1. System Introduction
1.1 System Overview
The computer room grounding busbar system is a core component of the computer room lightning protection and grounding system. As a key carrier for equipotential bonding, it undertakes the critical function of equipotentially connecting the working grounding, protective grounding, lightning protection grounding, and shielding grounding of various equipment in the computer room and diverting current to the earth. The KITOZER computer room grounding busbar system adopts T2 oxygen-free copper with tin/nickel plated surface treatment. Featuring high conductivity, excellent oxidation resistance and superior lightning current carrying capacity, it effectively protects computer room equipment from lightning surges and electrostatic interference, and ensures stable operation of electronic information systems and personal safety.
1.2 Design Standards
The system is strictly designed in accordance with the following national and industrial specifications:
- GB 50174-2017 Code for Design of Data Centers
- GB 50057-2010 Code for Design of Building Lightning Protection
- GB 50343-2012 Technical Code for Lightning Protection of Electronic Information Systems in Buildings
- GB 50689-2011 Code for Design of Lightning Protection and Grounding Engineering of Telecommunication Stations
- GB/T 5585.1-2019 Electrical Copper Busbars – Part 1: General Requirements
1.3 Core Functions
- Equipotential Bonding: Realizes equipotential connection of all metal components, equipment enclosures and pipelines in the computer room to eliminate potential differences.
- Lightning Current Discharge: Rapidly conducts huge current generated by lightning strikes to prevent equipment insulation breakdown.
- Interference Shielding: Suppresses electromagnetic interference (EMI) and radio frequency interference (RFI) to guarantee signal transmission quality.
- Safety Protection: Provides a safe grounding path for equipment and personnel to prevent electric shock accidents.
- System Stability: Supplies reference potential for electronic equipment to ensure accuracy of data processing and communication.
2. System Composition
The KITOZER computer room grounding busbar system consists of the following core components:
| Component Name | Function Description | Material / Specification |
| Main Grounding Busbar | General equipotential connection point of the computer room, connecting main grounding trunk and branch busbars | T2 oxygen-free copper, 40×4mm~100×10mm |
| Regional Grounding Busbar | Equipotential connection point for each functional area, connecting cabinets and main busbar | T2 oxygen-free copper, 30×3mm~80×8mm |
| Cabinet Grounding Busbar | Grounding connection point for internal cabinet equipment, installed at top/bottom of cabinets | T2 oxygen-free copper, 20×2mm~50×5mm |
| Insulating Support | Supports and fixes busbars to ensure insulation between busbars and floor/wall | High-strength insulating material, withstand voltage ≥3000V |
| Bolt Connection Assembly | Connection between busbars and between busbars and equipment | Stainless steel/copper alloy with lock washers |
| Copper Strip / Grounding Cable | Conductor for connections between busbars and between busbars and grounding body | Stranded copper wire / copper strip, cross-section ≥25mm² |
| Grounding Terminal Box | Connection interface between busbar system and external grounding grid | Metal enclosure with built-in terminals |
| Identification System | Functional marking for busbars to facilitate maintenance and management | Corrosion-resistant labels with grounding type marking |
3. System Classification
3.1 Classification by Installation Position
| Classification | Applicable Scenarios | Specification Features | Installation Method |
| Main Equipotential Busbar (MEB) | Computer room inlet, connected to building grounding grid | Cross-section ≥100×10mm, terminal quantity ≥24 | Floor-standing / wall-mounted with insulating brackets |
| Local Equipotential Busbar (LEB) | Functional areas such as server area and network area | Cross-section ≥50×5mm, terminal quantity ≥16 | Wall-mounted at cabinet row header |
| Cabinet Built-in Busbar | Inside cabinets for servers, switches and other devices | Cross-section ≥30×3mm, terminal quantity ≥8 | Guide rail installation at cabinet top/bottom |
| Equipment Dedicated Busbar | Large equipment such as UPS and precision air conditioners | Cross-section ≥80×8mm, terminal quantity ≥12 | Near-equipment installation with short connection distance |
3.2 Classification by Function
- Lightning Protection Grounding Busbar: Mainly used to discharge lightning impulse current, connecting SPDs and external lightning protection system, lightning current withstand capacity >300kA.
- Working Grounding Busbar: Provides DC logic ground for computer equipment to ensure data processing accuracy, grounding resistance ≤1Ω.
- Protective Grounding Busbar: Connects equipment enclosures to prevent electric shock, grounding resistance ≤4Ω.
- Shielding Grounding Busbar: Connects shielding layers of cables and shielded cabinets to suppress electromagnetic interference.
- Anti-static Grounding Busbar: Connects anti-static floors and workbenches to eliminate static accumulation.
3.3 Classification by Structure
- Strip Busbar: Standard type, flexible installation for most computer room scenarios.
- Grid Busbar: Applied in large-area computer rooms, laid under raised floors to form an equipotential grid.
- Combined Busbar: Modular design, expandable on demand for easy maintenance and upgrading.
- Box-type Busbar: Built-in busbar assembly with protective enclosure, suitable for high-safety computer rooms.
4. System Configuration List (KITOZER Brand)
4.1 Basic Configuration List (for 100㎡ Small & Medium-sized Computer Rooms)
| No. | Product Name | Model | Specification Parameters | Quantity | Remarks |
| 1 | Main Grounding Busbar | KT-MEB-10010 | T2 copper, 100×10×1000mm, 24×M10 terminals, tin-plated | 1 | Main equipotential connection |
| 2 | Regional Grounding Busbar | KT-LEB-6006 | T2 copper, 60×6×800mm, 16×M8 terminals, tin-plated | 4 | 1 per functional area |
| 3 | Cabinet Grounding Busbar | KT-RACK-4004 | T2 copper, 40×4×600mm, 8×M6 terminals, tin-plated | 32 | 1 per cabinet |
| 4 | Insulating Support Base | KT-INS-100 | Withstand voltage ≥5000V, load capacity ≥50kg | 48 | Busbar support |
| 5 | Bolt Connection Kit | KT-BOLT-M10 | Stainless steel with flat washers, spring washers and lock nuts | 64 | Busbar connection |
| 6 | Connection Copper Strip | KT-STRIP-50 | 50×5mm copper strip, customizable length | 16 | Inter-busbar connection |
| 7 | Grounding Cable | KT-CABLE-35 | 35mm² stranded copper wire, customizable length | 8 | Busbar-to-grounding-body connection |
| 8 | Grounding Terminal Box | KT-BOX-32 | 32-position terminal, IP65 protection | 1 | Main grounding connection |
| 9 | Identification Label | KT-LABEL-01 | Corrosion-resistant, waterproof, grounding type marked | 64 | Mark for busbars & connection points |
| 10 | Installation Accessories | KT-KIT-01 | Expansion bolts, fixing brackets, etc. | 1 | Complete installation accessories |
4.2 Extended Configuration List (Optional)
| No. | Product Name | Model | Specification Parameters | Applicable Scenarios |
| 1 | Intelligent Grounding Monitoring Module | KT-MON-01 | Grounding resistance monitoring with real-time alarm | Key computer rooms requiring remote monitoring |
| 2 | Lightning Strike Counter | KT-COUNT-01 | Records lightning strike times with sound & light alarm | Computer rooms in thunderstorm-prone areas |
| 3 | Busbar Protective Enclosure | KT-COVER-01 | IP30 protection, electric shock prevention | Areas with frequent personnel activities |
| 4 | Grounding Resistance Test Point | KT-TEST-01 | Convenient for grounding resistance measurement | Scenarios requiring regular detection |
| 5 | Busbar Expansion Module | KT-EXT-01 | Expandable terminals with connecting copper bar | Equipment capacity expansion scenarios |
5. System Schematic Diagram
5.1 System Architecture Diagram
[Building Grounding Grid] —— [Grounding Trunk] —— [KT-BOX-32 Grounding Terminal Box] —— [KT-MEB-10010 Main Grounding Busbar]
         │
         ├─── [KT-LEB-6006 Regional Busbar 1] —— [Cabinet Busbar Group 1] —— [Server / Network Equipment]
         ├─── [KT-LEB-6006 Regional Busbar 2] —— [Cabinet Busbar Group 2] —— [Server / Network Equipment]
         ├─── [KT-LEB-6006 Regional Busbar 3] —— [Cabinet Busbar Group 3] —— [Server / Network Equipment]
         └─── [KT-LEB-6006 Regional Busbar 4] —— [Cabinet Busbar Group 4] —— [Server / Network Equipment]
                 │         │
                 └─── [Large Equipment: UPS / Precision Air Conditioner]
                 └─── [SPD Surge Protector Device]
                 └─── [Anti-static Floor / Shielded Cabinet]
5.2 Equipotential Bonding Principle
- Main Equipotential Bonding (MEB): Connects building grounding grid, power inlet PE line, lightning down conductor and communication cable shielding layer to the main grounding busbar, realizing equipotential balance between computer room and building.
- Local Equipotential Bonding (LEB): Regional busbars are connected to the main busbar via copper strips, and all equipment in each area is connected to the regional busbar through short-distance paths.
- Equipment Equipotential Bonding: Internal cabinet equipment connects to cabinet busbars via grounding wires, and cabinet busbars connect to regional busbars via copper strips.
- Shielding Equipotential Bonding: Both ends of shielding cable layers are connected to grounding busbars; shielded cabinets are connected to busbars via dedicated grounding wires.
5.3 Lightning Current Discharge Path
[Lightning Strike] —— [Air Terminal] —— [Down Conductor] —— [Building Grounding Grid] —— [KT-BOX-32] —— [KT-MEB-10010]
         │                │
         └─── [SPD Surge Protector] —— [KT-LEB-6006] —— [Equipment Grounding]
                               │
                               └─── [KT-RACK-4004] —— [Equipment Enclosure]
6. Product Technical Parameters (KITOZER Brand)
6.1 Busbar Body Technical Parameters
| Parameter Item | Index Requirement | Test Standard |
| Material | T2 oxygen-free copper, purity ≥99.9% | GB/T 5231-2012 |
| Conductivity | ≥98% IACS, resistivity ≤0.01777Ω·mm²/m | GB/T 3048.2-2007 |
| Surface Treatment | Tin/nickel plating, coating thickness ≥5μm | GB/T 12599-2008 |
| Flatness | ≤1.5mm/m | GB/T 5585.1-2019 |
| Edge Treatment | Round chamfer R≥2mm, burr-free | GB/T 5585.1-2019 |
| Dimension Tolerance | Width ±0.5mm, thickness ±0.2mm | GB/T 5585.1-2019 |
| Terminal Hole Diameter | M6/M8/M10, H12 tolerance grade | GB/T 197-2003 |
| Current Withstand Capacity | >300kA (8/20μs waveform) | IEC 61643-1 |
| Contact Resistance | Single point ≤0.05mΩ | GB/T 3048.4-2007 |
| Temperature Rise Performance | Temperature rise ≤40K under 1.5× rated current | GB/T 2423.2-2008 |
| Corrosion Resistance | No rust after ≥96h neutral salt spray test | GB/T 10125-2012 |
| Service Life | ≥30 years | Industry Standard |
6.2 Connection Component Parameters
| Component Name | Technical Parameters | Remarks |
| Insulating Support | Insulation resistance ≥1000MΩ/500V, withstand voltage ≥3000V | Flame retardant grade V0 |
| Connection Bolt | 304/316 stainless steel, tensile strength ≥500MPa | With flat/spring/lock washers |
| Copper Strip / Cable | Stranded copper wire, DC resistance ≤0.715Ω/km (25mm²) | Insulation class B (130℃) |
| Grounding Terminal Box | IP65 protection, terminal current capacity ≥1000A | With grounding mark and lock |
6.3 System Performance Parameters
| Performance Index | Requirement Value | Applicable Standard |
| Grounding Resistance | Common grounding system ≤1Ω, independent lightning grounding ≤10Ω | GB 50057-2010 |
| Equipotential Bonding Resistance | ≤0.1Ω | GB 50343-2012 |
| Lightning Current Carrying Capacity | ≥100kA (10/350μs waveform) | IEC 61312-1 |
| System Response Time | ≤50ms | TIA-942-B |
| Insulation Performance | Insulation resistance between busbar and ground ≥100MΩ | GB/T 16927.1-2011 |
| Mechanical Strength | Support spacing ≤1000mm, deflection ≤2mm | Industry Standard |
7. Application Scope
7.1 Core Application Scenarios
- Data Center Computer Rooms: Large-scale data centers, cloud computing centers, IDC rooms
- Communication Computer Rooms: Telecom operator rooms, mobile base stations, communication hubs
- Financial Computer Rooms: Bank data centers, securities trading centers, insurance data centers
- Government Computer Rooms: Government cloud platforms, e-government rooms, public security command centers
- Enterprise Computer Rooms: Enterprise server rooms, network centers, storage rooms
- Special Computer Rooms: Medical imaging centers, industrial control rooms, military command centers
7.2 Extended Application Scenarios
- Rail Transit: Metro control centers, high-speed railway signal rooms, platform power distribution rooms
- Energy Industry: Power plant control rooms, substations, new energy energy storage stations
- Education & Research: University data centers, research laboratories, supercomputing centers
- Commercial Buildings: Office building computer rooms, hotel weak current rooms, mall central control rooms
- Industrial Automation: PLC control cabinets, DCS systems, industrial robot control centers
8. Product Advantages (KITOZER Brand)
8.1 Material Advantages
- High-purity T2 Oxygen-free Copper: Excellent conductivity with low resistivity of 0.01777Ω·mm²/m to ensure fast current conduction.
- Dual-layer Tin/Nickel Plating: Superior anti-oxidation and anti-corrosion performance, service life over 30 years with low maintenance costs.
- Precision Manufacturing: Flatness ≤1.5mm/m with rounded edge chamfers, avoiding tip discharge and personnel scratches.
8.2 Performance Advantages
- Super Lightning Current Withstand Capacity: Resists lightning surge over 300kA to prevent equipment lightning damage.
- Ultra-low Contact Resistance: Single-point contact resistance ≤0.05mΩ, reducing power loss and heat generation to improve system efficiency.
- Fast Equipotential Balancing: System response time ≤50ms, realizing instant potential balance during lightning strikes to eliminate potential differences.
8.3 Design Advantages
- Modular Structure: Flexible and expandable, configurable according to computer room scale and equipment quantity.
- Standardized Interface: Compatible with various equipment grounding requirements and different-spec grounding wires.
- Safety Protection Design: Insulating supports withstand voltage ≥3000V, IP30 electric shock protection grade.
- Clear Marking: Professional grounding labels for easy maintenance and reduced misoperation risks.
8.4 Service Advantages
- Customization Service: Custom special-spec busbars and connecting components available on customer demand.
- Professional Technical Support: Provides customized grounding system design and on-site installation guidance.
- Quality Assurance: All products pass ISO9001 certification with complete after-sales guarantee.
- Fast Delivery: Standard specifications in stock, rapid production for customized products.
9. Bid-winning Control Parameters (KITOZER Brand)
9.1 Core Bid Control Parameters
- Material Requirement: Adopt T2 oxygen-free copper with purity ≥99.9%, complying with GB/T 5231-2012.
- Surface Treatment: Dual-layer tin/nickel plating with coating thickness ≥5μm, complying with GB/T 12599-2008.
- Conductivity: Conductivity ≥98% IACS, resistivity ≤0.01777Ω·mm²/m, complying with GB/T 3048.2-2007.
- Lightning Current Capacity: ≥300kA (8/20μs waveform), tested per IEC 61643-1.
- Contact Resistance: Single-point contact resistance ≤0.05mΩ, complying with GB/T 3048.4-2007.
- Grounding Resistance: System grounding resistance ≤1Ω, complying with GB 50057-2010.
- Equipotential Resistance: ≤0.1Ω, complying with GB 50343-2012.
- Flatness: ≤1.5mm/m, complying with GB/T 5585.1-2019.
9.2 Technical Response Parameters
- Busbar Specification: Main busbar ≥100×10mm, regional busbar ≥50×5mm, cabinet busbar ≥30×3mm.
- Terminal Configuration: Main busbar ≥24 terminals, regional busbar ≥16 terminals, cabinet busbar ≥8 terminals.
- Insulation Performance: Busbar-to-ground insulation resistance ≥100MΩ, support withstand voltage ≥3000V.
- Connection Method: Bolt connection with lock washers, torque compliant with GB/T 16823.1-2014.
- Service Life: ≥30 years, no corrosion after 96h neutral salt spray test.
- Certification: ISO9001 certified with third-party test reports available.
9.3 Commercial Response Parameters
- Delivery Cycle: ≤7 working days for standard specs, ≤15 working days for customization.
- Warranty Period: ≥5 years with free replacement of damaged parts within warranty.
- After-sales Service: 24-hour technical support, on-site troubleshooting within 48 hours.
- Training Service: Free system installation, commissioning and maintenance training.
- Qualification: Possesses professional lightning protection engineering design & construction qualifications with project case proofs.
10. Customized Solutions
10.1 Small Computer Room Solution (≤100㎡)
10.1.1 Solution Overview
Designed for small and medium enterprise computer rooms and branch office rooms, adopting a three-level architecture of main busbar + regional busbar + cabinet busbar to meet basic lightning protection and grounding requirements with balanced economy and practicality.
10.1.2 Core Configuration
- 1 set KT-MEB-8008 Main Grounding Busbar (80×8×800mm, 16 terminals)
- 2 sets KT-LEB-5005 Regional Grounding Busbar (50×5×600mm, 12 terminals)
- 16 sets KT-RACK-3003 Cabinet Grounding Busbar (30×3×500mm, 8 terminals)
- Supporting insulating supports, bolt kits, copper strips and grounding terminal box
10.1.3 Implementation Key Points
- Lay 30×3mm copper strip grid under raised floor with grid spacing ≤1500mm.
- All cabinets connect to regional busbars via 6mm² stranded copper wires.
- Adopt common grounding system with grounding resistance ≤1Ω.
- Busbar-to-grounding-body connection uses ≥25mm² copper stranded wires.
10.2 Medium Computer Room Solution (100-500㎡)
10.2.1 Solution Overview
Suitable for enterprise data centers and financial institution computer rooms, adopting a four-level architecture of main busbar + regional busbar + cabinet busbar + dedicated equipment busbar to meet medium-to-high-end lightning protection and grounding demands for stable system operation.
10.2.2 Core Configuration
- 1 set KT-MEB-10010 Main Grounding Busbar (100×10×1000mm, 24 terminals)
- 4 sets KT-LEB-6006 Regional Grounding Busbar (60×6×800mm, 16 terminals)
- 32 sets KT-RACK-4004 Cabinet Grounding Busbar (40×4×600mm, 8 terminals)
- 4 sets KT-DEVICE-8008 Dedicated Equipment Busbar (80×8×600mm, 12 terminals) for UPS and precision air conditioners
- Intelligent grounding monitoring module for real-time grounding resistance monitoring
10.2.3 Implementation Key Points
- Lay 40×4mm copper strip grid under raised floor with grid spacing ≤1000mm.
- Adopt combined grounding method with grounding resistance ≤0.8Ω.
- Connect both ends of shielding cable layers to grounding busbars to suppress electromagnetic interference.
- Install lightning strike counter for operation and maintenance statistics.
10.3 Large Data Center Solution (≥500㎡)
10.3.1 Solution Overview
Applied to large-scale data centers and cloud computing centers, adopting a five-level architecture of main busbar + primary regional busbar + secondary regional busbar + cabinet busbar + dedicated equipment busbar to meet high-standard lightning protection and grounding requirements and ensure key business continuity.
10.3.2 Core Configuration
- 2 sets KT-MEB-12010 Main Grounding Busbar (120×10×1200mm, 32 terminals) for redundant backup
- 8 sets KT-LEB-10008 Primary Regional Busbar (100×8×1000mm, 24 terminals)
- 16 sets KT-LEB-6006 Secondary Regional Busbar (60×6×800mm, 16 terminals)
- 64 sets KT-RACK-5005 Cabinet Grounding Busbar (50×5×600mm, 10 terminals)
- 8 sets KT-DEVICE-10010 Dedicated Equipment Busbar (100×10×800mm, 16 terminals)
- Intelligent grounding monitoring system with remote monitoring and alarm functions
- Busbar protective enclosures for improved safety
10.3.3 Implementation Key Points
- Adopt copper strip grid + busbar combined layout with grid spacing ≤800mm for full equipotential balance.
- Grounding resistance ≤0.5Ω, utilizing building steel mesh as natural grounding body.
- Dual-path grounding connection for all equipment to enhance system reliability.
- Conduct grounding resistance testing and system maintenance at least twice a year.
10.4 Special Scenario Solutions
10.4.1 Container Data Center Solution
- Adopt KT-MEB-6006 dedicated container busbar suitable for narrow space installation.
- Busbars fixed on container side walls via insulating brackets.
- Utilize container metal frame as auxiliary grounding body to enhance grounding effect.
- Adopt ≥50mm² copper strip for connection between busbar and container frame.
10.4.2 Shielded Computer Room Solution
- Adopt KT-MEB-10010 dedicated shielded busbar with shielding layer connection terminals.
- Multi-point connection between busbar and shielded room enclosure to guarantee shielding efficiency.
- Connect shielding cable layers to busbars via dedicated grounding clips.
- Adopt independent grounding system with grounding resistance ≤0.5Ω.
11. Application Cases
11.1 Case 1: 280㎡ Quzhou Government Data Center Project (Zhejiang)
11.1.1 Project Overview
This government-level data center undertakes e-government systems and cloud computing platforms, requiring strict grounding performance with grounding resistance ≤0.8Ω.
11.1.2 Solution
Adopt KITOZER five-level grounding busbar system, lay 600×600mm copper strip grid under raised floor, and connect 32 cabinets to the MEB system via TD28 boxes.
11.1.3 Implementation Effect