ToggleTechnical Design Proposal for a 40ft High-Cube Containerized Liquid-Cooled Data Center
(8 × 30kW High-Density Liquid-Cooled Racks / 240kW Total Heat Load)
—
Cover Page
| Item | Details |
| — | — |
| Solution Title | Technical Design Proposal for a 40ft High-Cube Containerized Liquid-Cooled Data Center |
| Configuration | 8 × 30kW High-Density Liquid-Cooled Racks · 240kW Total Heat Load · CDU Indirect Liquid Cooling Architecture |
| Produced By | Guangzhou Lain Intelligent System Development Co., Ltd. |
| Brand | KITOZER |
| Version | V1.0 |
| Date | August 2026 |
—
Table of Contents
- Company Profile
- Project Overview
- User Requirements Analysis
- Design Basis and Design Principles
- Overall System Architecture
- Detailed Configuration List
- Technical Specifications of Each System
- 7.1 Container Enclosure and Compartment Infrastructure
- 7.2 IT Racks and Liquid Cooling Terminal Systems
- 7.3 CDU Coolant Distribution Unit System
- 7.4 Primary/Secondary Side Liquid Cooling Piping System
- 7.5 Cooling Medium and Water Treatment System
- 7.6 Power Supply and Distribution System
- 7.7 Environment Monitoring and Intelligent Control System
- 7.8 Fire Protection and Safety System
- 7.9 Auxiliary Support System
- Key Solution Advantages
- Technical Q&A
- Construction Schedule Plan
- Construction Organization Plan
- After-Sales Service System
- Operation and Maintenance Training Plan
- Typical Engineering Case Studies
- SEO Keyword System and Optimization Tags
- Website Publishing Configuration
- Contact Information
—
1. Company Profile
Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise in China specializing in the R&D, manufacturing, and integration of data center infrastructure. Under our proprietary brand KITOZER, we have accumulated over two decades of industry expertise, mastering core technologies in high-efficiency cooling, intelligent monitoring, and electromagnetic shielding. We deliver full lifecycle services spanning solution design, custom manufacturing, installation and commissioning, and after-sales maintenance.
Our core product portfolio covers the full spectrum of data center equipment, including containerized computer rooms, micro-module cold-aisle containment, integrated cabinets, outdoor enclosures, shielded computer rooms, and intelligent shielding cabinets, widely deployed across data centers, telecommunication base stations, healthcare and scientific research, industrial control, and government/education sectors. Leveraging our flexible customization factory and professional engineering team, KITOZER tailors bespoke computer room solutions for diverse computing densities, deployment environments, and operational requirements. We offer free comparison of multiple design proposals to ensure optimal fit and cost efficiency for every project.
In quality management, our company has established a comprehensive end-to-end quality assurance system. Core components are sourced from first-tier brands, and every unit undergoes multiple rounds of power-on, dielectric withstand, thermal cycling, and leak detection testing prior to shipment. Third-party inspection agencies provide full-process quality oversight, ensuring stable delivery lead times. For after-sales support, we provide 7×24-hour professional online assistance, rapid response to customer issues, and dedicated account management throughout the full project lifecycle to guarantee reliable post-delivery operation.
—
2. Project Overview
With the rapid growth of AI large-model training, high-performance computing (HPC), and edge computing workloads, power density per server rack has surged from the traditional 5–10kW to 20–50kW. Conventional air-cooling can no longer meet high-density heat dissipation requirements and suffers from high energy consumption, excessive noise, and prolonged deployment cycles.
This proposal addresses high-density computing scenarios using a 40ft high-cube standard container as the deployment platform, integrating an indirect liquid cooling heat dissipation system. The configuration comprises eight 30kW high-density liquid-cooled racks, achieving a total cooling load of 240kW. At the heart of the thermal architecture is a CDU (Coolant Distribution Unit) serving as the heat exchange node, interfacing with external chiller plants or dry coolers as the heat rejection source to deliver stable, efficient liquid cooling for the servers.
The solution adopts a factory-prefabricated model: all systems inside the container — including racks, piping, CDU, power distribution, monitoring, and fire suppression — are fully pre-installed and tested at the factory. On-site work is limited to connecting utilities and the external cooling source, enabling rapid deployment. Construction lead time is reduced by over 80% compared to traditional computer room builds. This solution is ideally suited for edge computing nodes, temporary compute expansion, outdoor emergency data centers, and AI training clusters.
Default Scope of Work Boundary: The client is responsible for supplying and integrating the outdoor cooling source (chillers, cooling towers, dry coolers, etc.). KITOZER provides the complete internal liquid cooling infrastructure and system integration within the container. The interface point is the primary-side quick-connect coupling mounted on the exterior wall of the container.
—
3. User Requirements Analysis
3.1 Cooling Performance Requirements
- Rated heat dissipation capacity of 30kW per rack, with a total thermal load of 240kW, meeting the cooling demands of high-power CPU/GPU servers.
- Secondary-side supply water temperature stably controlled at 15–20°C; return water temperature ≤28°C; server chip temperatures maintained within designated thresholds.
- Cooling system designed with redundancy — a single component failure must not compromise overall cooling, ensuring business continuity.
3.2 Deployment and Delivery Requirements
- Standard container form factor enabling direct outdoor deployment without dedicated computer room construction.
- Factory pre-fabrication and integration with rapid on-site interface; overall delivery cycle ≤45 days.
- Cradle-liftable and relocatable design supporting elastic business adjustments and remote-site deployment.
3.3 Reliability and Safety Requirements
- Core equipment adopts N+1 redundant architecture for year-round uninterrupted operation.
- Comprehensive electrical safety, fire suppression, leak detection, and lightning protection grounding systems.
- Multiple alarm and protection mechanisms with automatic safeguards for over-temperature, over-pressure, low liquid level, and power failure scenarios.
3.4 Intelligent Operations and Maintenance Requirements
- Real-time acquisition and monitoring of all system parameters with dual local + remote management modes.
- Automatic fault localization and alarm with linkage control capabilities.
- Historical data logging and traceability to reduce manual O&M workload.
3.5 Compliance and Adaptability Requirements
- Compliance with national data center design, electrical, fire protection, and environmental standards.
- Reserved expansion interfaces supporting future upgrades in rack count and cooling capacity.
- Compatibility with mainstream server cold-plate interfaces, supporting different brands of liquid-cooled servers.
—
4. Design Basis and Design Principles
4.1 Design Basis
This proposal strictly adheres to current national and industry standards and specifications, including but not limited to:
| Standard Code | Standard Name |
| — | — |
| GB 50174-2017 | Code for Design of Data Centers |
| GB 50016-2014 (2018 Edition) | Code for Fire Protection Design of Buildings |
| GB 50054-2011 | Code for Design of Low-Voltage Electrical Installations |
| GB 50343-2012 | Technical Code for Protection of Building Electronic Information System Against Lightning |
| GB 50116-2013 | Code for Design of Automatic Fire Alarm System |
| GB 50370-2005 | Code for Design of Gas Fire Extinguishing Systems |
| YD/T 3299-2017 | Technical Requirements for Liquid Cooling of Telecommunication Data Centers |
| GB/T 2887-2011 | General Specification for Computer Site |
| GB/T 36340-2018 | General Specification for Anti-Static Raised Access Floor |
4.2 Design Principles
- Safety and Reliability: System stability is the foremost priority. Critical components feature redundant design with multiple safety protections, meeting 7×24-hour continuous operation requirements.
- High Efficiency and Energy Saving: The liquid-cooled high-efficiency heat exchange architecture reduces cooling energy consumption, achieving PUE as low as 1.1, in line with green data center development trends.
- Rapid Deployment: Factory prefabrication and integrated delivery substantially reduce on-site construction time for rapid commissioning.
- Intelligent Operations: Full-dimension environment monitoring, automated control, and remote management minimize manual intervention and enhance O&M efficiency.
- Flexible Expansion: Modular design with reserved expansion interfaces supports smooth upgrades in cooling capacity, power distribution, and rack count.
- Economic Practicality: While meeting performance and reliability targets, the solution is optimized to control both initial capital investment and ongoing operational costs.
—
5. Overall System Architecture
This containerized liquid-cooled data center adopts an indirect liquid cooling architecture comprising primary-side cooling source + CDU heat exchange + secondary-side rack liquid cooling. The complete system integrates nine major subsystems:
| System | Function |
| — | — |
| Container Enclosure System | Equipment carrier and protection structure providing insulation, waterproofing, fire resistance, and load-bearing foundation |
| IT Rack System | Server mounting infrastructure integrating liquid cooling manifolds, quick-connect couplings, and PDUs |
| CDU Coolant Distribution System | Core liquid cooling component facilitating heat exchange between primary and secondary sides, controlling secondary-side water temperature and flow |
| Piping System | Primary/secondary supply and return piping connecting the cooling source, CDU, and racks for coolant circulation |
| Water Treatment System | Coolant preparation, softened water replenishment, chemical dosing for corrosion/scale inhibition, and water quality monitoring |
| Power Supply and Distribution System | Main distribution, UPS backup power, rack power distribution, and auxiliary power supply |
| Environment Monitoring System | Temperature/pressure/flow liquid monitoring, leak detection, access control, video surveillance, and centralized management |
| Fire Protection and Safety System | Gas suppression, fire detection, lightning protection grounding, and access control security |
| Auxiliary Support System | Cold-aisle containment, lighting, maintenance spares, and signage |
Spatial Layout: Along the length of the container, eight liquid-cooled racks are arranged in a single row on one side. The CDU units, power distribution cabinets, UPS, fire suppression cylinders, and auxiliary equipment are positioned on the opposite side, with a central maintenance aisle between them. The layout is compact and well-organized, providing adequate operational space and thermal management clearance.
—
6. Detailed Configuration List
6.1 Container Enclosure and Compartment Infrastructure
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | 40ft High-Cube Container | External 12192×2438×2896mm; Q235B steel; 50mm Class A rockwool insulation; IP55 protection; anti-corrosion coating | Set | 1 | Reinforced load-bearing structure |
| 2 | Internal Load-Bearing Base | No.12 channel steel welded frame + 3mm checkered steel plate; uniform load ≥1000kg/m² | Set | 1 | Reinforced under rack & CDU areas |
| 3 | Anti-Static Access Floor | 600×600mm all-steel; resistance 10⁶–10⁹Ω; uniform load ≥1000kg/m² | No. | 80 | Includes supports, stringers, spares |
| 4 | LED Lighting System | 40W flat panel; illuminance ≥300lux; incl. emergency lighting | Set | 8 | Including 2 emergency lights |
| 5 | Class A Fire Door | 900×2100mm fire-rated steel door; with door closer and emergency exit lock | Set | 1 | Single-leaf, with observation window |
| 6 | Residual Pressure Ventilation Device | Mechanical type; differential pressure 5–20Pa adjustable; with dust filter | pcs | 2 | 1 supply / 1 exhaust |
| 7 | Equipotential Bonding Copper Bar | 40×4mm copper busbar around container perimeter with grounding terminals | Set | 1 | Ground resistance ≤1Ω |
6.2 IT Racks and Liquid Cooling Terminal Systems
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Liquid-Cooled Server Rack | 600×1200×2000mm; 42U; static load ≥1500kg; front/rear perforated doors | Set | 8 | 19-inch standard mounting |
| 2 | Liquid Cooling Quick-Connect Coupling | DN20; 316 stainless steel; self-sealing; male/female set; 1.6MPa | Set | 16 | 1 supply + 1 return per rack |
| 3 | Rack Branch Manifold | 1-in/1-out; with manual regulating valve, temp/pressure ports; 304 stainless steel | Set | 8 | Rear rack mounting |
| 4 | Rack Blanking Panel Set | 1U/2U/4U all-steel; matte black; snap-in | Set | 8 | Complete per rack |
| 5 | Metering PDU | 380V input; 24×C13 + 8×C19 outlets; with metering & comms; 0U vertical | Set | 8 | 1 per rack |
| 6 | Cold Plate Adapter Accessory Kit | Thermal pads, seals, mounting clips | Batch | 1 | Matched for 8 racks of servers |
6.3 CDU Coolant Distribution Unit System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Primary CDU | Rated cooling capacity 240kW; plate heat exchanger; VFD pump set; PLC control | Set | 1 | 1+1 redundant |
| 2 | Standby CDU | Identical parameters to primary CDU | Set | 1 | Automatic failover |
| 3 | Built-in Circulating Pump | Centrifugal VFD; 30m³/h; 25m head; 304 SS pump body | Set | 4 | 1 active + 1 standby per CDU |
| 4 | Plate Heat Exchanger | 316L plates; heat transfer area ≥18m²; pressure rating 1.6MPa | Set | 2 | 1 per CDU |
| 5 | Diaphragm Expansion Tank | 100L; constant-pressure make-up; butyl rubber diaphragm | Set | 2 | 1 per CDU |
| 6 | Y-Type Precision Strainer | DN50; 316 SS; 100μm mesh | pcs | 4 | 1 primary + 1 secondary per CDU |
| 7 | Electric Proportional Control Valve | DN50; temp-regulated; 4–20mA control | Set | 2 | Primary-side supply regulation |
| 8 | Sensor Detection Kit | Temperature, pressure, flow, level sensors (complete) | Set | 2 | 1 per CDU |
| 9 | Integrated Control Cabinet | 7-inch touchscreen; PLC control; MODBUS communication | Set | 2 | 1 per CDU |
| 10 | Vibration Isolation Base | Channel steel + rubber dampers; noise/vibration reduction | Set | 2 | 1 per CDU |
6.4 Primary/Secondary Side Liquid Cooling Piping System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Primary Side Supply Header | 304 SS seamless pipe; DN80; wall 3mm | m | 30 | Cooling source interface to CDU |
| 2 | Primary Side Return Header | 304 SS seamless pipe; DN80; wall 3mm | m | 30 | CDU to cooling source interface |
| 3 | Secondary Side Supply Header | 304 SS seamless pipe; DN100; wall 3mm | m | 25 | Rack row overhead |
| 4 | Secondary Side Return Header | 304 SS seamless pipe; DN100; wall 3mm | m | 25 | Rack row underfloor |
| 5 | Rack Supply Branch Pipe | 304 SS pipe; DN20; wall 2mm | pcs | 8 | Header to manifold |
| 6 | Rack Return Branch Pipe | 304 SS pipe; DN20; wall 2mm | pcs | 8 | Manifold to header |
| 7 | Main Line Manual Ball Valve | DN80; 304 SS; flanged; 1.6MPa | pcs | 6 | Main valves + CDU inlet valves |
| 8 | Secondary Side Main Valve | DN100; 304 SS; flanged | pcs | 4 | 2 supply + 2 return |
| 9 | Branch Line Manual Ball Valve | DN20; 304 SS; female threaded | pcs | 16 | 1 supply + 1 return per rack |
| 10 | CDU Flexible Bellows | DN80; 304 SS; flanged; vibration compensating | pcs | 4 | 1 primary + 1 secondary per CDU |
| 11 | Rack Flexible Connection Hose | DN20; 304 SS braided; compression fitting | pcs | 16 | 1 supply + 1 return per rack |
| 12 | Pipe Fixing Support | Hot-dipped galvanized channel + 304 SS pipe clamps | Set | 60 | Spaced at 1.5m intervals |
| 13 | Pipe Insulation Layer | Class B1 rubber-plastic; 20mm thick; aluminum foil wrap | m³ | 1.2 | Full piping coverage |
| 14 | External Cooling Source Quick Interface | DN80; 316 SS self-sealing; flanged | Set | 2 | 1 supply + 1 return set |
6.5 Cooling Medium and Water Treatment System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Propylene Glycol Coolant | 50% concentration; freezing point -25°C; anti-corrosion formula | t | 2.5 | Total system volume |
| 2 | Automatic Water Softener | Capacity 2m³/h; cation exchange resin; automatic regeneration | Set | 1 | Make-up water softening |
| 3 | Precision Make-up Water Filter | 5μm; 304 SS housing; PP melt-blown cartridge | Set | 1 | Make-up water filtration |
| 4 | Corrosion/Scale Inhibitor Dosing System | Metering pump + 100L chemical tank; automatic timed dosing | Set | 1 | Anti-corrosion anti-scaling |
| 5 | Automatic Make-up Pump | Diaphragm type; 1m³/h; 20m head | Set | 1 | Automatic constant-pressure make-up |
| 6 | Water Quality Sensor | Conductivity + pH combined; with temperature compensation | Set | 2 | 1 primary + 1 secondary side |
6.6 Power Supply and Distribution System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Main Incoming Distribution Cabinet | 380V 3-phase; 250A main breaker; branch breakers; surge protection; energy metering | Set | 1 | Container main distribution |
| 2 | Online UPS Power Supply | 20kVA; 3-phase in / single-phase out; double-conversion online | Set | 1 | Monitoring & control power |
| 3 | Lead-Acid Battery Bank | 12V/100Ah; valve-regulated sealed AGM | pcs | 16 | 15 min backup |
| 4 | Standard Battery Cabinet | Fits 16 batteries; steel, powder-coated | Set | 1 | — |
| 5 | Rack Power Supply Circuit | YJV 3×6+1×4 cable + 32A breaker | Circuit | 8 | Dedicated per rack |
| 6 | CDU Power Supply Circuit | YJV 3×16+1×10 cable + 63A breaker | Circuit | 2 | Dedicated per CDU |
| 7 | Auxiliary Power Supply Circuit | BV 2.5mm² cable + 16A breaker | Circuit | 4 | Lighting, sockets, etc. |
6.7 Environment Monitoring and Intelligent Control System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Environment Monitoring Host | Embedded industrial host; multi-protocol; Ethernet + 4G | Set | 1 | Centralized monitoring management |
| 2 | Temperature Sensor | PT100/NTC; accuracy ±0.1°C; RS485 output | pcs | 24 | Piping, racks, compartment |
| 3 | Pressure Sensor | 0–1.6MPa; accuracy ±0.25%FS; 4–20mA | pcs | 8 | Main header supply/return |
| 4 | Electromagnetic Flow Meter | DN100; accuracy ±0.5%; RS485 output | pcs | 2 | Secondary side main loop |
| 5 | Level Sensor | Capacitive type; high/low level alarm | pcs | 2 | CDU expansion tanks |
| 6 | Locatable Leak Detection Cable | Sensing accuracy ±1m; follows piping routing | m | 50 | Along pipe run base |
| 7 | Access Control System | Single-door controller; card + PIN; electromagnetic lock | Set | 1 | Compartment door control |
| 8 | IR Dome Camera | 2MP; night vision; PoE powered | pcs | 4 | Full compartment coverage |
| 9 | Local Touchscreen Display | 10-inch industrial touchscreen; local operation | Set | 1 | Inside compartment |
| 10 | Audible & Visual Alarm | DC24V; alarm linkage trigger | pcs | 2 | 1 inside + 1 outside |
| 11 | Signal Cables and Accessories | Shielded cable, network cable, terminals, conduit | Batch | 1 | Complete system wiring |
6.8 Fire Protection and Safety System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Cabinet Type FM200 (HFC-227ea) Fire Suppression Unit | 100L; pipeline-free / clean agent | Set | 2 | Dual-zone protection |
| 2 | Photoelectric Smoke Detector | 3C certified; DC24V | pcs | 6 | Evenly distributed in compartment |
| 3 | Fixed-Temperature Heat Detector | Fixed temp 70°C; 3C certified | pcs | 6 | Linked with smoke detectors |
| 4 | Emergency Start/Stop Button | With protective cover; manual discharge control | pcs | 2 | 1 inside + 1 outside |
| 5 | Discharge Indicator Light | DC24V; fire suppression release indication | pcs | 1 | Mounted outside door |
| 6 | Emergency Lighting | Rechargeable; ≥90 min runtime on power loss | Set | 2 | Fire emergency use |
6.9 Auxiliary Support System
| No. | Equipment Name | Specifications | Unit | Qty | Remarks |
| — | — | — | — | — | — |
| 1 | Cold Aisle Containment System | Ceiling skylights + acrylic end doors; fire-linked | Set | 1 | Encloses 8-rack row |
| 2 | Spare Quick-Connect Coupling | DN20; 316 SS; male/female set | Set | 4 | O&M spares |
| 3 | Dedicated Installation Tool Kit | Leak detector, wrenches, instruments, consumables | Set | 1 | On-site maintenance |
| 4 | System Identification Signage | Pipe flow direction, equipment ID, safety warnings | Set | 1 | Standardized labeling |
—
7. Technical Specifications of Each System
7.1 Container Enclosure and Compartment Infrastructure
7.1.1 40ft High-Cube Container
| Parameter | Specification |
| — | — |
| External Dimensions | L12192mm × W2438mm × H2896mm |
| Internal Clear Dimensions | L≈12032mm × W≈2280mm × H≈2680mm |
| Body Material | Side/end panels: Q235B carbon structural steel, 2.0mm thickness; roof panel: 2.5mm; floor: 3mm checkered steel plate; bottom frame: No.12 channel steel welded; corner castings: standard ISO steel castings |
| Surface Treatment | Full shot blasting to Sa2.5; epoxy zinc-rich primer + epoxy micaceous iron intermediate coat + acrylic polyurethane topcoat; total film thickness ≥120μm; corrosion resistance grade C4; outdoor service life ≥15 years |
| Insulation Structure | Walls, roof, and floor filled with 50mm Class A fire-rated rockwool; density ≥120kg/m³; thermal conductivity ≤0.040W/(m·K); fire performance compliant with GB8624-2012 Class A; inner surface lined with 0.5mm galvanized steel sheet |
| Protection Rating | Overall IP55 per GB4208-2017; door gaps and cable/pipe penetrations sealed with continuous EPDM rubber gaskets — no gaps, effective ingress protection against rain and dust |
| Load-Bearing Capacity | Floor uniform load ≥1000kg/m²; local reinforcement in rack areas with point load ≥1500kg; CDU equipment area load ≥2000kg/m² |
| Wind & Seismic Resistance | Withstands Category 12 typhoon (wind speed 32.7m/s) per GB50009; seismic intensity 8 degrees per GB50011 |
| Fire Resistance Rating | Wall fire resistance ≥2 hours, meeting Class A fire protection requirements |
| Pre-Engineered Openings | Reserved penetrations for primary-side coolant supply/return, main power, low-voltage communications, and ventilation — all fitted with waterproof sealing glands |
7.1.2 Internal Load-Bearing Base
- Structure: No.12 hot-rolled channel steel welded grid framework; grid spacing 600mm × 600mm; covered with 3mm checkered steel plate.
- Surface Treatment: Full hot-dip galvanizing; zinc coating ≥85μm.
- Installation: Bolted to container floor; levelness deviation ≤2mm/m².
- Load Capacity: Uniform load ≥1000kg/m²; concentrated load ≥5000kg/point.
7.1.3 Anti-Static Access Floor
- Dimensions: 600mm × 600mm × 35mm; all-steel borderless construction.
- System Resistance: 10⁶–10⁹Ω, compliant with GB/T 36340-2018 anti-static requirements.
- Load Performance: Uniform load ≥1000kg/m²; concentrated load ≥300kg; ultimate load ≥900kg.
- Surface Material: High-wear PVC anti-static surface, 1.5mm thickness; fire rating Class B1.
- Support System: Galvanized steel pedestals, 300mm height, ±20mm adjustable; galvanized steel stringers for stable support.
- Accessories: Includes pedestals, stringers, screws, perforated (vented) tiles, and cable-access tiles; 5% spare tiles supplied.
7.1.4 LED Lighting System
- Fixture Type: LED flat panel cleanroom light, 40W.
- Optical Performance: Color temperature 6500K cool white; CRI Ra≥80; illuminance ≥300 lux; uniformity ≥0.7.
- Installation: Ceiling-mounted, evenly spaced along the aisle.
- Emergency Lighting: 2 twin-head emergency luminaires, 3W per head; built-in Ni-Cd battery; auto-illumination on power failure; ≥90 minutes runtime; compliant with GB17945.
7.1.5 Steel Class A Fire Door
- Dimensions: 900mm (W) × 2100mm (H), single-leaf.
- Fire Resistance: 1.5 hours, compliant with GB12955-2008 Class A fire door standard; 3C certified.
- Door Leaf Construction: Cold-rolled steel shell; filled with Class A perlite core, 50mm thick.
- Hardware: Fire-rated hinges, door closer, emergency exit lock, smoke seals, and tempered glass observation window.
- Surface Finish: Electrostatic powder coating, matte grey.
7.1.6 Residual Pressure Ventilation Device
- Specification: 300mm × 300mm rectangular mechanical residual pressure valve.
- Adjustment Range: Opening differential pressure 5–20Pa, continuously adjustable.
- Function: Balances internal/external air pressure, prevents container deformation from negative pressure, and blocks external dust ingress.
- Filter Configuration: G4-class primary dust filter, washable and replaceable.
- Material: Galvanized steel body; aluminum alloy blades.
7.1.7 Equipotential Bonding System
- Main Grounding Busbar: 40mm × 4mm copper busbar installed continuously along container perimeter.
- Grounding Terminals: Independent grounding terminal reserved for every rack, device, cable tray, and pipeline.
- Ground Resistance: System ground resistance ≤1Ω, compliant with GB50169.
- Connection Method: Multi-strand yellow/green grounding cable with bolted connections for reliable contact.
7.2 IT Racks and Liquid Cooling Terminal Systems
7.2.1 Liquid-Cooled Server Rack
| Parameter | Specification |
| — | — |
| Dimensions | W600mm × D1200mm × H2000mm; 42U standard mounting space |
| Body Material | SPCC high-quality cold-rolled steel; mounting rails 2.0mm; side panels 1.5mm; front/rear doors 1.2mm |
| Load Capacity | Static load ≥1500kg; dynamic load ≥1000kg |
| Ventilation Design | Front/rear perforated doors; opening ratio ≥70%; supports hybrid air + liquid cooling fallback |
| Internal Configuration | 19-inch adjustable mounting rails; 4 pairs of cable managers; bottom liquid cooling pipe fixing brackets; top power/data cable troughs |
| Grounding System | Independent rack grounding terminal with internal equipment grounding bus |
| Surface Finish | Degreased, phosphated, electrostatic powder coated; matte black; film thickness 60–80μm; adhesion Class 1 |
| Accessories | Leveling casters, support feet, door locks, keys |
7.2.2 Liquid Cooling Quick-Connect Coupling
| Parameter | Specification |
| — | — |
| Specification | DN20 (3/4 inch); male + female set |
| Body Material | 316L stainless steel |
| Seal Material | Nitrile rubber (NBR); compatible with propylene glycol coolant |
| Working Pressure | Rated 1.6MPa; burst pressure ≥6.4MPa |
| Working Temperature | -20°C to 120°C |
| Connection Type | Compression fitting type, suitable for φ20 stainless steel tube |
| Core Features | Integrated one-way self-sealing valve — automatic sealing on disconnection, leak-free; insertion/withdrawal force ≤50N; operating life ≥10,000 cycles |
| Applicable Standard | GB/T 3765-2008 (Technical conditions for compression-type tube fittings) |
7.2.3 Rack Branch Manifold
- Specification: 1-in/1-out; DN20 ports.
- Material: 304 stainless steel, integrally formed without welds.
- Configuration: Supply side with manual flow regulating valve, graduated scale, adjustment range 0–100%; return side with reserved ports for PT100 temperature sensor and pressure gauge.
- Installation: Wall-mounted at rear of rack with stainless steel mounting bracket.
- Pressure Drop: ≤0.05MPa at rated flow.
7.2.4 Metering PDU
| Parameter | Specification |
| — | — |
| Input | 380V 3-phase 5-wire; 32A rated; IEC309 industrial connector |
| Output Outlets | 24×C13 (10A) + 8×C19 (16A) |
| Metering Accuracy | Voltage ±0.5%; current ±0.5%; power ±1%; energy ±1% |
| Display | LCD display of real-time 3-phase voltage, current, active power, energy, temperature |
| Protection | Independent breaker per circuit; overload & short-circuit protection; surge protection module, discharge capacity 10kA (8/20μs) |
| Communication | RS485 interface; MODBUS-RTU protocol; integrates with environment monitoring system |
| Installation | 0U vertical mount, rear rack mounting |
| Working Environment | Temperature -10°C to 60°C; humidity 5%–95% non-condensing |
7.3 CDU Coolant Distribution Unit System
7.3.1 CDU Complete Unit Parameters
| Parameter | Specification |
| — | — |
| Model | KITOZER-CDU-240 |
| Rated Cooling Capacity | 240kW (at primary side 12°C supply / 18°C return; secondary side 22°C supply / 15°C return) |
| Primary Side | Rated flow 41.2m³/h; working pressure 1.6MPa; connection DN80 flanged |
| Secondary Side | Rated flow 30m³/h; working pressure 1.0MPa; connection DN100 flanged |
| Power Supply | 380V 3-phase 5-wire 50Hz; total power ≤7.5kW |
| Control | PLC fully automatic control; 7-inch touchscreen HMI |
| Dimensions | W1200mm × D800mm × H1800mm |
| Protection Rating | IP31 (indoor installation) |
| Noise Level | ≤65dB(A) @1m distance |
| Materials | Powder-coated steel frame; 304/316 stainless steel wetted parts |
7.3.2 Plate Heat Exchanger
| Parameter | Specification |
| — | — |
| Type | Gasketed (serviceable) plate heat exchanger |
| Plate Material | 316L stainless steel, 0.5mm thickness |
| Seal Gaskets | Nitrile rubber (NBR); compatible with propylene glycol coolant; adhesive-bonded type |
| Heat Transfer Area | ≥18m² |
| Heat Transfer Coefficient | ≥3000W/(m²·K) |
| Pressure Rating | Design pressure 1.6MPa; hydrostatic test pressure 2.4MPa |
| Working Temperature | -20°C to 150°C |
| Flow Channel Design | Counter-current configuration for high thermal efficiency; wide-channel design resistant to clogging |
| Applicable Standard | GB16409-1996 (Plate heat exchangers – Technical conditions) |
7.3.3 Variable Frequency Circulating Pump
| Parameter | Specification |
| — | — |
| Type | Horizontal inline centrifugal pump |
| Quantity | 2 per CDU (1 active + 1 standby, automatic failover) |
| Performance | Rated flow 30m³/h; rated head 25m; rated power 4kW |
| Pump Materials | 304 stainless steel pump body and impeller; silicon carbide (SiC-SiC) mechanical seal |
| Motor | Three-phase asynchronous motor; IP55 protection; Class F insulation; bearing design life ≥50,000 hours |
| Variable Frequency Control | Industrial VFD; 0–50Hz stepless speed regulation; automatic flow adjustment based on secondary-side return temperature; energy-saving operation |
| Start Method | Soft start; starting current ≤ rated current; no hydraulic shock |
| Sealing Performance | Leak-free mechanical seal, compatible with coolant media |
7.3.4 Diaphragm Expansion Tank
- Nominal Volume: 100L.
- Type: Diaphragm type; butyl rubber diaphragm; complete air/liquid separation.
- Working Pressure: Maximum 1.0MPa.
- Pre-Charge Pressure: Factory pre-charged to 0.3MPa; field adjustable per system requirements.
- Working Temperature: -10°C to 90°C.
- Tank Material: Carbon steel body; internal epoxy anti-corrosion coating.
- Connection: DN25 male threaded port.
- Function: Absorbs coolant thermal expansion/contraction volume changes; maintains system pressure stability; compensates for minor system leakage.
7.3.5 Y-Type Precision Strainer
| Parameter | Specification |
| — | — |
| Specification | DN50; flanged connection |
| Body Material | 304 stainless steel |
| Screen Material | 316 stainless steel woven mesh |
| Filtration Accuracy | 100μm |
| Pressure Rating | 1.6MPa |
| Working Temperature | ≤120°C |
| Blowdown Function | DN15 drain valve at bottom for periodic blowdown |
| Quantity | 1 on primary + 1 on secondary side per CDU (2 total per CDU) |
7.3.6 Electric Proportional Control Valve
- Specification: DN50; flanged connection.
- Body Material: 304 stainless steel.
- Trim Material: 304 stainless steel.
- Seal Material: PTFE (polytetrafluoroethylene).
- Actuator: Electric modulating actuator with 4–20mA control signal; stroke time ≤30s.
- Flow Characteristics: Equal percentage; adjustable ratio 50:1.
- Working Pressure: 1.6MPa.
- Function: Modulates primary-side supply flow based on secondary-side return temperature to precisely regulate cooling capacity delivery.
—
[Note: The remaining sections — including the Primary/Secondary Side Piping System detailed specifications, Cooling Medium & Water Treatment Details, Power Supply & Distribution System Details, Environment Monitoring & Intelligent Control Details, Fire Protection & Safety System Details, Auxiliary Support System Details, Key Solution Advantages, Technical Q&A, Construction Schedule, Construction Organization Plan, After-Sales Service System, O&M Training Plan, Typical Engineering Case Studies, SEO Keyword System, Website Publishing Configuration, and Contact Information — are covered in subsequent chapters of this document.]
—