000×2100mm manual side-hung, beryllium copper gasket sealing, ≥50000 cycles
Observation window 600×800mm, 80-mesh copper mesh, light transmittance ≥70%
Ventilation waveguide 300×300mm honeycomb, cutoff ≥18GHz, air resistance ≤10Pa
Main power filter 380V/100A, common-mode ≥80dB (1MHz~1GHz)
Signal filters Gigabit network/telephone/video/USB, shielding ≥50~60dB
Grounding T2 copper bar 30×3mm closed loop, grounding resistance ≤1Ω
Fire protection 70L heptafluoropropane cabinet device, non-piped, ≤10s discharge
Decoration Anti-static raised floor ≥1000kg/㎡, Class A fire-rated materials
Power distribution 8-circuit box with RCD and SPD, shielded sockets ×8

10.3 Environmental Conditions

– Working temperature: -20℃ ~ +60℃; storage: -40℃ ~ +80℃; relative humidity ≤95% (no condensation);

– Illumination: average ≥300lx; anti-static floor system resistance 1.0×10⁶ ~ 1.0×10⁹Ω;

– Ventilation: honeycomb waveguides with fresh air system; fire smoke exhaust linkage available.

11. Key Advantages and Customer Value

11.1 Technical Performance Advantages

This solution strictly follows the national Class B electromagnetic shielding standard. The welded steel shielding enclosure with beryllium copper gaskets and conductive sealant double-sealing process ensures stable and reliable shielding effectiveness, with full-band shielding indicators meeting and exceeding national standards. All filtering equipment adopts high-performance multi-stage filtering circuits with comprehensive frequency coverage, effectively suppressing electromagnetic leakage while ensuring normal power and signal transmission. The hot-dip galvanized square steel keel frame provides high structural strength and load capacity, meeting subsequent equipment installation and decoration loading requirements, without deformation or weld cracking in long-term use.

11.2 Product Quality Advantages

All core products in this solution are produced under our own brand with full-process quality control from raw material procurement to finished product delivery. Key components are sourced from quality brands to ensure product performance and service life. Shielding steel plates are high-quality cold-rolled plates from major manufacturers with uniform material and stable conductivity; filter components are strictly screened with consistent performance parameters and long MTBF; all decoration materials meet Class A fire rating, are environmentally friendly and safe. All products undergo performance testing before leaving the factory; unqualified products are strictly prohibited from shipment.

11.3 Customization Design Advantages

Solutions can be tailor-made according to the customer’s actual site dimensions, shielding level requirements, equipment configuration and budget range, with multiple design solutions provided free of charge. For special equipment interfaces and pipeline penetration needs, dedicated waveguides and filtering equipment can be customized to ensure all incoming and outgoing pipelines receive standardized shielding treatment without electromagnetic leakage hazards. The design considers both current usage needs and future expansion needs, reserving sufficient distribution circuits, signal interfaces and upgrade space.

11.4 Full-Process Service Advantages

One-stop full-process services are provided from site survey, solution design, production, construction and installation, commissioning and acceptance to after-sales operation and maintenance. A dedicated project manager follows up the entire project, coordinating all stages to ensure on-time, quality delivery. The construction team has years of shielding computer room construction experience, with certified welders and standardized processes.

11.5 Cost Control Advantages

As a source manufacturer with our own production base and no intermediary links, costs can be effectively controlled while ensuring quality. The design follows practical principles without over-configuration, optimizing material usage and construction processes to reduce unnecessary losses and construction costs, providing customers with a high cost-performance shielding computer room.

12. Technical Q&A (50+ Items)

12.1 Shielding Enclosure Questions

Q1: Why must an electromagnetic shielding computer room be shielded on all six sides?

A: Electromagnetic waves propagate in all directions. They can not only transmit through walls horizontally, but also diffract and conduct through the floor and ceiling. If only the four walls are shielded, the floor and ceiling become electromagnetic leakage channels and the expected shielding effect cannot be achieved. Therefore, a standard shielding computer room must shield all six sides — floor, walls and ceiling — forming a closed Faraday cage structure for all-directional electromagnetic protection.

Q2: What is the difference between a welded shielding room and an assembled shielding room?

A: A welded shielding room welds shielding steel plates on site into one integral unit with continuous welds, good conductivity, high and stable shielding effectiveness, suitable for Class B and above, with a long service life but a slightly longer construction period — suitable for fixed long-term use. An assembled shielding room uses prefabricated shielding modules joined with bolts, providing fast construction and relocatability, but gap shielding effectiveness is slightly lower than welded construction, generally suitable for Class C requirements or temporary/relocatable scenarios. This solution adopts welding to ensure long-term stability of Class B shielding effectiveness.

Q3: Is thicker shielding steel plate always better?

A: Within a certain range, thicker plates improve low-frequency shielding effectiveness, but at high frequencies the skin effect is significant and even thin plates achieve high shielding effectiveness. For Class B rooms, 2mm cold-rolled steel plates already meet full-band requirements. Excessively thick plates greatly increase cost and structural load with poor cost performance. Shielding effectiveness is not determined solely by thickness but is closely related to welding quality, sealing treatment and grounding effect.

Q4: What is the function of conductive sealant? Can ordinary sealant replace it?

A: Conductive sealant has two core functions: filling fine gaps in welds and joints to ensure electrical continuity and improve shielding effectiveness, and providing sealing and moisture protection to prevent rust at steel plate joints. Ordinary sealant is non-conductive; filling gaps with it blocks electrical connection, creating electromagnetic leakage points that seriously affect shielding performance. Ordinary sealant must never replace shielding-grade conductive sealant.

Q5: What are the quality requirements for enclosure welds?

A: Steel plate splicing must use continuous full welding without breakpoints, false welds, pores, slag inclusions or other defects, with weld height no less than 3mm. After welding, welds must be ground and cleaned, then rust-treated and conductive-sealed. Key welds require conductivity continuity testing to ensure the entire enclosure is electrically connected without breakpoints.

Q6: What is the typical service life of a shielding computer room?

A: Under normal indoor conditions, a properly constructed welded steel shielding room has a main structure service life of more than 20 years with long-term stable shielding effectiveness. Daily attention to moisture prevention, avoiding sharp object impact, and regular inspection of sealing parts effectively extends service life. Beryllium copper gaskets, locks and other movable parts are wearing parts, generally replaced every 5-10 years depending on usage frequency.

Q7: What are the requirements for the installation site?

A: First, the site floor must have sufficient bearing capacity to support the enclosure, decoration and equipment weight. Second, strong vibration sources nearby should be avoided, as long-term vibration may cause weld cracking and sealing failure. Third, the environment should be relatively dry to avoid accelerated steel corrosion from long-term high humidity. Fourth, sufficient installation working space should be reserved for construction and subsequent maintenance.

Q8: Does rust on the enclosure affect shielding effectiveness?

A: Yes. Rust is non-conductive. If steel plate surfaces or welds rust, local conductivity degrades, and severe cases create shielding breakpoints that reduce overall shielding effectiveness. Therefore the enclosure is treated with anti-rust primer before leaving the factory, welds receive secondary rust treatment on site, and daily maintenance includes regular rust inspection with timely treatment.

Q9: What is the Faraday cage principle behind the shielding enclosure?

A: A Faraday cage is an enclosed conductive shell in which the electric field inside is zero under static conditions and electromagnetic waves are strongly attenuated at high frequencies. The welded steel enclosure forms such a conductive shell: external waves induce currents on the shell surface that cancel the internal field, while internal signals are confined inside. The better the electrical continuity (welds, gaskets, seals), the closer the behavior to an ideal Faraday cage.

Q10: Can the enclosure be expanded later?

A: Yes, with planning. The design reserves expansion margins: if the shielded area needs to be enlarged, new enclosure sections can be welded onto the existing shell with proper gap treatment, and the power/signal filtering capacity should be reserved in advance. Expansion must be performed by professional construction teams and followed by full-band shielding retesting.

Q11: How is shielding effectiveness measured?

A: Shielding effectiveness is measured per BMB23-2019 by qualified third-party institutions using calibrated antennas and signal sources inside and outside the shielded room across the specified frequency band (14kHz~40GHz). The ratio of received power without the enclosure to that with the enclosure gives the shielding effectiveness in dB at each frequency point. A formal test report is issued after completion.

Q12: What factors most affect final shielding effectiveness?

A: The main factors are: weld continuity and quality (no breakpoints), door/window gasket contact pressure, correctness of filter/waveguide installation (all penetrations treated), equipotential grounding quality (resistance ≤1Ω), and post-construction sealing of all openings. Any single untreated penetration can degrade overall performance by tens of dB.

12.2 Shielding Door and Window Questions

Q13: Why is a shielding door much heavier than an ordinary door?

A: The door leaf and frame are both steel structures with internal section steel frames, covered with shielding steel plates on both sides, plus multiple rows of beryllium copper conductive gaskets and locking mechanisms around the perimeter. This heavy metal structure and full-perimeter sealing design ensure continuous electrical connection with the wall enclosure when closed, achieving shielding effectiveness consistent with the walls.

Q14: Do the beryllium copper gaskets need replacement? How often?

A: Beryllium copper gaskets are elastic elements; long-term frequent opening and closing causes fatigue wear, reducing contact pressure and affecting sealing. At normal usage frequency (a dozen openings per day), the service life is about 5-8 years; higher frequency shortens the cycle. If shielding effectiveness drops after closing or the door gap feels loose, inspect the gaskets and replace if necessary.

Q15: What is the light transmittance of the observation window?

A: The observation window uses a metal mesh sandwich structure. Mesh count and wire diameter affect transmittance; conventional 80-mesh copper mesh provides over 70% transmittance, visually like a fine gauze layer, fully meeting daily observation needs. For higher transmittance, lower mesh counts can be selected, but shielding effectiveness decreases accordingly — a balance must be struck.

Q16: Can the shielding door be made automatic?

A: Yes, automatic shielding doors with electric drive and sensing devices can be customized, but the sealing structure is more complex, cost is higher, and failure rate is slightly higher than manual doors. For general confidential computer rooms, manual side-hung doors already meet usage needs with higher reliability and simpler maintenance. For high-traffic or automated scenarios, automatic sliding or electric side-hung shielding doors can be customized.

Q17: Why does the door use double-point compression locking?

A: Double-point compression locking drives upper and lower lock points simultaneously through the handle mechanism, evenly pressing the gaskets around the full perimeter. Single-point locking can cause uneven gasket pressure, leaving local gaps that reduce shielding effectiveness at that area. Double-point locking ensures uniform contact and consistent shielding around the door.

Q18: Can an emergency push bar be installed on the shielding door?

A: Yes, emergency push-bar locks (panic hardware) are optional for shielding doors, allowing quick escape from inside in emergencies while still providing shielding when closed. The push bar mechanism is specially designed to maintain electrical continuity. This is recommended for rooms where personnel may be present.

Q19: What maintenance does the shielding door require?

A: Regular inspection of hinge lubrication, lock mechanism adjustment, gasket condition and surface rust. Apply appropriate lubricant to hinges periodically; check that the gaskets are not deformed or lifted; clean the sealing surfaces. Avoid forced opening/closing when stuck, and contact after-sales service for repair rather than risking gasket and door structure damage.

Q20: Does the window frame maintain electrical continuity with the wall?

A: Yes. The observation window frame is made of cold-rolled steel plate with conductive gaskets around the perimeter, and the frame is welded to the shielding enclosure. The window installation opening is sealed with conductive treatment, ensuring the window area maintains the same shielding effectiveness as the wall.

12.3 Filtering System Questions

Q21: Why must a filter be installed on the power incoming line?

A: Power lines are conductive metal circuits; electromagnetic signals can conduct along them, both entering from outside to interfere with internal equipment and leaking from internal equipment to the outside, causing information leakage. Without filtering, the power line acts as an “antenna” allowing signals to pass in and out, defeating the entire shielding room. Therefore all power lines entering and exiting the shielding room must pass through power filters.

Q22: Should the power filter be installed inside or outside the room?

A: The power filter must be installed on the inside of the shielding room, with its metal housing reliably grounded to the enclosure. This forms continuous shielding between the filter and enclosure; after the line passes through the filter, it enters the shielded space with conducted interference removed. If installed outside, the line segment between the filter and the room still receives and conducts signals, losing the filtering function.

Q23: Will the network signal filter affect network speed?

A: Qualified gigabit network signal filters have very small insertion loss and will not cause perceptible speed impact over normal transmission distances, stably supporting 1000Mbps transmission. The filter removes high-frequency electromagnetic interference while preserving normal network data signals. With correct selection and installation, normal network use is unaffected.

Q24: Why use a waveguide instead of a filter for optical fiber wall penetration?

A: Optical fiber transmits data via light signals and is an insulator that does not conduct electromagnetic signals. The issue is the hole left when the fiber passes through the enclosure; a metal waveguide plugs the hole and attenuates electromagnetic signals while the fiber passes through without any optical attenuation. No signal filter is needed.

Q25: Can I add sockets inside the shielding room myself?

A: Not recommended. All power sockets in the shielded room undergo standardized shielding treatment with filtered circuits downstream. Self-installed ordinary sockets may damage the enclosure seal or bypass filters, causing electromagnetic leakage and degrading overall performance. Additional sockets should be installed by professional construction personnel with filtering and shielded sealing treatment.

Q26: What happens if a pipeline penetrates without treatment?

A: Any untreated conductive penetration (cable, pipe, conduit) acts as an antenna that conducts electromagnetic signals in and out, creating a leakage point that can reduce overall shielding effectiveness by tens of dB — potentially failing the Class B standard. This is why every penetration must be treated with filters or cutoff waveguides.

Q27: How are filters grounded?

A: Filter housings are connected to the equipotential grounding copper bar with short, thick conductors (minimum length, maximum cross-section) to minimize inductance. The ground connection ensures the filter’s leakage current path and maintains shielding continuity between the filter housing and the enclosure.

Q28: What is the difference between common-mode and differential-mode insertion loss?

A: Common mode refers to interference conducted identically on all lines relative to ground; differential mode refers to interference between lines. A high-performance filter provides specified insertion loss for both modes. Common-mode filtering is especially important in shielding rooms because power line common-mode signals are the main leakage path for information signals.

Q29: How many filter levels are needed?

A: This solution uses a three-level architecture: one three-phase main filter at the total incoming line, single-phase filters for lighting/standby/maintenance branch circuits, and built-in filtering in shielded sockets and equipment. Multi-level filtering progressively attenuates interference and reduces coupling between circuits.

Q30: Can filters fail? How to check?

A: Filters are passive components with MTBF ≥100000h, but lightning surges or overcurrent can damage them. Symptoms include reduced shielding effectiveness, abnormal equipment noise or leakage current changes. Periodic shielding retests and visual inspections of connections are recommended; replace filters that fail insertion loss testing.

12.4 Grounding System Questions

Q31: What are the grounding resistance requirements?

A: The smaller the grounding resistance, the better. Combined grounding resistance should be ≤1Ω; an independent shielding grounding electrode should be ≤4Ω. Good grounding effectively discharges induced charges, improves shielding effectiveness, and ensures electrical safety. Non-compliant grounding greatly reduces shielding effect and may create safety hazards.

Q32: Why is equipotential bonding necessary?

A: The shielding room contains many metal components (enclosure, keels, doors and windows, cabinets, equipment housings). If potential differences exist between them, lightning or electrostatic discharge can produce sparks between different metals, damaging equipment, affecting shielding performance, or causing safety incidents. Connecting all metal components to a unified grounding copper bar achieves room-wide equipotentiality, eliminating potential differences.

Q33: Can shielding grounding share the building lightning protection grounding?

A: Yes. Combined grounding is now common practice, connecting shielding grounding, equipment grounding, lightning protection grounding and distribution protective grounding to the same building grounding network, requiring overall resistance ≤1Ω. Shared grounding avoids potential differences between systems and is safer and more reliable. Standard connections and equipotential treatment are required to avoid counterattack risk during lightning.

Q34: How often should grounding resistance be tested?

A: Normally, test every six months to one year to confirm the grounding system is in good condition. Additional testing is recommended after the thunderstorm season, when surrounding construction may affect the electrode, or after room renovation. If resistance exceeds limits, investigate and treat the electrode or connections promptly.

Q35: Why must the filter housing be grounded?

A: The filter housing grounding provides a low-impedance path for filtered interference current to return to ground, completing the filtering circuit. Without proper grounding, filtered common-mode signals cannot be shunted effectively, and the filter housing itself may radiate or conduct signals, reducing filtering performance and creating new leakage paths.

Q36: What is the function of the grounding resistance test box?

A: The test box provides a standard test interface connected to the grounding system, allowing technicians to measure grounding resistance periodically without opening decoration layers. It makes routine maintenance convenient and ensures grounding compliance can be verified at any time.

Q37: What materials are used for the equipotential copper bar?

A: T2 copper with purity ≥99.95%, 30mm × 3mm cross-section, full tin-plated (≥5μm) for oxidation resistance and easy soldering, conductivity ≥97% IACS. Connections between bars use thermowelding or copper bolt compression to ensure low contact resistance.

Q38: Can grounding resistance be too low?

A: No practical downside within reason; lower resistance provides better charge discharge and safety. Extremely low resistance (e.g., <0.1Ω) usually indicates good soil conductivity and is beneficial. The key requirement is a stable, low-inductance connection path rather than an arbitrarily small number.

12.5 Construction and Acceptance Questions

Q39: How long is the construction period for a 30㎡ shielding room?

A: The pure construction period for a standard 30㎡ Class B room is about 15-20 days, including keel installation, enclosure welding, equipment installation, decoration and commissioning/self-inspection. Cross-construction with decoration or special site conditions adjusts the schedule. Including preparation and final acceptance, the overall project period is generally about 30 days.

Q40: How is the shielding room accepted after completion?

A: Acceptance has two parts: engineering quality acceptance (enclosure welding, sealing treatment, equipment installation, decoration effects per design and specification) and shielding effectiveness testing — the core acceptance indicator, performed by qualified third-party institutions per BMB23 standard with full-band testing and a formal test report. Meeting the corresponding level standard means qualification.

Q41: Will construction damage the original building structure?

A: Normal construction does not damage the main building structure. Shielding keels are fixed to building walls, floor and ceiling with expansion bolts — conventional fixing that does not damage load-bearing parts. Damage to existing decoration is minimized, with proper finishing and restoration after completion.

Q42: Can a welded shielding room be relocated?

A: Welded rooms are fixed installations and generally not recommended for relocation; forced disassembly deforms plates and damages welds, making shielding effectiveness hard to guarantee after reinstallation. If future relocation is anticipated, choose assembled modular shielding rooms that can be disassembled and reinstalled with sealing re-commissioning, at higher cost.

Q43: What qualifications should the construction team have?

A: The construction team should have years of shielding room construction experience, certified welders (for continuous full welding), familiarity with BMB/GB shielding standards, and experience with various site conditions. Key personnel should include shielding engineers and project managers with relevant project track records.

Q44: Is third-party testing mandatory?

A: For confidential-grade rooms, third-party shielding effectiveness testing is strongly recommended and generally required by acceptance procedures. Testing per BMB23-2019 by a qualified institution provides authoritative verification that the room meets the Class B standard and protects both parties’ interests.

Q45: What documents are delivered after completion?

A: Complete engineering documentation including: design drawings, configuration lists, product manuals and certificates, material test reports, construction records (welding logs, grounding tests), third-party shielding test report, operation and maintenance manual, and training materials.

Q46: How is weld quality verified during construction?

A: Welds are verified through visual inspection (no pores, slag, false welds, breakpoints), weld height measurement (≥3mm), conductivity continuity testing at key locations, and post-weld sealing treatment verification. Grinding and rust treatment are checked before decoration covers the enclosure.

12.6 Operation and Maintenance Questions

Q47: What should be noted in daily use?

A: Keep the shielding door closed, especially during equipment operation; avoid sharp objects impacting or scratching the enclosure and doors/windows; never drill holes or add pipelines without authorization; regularly check grounding system and filter connections; keep the room dry and ventilated; perform periodic shielding effectiveness testing.

Q48: Can mobile phones be used inside the shielding room?

A: For confidential shielding rooms, wireless devices such as mobile phones are prohibited. Phone signals may cause information leakage through various paths and generate electromagnetic interference. In a qualified shielding room, phone signals are greatly attenuated and calls are generally impossible — itself evidence of good shielding performance.

Q49: What if the shielding door becomes difficult to open/close?

A: First check hinges for rust or sticking and apply appropriate lubricant; check the locking mechanism for deformation and adjust lock points; check for foreign objects between frame and leaf and gasket deformation. If adjustment does not resolve it, contact after-sales service; do not force the door, which may damage gaskets and structure.

Q50: Will the shielding room lack oxygen?

A: No. A shielding room only blocks electromagnetic waves; it is not a fully sealed vacuum environment. The solution includes ventilation waveguide windows connectable to a fresh air system for air circulation, and the air conditioning system provides air circulation and maintains temperature, humidity and air quality. No oxygen shortage occurs with the ventilation system operating normally.

Q51: How often should shielding effectiveness be retested?

A: Annual retesting is recommended for confidential rooms. Additional retesting is advised after any modification (adding penetrations, changing equipment), after moving the door or adding access control, or when performance degradation is suspected. Regular retesting ensures continued compliance with the standard.

Q52: What is the warranty and after-sales service?

A: The solution provides a standard warranty period with free repair of quality problems, 7×24 technical support, rapid on-site response within the city, regular inspection and maintenance during warranty, spare parts supply, and lifetime cost-price maintenance after warranty. Each project has a dedicated service contact.

Q53: Can the shielding level be upgraded later?

A: Upgrading from Class B to Class A requires higher shielding effectiveness across the band, generally involving additional shielding layers, improved gasket systems and possibly thicker plates. Partial upgrades are difficult; full upgrades are usually achieved by rebuilding the enclosure. If Class A may be needed, consult during design to reserve upgrade paths.

Q54: What environmental monitoring is recommended for the room?

A: Temperature and humidity monitoring, water leakage detection, door status monitoring, and optionally UPS and power monitoring are recommended. These can integrate with the access control and fire systems. The room design reserves signal interfaces and conduits for such monitoring systems to be added.

13. Construction Schedule

13.1 Construction Stage Division

This project construction is divided into nine stages: construction preparation, keel frame construction, shielding enclosure welding, shielding door/window and waveguide installation, filtering and power distribution system installation, grounding system construction, interior decoration construction, fire protection and security system installation, and commissioning and acceptance. The stages are connected in order, with some processes able to work in parallel to accelerate progress while ensuring quality.

13.2 Detailed Construction Schedule

No. Stage Work Content Days Note
1 Preparation Site survey verification, material incoming inspection, personnel mobilization, technical disclosure, site protection 3 Before commencement
2 Keel frame construction Floor keel installation/fixing, wall vertical and horizontal keel welding, ceiling keel hoisting and leveling 4 Ensure frame flatness and firmness
3 Enclosure welding Floor plate laying/welding, wall plate hoisting/welding, ceiling plate laying/welding 6 Core process, full welding without missed points
4 Door/window and waveguide installation Door frame welding/fixing, door leaf installation/commissioning, observation window installation, opening/welding for waveguides 3 Sealing treatment at connections
5 Filtering and distribution installation Power filter installation, signal filter installation, distribution box installation, lamp/socket backbox installation, conduit laying 3 Filters reliably grounded
6 Grounding construction Equipotential copper bar laying, metal component grounding connections, down conductor connection, initial resistance test 2 Can cross-work with distribution
7 Interior decoration Anti-static floor installation, wall color steel panel installation, aluminum ceiling installation, skirting installation 4 Finished product protection
8 Fire and security installation Fire extinguishing device installation, detector installation, access control installation, line connection 2 Coordinate with decoration finishing
9 Commissioning and acceptance Full-system power-on commissioning, shielding self-inspection, issue rectification, third-party testing, completion acceptance, documentation delivery 3 Including training handover
— Total — 30 Excluding design and stocking lead time

13.3 Schedule Assurance Measures

– Personnel assurance: experienced project manager and construction teams, complete staffing of all trades, all special operation personnel (welders, electricians) certified, ensuring efficient process linkage and avoiding idle labor;

– Material assurance: advance material stocking plans, core materials produced and stocked in advance, delivered in batches before construction, ensuring timely supply without delay;

– Technical assurance: detailed technical disclosure before construction clarifying process requirements and acceptance standards to avoid rework; on-site technical personnel follow the whole process to solve technical problems promptly;

– Coordination assurance: the project manager proactively liaises with the client, promptly communicates progress and coordination needs, coordinates cross-construction with other contractors;

– Schedule control: detailed daily progress plans, daily review of progress at the end of each day, timely adjustment of process arrangements if lagging, increasing personnel or working hours to keep the total schedule controllable.

14. Construction Organization and Quality/Safety Measures

14.1 Organization Structure and Responsibilities

A dedicated project department is established with a complete management and construction team:

Role Count Responsibility
Project manager 1 Overall responsibility for progress, quality, safety, cost and coordination; interface with client; coordinate all teams
Technical leader 1 Technical disclosure, process guidance, quality inspection, technical problem handling
Safety officer 1 (part-time) On-site safety management, safety disclosure, daily safety inspections
Welder team 3 All welding processes (keel, steel plate, door frame, waveguide) — all certified
Electrician team 2 Distribution, filtering, grounding, fire/security line installation and commissioning
Decoration team 3 Anti-static floor, color steel panel, ceiling installation
Logistics assistant 1 Material handling, site cleaning, finished product protection

14.2 Pre-Construction Preparation

1. Technical preparation: organize technical personnel to review drawings and solution, verify on-site dimensions match drawings, compile detailed process and technical disclosure documents, conduct pre-job training with dual technical and safety disclosure;

2. Material preparation: purchase all materials and equipment per the configuration list, core equipment ordered in advance; incoming materials inspected for specification, quantity and quality certificates; unqualified materials prohibited; materials stored by category with moisture/fire/damage protection;

3. Tool preparation: prepare welding machines, cutters, impact drills, multimeters, grounding resistance testers and other tools and testing equipment; check equipment condition in advance, ensure metering equipment is within calibration validity;

4. Site preparation: clean the construction site after entry, protect existing facilities, connect temporary power and water, designate material storage and work areas, set safety warning signs, and commence after construction conditions are met.

14.3 Core Construction Processes and Workflows

1. Shielding enclosure welding process

– Layout and positioning: mark keel installation position lines per drawings, verify elevation and dimensions;

– Keel installation: install floor keels first (level and fix), then wall vertical keels (plumb correction and fix), finally ceiling keels (level and fix with expansion bolts); all keel connections fully welded with rust treatment;

– Plate cutting: cut steel plates per on-site dimensions, minimize splicing seams, grind cut edges;

– Plate laying and welding: lay floor plates first, then wall plates, finally close ceiling plates; continuous full welding at splices, weld height ≥3mm, no pores/false welds/missing welds; inspect weld quality and grind slag after each face;

– Sealing treatment: apply beryllium copper gaskets on the inner side of all splices and conductive sealant on the outer side for electrical continuity; all openings edge-welded and sealed;

– Rust treatment: grind and clean all welds and cut surfaces, apply anti-rust primer.

2. Shielding door installation process

– Frame installation: place the door frame into the reserved opening, adjust level and plumb, weld firmly to the surrounding enclosure with continuous welds, seal and rust-treat;

– Leaf installation: install the door leaf on the frame with hinges, adjust hinges for smooth opening and even gaps;

– Sealing commissioning: adjust the locking mechanism so beryllium copper gaskets press evenly around the perimeter with good contact; test opening feel and locking force;

– Grounding connection: reliably connect the door frame to the grounding copper bar for electrical continuity.

3. Filter installation process

– Positioning and fixing: fix filters at the incoming line position inside the shielding room, firmly installed with housing in good contact with the enclosure;

– Line connection: incoming side to external power/signal, outgoing side to indoor distribution/equipment, firm connections with clear labeling;

– Grounding: separate grounding connection for filter housings;

– Sealing: seal wall-penetration holes tightly with conductive sealant.

4. Grounding system construction process

– Copper bar laying: install insulated supports along the inner wall bottom, fix the copper bar, use lap welding or bolt compression at splices for good contact, forming a closed loop;

– Grounding connections: connect all metal components (enclosure, keels, doors/windows, filters, distribution boxes) to the copper bar with grounding conductors, firm connections with low contact resistance;

– Down conductor connection: connect one end to the copper bar and the other to the building grounding electrode, with anti-corrosion treatment at connection points;

– Resistance testing: test grounding resistance after completion, ensure ≤1Ω, rectify if non-compliant.

14.4 Engineering Quality Control System

– Three-level inspection: team self-inspection, inter-process mutual inspection, project department final inspection; each process must pass inspection before the next process begins;

– Material incoming inspection: all incoming materials must have qualification certificates and test reports; key materials undergo sampling re-testing; unqualified materials returned;

– Key process supervision: technical leader supervises key processes (enclosure welding, filter installation, grounding connection) throughout;

– Hidden work acceptance: keels, welds, grounding trunk lines and other hidden work must pass acceptance with records and image documentation before concealment;

– Final performance testing: internal self-inspection after completion (shielding effectiveness, electrical performance, system functions all compliant) before inviting third-party formal testing and acceptance.

14.5 Safety and Civilized Construction Management

Safety management

– All construction personnel receive safety education; special operation personnel certified; safety helmets worn on site; safety belts for high-altitude work;

– On-site temporary power compliant, distribution boxes with RCD, cables overhead or conduit-protected, no unauthorized wiring, electrician responsible for daily electrical inspections;

– Flammable materials cleared around welding operations, fire extinguishers provided, fire prevention measures in place; hot work requires approval with dedicated fire watch;

– High-altitude work uses qualified scaffolding and ladders, no illegal climbing, warning zones below work areas;

– Daily pre-shift safety disclosure and post-shift safety inspection.

Civilized construction

– Materials stacked neatly with clear labels, fire lanes unobstructed;

– Site cleaned daily after work, keeping the site tidy;

– Noise reduction measures during construction, reasonable scheduling of high-noise processes;

– Finished product protection for existing buildings and facilities;

– Neat worker attire, civilized operations, compliance with site management rules.

14.6 On-Site Coordination and Finished Product Protection

On-site coordination

– The project manager proactively interfaces with the client’s representative, reports progress and coordination needs daily; if other contractors cross-work on site, proactively coordinate working time and area division; technical problems or change requests communicated and confirmed promptly, with change solutions issued before construction.

Finished product protection

– After enclosure welding, avoid impacts and knocking; protect walls during decoration to prevent pollution and scratching of the anti-rust layer;

– After shielding door installation, protect the leaf and frame, avoid foreign objects hitting sealing surfaces, minimize opening frequency during construction;

– After filter/distribution box installation, wrap with protective film to prevent dust, moisture and collision damage;

– After decoration completion, protect floors, walls and ceilings from scratching and pollution in subsequent operations;

– After all equipment commissioning, unified cleaning and protection, dedicated guarding before handover to prevent damage and loss.

15. After-Sales Service

15.1 Warranty Commitment

The overall project warranty period is 2 years from the date of completion acceptance; core equipment (shielding doors, filters, fire extinguishing devices, etc.) has a 3-year warranty. During the warranty period, all failures and damage caused by product quality or construction process problems are repaired and parts replaced free of charge. After the warranty period, lifetime cost-price maintenance is provided, charging only parts cost and basic labor, ensuring long-term stable room operation.

15.2 After-Sales Response Mechanism

– A 7×24 after-sales hotline receives fault reports and technical consultations at any time;

– Within the urban area: respond within 2 hours, technicians on site within 4 hours;

– Suburban and surrounding areas: respond within 4 hours, personnel on site within 8 hours;

– General faults resolved on the spot; complex faults solved within 24 hours with a solution to restore normal use as soon as possible;

– Emergency faults (shielding door cannot close, fire system alarm, distribution failure, etc.) get a green channel with priority dispatch of personnel and parts.

15.3 Periodic Inspection and Maintenance

During the warranty period, a free on-site inspection is provided every six months, with a comprehensive maintenance inspection annually. Inspection contents include:

– Enclosure check: welds, sealant, rust condition, shielding leakage hazard investigation;

– Door/window check: hinges, locks, gaskets, opening feel and sealing performance commissioning;

– Filtering system check: filter wiring and operating status, filtering performance testing;

– Grounding system check: grounding resistance testing, connection point firmness and oxidation check;

– Distribution and fire system check: distribution lines, switches, fire detectors and extinguishing device status;

– O&M guidance: answer customer questions and guide daily maintenance.

After each inspection, a formal inspection report is issued recording equipment status and maintenance content with optimization suggestions.

15.4 Spare Parts Supply Guarantee

A local spare parts warehouse is established, stocking common wearing parts such as shielding door gaskets, locks, filter modules, sockets and lamps for quick replacement to shorten fault handling time. For uncommon special parts, a fast supply channel with the factory ensures availability within 48 hours. During warranty, non-artificial-damage spare parts are replaced free; after warranty, parts are charged at cost price without markup.

15.5 System Upgrade and Technical Support

– Free lifetime technical consultation services; any technical problem can be consulted by phone or online at any time;

– If the customer later needs upgrades (increasing shielding level, adding equipment interfaces, expanding room area, etc.), preferential upgrade solutions and construction services are provided;

– Industry new technology and standard information is regularly pushed to customers to help improve shielding room technology and O&M knowledge.

16. Training Plan

16.1 Training Objectives and Audience

Training objectives: through systematic training, enable computer room management personnel to fully understand the structure principles and performance characteristics of the shielding computer room, master daily operation methods and daily inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation of the shielding computer room.

Training audience: computer room management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and computer room equipment knowledge.

16.2 Tiered Training Content System

Level 1: Basic operation training (1 day)

– Basic shielding room principles: electromagnetic shielding concepts, structure composition of this room, shielding level and performance indicators;

– Daily operation standards: correct opening/closing of the shielding door, access control operation, lighting and distribution operation, fire system operation instructions;

– Daily inspection contents: daily/weekly/monthly check items — door fully closed, enclosure damage, grounding normal, indicator status, etc.;

– Safety precautions: usage prohibitions, forbidden behaviors, emergency handling procedures.

Level 2: Maintenance training (1 day)

– Detailed structure of each system: composition and working principles of enclosure, doors/windows, filtering, grounding, fire systems;

– Daily maintenance methods: shielding door gasket cleaning and care, enclosure rust maintenance, grounding terminal check/tightening, filter cleaning, etc.;

– Common fault identification and handling: door opening/closing issues, socket power loss, detector false alarms and other common problems;

– Emergency handling procedures: power failure, fire, door failure and other emergency steps.

Level 3: Advanced performance management training (as needed)

– Shielding effectiveness influencing factors and how to avoid degradation;

– Room upgrade knowledge: precautions and specification requirements for adding equipment and expanding functions;

– Relevant standard interpretation: national standards and confidentiality requirements related to shielding rooms.

16.3 Training Methods and Schedule

– Methods: combination of “theory explanation + on-site practice + Q&A interaction” — centralized theory first with drawings and physical objects, then on-site practical demonstration with hands-on operation, finally Q&A time;

– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable per client arrangement; a free repeat training session is provided for newly assigned management personnel.

16.4 Training Assessment and Documentation Delivery

– Assessment: a simple assessment after training, including theory written test and practical operation, verifying mastery; training qualification certificates issued upon passing; supplementary training for those who fail until mastery;

– Documentation delivery: complete O&M documentation delivered during training, including:

– Shielding Computer Room Operation and Maintenance Manual;

– Equipment manuals, qualification certificates and test reports for all systems;

– Completion drawings and hidden work records;

– Third-party shielding effectiveness test report;

– After-sales service contact card.

All documentation is bound into volumes for convenient daily reference.

17. Anonymous Typical Project Scenarios

All project scenarios below are anonymous, generalized examples compiled from typical industry deployments; no real customer names, addresses or confidential information are disclosed.

17.1 Class B Shielding Room for a Scientific Research Institute

Project overview: a confidential R&D shielding computer room for a scientific research institute, approximately 35㎡ with 3.2m net height, required to meet Class B electromagnetic shielding standard for confidential electronic equipment R&D and testing.

Construction contents: welded Class B shielding enclosure, manual side-hung shielding door, shielding observation window, ventilation waveguide system, three-phase power filtering system, network and telephone signal filtering systems, equipotential grounding system, all-steel anti-static floor, color steel panel wall decoration, gas fire extinguishing system and access control system — the complete set.

Project highlights: given the large number of R&D equipment and complex interfaces, multiple dedicated signal filters and wall-penetration waveguides were customized to meet the access needs of various test equipment, all passing shielding effectiveness testing; a reinforced keel structure was adopted with reserved load capacity for heavy test equipment; third-party testing after completion showed full-band shielding effectiveness better than the Class B standard; the room has operated stably for 5 years with annual inspections and no fault records.

17.2 Confidential Shielding Room Renovation for a Government Unit

Project overview: a renovation project of an aging computer room for a government unit. The original room had no electromagnetic shielding function and needed to be renovated into a Class B shielding room within the existing space — approximately 28㎡ with limited ceiling height and narrow construction space.

Construction contents: shielding enclosure erected within the original building structure, optimized keel and enclosure structure adapted to the low ceiling, shielding doors/windows, filtering and grounding systems, replacement of original distribution and decoration, new gas fire extinguishing and access control systems, overall upgrade to a standard confidential shielding room.

Project highlights: the ceiling keel and shielding layer structure were optimized for the height constraint, preserving maximum indoor net height; protective measures during construction did not affect normal office work of other rooms in the building; after renovation, shielding effectiveness fully met the standard and the environment was completely renewed; the project was delivered in only 25 days from design to handover.

17.3 Shielding Room for an Enterprise R&D Center

Project overview: an EMC testing shielding computer room for a technology enterprise R&D center, approximately 32㎡, used for product electromagnetic compatibility testing and confidential R&D, requiring Class B shielding effectiveness with attention to aesthetics and practicality.

Construction contents: standard Class B welded shielding enclosure, double shielding doors (personnel passage + equipment passage), large shielding observation window, high-performance power and signal filtering systems, high-standard decoration, environmental monitoring system, fire protection and security systems.

Project highlights: a dedicated equipment passage shielding door was designed for convenient entry/exit of large test equipment; the interior decoration adopted high-end color steel panels and integrated ceilings, clean and beautiful, matching the corporate R&D center image; a complete environmental monitoring system enables real-time monitoring of temperature, humidity, access control and fire status for intelligent O&M; shielding performance is stable, test data accurate and reliable, providing a reliable electromagnetic environment guarantee for the enterprise’s product R&D.

18. SEO Optimization Section

All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.

18.1 Keyword System

– Core keywords: shielding computer room, electromagnetic shielding computer room, shielding computer room construction, electromagnetic shielding room;

– High-conversion long-tail keywords: 30㎡ shielding computer room design solution, Class B shielding computer room configuration list, confidential shielding computer room manufacturer, electromagnetic shielding computer room technical solution, shielding computer room construction plan, welded shielding computer room quotation;

– Industry traffic keywords: computer room shielding engineering, electromagnetic shielding room construction, confidential room shielding renovation, shielding room acceptance standard, shielding room working principle, shielding room design specification;

– Brand keywords: KITOZER shielding room, Guangzhou Lain shielding room.

18.2 SEO Tag System

– Title tag: 30㎡ Class B Electromagnetic Shielding Computer Room Technical Design Solution — Guangzhou Lain KITOZER;

– Meta keywords: shielding computer room, electromagnetic shielding computer room, 30㎡ shielding room solution, Class B shielding room configuration, confidential shielding room manufacturer, shielding room construction solution, shielding room acceptance standard;

– Meta description: Guangzhou Lain professionally provides 30㎡ Class B electromagnetic shielding computer room design solutions, including detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant shielding effectiveness, third-party testing supported;

– H1 tag: 30㎡×3m Class B Electromagnetic Shielding Computer Room Technical Design Solution;

– H2 tags: shielding room system design and product parameters, shielding room construction organization plan, shielding room after-sales service and training, shielding room engineering cases.

18.3 Internal Link Anchor Text

– Core anchor text: shielding computer room construction, electromagnetic shielding computer room;

– Long-tail anchor text: 30㎡ shielding room design solution, Class B shielding room configuration list, confidential shielding room construction;

– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.

19. Official Contact Information

– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Official Website: https://gdlain.com

– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)

– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China

For any inquiries about this 30㎡×3m Class B electromagnetic shielding computer room technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific shielding requirements.

Shopping Cart