Cold Aisle Containment System Aisle Access Control

Manufacturer: Guangzhou Lain Intelligent System Development Co., Ltd.

Document Version: V2.0

Release Date: July 2026

Table of Contents

Preface

This manual is compiled for the aisle access control products specifically developed and manufactured by Guangzhou Lain Intelligent System Development Co., Ltd. for cold aisle containment systems. It comprehensively covers the full lifecycle of the product, including product introduction, composition and structure, technical parameters, installation and construction, wiring specifications, commissioning procedures, maintenance, troubleshooting, and acceptance criteria, aiming to provide standardized and refined operational guidance for construction engineers, operation and maintenance management personnel, and technical support staff.

This product is specifically designed as a supporting component for cold aisle containment systems in data centers, modular data centers, communication base stations, and similar scenarios. While providing personnel access permission control, it strictly complies with data center fire protection regulations and cold aisle sealing requirements. It can be linked with cold aisle skylights, lighting, and environmental monitoring systems, serving as the core safety component for intelligent cold aisle containment management.

All construction, commissioning, and maintenance operations must strictly follow the specifications in this manual. Improper operation may result in equipment damage, sealing failure, safety hazards, and voiding of the warranty. For technical inquiries, please contact our technical support hotline for professional guidance.

Chapter 1 Product Introduction

1.1 Product Definition

The cold aisle containment system aisle access control is an intelligent access control device installed at the head-end and tail-end doors of cold aisles. It integrates identity recognition, permission management, lock actuation, status feedback, and fire alarm linkage functions, and is an important component of the cold aisle containment system. Its core function is to perform identity verification and access management for personnel entering the cold aisle area while ensuring the air sealing effectiveness of the cold aisle, preventing unauthorized personnel from entering the cold aisle and touching IT equipment, while also meeting the rapid evacuation requirements under data center fire emergency conditions.

Unlike ordinary office access control systems, the cold aisle-specific access control system must simultaneously adapt to the sealing structure of cold aisle doors, the electromagnetic environment of the data center, fire alarm linkage logic, and low-temperature, high-humidity operating conditions. It features specialized designs in protection rating, anti-interference capability, sealing compatibility, and emergency release mechanisms, making it a dedicated security device for data center infrastructure.

1.2 Product Positioning

This product is positioned as the standard supporting security component for mid-to-high-end data center cold aisle containment systems. It is suitable for various new and retrofit modular data centers, traditional IDC data centers, carrier core data centers, enterprise private cloud data centers, government data centers, and similar scenarios. The product can be customized according to cold aisle width and door type (manual swing door, automatic sliding door, double-leaf door), supporting two deployment modes: single-door independent control and multi-door networked unified management.

In the overall cold aisle solution, the aisle access control, together with containment skylights, sealed side doors, intelligent lighting, and temperature/humidity monitoring, constitutes the intelligent cold aisle containment management system, achieving integrated operation of “air containment + security management + environmental sensing.”

1.3 Design Philosophy

1.3.1 Safety-First Design

Strictly complies with GB 50174 “Code for Design of Data Centers” and relevant fire protection standards. Features triple emergency door release mechanisms: automatic unlocking upon power failure, fire alarm signal linkage unlocking, and manual mechanical emergency release, ensuring personnel inside the aisle can evacuate quickly in emergency situations and eliminating safety hazards.

1.3.2 Sealing-Compatible Design

All access control component installations do not compromise the sealing structure of the cold aisle door. The lock body, card reader, and wiring channels all adopt recessed or surface-mounted designs, combined with sealing gaskets and brush strips to ensure the air tightness of the cold aisle after the door is closed, preventing cold air leakage that would affect cooling efficiency.

1.3.3 Stable and Reliable Design

The core controller uses industrial-grade chips with wide temperature and wide voltage design, adapting to continuous operation conditions in data centers. The lock uses pure copper coils and high-permeability magnetic materials, with no overheating or residual magnetism issues during prolonged energization. All interfaces are equipped with reverse-connection protection, short-circuit protection, and surge protection, reducing the probability of equipment damage caused by on-site construction errors.

1.3.4 Intelligent Expansion Design

Ample expansion interfaces are reserved, supporting various recognition terminals such as facial recognition, fingerprint recognition, and QR code scanning. It can interface with data center environment and power monitoring systems, building automation systems, and fire alarm systems, enabling data upload and remote management, and accommodating future data center intelligence upgrades.

1.4 Product Development and Technology Iteration

Cold aisle access control technology has been continuously iterating alongside the development of data center cooling technology. Early cold aisle end doors were only equipped with ordinary mechanical locks without identity recognition and access management functions. As data center security requirements have increased, card-based access control and PIN code access control were gradually introduced, evolving to today’s intelligent access control featuring biometric recognition combined with multiple authentication methods.

Our cold aisle access control products have undergone three generations of technological upgrades:

  • First Generation: Basic card-based access control, supporting only IC card recognition, single-door independent control, no networking capability.
  • Second Generation: Networked access control controller, supporting TCP/IP networking, unified management of permissions and door-open records, with a newly added fire alarm linkage interface.
  • Third Generation (current version): Multi-modal recognition intelligent access control, integrating card, PIN, fingerprint, and facial recognition, supporting deep integration with cold aisle systems and environment and power monitoring systems, featuring offline storage, remote upgrade, anomaly alarming, and other functions, suitable for high-grade data center requirements.

1.5 Product Implementation Standards

The design, production, and inspection of this product strictly follow the following national and industry standards:

Standard Description
GB 50174-2017 Code for Design of Data Centers
GB 50348-2018 Technical Code for Security Engineering
GB 12955-2008 Fire Resistant Doors
GA/T 394-2002 Technical Requirements for Access Control Systems
GB/T 2887-2011 General Specifications for Computer Field
YD/T 2165-2010 Modular Uninterruptible Power Supply for Telecommunications
GB 50054-2011 Code for Design of Low Voltage Electrical Installations
GB/T 50311-2016 Code for Engineering Design of Generic Cabling System

Chapter 2 Product Composition

The cold aisle containment system aisle access control is a complete system consisting of six major components: door body supporting components, access control main control unit, identity recognition unit, lock actuation unit, power supply unit, and auxiliary function components. Each unit works in coordination to achieve complete access control functionality.

2.1 Door Body Supporting Components

The door body supporting components serve as the installation carrier of the access control system and also perform the cold aisle sealing function. They are the core part combining the access control and cold aisle systems.

2.1.1 Door Frame Main Body

Manufactured from high-quality cold-rolled steel plate or aluminum alloy profiles, with electrostatic powder coating surface treatment, featuring high strength, corrosion resistance, and resistance to deformation. The door frame has pre-drilled mounting holes for access control equipment and wiring channels, eliminating the need for on-site hole cutting, ensuring installation precision and sealing performance. EPDM (ethylene-propylene-diene monomer) sealing gaskets are embedded on the inner side of the door frame, which tightly seal against the door leaf when closed, preventing cold air leakage.

2.1.2 Door Leaf Main Body

The door leaf frame is made of the same material as the door frame, with high-transmittance tempered glass embedded in the middle, allowing inspection personnel outside the aisle to observe the operating status of internal equipment. Glass thickness is ≥5mm, compliant with the GB 15763.2 tempered glass standard, with impact resistance. Sealing brush strips and gaskets are installed on the door leaf edges, forming a complete sealing surface with the door frame, floor, and top skylight when closed. Pre-drilled installation positions for card readers, exit buttons, and mechanical lock cylinders are provided on the door leaf, with holes pre-prepared before factory shipment; equipment can be directly fixed on site.

2.1.3 Door Hardware Accessories

Includes hinges/sliding rails, door closers, floor springs, door stops, and other components. Swing doors use stainless steel hinges and concealed door closers; sliding doors use silent sliding rails and damped pulleys, ensuring smooth and noiseless door operation. The door closer has adjustable closing speed and force, ensuring smooth door closing without impact causing loosening of access control equipment.

2.2 Access Control Main Control Unit

The access control main control unit is the “brain” of the entire system, responsible for identity information verification, permission determination, lock control, signal acquisition, data storage, and communication interaction.

2.2.1 Access Control Controller

Uses a 32-bit ARM industrial-grade processor with an embedded operating system for stable and reliable operation. The controller features multiple input/output interfaces and can connect to card readers, exit buttons, door contacts, fire alarm signals, alarm outputs, and other devices. Supports Wiegand 26/34 protocol, RS485 protocol, and TCP/IP protocol, adapting to various communication networking methods. Built-in large-capacity memory chip can store over 100,000 door-open records and 50,000 user card records. It can operate independently in offline mode, with automatic data upload after network recovery.

The controller housing uses a metal sheet metal structure with dustproof and electromagnetic interference protection capabilities, suitable for installation in data center weak-current rooms, above suspended ceilings, or in cable trays at the top of cold aisles.

2.2.2 Management Software

Comes with a matched access control management software system installed on the data center management workstation, enabling personnel information entry, permission assignment, door-open record query, device parameter configuration, alarm information viewing, and other functions. Supports multi-client login, hierarchical permission management, and report export for data center security audits. The software supports integration with environment and power monitoring systems via an SDK interface to integrate access control data into a unified monitoring platform.

2.3 Identity Recognition Unit

The identity recognition unit is the interactive interface for personnel permission verification, with different types of recognition terminals selectable based on requirements.

2.3.1 Card Reader

The standard configuration is an IC card reader supporting Mifare card and CPU card recognition, with a read range of 3-5cm and response time of ≤0.2 seconds. The card reader features a waterproof and dustproof design, acrylic panel, LED status indicator, and buzzer alerts. The card reader has a built-in tamper switch that automatically triggers an alarm signal uploaded to the controller when forcibly removed.

Optional card reader types include: ID card reader, ID card (national ID) reader, NFC reader, and QR code reader.

2.3.2 PIN Code Keypad

Some card reader models integrate a PIN code keypad, supporting a “card + PIN” dual authentication mode for enhanced security. The keypad features a backlit design for normal operation in low-light conditions, with anti-peeping keypad scrambling functionality.

2.3.3 Biometric Recognition Terminal

High-end configurations can select fingerprint recognition terminals and facial recognition terminals. The fingerprint terminal uses an optical fingerprint sensor with live fingerprint detection, with a false rejection rate of ≤0.01% and false acceptance rate of ≤0.001%. The facial recognition terminal uses a dual-lens camera with liveness detection, adaptable to low-light data center environments, with a recognition speed of ≤0.5 seconds and support for masked face recognition.

2.4 Lock Actuation Unit

The lock is the actuating component of the access control system, responsible for locking and unlocking the door. The standard configuration for cold aisle access control is a magnetic lock, with electric bolt locks or electromagnetic release devices optional for special scenarios.

2.4.1 Magnetic Lock (Electromagnetic Lock)

The standard configuration is a 280kg single-door magnetic lock, using a pure copper coil and high-permeability magnetic core. When energized, it generates strong magnetic attraction that firmly holds the door leaf against the door frame. In the locked state, there is no mechanical friction, providing long service life and low noise. The magnetic lock features fail-safe (power-off release) characteristics, compliant with fire protection code requirements. The lock body has a stainless steel housing, rust-proof and corrosion-resistant, with a lock status indicator and automatic signal feedback when holding force is insufficient.

For double-leaf doors, dual magnetic locks are configured with a total holding force of up to 560kg, meeting high-security requirements.

2.4.2 Lock Mounting Brackets

Includes L-type brackets, U-type brackets, ZL-type brackets, and others, selected according to door material and structure, used to securely fix the magnetic lock to the door frame and door leaf. The brackets are made of thickened steel plate with galvanized surface treatment, strong load-bearing capacity, and no looseness after installation.

2.4.3 Door Contact Sensor

Integrated into the lock or independently installed, used for real-time detection of the door open/closed status. When the door is fully closed, the door contact closes, and the controller detects the door-closed signal; when the door is opened, the contact opens, and the controller records the door-open event. The door contact signal can be used to determine door-not-closed timeout alarms, preventing prolonged cold air leakage.

2.5 Power Supply Unit

Provides stable and reliable power to the entire access control system, with backup battery capability in the event of power failure.

2.5.1 Access Control Dedicated Power Supply

Uses a linear regulated power supply design with AC 220V input and DC 12V/5A output, with low ripple and high stability, specifically adapted to access control equipment power requirements. The power supply features overcurrent, overvoltage, and short-circuit protection, automatically cutting off output upon fault to protect downstream equipment. The power supply has a metal chassis that can be wall-mounted, with a built-in cooling fan, suitable for long-term continuous operation.

2.5.2 Backup Battery

The power supply has an internal or external lead-acid battery with a capacity of 7Ah/12V. Upon mains power failure, it automatically switches to battery power, maintaining normal access control system operation for 4-8 hours. The battery has overcharge and over-discharge protection to extend battery service life.

2.5.3 Power Switch and Fuse

The power input is equipped with an air circuit breaker and fuse, providing dual protection against overload and short circuit, and facilitating on-site maintenance and power-off operations.

2.6 Auxiliary Function Components

2.6.1 Exit Button

Installed on the inner side of the cold aisle door leaf or wall. Personnel press the button to trigger the door release when leaving, without the need to swipe a card. The standard configuration is a stainless steel panel exit button with normally open contacts, self-resetting design, comfortable press feel, and service life of ≥100,000 cycles. Optional induction-type exit buttons and remote control exit buttons are available.

2.6.2 Fire Alarm Linkage Module

Used to connect to the data center fire alarm system signal. When a fire alarm linkage signal (dry contact signal) is received, the controller automatically releases all access control locks to ensure personnel evacuation. The module features optoelectronic isolation to prevent mutual interference between the fire protection system and access control system.

2.6.3 Audible and Visual Alarm

Optional accessory. When abnormal situations such as illegal intrusion, door-not-closed timeout, or device tamper triggering occur, the controller drives the alarm to emit audible and visual alerts to notify on-site management personnel.

2.6.4 Wiring Accessories

Includes terminal blocks, shielded cable, PVC conduit, cable clips, cable ties, waterproof putty, and others, used for standardized cabling and wiring to ensure stable system operation.

Chapter 3 Product List

3.1 Standard Configuration List (Single Door Kit)

No. Component Name Model/Specification Unit Qty Remarks
1 Access Control Main Controller LA-MJ-KZ01 Unit 1 Industrial grade, TCP/IP + Wiegand dual communication
2 IC Card Reader LA-MJ-DK02 Unit 1 Installed on cold aisle exterior side
3 280kg Magnetic Lock LA-MJ-S028 Set 1 Includes lock body and armature plate
4 Magnetic Lock Mounting Bracket LA-MJ-ZJ-L Set 1 L-type bracket, suitable for swing doors
5 Exit Button LA-MJ-AN01 Pcs 1 Stainless steel panel, self-resetting
6 Door Contact Sensor LA-MJ-MC01 Pair 1 Normally open type
7 Access Control Dedicated Power Supply LA-MJ-DY125 Unit 1 12V/5A, with battery interface
8 Backup Battery 12V/7Ah Pcs 1 Lead-acid, maintenance-free
9 IC Proximity Card Mifare S50 Pcs 10 10 cards standard, additional can be purchased
10 Management Software License LA-MJ-V2.0 Set 1 Single-site perpetual license
11 Installation Screw Kit Matching Pack 1 Includes expansion bolts, self-tapping screws, etc.
12 Terminal Blocks and Accessories Matching Pack 1 Includes terminals, heat-shrink tubing, cable ties, etc.
13 Product Manual This version Copy 1 Paper version
14 Product Certificate of Conformity Matching Sheet 1 Factory inspection and conformity certificate
15 Warranty Card Matching Sheet 1 Warranty service certificate

3.2 Optional Accessory List

No. Component Name Model/Specification Unit Application Scenario
1 Fingerprint Recognition Terminal LA-MJ-ZW03 Unit High-security data centers, replacement for standard card reader
2 Facial Recognition Terminal LA-MJ-RL05 Unit Contactless recognition, high-security scenarios
3 QR Code Reader LA-MJ-EWM02 Unit Visitor temporary authorization scenarios
4 560kg Double-Door Magnetic Lock LA-MJ-S056 Set Double-leaf cold aisle doors
5 Electric Bolt Lock LA-MJ-DC02 Set Sliding door cold aisles
6 Fire Alarm Linkage Module LA-MJ-XF01 Pcs Scenarios requiring fire protection system integration
7 Audible and Visual Alarm LA-MJ-BJ01 Pcs Scenarios requiring local alarm alerts
8 Access Control Management Workstation Custom Unit Multi-door networked unified management scenarios
9 Industrial Switch 8-port Gigabit Unit Multi-access-control networking scenarios
10 Shielded Signal Cable RVVP 4×0.5 Meter Long-distance cabling, strong interference environments
11 Stainless Steel Mechanical Lock Cylinder Matching Set Emergency mechanical unlocking backup
12 Door Closer Speed Regulator Matching Pcs Adjusting closing speed and force

3.3 Dedicated Installation Tool List (Provided by Contractor)

No. Tool Name Specification Purpose
1 Rotary Hammer Drill 13mm Drilling holes in walls and door frames for expansion bolts
2 Electric Drill 10mm Drilling metal components, screw fastening
3 Multimeter Digital Measuring voltage, continuity, cable fault troubleshooting
4 Wire Strippers Multi-function Stripping cable insulation
5 Crimping Tool Cold-press terminal type Crimping wire terminals
6 Phillips/Flathead Screwdriver Set Screw fastening and removal
7 Hex Key Set Set Magnetic lock bracket, hinge adjustment
8 Spirit Level 600mm Calibrating door body and equipment installation levelness
9 Tape Measure 5m Measuring installation dimensions, positioning
10 Marker Pen Oil-based Marking installation hole positions
11 Electrical Tape Insulating type Cable insulation wrapping
12 Cable Tie Gun Matching Cable bundling and fastening
13 Cable Tester Network cable type Testing network cable continuity
14 Ladder/Scaffolding 2m/3m Elevated installation operations
15 Insulated Gloves Electrician grade Protection during live operation

Chapter 4 Product Operating Principle

4.1 Overall System Operating Principle

The cold aisle access control system is centered on the access control controller. Front-end recognition terminals collect personnel identity information and transmit the data to the controller for permission comparison. Upon successful verification, the controller outputs a release signal to the lock, the lock releases, and personnel can push/pull the door to enter the cold aisle. After personnel enter, the door closes automatically under the action of the door closer, the lock re-engages, and the door contact detects the door-closed signal, after which the controller records and stores the door-open event.

Personnel inside the cold aisle can trigger the door release signal directly by pressing the exit button; the controller releases the lock and personnel leave the aisle. The system also connects to fire alarm linkage signals. When a fire alarm occurs in the data center, the fire protection system outputs a dry contact signal to the access control controller, which forcibly cuts off lock power supply, releasing the magnetic lock so the door can be pushed open freely, ensuring rapid personnel evacuation.

The entire system operates continuously under power from the access control dedicated power supply. When mains power is interrupted, it automatically switches to backup battery power, maintaining uninterrupted access control functionality.

4.2 Identity Recognition Principle

4.2.1 IC Card Recognition Principle

The card reader has a built-in RF antenna that emits electromagnetic waves at a fixed frequency during operation. When an IC card enters the read range, the coil inside the card receives the electromagnetic wave and generates induced current, powering the chip inside the card. The chip transmits the card serial number and encrypted data back to the card reader via the antenna. The card reader receives the data, performs verification, and transmits it to the access control controller via the Wiegand protocol. The controller retrieves the stored permission list and determines whether the card has door-open authorization.

4.2.2 PIN Code Recognition Principle

When the user presses keys on the PIN code keypad, the keypad matrix circuit identifies the key positions, generates corresponding key codes, and transmits them to the controller. The controller compares the entered PIN with the stored user PIN; a successful match results in permission approval. The PIN verification supports a multiple-error lockout function — after 5 consecutive incorrect entries, the keypad automatically locks for 3 minutes to prevent brute-force attacks.

4.2.3 Biometric Recognition Principle

  • Fingerprint recognition: The optical sensor captures fingerprint images, extracts fingerprint minutiae through algorithms, and compares them with pre-stored fingerprint templates. If the matching score exceeds the threshold, verification is approved.
  • Facial recognition: The dual-lens camera captures facial images, extracts facial feature values through algorithms, performs liveness detection to exclude photo and video spoofing, and compares with the database facial templates. Upon successful matching, a door release signal is output.

4.3 Magnetic Lock Operating Principle

The magnetic lock operates on the principle of the magnetic effect of electric current: when the electromagnetic coil inside the lock body is energized, it generates a strong magnetic field that attracts the armature plate mounted on the door leaf, achieving door locking through electromagnetic attraction. The holding force is related to coil power, core permeability, and contact surface area. The standard 280kg magnetic lock indicates a maximum static pulling force of up to 280 kilograms, sufficient to resist abnormal external force attempts to open.

When the controller cuts off power to the magnetic lock, the coil magnetic field disappears, the holding force is lost, and the door can be pushed open freely. This “fail-secure when energized, fail-safe when de-energized” characteristic fully complies with fire protection code requirements, ensuring automatic door release in power failure and fire conditions.

4.4 Door Contact Feedback Principle

The door contact consists of a reed switch and a permanent magnet. The reed switch is installed on the door frame side, and the permanent magnet is installed on the door leaf side. When the door is closed, the permanent magnet approaches the reed switch, the two metal reeds inside the tube are attracted together by the magnetic field, the circuit conducts, and the controller detects a closed signal. When the door is opened, the permanent magnet moves away from the reed switch, the reeds spring apart, the circuit opens, and the controller detects a door-open signal.

Through the door contact signal, the controller can implement real-time door status monitoring, door-not-closed timeout alarms, illegal intrusion alarms, and other functions.

4.5 Fire Alarm Linkage Principle

The access control controller has a reserved fire alarm linkage input interface using passive dry contact signals. Under normal conditions, the fire alarm interface is in open-circuit state and does not affect normal access control operation. When a fire alarm is triggered, the fire protection system outputs a closed dry contact signal. Upon detecting the signal, the controller immediately executes the fire alarm linkage plan:

  • Cuts off power to all access control locks, releasing the aisle doors;
  • Triggers the audible and visual alarm to emit alert notifications;
  • Uploads the fire alarm linkage event to the management platform;
  • Can link cold aisle skylights to open automatically, assisting with smoke exhaust and heat dissipation.

Fire alarm linkage has the highest priority. Regardless of the access control status, unlocking is executed immediately upon receiving the fire alarm signal, and this function cannot be disabled through software, ensuring fire safety.

4.6 Coordination Principle with the Cold Aisle Containment System

The aisle access control is installed at the cold aisle end doors, forming a complete enclosed cold aisle together with the top containment skylights, side cabinets, and bottom sealing structure. The sealing structure of the access control door body ensures that cold air does not leak from the end doors. The door contact signal can be connected to the cold aisle environmental monitoring system — when a door remains open for an extended period, the system issues an alarm to remind O&M personnel to close the door, preventing cooling capacity loss. Door-open records from the access control can be correlated with cold aisle temperature and humidity data to analyze the impact of personnel entry/exit on the temperature field within the aisle, optimizing cooling strategies.

In automatic sliding door cold aisles, the access control system can also be linked with the door motor drive — after identity verification, the door is automatically driven open, and after a delay, automatically closed, further enhancing sealing effectiveness and operational convenience.

Chapter 5 Product Technical Parameters

5.1 Overall System Parameters

Parameter Item Technical Specification Remarks
System Capacity Single controller supports 50,000 users, 100,000 event records Expandable
Recognition Response Time ≤0.2s (card), ≤0.5s (facial) Includes permission comparison time
Unlock Delay 1-255 seconds, configurable Default 3 seconds
Communication Methods TCP/IP, RS485, Wiegand 26/34 Optional
Power Supply AC 220V ±15%, 50Hz With backup battery
Backup Runtime ≥4 hours (standard battery) Extended with additional batteries
Operating Temperature -10°C ~ 60°C Suitable for data center environments
Operating Humidity 10% ~ 90%, non-condensing
Mean Time Between Failures (MTBF) ≥50,000 hours
Protection Rating Controller IP40, card reader IP54
Electromagnetic Interference Resistance Compliant with GB/T 17626.2 Suitable for data center electromagnetic environments
Fire Alarm Linkage Response Time ≤1 second Immediate unlock upon signal reception

5.2 Access Control Controller Technical Parameters

Parameter Item Technical Specification
Processor 32-bit ARM Cortex-M4, 120MHz main frequency
Memory 256KB SRAM
Storage 8MB Flash, supports TF card expansion
Card Reader Interface 2 Wiegand interfaces, supports WG26/WG34, transmission distance ≤100m
Lock Output 2 relay outputs, contact capacity 10A/120VAC, 10A/24VDC
Input Interface 8 switch inputs, supports door contact, exit button, fire alarm, tamper, etc.
Alarm Output 2 relay alarm outputs
Communication Interface 1 TCP/IP Ethernet port (10/100Mbps), 1 RS485 interface
Supply Voltage DC 12V ±10%
Operating Current Static ≤100mA, dynamic ≤300mA
Dimensions 200mm × 150mm × 30mm
Mounting Method Wall-mount, DIN rail
Housing Material Cold-rolled steel plate, powder coated

5.3 IC Card Reader Technical Parameters

Parameter Item Technical Specification
Supported Card Types Mifare S50/S70, CPU card, NFC card
Operating Frequency 13.56MHz
Read Range 30mm ~ 50mm
Communication Protocol Wiegand 26/34 auto-adaptive
Supply Voltage DC 12V ±10%
Operating Current ≤80mA
Status Indication Dual-color LED (red/green) + buzzer
Tamper Function Built-in tamper switch, triggers alarm upon removal
Operating Temperature -20°C ~ 70°C
Protection Rating IP54
Dimensions 86mm × 86mm × 20mm
Mounting Method 86-type junction box mounting, surface mounting
Housing Material ABS + acrylic panel

5.4 280kg Magnetic Lock Technical Parameters

Parameter Item Technical Specification
Rated Holding Force 280kg (static linear pulling force)
Supply Voltage DC 12V / DC 24V optional
Operating Current 12V/500mA; 24V/250mA
Lock Body Material Silicon steel core + stainless steel housing
Armature Plate Galvanized steel plate, with rubber buffer pad
Lock Status Signal Built-in door contact signal output (optional)
Delay Function 0/3/6/9 seconds adjustable (on some models)
Residual Magnetism ≤3kg
Operating Temperature -40°C ~ 80°C
Service Life ≥1,000,000 cycles
Protection Rating IP65
Lock Body Dimensions 250mm × 47mm × 25mm
Mounting Method Flush mount, surface mount, bracket mount

5.5 Access Control Dedicated Power Supply Technical Parameters

Parameter Item Technical Specification
Input Voltage AC 185V ~ 265V, 50Hz/60Hz
Output Voltage DC 12V regulated output
Rated Output Current 5A
Ripple Voltage ≤50mV
Battery Interface Supports 12V lead-acid battery, automatic charge/discharge management
Protection Functions Overcurrent, overvoltage, short-circuit, reverse-connection protection
Charging Method Constant current, constant voltage float charging
Conversion Efficiency ≥85%
Operating Temperature -10°C ~ 50°C
Dimensions 200mm × 160mm × 70mm
Mounting Method Wall-mount
Housing Material Metal sheet metal

5.6 Door Body Technical Parameters

Parameter Item Technical Specification
Standard Door Width 1000mm / 1200mm / 1500mm optional
Standard Door Height 2000mm / 2200mm optional
Door Frame Material 1.5mm high-quality cold-rolled steel plate, electrostatic powder coated
Door Leaf Glass 5mm tempered transparent glass
Sealing Method EPDM gasket + sealing brush strips
Air Leakage Rate ≤0.5m³/(h·m²)
Opening Method Single swing, double-leaf swing, sliding — optional
Closing Method Hydraulic door closer automatic closing
Fire Resistance Rating Class B fire-resistant (optional)
Grounding Resistance ≤4Ω

Chapter 6 Product Functions and Features

6.1 Core Security Functions

6.1.1 Multi-factor Identity Authentication

Supports multiple authentication methods including single card, single PIN, card + PIN, fingerprint, and facial recognition, flexibly configurable according to data center security level. High-security areas can be configured with dual authentication or multi-person combined authentication, requiring two people to verify simultaneously before the door can be opened, preventing unauthorized actions by a single individual.

6.1.2 Hierarchical Permission Management

Personnel can be authorized at different levels with different door-open time periods and access points. For example, O&M personnel can access all cold aisles during working hours, while visitors can only enter designated aisles at designated times, with permissions automatically expiring after the time period. Supports temporary permission distribution to meet short-term access requirements for construction and maintenance personnel.

6.1.3 Real-time Monitoring and Alarming

The system monitors door status, equipment operating status, and communication status in real time. Local and remote alarms are automatically triggered in the following situations:

  • Illegal intrusion: Door opened through unauthorized means;
  • Door-not-closed timeout: Door remains open beyond the set time without closing;
  • Device tamper: Card reader or controller forcibly removed;
  • Communication interruption: Controller loses connection with the management platform;
  • Power failure: Mains power outage, low battery voltage.

Alarm information can be pushed to management personnel via software pop-ups, audible/visual alerts, SMS notifications, and other means.

6.1.4 Fire Emergency Unlock

Provides triple emergency unlock protection:

  • Fire alarm signal linkage unlock: Connected to the data center fire protection system, automatic unlock upon alarm;
  • Automatic unlock upon power failure: When both mains and battery power are lost, magnetic locks release automatically;
  • Mechanical emergency unlock: Equipped with mechanical lock cylinder, door can be opened manually with a key in emergency situations.

The triple mechanism fully complies with fire protection code requirements, eliminating evacuation hazards.

6.2 Intelligent Management Functions

6.2.1 Event Recording and Auditing

The system completely records all door-open, alarm, and device operation events, including personnel information, time, location, event type, door-open method, and other fields. Records are tamper-proof and can be queried, filtered, and exported as reports by condition, meeting data center security audit and traceability requirements.

6.2.2 Multi-Door Networked Management

Supports TCP/IP networking; a single management software instance can manage thousands of access control controllers, enabling unified configuration, unified authorization, and unified monitoring of all cold aisle access control throughout the data center. Supports cross-region distributed deployment, with centralized management of multiple data center access control systems via the Internet or dedicated lines.

6.2.3 Offline Independent Operation

The controller has built-in storage; all permission data and event records are stored locally. Network interruption does not affect normal card-swipe door opening. Upon network recovery, records are automatically uploaded with breakpoint continuation, ensuring no data loss. All local management logic remains operational offline, ensuring system availability.

6.2.4 Remote Management and Maintenance

Management personnel can remotely perform permission distribution, parameter modification, firmware upgrades, remote door release, and other operations through the management software without visiting the site, improving O&M efficiency. Supports remote device fault diagnosis, resolving most issues and reducing on-site maintenance visits.

6.3 Cold Aisle Specific Adaptation Functions

6.3.1 Zero-Damage Sealed Installation

All access control components use pre-drilled mounting holes, eliminating the need for on-site cutting or drilling, avoiding damage to the door sealing structure. Lock body and card reader wiring all passes through built-in door wiring channels, without compromising the sealing surface, ensuring cold aisle air tightness and not affecting cooling efficiency.

6.3.2 Door Status Linked Cooling Capacity Management

The door contact signal can be connected to the data center precision air conditioning control system. When a cold aisle door remains open for an extended period, the corresponding area’s air conditioning airflow is automatically adjusted to avoid cooling capacity waste; normal cooling strategies are restored after door closing, achieving energy savings.

6.3.3 Linkage with Cold Aisle Skylights

Can work in coordination with cold aisle fire-linked skylights. Upon receiving a fire alarm signal, the access control unlocks while skylights automatically open, forming an upper and lower ventilation path that works with fire smoke exhaust, enhancing data center fire safety.

6.3.4 Aisle Lighting Linkage

When personnel swipe their card to open the door, LED lighting inside the cold aisle automatically turns on, and automatically turns off after a delay, eliminating the need for manual switching, improving O&M convenience while achieving energy savings.

6.4 Product Performance Features

6.4.1 High Reliability

Core components all use industrial-grade brands with wide temperature and wide voltage designs, suitable for 24/7 continuous operation in data centers. All interfaces have electrical isolation and protection circuits, with surge resistance, static protection, and reverse-connection protection, reducing failure rates caused by on-site construction and environmental interference.

6.4.2 Strong Anti-Interference Capability

Targeting the complex electromagnetic environment generated by servers, UPS, power distribution cabinets, and other equipment in data centers, the product features dedicated electromagnetic compatibility design. Communication lines use shielded cable, and the controller has a metal housing for shielding, ensuring stable operation in strong electromagnetic interference environments without false operation or data loss.

6.4.3 Low Power Consumption Design

The entire unit uses low-power circuit design with low static power consumption, reducing overall data center energy consumption. Backup battery runtime is long, maintaining access control functionality for extended periods after power failure.

6.4.4 Easy Installation and Maintenance

Modular design with independent installation of each component. Terminal blocks have clear markings, allowing construction personnel to complete wiring according to labels without complex commissioning. Equipment supports tool-free disassembly and repair, with failed components quickly replaceable, minimizing downtime.

6.4.5 Flexible Expandability

Ample expansion interfaces and protocols are reserved, supporting flexible addition of recognition terminals, sensors, and linkage modules, and integration with third-party systems, protecting user investment and adapting to future data center upgrade requirements.

Chapter 7 Product Application Scenarios

7.1 Large Data Center IDC Facilities

Large data centers have numerous and widely distributed cold aisles, with high requirements for networked access control management, hierarchical permissions, and audit traceability. This product supports large-scale networking and can be deeply integrated with data center environment and power monitoring systems, achieving unified platform management and meeting security requirements of Class 2.0 Cybersecurity Law compliance and IDC qualification certification. The high-reliability design ensures 7×24 uninterrupted operation, meeting high-availability requirements of data centers.

7.2 Modular Container Data Centers

Modular data centers have short construction cycles and flexible deployment, with cold aisles as prefabricated integrated structures. This product can be pre-installed at the factory on cold aisle end doors, requiring only on-site power connection for use, without additional construction, adapting to modular rapid delivery modes. The product features anti-vibration and transport-shock-resistant design, suitable for container data center transportation and on-site hoisting scenarios.

7.3 Carrier Core Data Centers

Carrier data centers have numerous equipment and complex O&M personnel, requiring strict access control. The product supports multi-factor authentication combinations, can interface with carrier employee badge systems for badge all-in-one access, and the comprehensive door-open records satisfy carrier O&M security management standards. The wide voltage design adapts to complex power supply environments in data centers with strong power supply stability.

7.4 Enterprise Private Cloud Data Centers

Enterprise data centers are medium-sized, balancing security and ease of use. The product offers flexible configuration, allowing selection of card swipe, fingerprint, and other recognition methods based on enterprise requirements. The management software is simple to operate and does not require dedicated maintenance personnel. It can also interface with enterprise all-in-one access control systems, achieving unified management of office building and data center access control.

7.5 Government/Classified Data Centers

Government and classified data centers have high security levels with strict personnel access control. The product supports dual-person authentication, anti-tailgating, multi-factor identity verification, and encrypted, tamper-proof storage of door-open records, meeting classified data center security standards. An optional national cryptographic algorithm encrypted version is available, with data transmission and storage fully compliant with national confidentiality requirements.

7.6 Edge Computing Base Station Data Centers

Edge data centers are distributed and unattended, requiring high remote management and offline operation capability for access control. The product supports 4G/5G wireless communication modules, enabling networked management without cabling. Offline independent operation capability ensures normal access control operation during network failures, suitable for deployment at remote sites.

7.7 Pharmaceutical/Laboratory Cleanroom Data Centers

Pharmaceutical and laboratory data centers have cleanliness requirements, and personnel access must be controlled. The product housing uses smooth, easy-to-clean materials with no sanitary dead corners, compatible with cleanroom disinfection procedures. Contactless facial recognition access control is optional to reduce the risk of cross-infection through contact.

7.8 Financial Data Centers

The financial industry has extremely high requirements for data security and data center security. This product features comprehensive permission auditing and operation traceability functions, compliant with financial industry regulatory requirements. An optional dual-machine hot standby configuration avoids single points of failure, ensuring high availability of the access control system.

Chapter 8 Product Installation

8.1 Pre-Construction Preparation

8.1.1 Technical Preparation

  • Familiarize with this manual and construction drawings, clarify access control installation positions, cable routing, and equipment points;
  • Confirm the cold aisle door model, dimensions, and opening direction; verify that access control accessories match the door;
  • Confirm on-site power supply locations and network point locations; verify voltage and network parameters meet equipment requirements;
  • Confirm fire protection system interface points and signal types; clarify the linkage wiring plan;
  • Conduct technical briefing for construction personnel, clarifying construction specifications, safety requirements, and quality standards.

8.1.2 Material Preparation

  • Count all equipment and accessories according to the product list; check for transportation damage and verify model specifications match the order;
  • Prepare construction cables including power cables, signal cables, network cables, shielded cables, etc.; verify cable specifications and lengths;
  • Prepare auxiliary materials including PVC conduit, cable clips, expansion bolts, self-tapping screws, terminal blocks, insulating tape, cable ties, etc.;
  • Perform powered pre-inspection of equipment to confirm normal factory functionality, avoiding rework caused by discovering faults after installation.

8.1.3 Tool Preparation

  • Prepare all installation tools according to Section 3.3 of Chapter 3; verify tools are in good working condition; measuring instruments such as multimeters and spirit levels must have verified measurement accuracy. Prepare qualified ladders or scaffolding for elevated work, with proper safety protection measures in place.

8.1.4 On-Site Survey and Positioning

  • Measure cold aisle end door dimensions on site, confirming that door frame and door leaf mounting surfaces are flat without deformation or protrusions;
  • Mark the installation positions of the card reader, exit button, magnetic lock, controller, and power supply;
  • Card reader installation height: bottom edge 1.3m~1.5m from the floor, located on the exterior side of the cold aisle door leaf or side wall, convenient to operate without obstruction;
  • Exit button installation height: bottom edge 1.3m~1.5m from the floor, located on the interior side of the cold aisle, near the door opening side;
  • Magnetic lock installation position: for swing doors, installed centered at the top of the door frame; for sliding doors, installed at the top of the door side;
  • Controller installation position: in the cable tray at the top of the cold aisle or in a nearby weak-current room, ventilated and dry, convenient for maintenance;
  • Power supply installation position: near the controller, wall-mounted or in a cabinet, avoiding humid and high-temperature areas;
  • Plan cable routing paths, avoiding high-voltage lines, heat-generating equipment, and sharp edges; keep a separation distance of ≥20cm between strong-current and weak-current conduits;
  • Confirm on-site wall and floor materials, and select appropriate fixing methods and expansion bolt types.

8.2 Door Pre-Installation and Positioning

If the cold aisle door is not installed, first complete the installation and fixation of the door frame and door leaf according to the cold aisle installation manual. Calibrate the level and verticality — the door frame verticality deviation shall be ≤2mm/m, and the levelness deviation shall be ≤1mm/m.

After door installation is completed, open and close the door repeatedly to confirm smooth operation, smooth door closer action, and no jamming or impact phenomena.

Mark the installation centerlines for the magnetic lock and door sensor on the door leaf and door frame to ensure accurate alignment between the lock body and the armature plate, with a flush and gap-free contact surface.

8.3 Magnetic Lock Installation

8.3.1 L-Bracket Installation (Common for Swing Doors)

1. Align the L-bracket with the installation marks at the top of the door frame, and mark the screw hole positions with a marker pen.

2. Drill holes with a portable electric drill, insert expansion sleeves, secure the L-bracket to the door frame with screws, and tighten the screws to ensure no loosening.

3. Insert the magnetic lock body into the mounting slot of the L-bracket, pass through the fixing screws, and initially tighten without fully securing, leaving adjustment allowance.

4. Fix the armature plate to the corresponding position on the door leaf via the rubber buffer pad. Tighten the screws only lightly — do not fully lock down.

8.3.2 Alignment and Commissioning

1. Close the door leaf and observe the contact condition between the magnetic lock and the armature plate. Adjust the lock body position so that the two fully mate, with the contact surface ≥95%.

2. Connect temporary power to test the magnetic lock holding force, confirming firm attraction with no offset and no bouncing.

3. After adjustment is complete, tighten all fixing screws, and add anti-loosening washers between the lock body and bracket to prevent loosening during long-term use.

4. Install the lock body decorative cover plate to conceal screws and wiring terminals, maintaining a neat appearance.

8.3.3 Sliding Door Magnetic Lock Installation

  • Sliding doors adopt a side-mounted installation method, with the lock body fixed to the mounting position at the top of the door frame side.
  • The armature plate is fixed to the corresponding position on the door leaf side. Adjust the door leaf roller position to ensure the armature plate fully contacts the lock body when the door is closed.
  • Test that during translation, the door has no scraping, the lock engages properly, and the holding force is normal.

8.3.4 Door Sensor Installation

1. The reed switch portion of the door sensor is installed on the door frame side, and the permanent magnet portion is installed on the corresponding side of the door leaf. The gap between the two shall be ≤5mm.

2. With the door closed, use a multimeter to verify good continuity of the door sensor contacts; the circuit should open when the door is opened.

3. Secure firmly with screws, and route the leads along the door frame wire channel to avoid the leads being pulled during door opening and closing.

8.4 Card Reader Installation

1. For 86-type backbox installation, first pre-embed the 86-type junction box in the door leaf or wall, with the box opening flush with the wall/door surface.

2. Pass the card reader wiring out through the backbox, and connect the pre-routed cables according to the markings.

3. Align the card reader with the backbox holes, tighten with fixing screws, ensuring the panel is straight, tightly fitted, with no loosening or tilting.

4. Apply the protective film on the card reader panel finish to avoid scratches during construction.

8.5 Exit Button Installation

1. Mark the position on the inside of the cold aisle, drill holes, and either pre-embed a backbox or surface-mount directly.

2. Connect the two leads of the button (no polarity distinction).

3. Secure the exit button panel, ensuring smooth pressing and positive spring return with no sticking.

8.6 Access Controller Installation

1. The controller installation location shall be dry, ventilated, and dust-protected, avoiding areas with water leakage, high temperature, or strong electromagnetic interference.

2. Wall mounting: Mark the mounting holes, drill and insert expansion tubes, fix the controller mounting plate to the wall with screws, then clip the controller main unit onto the mounting plate.

3. Cabinet/trunking mounting: Fix the controller to cabinet uprights or cable trough inner walls with self-tapping screws, ensuring secure installation that does not detach under vibration.

4. The controller mounting height shall facilitate wiring and maintenance, with the bottom ≥1.5m above the floor, and positioned away from areas of personnel contact.

8.7 Access Control Power Supply Installation

1. The power supply is wall-mounted in the nearest location or inside the cabinet. The input side connects to the mains supply, and the output side connects to the access controller and locks.

2. The power supply shall be positioned away from water sources and heat sources, with heat dissipation space reserved — maintain ≥10cm clearance on all sides.

3. The power input must be connected to the protective ground wire, with grounding resistance ≤4Ω, ensuring electrical safety.

4. Place the battery into the battery compartment of the power supply enclosure, connect the positive and negative terminals correctly, and secure it firmly to prevent movement.

8.8 Cabling Works

8.8.1 Conduit Installation

1. All cables must be routed through PVC conduits or galvanized steel conduits for protection — no exposed wiring is permitted.

2. Use a conduit bender for turns; no sharp kinks are allowed, and wire pulling must be smooth.

3. Use dedicated couplers or elbows for conduit joints, with firm adhesion. Polish conduit openings smooth to avoid scratching cable insulation.

4. Power and signal cables shall be laid in separate conduits, with parallel spacing ≥20cm. Where crossing, they shall intersect at right angles, avoiding long parallel runs that can cause interference.

8.8.2 Cable Laying

1. Before laying cables, check that the cable outer sheath has no damage or breaks, and use a multimeter to verify continuity.

2. Reserve 30cm of slack at both cable ends for termination and maintenance.

3. Use a wire-pulling fish tape when pulling cable through conduits. Do not pull forcefully, to avoid damaging conductors and the screen/shield.

4. Label both ends of each cable, indicating the purpose and the termination points at each end, to facilitate later termination and fault tracing.

5. After cabling is complete, dress the cables and bind them neatly with cable ties, keeping them straight, level, and aesthetically compliant.

8.9 Earthing Works

1. All metal equipment enclosures of the access control system and the screens of screened cables must be reliably earthed.

2. The earthing down-conductor shall use ≥1.5mm² stranded copper wire, connecting to the equipment room earthing copper bar, with earthing resistance ≤4Ω.

3. The cable screen shall be earthed at one end only, to avoid forming earth loops that introduce interference.

4. The power protective earth and equipment earth shall be connected separately and ultimately converge into the same earthing system.

8.10 Installation Appearance and Quality Inspection

  • All equipment shall be installed squarely and securely, without loosening or tilting, and the surfaces free from scratches and stains.
  • Door opening and closing shall be smooth, lock engagement noiseless, and the door closer force moderate.
  • Cabling shall be neat and aesthetically routed, with clear identification and no exposed cables. Conduits shall be securely fixed.
  • All screws shall be fully tightened with none missing, and anti-loosening washers correctly installed.
  • The site shall be cleaned up, with construction debris completely removed.

9.1 Cable Selection Specifications

9.1.1 Power Cables

Application Cable Specification Remarks
Mains input RVV 3×1.5mm² stranded copper For 220V power supply input
Lock power supply RVV 2×1.0mm² stranded copper For distance ≤10m
Lock power supply RVV 2×1.5mm² stranded copper For distance 10–20m
Lock power supply RVV 2×2.5mm² stranded copper For distance >20m; to avoid excessive voltage drop resulting in insufficient lock force
Controller power supply RVV 2×0.75mm² stranded copper —

9.1.2 Signal Cables

Application Cable Specification Remarks
Card reader signal RVVP 4×0.5mm² shielded Contains power +, power GND, D0, D1; transmission distance ≤100m
Exit button wire RVV 2×0.5mm² stranded copper Non-polarized
Door sensor signal RVV 2×0.5mm² stranded copper —
Fire alarm linkage wire RVVP 2×0.5mm² shielded —
RS485 communication wire RVSP 2×0.75mm² twisted shielded pair Transmission distance ≤1200m
Network communication wire Cat5e UTP Transmission distance ≤100m

9.1.3 Cable Selection Notes

  • All cables must be national-standard copper-core wires. Copper-clad aluminum and iron-core wires are prohibited.
  • The screen of shielded cables must be intact without damage.
  • Different types of signals shall not share a single cable, and power/signal cables shall not be routed in the same conduit.
  • Cable joints must be soldered or terminated with crimp terminals. Direct twisting/wrapping connections are prohibited.

9.2 General Wiring Specifications

1. Power-off operation: All wiring operations must be performed with power completely disconnected. Live wiring is strictly prohibited to prevent short circuits and equipment damage.

2. Wire-end treatment: Strip the cable ends to a suitable length (approximately 5–8mm). Do not leave exposed conductors overly long (causing short circuits) or too short (causing poor contact). Twist the strands of multi-strand cores tightly and terminate with cold-press crimp terminals to avoid loose strands.

3. Terminal wiring: Tighten terminal screws, verify the wire does not pull out with light tugging, and torque down a further half-turn for anti-loosening. Avoid clamping the screw onto the insulation to prevent false connections.

4. Polarity distinction: Strictly distinguish positive and negative terminals for DC-powered equipment. Red is positive, black is negative. Reversed polarity may damage equipment.

5. Screen treatment: The screen of shielded cables shall be earthed at the controller GND end only, with the other end left floating. Do not earth both ends.

6. Identification management: After wiring, fit each cable with a numbered ferrule, marking the conductor number and function for ease of later maintenance.

7. Insulation protection: Wrap exposed connection parts with insulating tape or heat-shrink tubing to prevent short circuits.

8. Wiring sequence: First connect the low-voltage signal terminals, then the DC power supply terminals, and finally the mains input. Before powering up for testing, recheck the wiring and confirm correct, then energize.

9.3 Access Controller Wiring Details

The controller terminal area is divided into five zones — power supply terminals, card reader terminals, lock output terminals, input terminals, and communication terminals. Each terminal is marked with silkscreen identification; connect according to the markings.

9.3.1 Power Terminal Wiring

  • Terminal markings: 12V+, GND
  • Connection method: Connect the DC 12V positive output from the access control power supply to the controller 12V+ terminal, and the negative to the GND terminal.
  • Notes: Confirm the voltage is DC 12V, and do not reverse the polarity. Measure the power supply output voltage as normal before connecting to the controller.

9.3.2 Card Reader Terminal Wiring

A standard Wiegand card reader has 4 wires: 12V, GND, D0, D1:

Card Reader → Controller Terminal
12V → Reader 12V
GND → Reader GND
D0 → W0/D0
D1 → W1/D1

Notes:

  • D0 and D1 have no polarity, but they must not be reversed, otherwise card reading will be unresponsive.
  • When the card reader is powered from the controller, the distance shall not exceed 50m. For longer distances, the reader must be powered separately with a common earth connection.
  • The screen shall be connected to the controller GND side.

9.3.3 Lock Output Terminal Wiring

The controller lock output is a relay dry contact, marked as LOCK_NO, LOCK_COM, LOCK_NC.

Standard connection for magnetic lock (fail-secure, powered-to-lock type):

From → To
Access control power 12V+ → Controller LOCK_COM
Controller LOCK_NC → Magnetic lock positive
Magnetic lock negative → Power supply GND

Principle: Normally, the COM–NC contacts are closed, so the magnetic lock remains energized and locked. When a card is presented to open the door, the relay operates, COM and NC open, the magnetic lock de-energizes, the holding force is released, and the door can be opened. After the delay elapses, the relay resets and the lock is re-energized to lock.

Supplementary notes:

  • For an electric bolt lock (fail-open, powered-to-unlock type), connect to NO and COM. Normally open; when unlocking, it conducts and energizes.
  • Ensure the lock operating voltage matches the power supply output.
  • The lock current is considerable. Verify that the relay contact rating is sufficient. For high-current locks, an external relay must be added for capacity expansion.

9.3.4 Exit Button Wiring

  • Terminal markings: PUSH, GND (or BUTTON_IN, GND)
  • Connection method: Connect the two wires of the exit button to PUSH and GND respectively. No polarity.
  • Principle: Pressing the button completes the circuit; the controller detects the conduction signal and triggers unlocking.

9.3.5 Door Sensor Wiring

  • Terminal markings: SENSOR, GND (or door sensor input, GND)
  • Connection method: Connect the two wires of the door sensor reed switch to the door sensor input terminal and GND respectively. No polarity.
  • The door sensor type (normally-open/normally-closed) can be set in software to match the actual sensor.

9.3.6 Fire Alarm Linkage Wiring

  • Terminal markings: FIRE, GND
  • Connection method: Connect the two outputs of the fire alarm system dry contact to FIRE and GND respectively.
  • Note: The fire alarm signal is a passive dry contact — connecting mains power is prohibited. For applications requiring galvanic isolation, use an external fire alarm linkage module for isolation.

9.3.7 Communication Terminal Wiring

  • TCP/IP communication: Insert the RJ45 plug of the network cable into the controller network port, and connect the other end to the equipment room switch.
  • RS485 communication: Connect 485A to the controller A terminal, 485B to the B terminal. Install 120Ω termination resistors at both ends of the bus.

9.3.8 Alarm Output Wiring

  • Terminal markings: ALARM_NO, ALARM_COM
  • Connect the audible/visual alarm positive to ALARM_NO, the negative to the power supply GND, and the power supply 12V+ to ALARM_COM.
  • On alarm, the relay closes, energizing the alarm device.

9.4 Access Control Power Supply Wiring

9.4.1 Mains Input Wiring

  • Power supply input terminals: L (live), N (neutral), G (earth)
  • Connection: Connect the mains live to L, neutral to N, and the protective earth to G.
  • A circuit breaker must be installed in front of the input for power-off maintenance.

9.4.2 DC Output Wiring

  • Output terminals: +12V, GND
  • Connect the output positive to the access control system supply positive, and the negative to the common ground.
  • For multiple outputs, note that the total current must not exceed the rated current of the power supply.

9.4.3 Battery Wiring

  • Battery terminals: BAT+, BAT−
  • Connect the battery positive to BAT+, and negative to BAT−. Reversing the polarity is strictly prohibited.
  • After first connecting the battery, the power supply automatically enters float charge state.

9.5 Wiring Inspection Standards

1. All wiring corresponds one-to-one with terminal markings — no wrong or missed connections.

2. Use the multimeter continuity mode to test each circuit — no short circuits, no open circuits.

3. Measure the power supply output voltage as normal, with correct polarity.

4. All wiring terminals shall be tight, with no false or loose connections; light tugging on wires shall not pull them out.

5. The screen earth connection is correct with no earth loops.

6. Cable identification is clear, accurate, and consistent with the drawings.

7. No exposed conductors; insulation protection is in place.

9.6 Common Wiring Errors and Avoidance

Error Hazard Avoidance
Reversed polarity May burn out equipment Re-measure the voltage polarity with a multimeter before power-up; strictly follow red-positive/black-negative at the device end
Connecting the lock directly to the controller High-current locks must be powered directly from the power supply; the controller only performs switching control, otherwise the controller relay may burn out Use a dedicated lock power supply circuit
Earthing the screen at both ends Forming a ground potential difference, introducing interference, causing unstable communication Strictly single-end earthing
Insufficient wire gauge For long-distance lock supply lines, insufficient gauge causes excessive voltage drop, reducing lock holding force Select the correct gauge based on distance
Power and signal in the same conduit Introduces electromagnetic interference, causing insensitive card reading and communication anomalies Separate conduits with adequate spacing
False/loose connections Scattered strands or screw clamped onto insulation causing intermittent faults After wiring, lightly pull to confirm the connection is secure

10.1 Comprehensive Pre-Power-On Inspection

1. Recheck all wiring to confirm no wrong connections or short circuits, especially the power supply polarity and mains input wiring.

2. With all equipment switches off, close the mains main breaker and measure the power supply input voltage as normal.

3. Confirm that all equipment has no water ingress, no short circuits, and no metal debris on the circuit boards.

4. Prepare a multimeter to monitor voltage status at any time; immediately cut power if any abnormality appears.

10.2 Single-Unit Power-On Commissioning

10.2.1 Power Supply Power-On Test

1. Close the access control power supply input breaker; the power indicator LED lights up.

2. Use a multimeter to measure the DC output voltage at the power supply output — it should be DC 12V ±0.5V, stable and without fluctuation.

3. Test battery switching function: Disconnect the mains input, measure the output voltage as normal, and the battery power indicator lights up. Restore mains power — the unit automatically switches back to mains supply, and the charging indicator operates normally.

4. Test short-circuit protection: Briefly short the output terminals; the power supply automatically protects with no output. After removing the short, normal operation resumes.

10.2.2 Controller Power-On Test

1. Close the controller power supply breaker; the controller power indicator lights up and the running indicator flashes.

2. Observe that the controller has no abnormal heating, no odor, and no smoke.

3. Use a multimeter to measure the voltage at each controller output port as normal, with no abnormal outputs.

10.2.3 Card Reader Power-On Test

1. The card reader indicator lights up; in standby state it is typically a steady red LED or slow flashing.

2. Approach the card reader with a test card — the reader should emit a “beep”, the indicator turns green, indicating normal card reading.

3. Test the card reader tamper function: tamper with the reader panel; the controller should receive a tamper alarm signal.

10.2.4 Lock Power-On Test

1. Temporarily energize the magnetic lock — the lock body produces holding force, attracting the armature plate, with no abnormal noise.

2. After power-off, the holding force disappears immediately, with no significant residual magnetism, and the armature plate can be separated easily.

3. Cycle power on/off 10 times consecutively — the lock operates normally with no jamming or failure.

10.3 System Function Joint Commissioning

10.3.1 Card Access Opening Commissioning

1. Through the management software or controller keypad, register a test card with access permissions.

2. Swipe the test card outside the cold aisle — the card reader beeps, the controller outputs the unlock signal, and the magnetic lock releases.

3. Push the door open; the door sensor detects the open-door signal and the controller records the door open event.

4. Release the door; it automatically closes under the door closer action. The magnetic lock re-energizes and attracts, and the door sensor detects the door closed signal.

5. Test the door open delay function: Modify the unlock delay parameter and verify the delay time accuracy.

6. Test an unauthorized card: Swipe an unregistered card — no response or an error prompt at the reader, the lock does not operate, and access control operates correctly.

10.3.2 PIN Code Access Commissioning (Keypad models)

1. Register a test PIN code; enter the correct PIN on the keypad and the lock unlocks normally.

2. Enter an incorrect PIN — the lock does not operate. After consecutive errors reach the limit, the keypad locks.

3. Test the “card + PIN” dual authentication mode — both presenting the card and entering the correct PIN must occur to open the door.

10.3.3 Exit Button Commissioning

1. Press the exit button inside the cold aisle — the lock immediately unlocks and the door can be pushed open.

2. Release the button; after the delay, the lock re-locks.

3. Press the button 10 times consecutively; each press must successfully trigger unlocking with no failure.

10.3.4 Door Sensor and Alarm Commissioning

1. With the door closed, the management software displays the door status as “Closed”.

2. Manually push the door open — the software displays the door status as “Open”, with real-time accurate status switching.

3. Set the door left open timeout to 30 seconds. Hold the door open; after 30 seconds, a timeout alarm is triggered, the audible/visual alarm activates, and an alarm message appears in the software.

4. Close the door — the alarm automatically clears.

10.3.5 Fire Alarm Linkage Commissioning

1. Simulate a fire alarm signal by shorting the fire alarm input terminals.

2. The access control system immediately unlocks, the magnetic lock releases, and an alarm output is simultaneously triggered.

3. The management software displays the “fire alarm linkage” event and records the trigger time.

4. Disconnect the fire alarm signal; the access control system returns to normal control state.

5. Repeat the test 3 times; each test must trigger reliably with no missed or false triggers.

10.3.6 Power Failure Unlock Test

1. Disconnect the mains input of the access control power supply — the system switches to battery power and access control still manages normally.

2. Disconnect the battery supply — with complete power off, the magnetic lock automatically releases and the door can be pushed open freely.

3. Restore power — the lock automatically re-locks and the system returns to normal operation.

10.4 Management Software Commissioning

10.4.1 Communication Connection Commissioning

1. Set the correct IP address, subnet mask, and gateway on the controller, ensuring it is on the same network segment as the management computer.

2. Add the controller device in the management software, search, and connect.

3. Test communication stability: Ping the controller continuously for 10 minutes — no packet loss or interruptions.

4. Test RS485 communication (if used) — all controllers on the bus must communicate normally with no packet loss.

10.4.2 Access Permission Commissioning

1. Add personnel information in the software and register card, fingerprint, and face data.

2. Assign door access permissions and valid time periods, and download to the controller.

3. Test on-site that the permissions take effect — authorized personnel can open the door, unauthorized personnel cannot.

4. Test permission modification and deletion — modifications take effect in real time and data synchronizes correctly.

10.4.3 Records and Alarm Commissioning

1. Perform multiple door-open, button, and alarm operations — the software receives event records in real-time with no omissions.

2. Test record query, filtering, and export functions — data is accurate and complete.

3. Test alarm notification functions — after triggering an alarm, the software pop-up and audible prompts work normally.

10.4.4 Linkage Function Commissioning

1. If integrated with the cold aisle lighting system, test that lighting automatically turns on when a card opens the door, and turns off after a delay.

2. If integrated with the environment monitoring system (EMS), test that the access control data uploads to the EMS platform and the status display is correct.

3. Test the linkage with the skylight fire alarm — when the fire alarm signal triggers, the access control and skylight act simultaneously.

10.5 Performance and Stability Commissioning

10.5.1 Continuous Operation Test

Run the system continuously for 24 hours with power applied. During this period, perform card swiping and door opening at scheduled intervals. The equipment must run stably with no crashes, restarts, or functional failures.

10.5.2 Concurrency and Stress Test

In a multi-door networked scenario, simultaneously perform card operations at multiple points — the system responds normally with no lag or data loss. The management software simultaneously processes data from multiple controllers with smooth operation.

10.5.3 Anti-Interference Test

Start interference sources near the access control equipment such as electric drills and two-way radios — the card reading and communication functions must operate normally with no false actions or data loss, verifying the anti-interference capability meets requirements.

10.6 Commissioning Completion

1. After all functional tests pass, organize the controller parameter configuration and back up the configuration files.

2. Clean up excess wire ends at the wiring terminals, dress the cables in the enclosure, and close the equipment cover plates.

3. Fill out the commissioning record, documenting commissioning items, test results, and parameter configurations, with signatures from both parties for confirmation.

4. Provide operation training to the owner’s operations and maintenance personnel, covering daily usage and simple fault handling methods.

11.1 Construction Safety Precautions

1. Use qualified ladders or scaffolding for work at height, wear safety helmets, and strictly prohibit dropping objects from height.

2. Electrical work must be performed with power disconnected — live wiring is strictly prohibited. Hang a “Construction in Progress — Do Not Close” sign on the distribution box.

3. When using power tools such as impact drills or electric drills, wear protective goggles and comply with power tool safety operating procedures.

4. On-site construction shall comply with the equipment room safety management regulations. Touching running equipment room equipment and unauthorized wiring of power supplies is strictly prohibited.

5. Protect the construction area to prevent debris from falling into the cold aisle or equipment.

6. At the end of each day’s construction, disconnect the construction power supply, clean the site, and confirm no safety hazards before leaving.

11.2 Installation Operation Precautions

1. Before installation, verify model and specification match the design — mixing unmatched accessories is prohibited.

2. The magnetic lock must be installed with the lock body and armature plate fully mating. The mating surface must be free of foreign objects, paint, or adhesive layers — otherwise the holding force will decrease.

3. The armature plate shall not be over-tightened; retain the clearance allowance of the rubber buffer pad to avoid door leaf deformation affecting proper contact.

4. Install the card reader away from strong magnetic fields and large metal obstructions to avoid affecting reading distance and sensitivity.

5. When installing equipment on glass doors, never drill forcibly — use dedicated glass drilling tools to prevent glass breakage.

6. All fixing screws must be fitted with anti-loosening washers or thread-locking adhesive to prevent loosening from long-term door vibration.

7. Protect the door sealing rubber strips and brushes during installation — damage will affect the sealing effectiveness.

8. After equipment installation, remove protective film and clean surface smudges to avoid residual adhesive marks.

11.3 Wiring Operation Precautions

1. Strictly follow the principle “signal first, power last; disconnect power before wiring”. Live work is strictly prohibited.

2. Before wiring, confirm the input voltage matches the device rated voltage — overvoltage supply is strictly prohibited.

3. DC equipment polarity must be correctly matched — reversed polarity may permanently damage equipment. Confirm polarity with a multimeter before wiring.

4. All connections must use crimped terminals or soldering — direct twisted connections are prohibited to prevent poor contact and overheating.

5. Exposed conductors shall not be overly long to prevent short circuits. Apply insulation protection after wiring.

6. The cable screen shall be earthed at one end only — earthing both ends creates a ground loop, introduces interference, and may damage equipment.

7. Cables of different voltage levels and different signal types shall not be laid in the same conduit or trunking.

8. After wiring, a comprehensive check is mandatory — confirm no short circuits or wrong connections before energizing.

11.4 Commissioning and Operation Precautions

1. Someone must be present during initial power-up, observing for smoke, odor, or abnormal heating. Immediately cut power upon any abnormality.

2. Commission in sequence: single-unit test → partial joint test → system joint test, to avoid expanding faults by energizing everything at once.

3. Follow the principle “backup first, then modify” for parameter changes; save configuration in a timely manner after modification.

4. Fire alarm linkage commissioning must be coordinated with the fire system manager — do not trigger the main fire system without authorization.

5. Keep records during commissioning, documenting abnormal phenomena in detail for later analysis and troubleshooting.

6. Before system delivery, restore the default administrator password and set a strong password to avoid security risks from weak passwords.

11.5 Daily Use Precautions

1. When swiping a card, present it close to the reader sensing area; only push the door after a successful prompt. Do not swipe rapidly and repeatedly.

2. Prohibit striking or scratching the card reader panel and glass with hard objects, and prohibit violent impact on the door and lock.

3. Open and close the door gently — avoid hard impacts to prevent damage to the lock and door hardware.

4. Prohibit hanging heavy objects on the door and blocking the card reader or access control equipment.

5. Personnel leaving the cold aisle should close the door promptly, avoiding prolonged door opening causing cold air loss and triggering alarms.

6. Unauthorized disassembly of access control equipment or modification of wiring is prohibited — contact professional technical personnel for any modifications.

7. Take good care of access control cards. Report and invalidate lost cards promptly to prevent unauthorized persons from entering the cold aisle.

8. Keep equipment surfaces clean and dry. Avoid water splashes and heavy dust accumulation. Use a dry cloth for cleaning — wet cloth and corrosive cleaning agents are strictly prohibited.

11.6 Environment and Storage Precautions

1. Maintain a dry, ventilated operating environment for equipment, avoiding dampness, standing water, and high temperatures.

2. Controllers and power supplies shall not be installed in direct sunlight or near heat sources.

3. For long-term idle equipment, disconnect power and store in a dry, dust-protected, corrosion-free gas environment.

4. Batteries in long-term storage require periodic recharging to avoid damage from deep discharge.

12.1 Daily Inspection and Maintenance (Daily)

Performed by the equipment room duty or operations personnel. Inspection items:

  • Visually check that access control equipment has a sound appearance — no damage, no tilting, no obvious stains.
  • Test that card access opening works normally, lock action is smooth, and there are no abnormal sounds.
  • Check that the exit button presses and returns normally without sticking.
  • Verify that the door closes with good sealing, no visible gaps, and the lock engages correctly.
  • Check that indicator light status is normal, with no abnormal alarm lights staying lit.
  • Check that cables have no exposed conductors or damage, and conduits have no detachment.

12.2 Monthly Maintenance

Performed by professional operations and maintenance personnel. Maintenance items:

  • Clean dust from card reader, controller, and power supply surfaces; keep vents unobstructed.
  • Check all fixing screws for loosening, especially magnetic lock bracket and hinge screws — tighten immediately if loose.
  • Adjust the door closer force and speed if door opening/closing is not smooth.
  • Check door sealing rubber strips and brushes for detachment or aging — repair or replace in time.
  • Review the system operation log via the management software for abnormal alarms or communication interruption records.
  • Test the fire alarm linkage and door-left-open alarm functions.
  • Check the backup battery voltage — charge or replace if too low.
  • Back up the access control system data and configuration files.

12.3 Quarterly Maintenance

Performed by professional technical personnel. Maintenance items:

  • Open the controller and power supply enclosures, clean internal dust, and check circuit boards for oxidation or dampness.
  • Check all wiring terminals for loosening or oxidation; re-tighten terminal screws.
  • Measure the power supply output voltage and battery voltage; assess power supply health.
  • Clean the magnetic lock contact surfaces and armature plate surface, removing rust and smudges to ensure tight contact.
  • Lubricate moving parts such as door hinges and sliding tracks to ensure smooth operation.
  • Test lock holding force and check for decline — investigate promptly if insufficient.
  • Verify reliable earth connections and test earth resistance meets requirements.
  • Upgrade controller and software firmware to the latest stable version to fix known issues.

12.4 Annual Maintenance

Performed by the manufacturer or professional service provider. Maintenance items:

  • Perform comprehensive performance testing of the system and assess equipment aging level.
  • Deep-clean all equipment interiors; check components for bulging, leakage, or overheating marks.
  • Calibrate card reader sensitivity, lock holding force, and sensor thresholds to ensure optimal performance.
  • Replace aging cables, sealing strips, batteries, and other consumable parts.
  • Conduct comprehensive functional and safety testing to identify potential hazards.
  • Issue an annual maintenance report with system optimization and upgrade recommendations.
  • Reconcile the access permission list; remove permissions of departed or expired personnel to ensure system security.

12.5 Fault Repair Process

1. Fault reporting: Upon detection of a fault, record the fault phenomenon, time of occurrence, and equipment model, and contact technical support.

2. Remote troubleshooting: Technical personnel conduct preliminary troubleshooting via phone or remote guidance, determine the cause, and guide on-site resolution for simple problems.

3. On-site repair: For faults that cannot be resolved remotely, dispatch technical personnel for on-site handling. Cut power first and apply safety protection before repair work.

4. Component replacement: After confirming a component is damaged, replace it with the same model genuine spare part. Use of non-compatible substitutes is prohibited. Test the function as normal after replacement.

5. Repair records: Fill out a repair record after the repair is completed, noting the fault cause, handling method, and replaced components, and file for reference.

6. Acceptance confirmation: After repair, verify functional testing is normal and obtain the user’s signature confirming repair completion.

12.6 Consumable Parts Replacement Specifications

12.6.1 Battery Replacement

1. Battery service life is typically 2–3 years. Replace promptly when the age is reached or capacity is insufficient.

2. Before replacement, disconnect the power input and battery switch, and remove the old battery.

3. The new battery model, voltage, and capacity must be the same as the original.

4. Connect the positive and negative terminals correctly — reversing is strictly prohibited. Tighten the terminal connections.

5. After replacement, test the battery switching and charging functions.

6. Old batteries must be recycled as hazardous waste — no discarding.

12.6.2 Magnetic Lock Replacement

1. After cutting power, disconnect the lock wiring and label the wire sequence.

2. Remove the fixing screws and take off the old lock body and bracket.

3. Install the new lock body, adjust alignment, and ensure full contact with the armature plate.

4. Reconnect the wiring according to the labels, energize, and test the holding force and unlocking function.

5. Adjust the door closer force to ensure smooth closing and no impact on lock engagement.

12.6.3 Card Reader Replacement

1. After cutting power, disconnect the card reader wiring and record the wire sequence.

2. Remove the old card reader and clean the mounting surface.

3. Connect the new card reader wires correspondingly, verify correct, and power on for testing.

4. Secure the card reader panel, adjust for squareness, and test normal card reading.

12.7 Repair Safety Specifications

1. All repair operations must be performed with power off. Live work may only be performed by a certified electrician with proper insulation protection.

2. Replacement parts must be authentic original parts. Use of inferior parts that may expand faults or create safety hazards is prohibited.

3. During repair, protect the equipment room environment — arrange tools and materials neatly to prevent debris from falling into equipment.

4. Repairs involving fire alarm linkage functions require notification of the fire management personnel. Restore the linkage function after the repair and test it.

5. After repair, clean the site, restore the equipment to its original appearance, and confirm no tools or debris are left behind before leaving.

13.1 Access Recognition Faults

Fault 1: No response when swiping card, card reader indicator does not light up

Cause analysis:

  • Card reader power circuit open circuit or poor contact
  • Card reader power polarity reversed
  • Card reader itself damaged
  • Controller card reader power port failure

Troubleshooting steps:

1. Cut power, check card reader wiring, confirm 12V and GND connections are correct, with no looseness or open circuits.

2. With power on, measure the supply voltage at the card reader end with a multimeter — should be approximately 12V.

3. If no voltage, trace the line back to the controller end and measure the controller card reader output voltage.

4. If voltage is present at the controller end but absent at the card reader end, the wiring is open — replace or repair the cable.

5. If no voltage at the controller end, check the controller power supply and port settings, confirming the port power output is enabled.

6. If voltage is normal but the reader does not light up, replace with a spare card reader for testing. If normal after replacement, the original reader is damaged.

Solutions:

  • Wiring issues: re-terminate crimp connectors, repair open circuit points, replace damaged cables.
  • Reverse polarity: swap the positive and negative connections.
  • Equipment damage: replace with the same model card reader and re-register permissions for testing.

Fault 2: Card reader lights up, but no response when swiping and door does not open

Cause analysis:

  • Wiegand data lines D0/D1 reversed or open circuit
  • Wiegand protocol mismatch between reader and controller
  • Card reader damaged, card reading function failed
  • Card damaged or not authorized
  • Controller card reader interface damaged

Troubleshooting steps:

1. First test with a known authorized card to rule out card non-authorization issues.

2. Cut power, check D0/D1 wiring, confirm corresponding connection to the controller, with no looseness or reversal.

3. Use the multimeter continuity mode to test the data lines, ruling out open circuits.

4. Enter the controller settings and confirm the Wiegand protocol (WG26/WG34) matches the card reader.

5. Replace with a spare card reader for testing to determine whether the fault is the reader or the controller interface.

Solutions:

  • Wiring problems: reconnect data lines correctly and tighten terminals.
  • Protocol mismatch: modify the Wiegand protocol settings in the controller.
  • Card problems: replace with a new card and re-authorize.
  • Hardware damage: replace the corresponding faulty device.

Fault 3: Short reading distance, insensitive card reading

Cause analysis:

  • Large metal mounting surface causing a shielding effect
  • Dirt, scratches, or metal stickers on the card reader surface
  • Insufficient supply voltage reducing reading power
  • Strong electromagnetic interference sources nearby
  • Card reader antenna offset or aging

Troubleshooting steps:

1. Clean the card reader surface and remove obstructions.

2. Measure the card reader supply voltage and confirm it is within the rated range.

3. Check for high-power equipment, frequency converters, or power cables near the reader.

4. Temporarily remove the reader from the mounting surface and test whether the reading distance recovers.

5. If the metallic mounting surface is the cause, add an insulating spacer or use a non-metallic mounting backbox.

Solutions:

  • Metal shielding: insert a 3–5mm thick insulating spacer between the reader and the mounting surface.
  • Interference: adjust wiring away from interference sources, or replace with a shielded card reader.
  • Insufficient voltage: check the supply line, replace with a heavier gauge cable, or supply power locally.
  • Equipment aging: replace the card reader.

Fault 4: Keypad input ineffective

Cause analysis:

  • Keypad data line connection fault
  • Keypad locked due to excessive error attempts
  • PIN not correctly registered or expired
  • Keypad keys damaged

Troubleshooting steps:

1. Wait for the lockout period to end, or restart the controller to clear the lockout.

2. Check the keypad wiring and confirm secure connection.

3. Re-register a test PIN and verify PIN function.

4. Test each key individually to determine whether any keys are non-functional.

Solutions:

  • Lockout issue: reset the keypad lockout and set a reasonable error attempt count.
  • Wiring problem: reconnect the data cable properly.
  • Key damage: replace the keypad or card reader.

13.2 Lock Faults

Fault 5: Card swipe is acknowledged, but the lock does not open; magnetic lock remains engaged

Cause analysis:

  • Lock power supply circuit open; controller unlock signal not delivered
  • Controller lock relay damaged, no output
  • Incorrect magnetic lock wiring — not controlled through the controller relay
  • Lock mechanism mechanically stuck or excessive residual magnetism
  • Unlock delay set to 0; instantaneous unlock not noticed

Troubleshooting steps:

1. Listen for the relay click sound at the controller during unlocking, or use a multimeter to measure the voltage change at the lock output terminals.

2. Measure the voltage across the magnetic lock terminals when swiping — under normal unlocking, the voltage should drop to zero.

3. If the voltage does not change, check the controller relay output and wiring.

4. If the voltage is already disconnected but the lock still holds, disconnect the lock wiring and test whether it can be separated, to determine residual magnetism or mechanical jamming.

5. Check the unlock delay setting in the software; increase the delay and test.

Solutions:

  • Wiring error: reconnect the lock circuit according to the correct wiring diagram.
  • Relay failure: replace the controller or add an external relay for capacity expansion.
  • Residual magnetism: clean the contact surfaces, adjust the armature plate gap; if residual magnetism is severe, replace the magnetic lock.
  • Delay issue: increase the unlock delay in the software — 3–5 seconds is the default recommendation.

Fault 6: Insufficient magnetic lock holding force; the door can be pushed open with force

Cause analysis:

  • Lock body and armature plate do not fully contact — gaps or foreign objects present
  • Insufficient supply voltage — thin wire gauge, long distance, high voltage drop
  • Magnetic lock coil aging, reduced power
  • Armature plate fixed too tightly, rubber buffer pad not functioning, uneven force distribution on the contact surface
  • Lock body installation offset, insufficient contact area

Troubleshooting steps:

1. Check the contact surface for dust, paint, or pads. Clean and retest the holding force.

2. Observe the contact condition between the lock body and armature plate. Check for gaps after closing, and adjust alignment.

3. Measure the voltage at the lock body end under power. Below 11V indicates a voltage drop problem.

4. Check the armature plate fixing screws. Loosen appropriately to retain the clearance allowance.

5. Connect 12V directly to the lock body and test the holding force. If still insufficient, the lock body itself is aging.

Solutions:

  • Poor contact: adjust lock body and armature plate position for full contact, and clean the contact surfaces.
  • Voltage drop: replace with a heavier gauge supply cable, or install a power supply nearby.
  • Installation problem: adjust the armature plate tightness to ensure full contact when engaged.
  • Lock aging: replace with the same specification magnetic lock.

Fault 7: Magnetic lock overheating

Cause analysis:

  • Supply voltage too high, exceeding the rated voltage
  • Lock body continuously energized for extended periods with poor heat dissipation
  • Partial short circuit in the lock coil, excessive current
  • Gaps in the contact surface, high magnetic reluctance, causing increased coil current and heating

Troubleshooting steps:

1. Measure the lock supply voltage and confirm it is within the rated range.

2. Check the contact surface contact condition for gaps or foreign objects.

3. Measure the lock operating current and compare to the rated current. Excessive current may indicate a coil short circuit.

Solutions:

  • Voltage too high: adjust the power supply output voltage to the rated value.
  • Poor contact: adjust the installation for full contact, reducing magnetic reluctance.
  • Coil fault: replace the magnetic lock to avoid damage or even fire from prolonged overheating.

Fault 8: Lock does not automatically engage after door closes

Cause analysis:

  • Door closer force insufficient; door does not close fully
  • Door leaf deformed or sagging, causing lock misalignment
  • Lock supply fault; power not restored after closing
  • Controller relay contacts welded, permanently in the unlocked state

Troubleshooting steps:

1. Manually push the door fully closed and observe whether the lock engages — determine whether the door is not fully closed.

2. Adjust the door closer force and speed to ensure the door closes fully.

3. Measure the lock voltage after closing to confirm the power supply is restored.

4. Power-cycle the controller and test whether the relay returns to normal. If still welded, replace the relay.

Solutions:

  • Door closer problem: adjust the hydraulic valve on the door closer to increase closing force.
  • Door leaf deformation: adjust the door hinges and correct the door leaf position.
  • Relay welding: replace the controller relay or the entire unit.

13.3 Power System Faults

Fault 9: Power indicator does not illuminate, system completely unpowered

Cause Analysis:

  • Mains power failure or air circuit breaker tripped
  • Power input fuse blown
  • Power input terminal wiring loose or disconnected
  • Power module damaged

Troubleshooting Steps:

1. Check whether mains power supply is normal and whether the air circuit breaker has tripped

2. Check the power input wiring and measure whether the input terminal voltage is 220V

3. Inspect whether the power fuse is blown; replace with a fuse of the same specification for testing

4. If input is normal but there is no output, determine whether the power module is damaged

Solutions:

  • Mains issue: Restore mains power supply and close the tripped circuit breaker
  • Blown fuse: Replace with a fuse of the same specification, investigate the short circuit cause before restoring power
  • Loose wiring: Re-tighten the input wiring terminals
  • Power supply damage: Replace with an access control dedicated power supply of the same model

Fault 10: After mains power failure, battery does not supply power, system shuts down immediately

Cause Analysis:

  • Battery wiring loose or reversed polarity
  • Battery depleted or damaged, no output
  • Power battery management circuit faulty, unable to switch to battery power
  • Battery switch not turned on

Troubleshooting Steps:

1. Check whether the battery switch is in the ON position

2. Measure battery terminal voltage — normal should be above 12V; below 10V indicates depletion or damage

3. Inspect battery wiring, confirm positive and negative terminals are correct and terminals are tightened

4. If battery voltage is normal but cannot supply power, determine whether the battery switching circuit is faulty

Solutions:

  • Wiring issue: Correctly connect battery positive and negative terminals, tighten terminals
  • Battery depleted: Charge for 8 hours and test; replace the battery if still unusable
  • Power supply fault: Repair or replace the access control power supply

Fault 11: Power supply output voltage fluctuates significantly, system operates intermittently

Cause Analysis:

  • Unstable mains input voltage
  • Power supply overloaded, exceeding rated current
  • Output line has loose connections or short circuit hazards
  • Internal voltage regulator circuit fault in power supply

Troubleshooting Steps:

1. Measure mains input voltage to confirm it is within allowable range

2. Disconnect part of the load and measure whether voltage stabilizes to determine if overloaded

3. Inspect output lines for loose connections, heating, or short circuit points

4. Test power supply output voltage under no-load conditions; if still fluctuating, the power supply itself is faulty

Solutions:

  • Unstable mains: Install a voltage stabilizer or UPS at the front end
  • Overloaded: Replace with a higher-power supply, or use separate power supplies for different loads
  • Wiring issue: Repair loose connections, eliminate short circuit points
  • Power supply fault: Replace with a regulated power supply

13.4 Communication Faults

Fault 12: Management software cannot discover the controller, communication fails

Cause Analysis:

  • Network cable/communication line broken or incorrectly connected
  • Controller IP address incorrectly configured, not on the same subnet as the computer
  • Switch port faulty or network not communicating
  • Controller communication port damaged
  • Firewall or antivirus software blocking the communication port

Troubleshooting Steps:

1. Check network cable connection, use a cable tester to verify connectivity

2. Verify controller IP address, subnet mask, and gateway settings; compare with computer subnet

3. Ping the controller IP from the computer to test connectivity

4. Try a different switch port to rule out switch issues

5. Temporarily disable computer firewall and antivirus software to test for port blocking

6. For RS485 communication, check if A/B lines are reversed and verify termination resistor is correct

Solutions:

  • Wiring issue: Re-terminate RJ45 connectors, repair or replace communication cables
  • Configuration error: Modify controller IP to match computer subnet, ensure gateway is correct
  • Port blocked: Open the access control communication port (default 8000) and add to firewall whitelist
  • Hardware fault: Replace controller communication module or the entire unit

Fault 13: Communication intermittent and unstable

Cause Analysis:

  • Poor line contact, oxidized RJ45 connectors
  • Strong electromagnetic interference nearby
  • Network IP conflict
  • Communication distance too long, signal attenuation
  • Controller firmware bug

Troubleshooting Steps:

1. Inspect wiring terminals and RJ45 connectors, re-crimp and test

2. Check for high-power interference sources nearby, and whether cables share conduit with power lines

3. Scan network IPs to identify duplicate IP addresses

4. Test whether communication distance exceeds specification; add repeaters for long distances

5. Upgrade controller firmware to the latest version

Solutions:

  • Poor contact: Re-crimp terminals and RJ45 connectors, clean oxidized areas
  • Interference: Replace with shielded cables, avoid interference sources, ensure proper grounding
  • IP conflict: Change controller IP to a unique address
  • Excessive distance: Install signal repeaters or switch to fiber optic transmission

13.5 System Linkage and Alarm Faults

Fault 14: Door sensor status not updating, door opening no response

Cause Analysis:

  • Door sensor wiring broken or loose
  • Distance between door sensor and permanent magnet too far to engage
  • Controller door sensor input port faulty
  • Door sensor type incorrectly set in software (normally open/normally closed reversed)

Troubleshooting Steps:

1. Manually short-circuit the controller door sensor input terminals and check if software status changes; rule out controller port issues

2. Check door sensor wiring and measure continuity

3. With door closed, observe the gap between sensor and magnet; adjust position

4. Verify door sensor parameter settings in software match the actual sensor type

Solutions:

  • Wiring issue: Repair door sensor wiring and tighten terminals
  • Gap too large: Adjust door sensor mounting position to ensure proper alignment when closed
  • Setting error: Modify the normally open/normally closed type in the software

Fault 15: Door access does not unlock after fire alarm signal triggers

Cause Analysis:

  • Fire alarm signal line broken or connected to wrong port
  • Fire alarm signal type mismatch (active/passive reversed)
  • Controller fire linkage function not enabled
  • Fire linkage priority set too low

Troubleshooting Steps:

1. Short-circuit the controller fire input terminals to test if unlock is triggered; rule out controller issues

2. Measure whether the fire alarm signal terminal has output and whether the signal type is dry contact

3. Enter controller settings to confirm fire linkage function is enabled and unlock logic is correct

4. Check fire alarm line continuity and wiring port connections

Solutions:

  • Function not enabled: Enable fire linkage function in both controller and software
  • Signal mismatch: Install a fire linkage module to convert signal type
  • Wiring issue: Repair fire alarm wiring to ensure continuity

Fault 16: Frequent false alarms, door-not-closed alarms when door is actually closed

Cause Analysis:

  • Door sensor poor contact, intermittent connection
  • Door not sealing properly, slight movement causing sensor to disengage
  • Alarm delay time set too short
  • Controller input port affected by interference, false triggering

Troubleshooting Steps:

1. Adjust door sensor position to ensure tight engagement when door is closed

2. Increase the door-open alarm delay time

3. Check whether door sensor wiring shares conduit with power lines, introducing interference

4. Add filter capacitors to door sensor wiring, or replace with shielded cable

Solutions:

  • Door not sealing properly: Adjust door closer and door catch to ensure door fully closes
  • Delay too short: Set alarm delay to 30-60 seconds
  • Interference false triggering: Add shielding to wiring, implement anti-interference measures

13.6 Software and Management Faults

Fault 17: Door opening records lost or incomplete

Cause Analysis:

  • Events not uploaded during communication interruption, no synchronization after recovery
  • Controller storage overflow, old records overwritten
  • Software database corrupted
  • Controller time not synchronized, record timestamps incorrect

Troubleshooting Steps:

1. Manually trigger record upload to see if records can be re-transmitted

2. Check controller storage capacity and whether too many records remain uncleaned

3. Verify controller and server time are synchronized

4. Backup database and repair database files

Solutions:

  • Not synchronized: Manually upload historical records, configure automatic scheduled upload
  • Storage overflow: Regularly export backup records, clear old controller records
  • Time not synchronized: Enable network time synchronization to unify system time
  • Database corrupted: Repair the database or restore from backup data

Fault 18: Permission distribution failed

Cause Analysis:

  • Controller offline, communication interrupted
  • Permission data format error
  • Controller user capacity full
  • Software and controller firmware versions incompatible

Troubleshooting Steps:

1. Check controller communication status to ensure it is online

2. Test distributing a single permission to determine if it is a batch data issue

3. Check the number of controller users to see if capacity limit is reached

4. Verify software and controller versions are compatible

Solutions:

  • Communication issue: Restore controller network connection
  • Capacity full: Clean up expired and unused users to free capacity
  • Version incompatibility: Upgrade software or controller firmware to matching versions

Chapter 14 Product QA

14.1 Basic Knowledge Category

Q1: What is the difference between cold aisle access control and ordinary office access control?

A: Cold aisle access control is specifically designed for data center cold aisle containment scenarios. Compared with ordinary office access control, there are three core differences: First, it must comply with fire protection regulations, automatically unlock upon power failure, and support fire linkage to ensure personnel evacuation; Second, it is adapted to cold aisle containment structures, installation does not compromise airtightness, reducing cold air leakage; Third, it features interference-resistant design for the strong electromagnetic environment of data centers, with higher reliability for 24-hour continuous operation. Ordinary office access control cannot directly meet the fire protection, sealing, and environmental adaptation requirements of cold aisles.

Q2: Must cold aisle access control be configured with fire linkage?

A: According to the requirements of GB 50174 “Code for Design of Data Centers,” evacuation passage doors in computer rooms must be easily openable from the inside during a fire. Cold aisle access control with automatic unlock upon power failure already meets the basic requirements. However, for higher-grade data centers, it is recommended to integrate with the fire linkage system to achieve automatic unlocking of all passage doors upon fire alarm, further enhancing safety. Specific requirements should follow local fire protection review regulations.

Q3: Which is more suitable for cold aisles — magnetic lock or electric bolt lock?

A: The standard configuration for cold aisles is the magnetic lock. Its advantages are automatic unlock upon power failure, fully compliant with fire protection requirements, no mechanical latch, no wear from opening and closing, long service life, and good sealing performance. Electric bolt locks are power-to-unlock type and lock upon power failure, which does not meet fire evacuation requirements. If an electric bolt lock must be used, it requires a fire linkage power-off unlock mechanism, and is therefore only optional for special sliding door scenarios. The magnetic lock solution is the preferred recommendation.

Q4: How long can the access control system last after a power outage?

A: With the standard 7Ah backup battery, a single-door access control system can operate continuously for 4-8 hours after power failure, depending on the number of devices and operating frequency. For longer backup time, a larger capacity battery can be installed, or the system can be connected to the data center UPS power supply.

Q5: Can access control cards be duplicated? How secure is the system?

A: The standard Mifare IC card has encryption mechanisms; ordinary devices cannot directly duplicate the card. Cards in the system have unique serial number authentication, and cloned cards cannot pass verification. For high-security scenarios, CPU cards or national cryptography algorithm cards can be selected to further enhance anti-duplication capability and meet high-level security requirements.

14.2 Installation and Construction Category

Q6: Can access control be retrofitted after the cold aisle is already installed?

A: Yes, it can be retrofitted. Our access control products support post-installation modification without damaging the original door structure, using surface-mount brackets and exposed wiring methods. Construction is simple with a short modification period. Before retrofitting, a site survey of the door structure is required to confirm compatible locking hardware and installation methods.

Q7: Can access control wiring share the same conduit as power lines?

A: Absolutely not. Power lines generate electromagnetic interference, which can cause insensitive card reading, unstable communication, and even device damage. Low-voltage and high-voltage lines must be run in separate conduits, with a parallel separation distance of no less than 20cm and perpendicular crossing at intersections. If space is restricted, galvanized steel conduit shielding must be used while maintaining adequate separation.

Q8: What are the reasons for insufficient magnetic lock holding force after installation?

A: There are four common causes: First, the lock body and armature plate are not in close contact, with gaps or foreign objects causing increased magnetic resistance and reduced holding force; Second, the power supply wire gauge is too thin or distance too long, causing voltage drop and insufficient actual working voltage at the lock; Third, misaligned installation orientation, resulting in insufficient effective contact area; Fourth, the lock itself has quality issues or has aged. Following the manual during installation to adjust alignment and selecting appropriate wire gauge will ensure rated holding force.

Q9: Must the access controller be installed inside the cold aisle?

A: Not necessarily. The controller can be installed in the cable tray at the top of the cold aisle, a nearby weak current room, inside a cabinet, or other locations. The principles are good ventilation, dryness, easy maintenance access, and avoidance of strong interference sources. It is not recommended to install inside the cold aisle to avoid low-temperature condensation affecting equipment lifespan, and to allow external maintenance without frequent entry into the aisle.

Q10: Can a magnetic lock be installed on a glass cold aisle door?

A: Yes. Dedicated glass door clamps and U-brackets are used for installation. No drilling is required — the clamps secure the lock to the glass door reliably without damaging the glass structure. During installation, attention must be paid to matching glass thickness with the bracket, and the glass door must have a frame or reinforced structure to avoid deformation from excessive holding force.

14.3 Operation Category

Q11: What should be done if an access control card is lost?

A: Immediately contact the system administrator to revoke the lost card’s permissions in the access control management software to prevent unauthorized use. Then apply for a replacement card and configure permissions for use. It is recommended to label cards with serial numbers for quick identification and revocation if lost.

Q12: How to reset a forgotten password?

A: If an ordinary user forgets their password, contact the administrator to reset it in the software. If the administrator password is forgotten, the controller reset button can restore factory settings, or contact manufacturer technical support for a super password reset. After resetting, reconfigure parameters and permissions.

Q13: If someone is trapped inside the cold aisle and the door won’t open, what should be done?

A: There are three emergency door opening methods: First, press the interior exit button to open the door; Second, if locked due to power failure, the magnetic lock will automatically release upon power loss and the door can be pushed open directly; Third, use the mechanical emergency key to open from outside, or manually push the lock body to release from inside. If the door still cannot be opened, immediately contact the data center duty personnel and technical support. Forcible door breaking is strictly prohibited.

Q14: How to turn off the continuous alarm from the access control system?

A: First check the alarm cause. If it is a door-not-closed alarm, close the door properly. If it is a tamper alarm, secure the device cover. If it is an unauthorized intrusion alarm, verify personnel identity. After confirming no abnormality, acknowledge and clear the alarm in the management software. If it is a false alarm due to fault, contact technical personnel to investigate. Do not simply disconnect power to disable the access control system.

Q15: Can the door be opened remotely?

A: Yes. The management software supports remote manual door opening. The administrator selects the corresponding door in the software and clicks remote open to unlock. Remote opening can also be performed via mobile app or dynamic environment monitoring platform, meeting requirements for remote visitor access and emergency unlocking.

14.4 Maintenance Category

Q16: How often does the access control system need maintenance?

A: Daily inspection is recommended — visual check that functions are operating normally. Monthly maintenance by operations personnel includes simple cleaning, tightening, and functional testing. Quarterly maintenance by professionals includes in-depth inspection. Annual comprehensive maintenance is recommended to be performed by manufacturer professional engineers to ensure long-term stable system operation.

Q17: The magnetic lock contact surface is dirty. Can it be wiped with a wet cloth?

A: Yes, but the power must be disconnected first. Use a dry cloth with a small amount of alcohol to clean, allow to dry completely before restoring power. Avoid allowing large amounts of water to enter the lock body, which could cause coil short circuit damage. After cleaning, a thin layer of anti-rust oil can be applied to prevent rust formation affecting holding force.

Q18: Do backup batteries need replacement? How often?

A: Backup batteries are consumable items that require periodic replacement. Under normal use conditions, lead-acid battery lifespan is 2-3 years. When backup time noticeably shortens after power failure, battery swelling or leakage occurs, or voltage drops below normal, replacement is required promptly. It is recommended to test battery capacity annually to assess health status.

Q19: Can a hair dryer be used to blow dust off access control equipment?

A: The cool air setting can be used; hot air is prohibited as high temperature can damage electronic components. For internal dust, use an anti-static brush for cleaning, combined with a vacuum cleaner to remove dust, avoiding dust scattering into the circuit board and causing short circuits. Cleaning must be performed with power disconnected.

Q20: How should equipment be stored if not used for an extended period?

A: Disconnect power, clean thoroughly, seal in anti-static bags or original packaging, and store in a dry, ventilated, room-temperature environment, avoiding moisture, high temperature, and corrosive gases. The backup battery should be removed and stored separately, with a supplementary charge every 3 months to prevent damage from depletion.

14.5 Fault Troubleshooting Category

Q21: After card swipe, the light turns green but the door won’t open. Is the lock broken?

A: Not necessarily. First perform three troubleshooting steps: First, check whether the lock body makes a “click” release sound — if there is sound but the door won’t open, it may be door jamming or incomplete release of holding force; Second, measure the lock voltage — whether power is cut during card swipe. If voltage disconnects normally, the issue is with the lock itself; Third, check the mechanical structure — whether the door is deformed or the floor spring is sticking. Most cases involve installation alignment or wiring issues; lock body failure rate is relatively low.

Q22: The access control sometimes opens and sometimes doesn’t. What’s the problem?

A: Intermittent failures like this are most likely caused by poor contact or interference. Focus on checking: whether wiring terminals are loose or have poor connections; whether wires have partial breaks; whether there are interference sources near the card reader; whether power supply is stable; whether the lock contact surface has foreign objects causing inconsistent engagement. Test by replacing components one by one to isolate the fault point.

Q23: The controller indicator light doesn’t illuminate. Is it burnt out?

A: Don’t rush to judge it as damaged. First measure the supply voltage to confirm 12V power is normal. Then check whether the power switch is on and whether the fuse is blown. Often the issue is in the power supply wiring rather than the controller itself. If power is normal and the light still doesn’t illuminate, then consider controller hardware failure and contact the manufacturer for testing and repair.

Q24: The door bounces open repeatedly after closing and won’t lock. What should be done?

A: This is common with magnetic lock solutions. The causes are current surge at the moment of engagement causing controller misjudgment, or the door closer force being too strong causing bounce-back upon impact. Solutions: First, reduce the door closer force to allow slow door closure; Second, enable the controller lock delay function to delay locking after door closure; Third, check the door sensor position to ensure accurate door-closed detection.

Q25: What to do if functions become abnormal after firmware upgrade?

A: Immediately stop operations and do not repeatedly upgrade. First restore factory settings and reflash the original stable firmware version. If recovery fails, contact manufacturer technical support. Do not flash third-party firmware, which could brick the device. Before upgrading, always backup configuration data and select officially released stable versions.

Chapter 15 Product Acceptance

15.1 Acceptance Basis Standards

  • GB 50348-2018 “Technical Code for Engineering of Security and Protection System”
  • GB 50174-2017 “Code for Design of Data Centers”
  • GA/T 394-2002 “Technical Requirements for Access Control System”
  • Project design drawings and technical contract requirements
  • Technical parameters and functional requirements specified in this product manual
  • Relevant acceptance specifications for data center construction projects

15.2 Acceptance Items and Technical Indicators

15.2.1 Appearance and Installation Quality Acceptance

Acceptance Item Acceptance Standard Inspection Method
Equipment appearance No scratches, deformation, or rust on surface; labels clear and complete Visual inspection
Installation firmness All equipment securely installed, no looseness, no displacement when shaken Manual push test, tension test
Installation position and height Card readers and buttons at 1.3-1.5m height, reasonable position, easy operation Tape measure measurement
Levelness and verticality Equipment installed straight, verticality deviation ≤ 2mm/m Spirit level, plumb line measurement
Wiring workmanship Cables protected by conduit, horizontal and vertical routing, neat bundling, clear labeling Visual inspection
Sealing integrity Access control installation does not compromise cold aisle sealing structure; gaskets and brushes intact Visual inspection, air leakage test
Grounding reliability All metal equipment reliably grounded, grounding resistance ≤ 4Ω Ground resistance tester measurement

15.2.2 Functional Performance Acceptance

Acceptance Item Acceptance Standard Inspection Method
Card swipe door opening Response time ≤ 0.2 seconds, 100% recognition rate, normal unlocking 20 consecutive card swipe tests
Password door opening Correct password unlocks, incorrect password rejected, error lockout function works 10 positive and 10 negative tests
Exit button Unlocks immediately when pressed, smooth return, no failure 20 consecutive press tests
Unlock delay Delay time configurable, error ≤ 0.5 seconds Stopwatch timing test
Magnetic lock holding force Static pull force ≥ 280kg, no significant residual magnetism Force gauge test
Door sensor Open/closed status real-time and accurate, response time ≤ 1 second Open/close door test
Fire linkage Unlocks within 1 second upon receiving fire signal, highest priority 3 simulated fire signal tests
Power-failure unlock Lock releases automatically upon complete power loss, door can be manually opened Power cutoff test
Permission control Authorized cards open door, unauthorized cards rejected, time-zone permissions effective Multiple card verification test
Event records Door opening and alarm events completely recorded, no omissions, queryable and exportable Query records after operation
Alarm functions Unauthorized intrusion, door-not-closed, tamper alarms trigger accurately with audible/visual indication Simulated alarm scenario tests
Communication function TCP/IP communication stable, no packet loss, real-time and accurate data upload Continuous 2-hour communication test
Backup power supply Automatic switch to battery upon power failure, backup time ≥ 4 hours Power failure test with timing verification

15.2.3 Documentation Acceptance

Acceptance Item Acceptance Requirement
Product documentation Product manual, certificate of conformity, warranty card complete
Construction documentation As-built drawings, wiring diagrams, connection diagrams, installation records complete
Commissioning documentation Commissioning records, test reports, parameter configuration tables complete
Training records Operations personnel training records, assessment passed
Software documentation Management software installation package, license files, user manual complete

15.3 Acceptance Procedure

15.3.1 Acceptance Preparation

1. The contractor completes all installation and commissioning, passes self-inspection, and organizes acceptance documentation

2. The contractor submits acceptance application to the client and supervision party, and agrees on acceptance schedule

3. Acceptance participants include client representatives, supervision engineers, contractor technical director, and manufacturer technical representatives

15.3.2 On-site Acceptance

1. First conduct appearance and installation quality inspection, verifying item by item

2. Test functional acceptance items one by one and record test results

3. Randomly select test points for spot checks, with sampling ratio not less than 30%; expand sampling scope if any items fail

4. Problems identified during testing shall be recorded in the acceptance issue list with clear rectification deadlines

15.3.3 Documentation Review

1. The contractor submits all acceptance documentation

2. The acceptance team reviews completeness, accuracy, and standardization of documentation

3. Verify consistency between drawings and actual site conditions to ensure traceability

15.3.4 Rectification and Re-inspection

1. For non-conforming items identified during acceptance, the contractor completes rectification within the specified deadline

2. After rectification, apply for re-inspection and retest the non-conforming items

3. Acceptance passes only when all items are qualified

15.3.5 Acceptance Sign-off

1. After all acceptance items pass and documentation is complete, all parties sign the acceptance report

2. Complete equipment and documentation handover procedures, entering the warranty period

3. If acceptance fails, sign a rectification notice and re-organize acceptance after rectification

15.4 Acceptance Determination Rules

1. Critical items (fire linkage, power-failure unlock, lock holding force, permission control) must all pass — one-vote veto applies

2. General item pass rate ≥ 95% — judged as passed

3. General item pass rate < 95% but ≥ 80% — rectification required within deadline, then re-inspection

4. Pass rate < 80% — judged as failed, comprehensive rectification and re-acceptance required

15.5 Post-Acceptance Handover

1. After acceptance passes, the contractor hands over equipment, keys, cards, software, and documentation to the client

2. Conduct on-site operation training for client operations personnel, covering daily use, simple fault handling, and precautions

3. Clarify warranty period, service contact information, and maintenance procedures

4. Both parties sign the handover confirmation form for formal delivery and use

Chapter 16 SEO Optimization System and Keyword Layout

16.1 Search Keyword Classification System

16.1.1 Core Primary Keywords

Cold aisle access control, cold aisle containment system access control, data center cold aisle access control, aisle access control system, cold aisle end door access control

16.1.2 High-Conversion Long-Tail Keywords

Cold aisle access control installation, cold aisle access control wiring and commissioning, data center cold aisle access control manufacturer, cold aisle magnetic lock access control, cold aisle access control system quotation, cold aisle containment access control installation manual, data center cold aisle access control, cold aisle access control fire linkage, cold aisle sliding door access control, cold aisle access control repair and maintenance

16.1.3 Industry Traffic Keywords

Data center access control system, data center access control, IDC data center access control, modular data center access control, cold aisle security system, data center entrance/exit control, cold aisle intelligent access control, data center access control solution, shielded data center access control, classified data center access control system

16.1.4 Brand-Specific Keywords

KITOZER cold aisle access control, Guangdong KITOZER aisle access control, KITOZER intelligent data center access control, LA-MJ series access control, KITOZER cold aisle containment system, KITOZER access control manual, KITOZER access control technical parameters, Guangzhou cold aisle access control manufacturer

16.1.5 Dropdown/Related Search Keywords

How to install cold aisle access control, cold aisle access control wiring diagram, cold aisle access control fault troubleshooting, does cold aisle access control meet fire protection requirements, difference between cold aisle and ordinary access control, how much holding force does cold aisle access control have, what lock is used for cold aisle access control, how to commission cold aisle access control

16.2 SEO Optimization Tag System

16.2.1 Page Core Optimization Tags

  • Page core topic: Cold aisle containment system door access control installation, wiring, and commissioning manual
  • Core semantics: Comprehensive technical guide for cold aisle access control installation, wiring, commissioning, maintenance, and acceptance
  • Content positioning: Professional technical reference for data center construction personnel, operations personnel, and procurement personnel

16.2.2 Title Tag

Cold Aisle Access Control Installation Wiring Commissioning Manual_Cold Aisle Containment System Access Control Manufacturer – Guangdong KITOZER Intelligent Data Center Equipment

16.2.3 Meta Keywords

Cold aisle access control, cold aisle containment system access control, data center cold aisle access control installation, aisle access control wiring commissioning, cold aisle magnetic lock access control, data center access control system, cold aisle access control manufacturer, Guangdong KITOZER access control

16.2.4 Meta Description

Guangdong KITOZER Intelligent Data Center Equipment professionally provides cold aisle containment system access control. This manual provides comprehensive technical content including cold aisle access control product introduction, technical parameters, installation steps, wiring specifications, commissioning methods, maintenance, fault troubleshooting, and acceptance standards, suitable for data centers and modular data centers, compliant with fire protection regulations and supporting fire linkage.

16.2.5 H1 Tag

Cold Aisle Containment System Door Access Control Installation Wiring Commissioning Manual

16.2.6 H2 Tags

Product Introduction, Product Composition, Product List, Product Working Principle, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation, Product Wiring, Product Commissioning, Product Precautions, Product Repair and Maintenance, Product Common Problems and Solutions, Product QA, Product Acceptance

16.3 Internal Link Optimization Tags (Natural Anchor Text Placement)

16.3.1 Core Anchor Text

Cold aisle access control, cold aisle containment system, data center access control system, aisle access control installation

16.3.2 Long-Tail Anchor Text

Cold aisle access control wiring commissioning methods, cold aisle magnetic lock working principle, data center cold aisle access control fire linkage requirements, data center cold aisle access control solutions

16.3.3 Related Anchor Text

Cold aisle containment skylight, data center dynamic environment monitoring system, modular data center construction, precision air conditioning cooling system, cabinet cold aisle containment

Chapter 17 Copyright Notice and Contact Information

17.1 Copyright Notice

This document is copyrighted by Guangdong KITOZER Intelligent Data Center Equipment Co., Ltd. and is protected by national copyright law. No individual or organization may copy, reproduce, adapt, excerpt, translate, distribute, or otherwise use this document in whole or in part for commercial purposes or public distribution without the written authorization of our company.

For reprinting or quoting content from this document, the source must be credited as “Source: Guangdong KITOZER Intelligent Data Center Equipment Co., Ltd.” with the complete copyright information retained, and the content shall not be used for commercial purposes. Our company will pursue legal liability against unauthorized copying, alteration, or misappropriation of our document content for commercial purposes.

The content of this document is continuously updated with product technology iterations. Any changes are subject to change without prior notice. The latest version published by our company shall prevail. This document serves as a technical reference guide. Our company has made every effort to ensure content accuracy. Our company shall not be liable for equipment damage or safety incidents caused by improper operation or failure to follow specification during construction.

17.2 Manufacturer Contact Information

  • Manufacturer: Guangdong KITOZER Intelligent Data Center Equipment Co., Ltd.
  • Service Hotline: +86 13538869979 (also available on WeChat)
  • Technical Support: +86 13538869979
  • Company Address: Zhongrun Industrial Park, No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou
  • Official Website: https://gdlain.com