This manual is compiled by Guangdong Lain Intelligent Machine Room Equipment Co., Ltd. (Guangzhou Lain Intelligent System Development Co., Ltd.), aiming to provide comprehensive, standardized, and actionable technical guidance for the installation, wiring, commissioning, operation & maintenance, and acceptance of core switches. This manual covers the full lifecycle content from basic product knowledge to in-depth operations and maintenance, applicable to core switch deployment projects in various scenarios including data centers, enterprise campuses, smart campuses, government machine rooms, and industrial plants. It serves as a reference for network engineers, system integrators, machine room operation personnel, project acceptance personnel, and related technical management staff.
This manual is compiled in strict compliance with the IEEE 802.3 series Ethernet standards, TCP/IP protocol suite specifications, national machine room construction standards, and industry operation & maintenance specifications. All operational procedures have been verified through actual engineering practice and possess a high degree of executability and safety. Users must carefully read this manual in its entirety before operation and strictly follow the standardized procedures to avoid equipment damage, network failures, or personal safety accidents caused by improper operation.
Guangdong Lain Intelligent Machine Room Equipment Co., Ltd. holds all intellectual property rights of this manual. Without written authorization, no individual or organization may copy, reprint, or alter the contents of this manual. Violators will be pursued for legal liability.
Chapter 1 Product Introduction

1.1 Definition and Positioning of Core Switch
A core switch is a high-end switching device located at the core layer of a computer network architecture. It serves as the data forwarding hub and traffic scheduling core of the entire network, undertaking the core functions of high-speed data exchange, route forwarding, and network reliability assurance across regions and aggregation nodes. In the classic three-tier network architecture (access layer – aggregation layer – core layer), the core switch is positioned at the top tier, analogous to the main traffic artery hub of a city. Its performance, reliability, and stability directly determine the carrying capacity and operational quality of the entire network.
Unlike access-layer switches and aggregation-layer switches, the core design objectives of a core switch are ultimate forwarding performance, ultra-high reliability, and strong scalability. It typically does not undertake terminal access, edge security policies, and other underlying functions. It follows the design principle of “minimal policies, high bandwidth, low latency, and strong redundancy” to ensure that all network data can be forwarded stably at wire speed.
1.2 Development History of Core Switches
The development of core switches has evolved in tandem with the advancement of Ethernet technology, roughly through the following four stages:
First Generation: 100M Backbone Core Switches (1990-2000)
With the popularization of Fast Ethernet technology, 100M core switches began to be applied in enterprise networks. They adopted a shared bus architecture with switching capacities mostly at the tens of Gbps level, primarily addressing the basic needs of multi-department network interconnection in enterprises. Functions were mainly Layer 2 switching with relatively weak Layer 3 forwarding capabilities.
Second Generation: Gigabit Box-Type Core Switches (2000-2008)
After Gigabit Ethernet technology matured, box-type Gigabit core switches became the mainstream choice for medium-sized enterprises. They adopted a shared memory architecture, with switching capacity increased to hundreds of Gbps. They began to support Layer 3 routing functions, VLAN partitioning, and basic QoS capabilities, meeting the bandwidth requirements of enterprise multimedia office and data sharing.
Third Generation: 10G Chassis Core Switches (2008-2018)
With the rise of data centers and the popularization of 10G Ethernet, chassis-type modular core switches became mainstream. They adopted CLOS multi-stage multi-plane switching architectures, with switching capacity breaking through the Tbps level. They supported high-density deployment of 10G ports and featured high-reliability designs such as active/standby control redundancy, power redundancy, and fan redundancy. They also supported advanced functions including MPLS, IPv6, and virtualization, and were widely applied in large campuses and data centers.
Fourth Generation: 100G/400G Intelligent Core Switches (2018 to Present)
The development of cloud computing, big data, and AI computing power networks has driven core switches into the high-speed intelligent era. Single-port rates have increased to 100G, 400G, and even 800G, with switching capacities reaching tens of Tbps or even hundreds of Tbps. These switches integrate cutting-edge technologies such as SDN programmability, intelligent traffic scheduling, AI fault prediction, and lossless networks, while supporting intelligent capabilities including network virtualization, network telemetry, and automated operations & maintenance, fully adapting to the high-end requirements of cloud data centers and computing power networks.
1.3 Core Value of Core Switches
High-Speed Forwarding Ensures Smooth Business Operations
Core switches possess wire-speed forwarding capabilities, capable of carrying the peak aggregated traffic of the entire network, ensuring non-blocking transmission of cross-regional and cross-departmental business data. They effectively avoid network bottlenecks and guarantee the smooth operation of high-bandwidth services such as video conferencing, data backup, and cloud computing access.
High-Reliability Design Ensures Continuous Network Operation
Mainstream core switches adopt multiple redundancy architectures including control engine redundancy, power module redundancy, fan redundancy, and link redundancy. They support hot-swapping, non-stop forwarding, and graceful restart and other high-reliability technologies. The Mean Time Between Failures (MTBF) can reach hundreds of thousands of hours, ensuring 7×24 uninterrupted operation of the core network.
Flexible Expansion Adapts to Business Growth
Modular core switches support flexible expansion of service line cards, optical modules, and power supplies. Port rates and quantities can be progressively upgraded according to business development, protecting the user’s initial investment and adapting to the business growth needs of enterprises over 3-5 years.
Intelligent Scheduling Optimizes Network Quality
Core switches support rich QoS policies, traffic engineering, load balancing, and other functions. They can perform tiered scheduling for different business traffic, prioritizing the bandwidth and latency requirements of core services, improving overall network resource utilization and user experience.
Security Protection Fortifies Network Boundaries
Core switches integrate basic security protection capabilities, supporting access control lists, ARP protection, DoS attack defense, and user authentication. Working in conjunction with security devices such as firewalls, they collectively build a multi-layered network security system.
1.4 Overview of Lain Core Switch Products
The LA-Core series core switches launched by Guangdong Lain Intelligent Machine Room Equipment Co., Ltd. are high-performance core switching products designed for next-generation enterprise campuses, smart machine rooms, and data center scenarios. The series covers the full range from box-type entry-level core switches to chassis-type high-end core switches, fully adapting to the network construction needs of users of different scales.
The LA-Core series core switches adopt industry-leading switching chip solutions and mature network operating systems, possessing the core advantages of high cost-effectiveness, high stability, and easy operation & maintenance. They also provide comprehensive technical support and after-sales service, making them the preferred solution for network core construction across various industries. The products are fully compatible with network equipment from mainstream manufacturers, support standard Ethernet protocols, and can seamlessly integrate into existing network architectures, reducing user deployment costs and operation & maintenance complexity.
Chapter 2 Product Composition

2.1 Hardware Components of Chassis-Type Core Switch
Chassis-type core switches adopt a modular design, mainly consisting of core components such as the chassis, control engine units, switching fabric boards, service line cards, power modules, fan modules, backplane/midplane, and interface modules. All components work collaboratively to achieve high-speed data switching functions.
2.1.1 Chassis
The chassis is the physical carrier and structural support of the core switch. It is made of high-strength cold-rolled steel sheet, possessing good electromagnetic shielding performance and structural strength. The interior features precise line card slots, air duct structures, and installation rails. The chassis can be classified by slot count into 4-slot, 8-slot, 12-slot, 16-slot, and other specifications. The slot count determines the maximum expansion capability of the device.
The front of the chassis typically houses service line card and control engine card slots, while the rear houses power module and fan module slots. Some models adopt a front-to-rear air duct design to ensure heat dissipation efficiency. Both sides of the chassis are equipped with mounting brackets that can be secured to standard 19-inch server racks, and handles are provided for convenient equipment handling and installation.
2.1.2 Main Control Engine Unit (MPU)
The main control engine is the “brain” of the core switch, responsible for control plane management of the entire system. Its main functions include: running the network operating system, processing routing protocols, maintaining routing tables and MAC address tables, managing device configurations, monitoring device operating status, and providing management interfaces.
High-end core switches are all configured with dual main control engines supporting 1:1 redundant backup. When the active control engine fails, the standby control engine can seamlessly take over services, achieving non-stop forwarding and ensuring network continuity. The control engine is typically equipped with a Console management port, MGMT Ethernet management port, USB interface, and status indicators for local device management and status monitoring.
2.1.3 Switching Fabric Unit (SFU)
The switching fabric unit is the “heart” of the core switch, responsible for high-speed forwarding on the data plane. It is the core component for achieving large-capacity non-blocking switching. Core switches adopting the CLOS architecture construct multi-stage switching planes through multiple switching fabric boards. Data packets are transmitted at high speed between service line cards and switching fabric boards, achieving wire-speed forwarding across line cards.
The number of switching fabric boards and the capacity of a single board determine the overall switching capacity of the device. High-end models typically feature N+M redundant switching fabric boards. Failure of a single fabric board does not affect the overall forwarding performance of the device, further enhancing system reliability.
2.1.4 Service Line Card (LPU)
Service line cards are the “interface gateway” of the core switch, providing various network interfaces and responsible for receiving, transmitting, and preliminary processing of data packets. Service line cards can be classified by interface type into electrical port line cards, optical port line cards, and hybrid interface line cards. By interface rate, they can be classified into Gigabit line cards, 10G line cards, 25G line cards, 40G line cards, 100G line cards, and 400G line cards.
Service line cards integrate local forwarding chips, packet buffer memory, and interface PHY chips. They possess local Layer 2 forwarding capabilities, which can reduce the forwarding pressure on the switching fabric boards and improve overall forwarding efficiency. Some high-end line cards also support value-added service functions such as firewall modules, load balancing modules, and deep packet inspection modules.
2.1.5 Power Modules
Power modules provide stable DC power to the entire device. Core switches commonly adopt redundant power supply designs supporting 1+1 or N+N redundancy. When a single power supply fails, the remaining power supplies can carry the full device load without affecting device operation. Power modules can be classified by power supply type into AC power modules and DC power modules, adapting to AC mains power and machine room DC power supply systems respectively.
Power modules feature multiple safety mechanisms including overvoltage protection, undervoltage protection, overcurrent protection, and overtemperature protection. They support hot-swapping and can be replaced while the device is in operation, enhancing maintenance convenience. Power module rated power covers multiple specifications including 300W, 650W, 1200W, and 2000W, flexibly selected based on the overall device configuration.
2.1.6 Fan Modules
Fan modules are responsible for the heat dissipation of the entire device, ensuring stable operation within a constant temperature range. Core switches adopt intelligent speed-regulating fan systems that automatically adjust fan speed based on device temperature, balancing heat dissipation effectiveness with energy efficiency and noise reduction. Fan modules also support redundant design and hot-swapping. Failure of a single fan does not affect overall heat dissipation, and online replacement is possible.
Air duct designs are divided into two mainstream modes: front-to-rear and side-to-side. Data center models predominantly use front-to-rear direct-flow air ducts, adapting to machine room environments with hot/cold aisle isolation.
2.1.7 Backplane/Midplane
The backplane is the signal transmission carrier inside the chassis, located at the rear of the chassis. It integrates high-density connection buses to achieve signal interconnection and power transmission between control boards, switching fabric boards, service line cards, and power modules. The backplane is designed with high-speed signal integrity to ensure stable transmission of high-speed differential signals, serving as the fundamental guarantee of chassis-type switch performance.
Some high-end models adopt orthogonal architecture and backplane-free design, achieving board-to-board interconnection through midplane and orthogonal connectors, further improving signal quality and heat dissipation efficiency while supporting higher port rates.
2.2 Hardware Components of Box-Type Core Switch
Box-type core switches adopt an integrated design with a relatively compact structure, mainly consisting of the chassis mainboard, power units, fan units, fixed interface panel, and management interfaces.
Mainboard: Integrates core components such as the control chip, switching chip, memory, storage chip, and PHY chips. It is the core carrier of the box-type switch, implementing control and forwarding functions.
Power Unit: Divided into internal power supply and external power adapter types. Mid-to-high-end box-type core switches support dual power supply redundant design.
Fan Unit: Integrated inside the chassis, adopting intelligent speed control design to ensure device heat dissipation.
Interface Panel: The front panel integrates a fixed number of service interfaces and status indicators, including Ethernet electrical ports, SFP/SFP+/QSFP+ optical port slots, etc.
Management Interfaces: Equipped with a Console port and Ethernet management port. Some models support USB interfaces for system upgrades and configuration import.
2.3 Software System Composition
The software system of a core switch is the network operating system, which is the core for implementing device functions. It mainly includes the following modules:
System Kernel Module: Provides basic operating system functions such as process management, memory management, file system, and device drivers.
Layer 2 Protocol Module: Implements Ethernet switching-related protocols, including VLAN, STP/RSTP/MSTP, LACP link aggregation, LLDP, IGMP Snooping, etc.
Layer 3 Protocol Module: Implements routing and forwarding functions, including static routing, dynamic routing protocols such as RIP, OSPF, IS-IS, and BGP, as well as reliability protocols such as VRRP and ECMP.
Security Function Module: Implements security functions such as ACL access control, ARP protection, DoS defense, 802.1X authentication, and port security.
QoS and Traffic Management Module: Implements service quality functions such as traffic classification, queue scheduling, congestion control, and traffic shaping.
Management and O&M Module: Provides management interfaces and operations & maintenance functions such as CLI command line, Web network management, SNMP, Telnet/SSH, Syslog, and NETCONF.
Advanced Function Module: Includes value-added functions such as MPLS VPN, EVPN VXLAN, SDN, virtualization, and data center large Layer 2.
Chapter 3 Product Classification
3.1 Classification by Architecture Form
3.1.1 Box-Type Core Switch
Box-type core switches are integrated devices with fixed port configurations, featuring a standard rack-mount box structure, typically 1U-4U in height. Port quantities and types are basically fixed at the factory, with some models supporting expansion through extension cards.
Advantages: Small footprint, convenient deployment, lower cost, simple operation & maintenance, suitable for small-to-medium scale network core deployment.
Disadvantages: Limited expansion capability, relatively lower redundancy, not suitable for ultra-large-scale networks.
Applicable Scenarios: Network cores for small-to-medium enterprise campuses, branch offices, small data centers, and campus sub-campuses.
3.1.2 Chassis-Type Core Switch
Chassis-type core switches adopt a modular slot design. Users can flexibly select and configure components such as control boards, switching fabric boards, service line cards, and power modules according to their needs. Port quantities and types can be configured as required.
Advantages: Extremely strong expansion capability, high redundancy, powerful performance, smooth upgradability, adaptable to long-term business growth.
Disadvantages: Large footprint, high cost, higher deployment and operation & maintenance complexity.
Applicable Scenarios: High-end scenarios such as large enterprise headquarters, main university campuses, government external network cores, large data centers, and metropolitan area network aggregation.
3.2 Classification by Application Scenario
3.2.1 Campus Network Core Switch
Campus network core switches are designed for enterprise, campus, and government park scenarios. They focus on multi-service carrying capability, user management capability, and WAN interconnection capability. They support rich routing protocols, security authentication, and QoS functions, adapting to complex network environments with multiple buildings and departments. They typically feature high-density Gigabit/10G optical ports for connecting aggregation switches across buildings, while also supporting WAN interfaces for interconnection with egress routers.
3.2.2 Data Center Core Switch
Data center core switches are designed for cloud computing data center scenarios. They focus on ultimate forwarding performance, low latency, high-density high-speed ports, and virtualization capabilities. They support data center-specific functions such as CLOS non-blocking architecture, VXLAN/EVPN large Layer 2, RDMA lossless networks, and network telemetry. Ports are primarily 25G/100G/400G high-speed optical ports, adapting to server access and data center interconnection needs. Some models support intelligent traffic scheduling for AI computing power networks.
3.2.3 Industrial-Grade Core Switch
Industrial-grade core switches are designed for harsh industrial environments such as factories, mines, and rail transit. They adopt wide-temperature design and industrial-grade components, possessing strong anti-interference, shock resistance, dustproof, and moisture-proof capabilities. They support industrial Ethernet protocols and redundant ring network technologies, adapting to the high-reliability requirements of industrial control networks. They typically support DIN-rail or rack mounting, with an operating temperature range of -40°C to 75°C.
3.2.4 Xinchuang (Indigenous Innovation) Core Switch
Xinchuang core switches are designed for industries with high autonomous controllability requirements such as Party and government agencies, finance, and energy. They adopt domestically produced CPUs, domestic switching chips, and domestic network operating systems, achieving full-chain autonomous and secure controllability from hardware to software. They fully adapt to the domestic ecosystem and meet Classified Protection 2.0 and Xinchuang compliance requirements.
3.3 Classification by Port Rate
Gigabit Core Switch: Primarily Gigabit ports with a few 10G uplink ports, with switching capacity mostly below 100Gbps. Suitable for small network cores or legacy network upgrades.
10G Core Switch: 10G ports are the primary ports, with switching capacity ranging from hundreds of Gbps to several Tbps. This is the current mainstream core level for campus networks, adapting to the majority of medium-sized enterprises and campus networks.
100G Core Switch: 100G ports serve as the core backbone ports, backward-compatible with 10G/40G. Switching capacity reaches tens of Tbps. Suitable for large campuses and medium-sized data centers.
400G Core Switch: Supports 400G high-speed ports with switching capacity reaching hundreds of Tbps. Designed for ultra-large-scale data centers, computing power networks, and other high-end scenarios.
3.4 Lain Product Series Classification
The core switch product matrix of Guangdong Lain Intelligent Machine Room Equipment Co., Ltd. is comprehensive, covering full-scenario requirements and mainly divided into three major series:
LA-Core 1000 Series — Box-Type Entry-Level Core Switch
Positioned for small-to-medium network cores. Includes 1U and 2U models, providing 24-port/48-port Gigabit + 4-port/8-port 10G optical port configurations. Supports Layer 3 routing, static routing, and basic OSPF functions. Offers high cost-effectiveness, suitable for enterprise office networks with 100-500 terminals.
LA-Core 3000 Series — Box-Type High-End Core Switch
Positioned for medium-to-large network cores and small data center aggregation. Provides high-density 10G optical ports and 100G uplink ports. Supports complete dynamic routing protocols, MPLS, and virtualization functions. Supports dual power supply redundancy. Suitable for campus networks with 500-2000 terminals.
LA-Core 7000 Series — Chassis-Type Flagship Core Switch
Positioned for large campus and data center cores. Provides 4-slot, 8-slot, and 12-slot chassis specifications. Supports dual control engines and multiple switching fabric board redundancy. Line cards cover the full rate range from Gigabit to 400G. Supports cutting-edge technologies including SDN, VXLAN, and EVPN. Capable of carrying complex networks with tens of thousands of terminals.
Chapter 4 Product List
4.1 Standard Complete Device Configuration List
Taking the LA-Core 7808 chassis-type core switch as an example, the standard factory configuration list is as follows:
| No. | Item Name | Specification/Model | Qty | Remarks |
|---|---|---|---|---|
| 1 | Core switch chassis | LA-Core 7808 8-slot chassis | 1 unit | Includes backplane, rack mounting brackets, chassis handles |
| 2 | Control engine board | LA-MPU-7800-A | 2 pcs | Dual control redundancy configuration |
| 3 | Switching fabric board | LA-SFU-7800-F | 4 pcs | 4+1 redundancy configuration |
| 4 | AC power module | LA-PWR-2000W-AC | 4 pcs | 2+2 redundancy configuration |
| 5 | Fan module | LA-FAN-7800-F | 2 sets | Front-to-rear air duct, redundant design |
| 6 | Console configuration cable | RJ45 to DB9 serial cable | 1 pc | Length 1.5m |
| 7 | Ethernet management cable | Cat5e shielded patch cable | 1 pc | Length 2m |
| 8 | AC power cable | 16A national standard 3-core power cable | 4 pcs | Length 3m |
| 9 | Rack mounting screw kit | M6 rack screws + nuts | 1 set | Includes 16 sets of screw accessories |
| 10 | Anti-static wrist strap | Adjustable anti-static wrist strap | 2 pcs | For installation and maintenance use |
| 11 | Product certificate of conformity | Lain original certificate of conformity | 1 copy | Includes factory inspection stamp |
| 12 | Warranty card | Lain product warranty card | 1 copy | Effective after completion |
| 13 | Quick installation guide | Paper installation instructions | 1 copy | Includes key installation steps |
| 14 | Manual CD | Electronic complete manual | 1 disc | Includes configuration guide, operation & maintenance manual |
4.2 Optional Accessory List
| No. | Accessory Name | Specification/Model | Description |
|---|---|---|---|
| 1 | 24-port Gigabit electrical service board | LA-LPU-24GT | 24 × 10/100/1000BASE-T RJ45 electrical ports |
| 2 | 48-port Gigabit optical service board | LA-LPU-48GSFP | 48 × SFP Gigabit optical port slots |
| 3 | 24-port 10G optical service board | LA-LPU-24SFP+ | 24 × SFP+ 10G optical port slots |
| 4 | 8-port 40G optical service board | LA-LPU-8QSFP+ | 8 × QSFP+ 40G optical port slots |
| 5 | 32-port 100G optical service board | LA-LPU-32QSFP28 | 32 × QSFP28 100G optical port slots |
| 6 | Gigabit SFP optical module | LA-SFP-GE-LX | Single-mode 1310nm, 10km, LC interface |
| 7 | 10G SFP+ optical module | LA-SFP+-10G-LR | Single-mode 1310nm, 10km, LC interface |
| 8 | 40G QSFP+ optical module | LA-QSFP+-40G-LR4 | Single-mode, 10km, LC interface |
| 9 | DC power module | LA-PWR-2000W-DC | -48V DC input, adapts to machine room DC power supply |
| 10 | Optical module cleaning tool kit | Includes cleaning pen, lint-free wipes, alcohol swabs | For fiber optic interface cleaning |
| 11 | Cable management rack | 19-inch standard cable management rack | For rack cable organization |
| 12 | Fiber optic distribution frame | 24-port ODF fiber optic distribution frame | For fiber splicing and patching |
4.3 Unpacking and Inspection Standards
Outer Packaging Inspection: Upon receipt of goods, first check whether the outer packaging box is intact, without damage, water stains, severe compression deformation, etc. If the outer packaging is damaged, take photos on-site as evidence and contact the supplier.
Item Verification: After opening the box, verify item names, models, and quantities one by one against the packing list. Check whether they are consistent with the order and whether there are any missing or incorrect items.
Appearance Inspection: Check whether the device host and each module appear undamaged, without scratches, paint chipping, deformation, or interface damage. Check gold finger areas for oxidation or scratches.
Serial Number Verification: Verify that the chassis serial number and each module serial number are consistent with the packing list. Retain serial number information for warranty registration.
Acceptance Confirmation: After inspection confirms no issues, sign the delivery note to confirm acceptance. If any abnormalities exist, note them on-site and reject the delivery or contact the manufacturer for resolution.
Chapter 5 Product Working Principles
5.1 Basic Principles of Ethernet Switching
5.1.1 OSI Model and Switch Operating Layers
The Open Systems Interconnection reference model (OSI model) divides network communication into seven layers, from bottom to top: Physical Layer, Data Link Layer, Network Layer, Transport Layer, Session Layer, Presentation Layer, and Application Layer.
Layer 2 switches operate at the Data Link Layer, forwarding data frames based on MAC addresses, primarily solving data exchange problems within the same local area network.
Layer 3 core switches operate at both the Network Layer and Data Link Layer, possessing both Layer 2 switching and Layer 3 routing functions. They can perform Layer 2 forwarding based on MAC addresses and Layer 3 routing based on IP addresses, solving data exchange problems across network segments.
5.1.2 Layer 2 Switching Principles
The core of Layer 2 switching is MAC address learning and data frame forwarding. The core workflow is as follows:
MAC Address Learning: When a switch port receives a data frame, it reads the source MAC address in the frame header, records the correspondence between that MAC address and the receiving port in the MAC address table, and starts an aging timer.
Data Frame Forwarding Decision: Read the destination MAC address of the data frame and query the MAC address table:
- If the destination MAC address exists and the corresponding port is different from the receiving port, forward the data frame from the corresponding port;
- If the destination MAC address exists and the corresponding port is the same as the receiving port, discard the data frame;
- If the destination MAC address does not exist, flood the frame to all ports except the receiving port (broadcast).
Broadcast and Multicast Processing: For broadcast frames (destination MAC all F), flood to all ports. For multicast frames, when IGMP Snooping is enabled, forward to multicast member ports; when not enabled, process the same as broadcast frames.
5.1.3 Layer 3 Routing Principles
Layer 3 core switches achieve wire-speed Layer 3 forwarding through hardware switching chips. The core principle is “route once, switch many.” The workflow is as follows:
First Packet Routing Processing: When the first cross-network-segment data packet arrives, the switch uploads it to the main control CPU for software routing processing. The routing table is queried to find the next-hop IP address and egress port, and the next-hop MAC address is resolved simultaneously. After packet encapsulation is completed, the packet is forwarded.
Forwarding Table Generation: After CPU processing is complete, the forwarding information for this data flow (source IP, destination IP, next-hop MAC, egress port, etc.) is written into the hardware forwarding table (FIB table).
Subsequent Packet Hardware Forwarding: When subsequent packets of the same data flow arrive, the switching chip directly queries the hardware forwarding table and performs Layer 2 encapsulation and forwarding directly without CPU involvement, achieving wire-speed forwarding and greatly improving forwarding efficiency.
5.2 Core Switch Architecture Principles
5.2.1 Shared Bus Architecture
Early core switches adopted a shared bus architecture, where all line cards shared a single high-speed bus for data transmission, and all data packets were forwarded through the bus. This architecture is simple in structure and low in cost, but the bus bandwidth becomes a performance bottleneck and cannot support high-density high-speed ports. It is only found in low-end box-type devices.
5.2.2 Shared Memory Architecture
The shared memory architecture stores all data packets in a central shared memory pool, with each port achieving data exchange through memory reads and writes. This architecture offers flexible forwarding and supports complex traffic management, but memory bandwidth and access latency limit overall performance. It is primarily used in mid-to-low-end box-type core switches.
5.2.3 CLOS Multi-Stage Multi-Plane Switching Architecture
The CLOS architecture is the mainstream architecture for high-end chassis-type core switches. It was proposed by Charles Clos in 1953 and constructs a non-blocking switching network through multi-stage switching units. The three-stage CLOS architecture includes the ingress switching stage, middle switching stage, and egress switching stage. Data packets complete cross-board forwarding through three stages of switching.
In chassis-type switches, the local switching chips of service line cards constitute the ingress and egress stages, switching fabric boards constitute the middle stage, and multiple switching fabric boards form multiple parallel switching planes. This architecture offers the following advantages:
Non-blocking Forwarding: By properly configuring the number of switching planes, non-blocking wire-speed forwarding of all device ports can be achieved.
High Scalability: By increasing the number of switching fabric boards and service line cards, the overall switching capacity can be smoothly upgraded.
High Reliability: Multiple switching plane redundancy means that a single plane failure does not affect overall forwarding, only resulting in partial bandwidth loss.
Low Latency: The data forwarding path is fixed, and forwarding latency is stable and controllable.
5.3 Core Functional Technology Principles
5.3.1 VLAN Working Principles
Virtual Local Area Network (VLAN) logically divides a physical LAN into multiple broadcast domains by inserting a VLAN tag (802.1Q tag) into the Ethernet frame. Different VLANs are isolated at Layer 2 by default.
Access Port: Belongs to a single VLAN. Strips the VLAN tag when sending data and adds the port default VLAN tag (PVID) when receiving untagged data.
Trunk Port: Allows data from multiple VLANs to pass through. When sending data, tags are retained for all VLANs except the PVID-corresponding VLAN. When receiving, tags are recognized and forwarded to the corresponding VLAN.
Core switches implement service isolation, security control, and broadcast storm suppression through VLANs, making it a foundational technology for campus networks.
5.3.2 Link Aggregation Principles
Link Aggregation (LACP, IEEE 802.3ad) bundles multiple physical links into a single logical aggregate link, achieving bandwidth stacking and link redundancy.
Bandwidth Enhancement: After aggregating N Gigabit links, a logical bandwidth approaching N times can be obtained, increasing backbone link capacity.
Redundancy Backup: When a physical link within the aggregation group fails, traffic automatically switches to the remaining healthy links, achieving millisecond-level convergence and ensuring uninterrupted business operations.
Load Sharing: Based on hash algorithms using source MAC, destination MAC, source IP, destination IP, etc., traffic is evenly distributed across each physical link, improving link utilization.
5.3.3 Spanning Tree Protocol Principles
Spanning Tree Protocol (STP/RSTP/MSTP) logically blocks certain ports to prune a Layer 2 network with physical loops into a loop-free tree topology, preventing broadcast storms and MAC address table flapping.
STP (802.1D): Standard spanning tree protocol, convergence time approximately 30-50 seconds, slow convergence speed.
RSTP (802.1w): Rapid spanning tree protocol. Through edge ports and point-to-point link optimization, convergence time is reduced to the second level.
MSTP (802.1s): Multiple spanning tree protocol. Can divide spanning tree instances based on VLANs, achieving traffic load sharing while remaining compatible with STP and RSTP.
5.3.4 Dynamic Routing Protocol Principles
Core switches support dynamic routing protocols such as OSPF, IS-IS, and BGP, automatically learning network routing information to achieve dynamic route updates and optimal path selection.
OSPF: Link-state routing protocol. Calculates the shortest path based on the SPF algorithm and supports area partitioning. Suitable for internal routing in medium-sized campus networks.
IS-IS: Also a link-state protocol with stronger scalability. Commonly used in carrier networks and large campus backbones.
BGP: Path-vector routing protocol. Used for route exchange between different autonomous systems. It is the core routing protocol of the Internet and is also used in large enterprise multi-egress scenarios.
5.3.5 VRRP Redundancy Principles
The Virtual Router Redundancy Protocol (VRRP) groups multiple Layer 3 switches into a virtual router group sharing a virtual IP address. One device serves as the active router while the others serve as standby routers. When the active device fails, the standby device automatically takes over the virtual IP, achieving gateway redundancy and ensuring uninterrupted default gateway service for end users.
VRRP supports priority settings, preemption mode, and authentication mechanisms. It can work in conjunction with link tracking to achieve more granular failover.
5.4 High-Reliability Technology Principles
5.4.1 Non-Stop Forwarding (NSF)
Non-Stop Forwarding technology separates the control plane from the forwarding plane. During main control engine switchover, system upgrades, or protocol restarts, the forwarding plane continues to operate normally and data forwarding is not interrupted. Only the control plane experiences a brief interruption, greatly improving network availability.
5.4.2 Graceful Restart (GR)
Graceful Restart is a high-reliability technology for routing protocols. During device restart or active/standby switchover, protocol negotiation with neighboring devices ensures that neighboring devices maintain routing entries without aging for a certain period, ensuring that forwarding paths remain unchanged and avoiding route flapping and service interruption. Core switches support graceful restart for multiple protocols including OSPF GR, BGP GR, and IS-IS GR.
5.4.3 Hot-Swap Technology
The control boards, power modules, fan modules, and service line cards of core switches all support hot-swapping. Module replacement and expansion can be performed while the device is powered on and operating, without requiring a full device restart, ensuring uninterrupted network services. Hot-swapping is achieved through hardware-software coordination: when inserting a module, it is automatically recognized, powered on, and drivers are loaded; when removing a module, power is first cut off and services are stopped before physical removal is permitted.
Chapter 6 Product Technical Parameters
6.1 LA-Core 7808 Chassis-Type Core Switch Technical Parameters
6.1.1 Basic Performance Parameters
| Parameter Category | Parameter Item | Specific Specification |
|---|---|---|
| Chassis Specifications | Chassis slots | 8 service slots + 2 control slots + 6 switching fabric board slots |
| Chassis height | 12U (standard 19-inch rack-mount) | |
| Chassis dimensions (W × D × H) | 442mm × 650mm × 530mm | |
| Total device weight | Approximately 85kg (fully configured) | |
| Switching Performance | Switching capacity | 76.8Tbps / 153.6Tbps (dual plane) |
| Packet forwarding rate | 38400 Mpps | |
| Switching architecture | Three-stage CLOS multi-plane non-blocking switching | |
| Forwarding latency | ≤3μs (10G port, 64-byte packet) | |
| Address Table | MAC address table capacity | 512K |
| ARP table capacity | 256K | |
| IPv4 routing table capacity | 512K | |
| IPv6 routing table capacity | 256K | |
| VLAN Specifications | Number of VLANs | Supports 4094 VLAN IDs, simultaneously active VLANs ≥2000 |
| Supported VLAN types | Port-based VLAN, protocol-based VLAN, MAC-based VLAN, Super VLAN | |
| VLAN aggregation | Supports VLAN Stacking (QinQ) |
6.1.2 Hardware Reliability Parameters
| Parameter Item | Specific Specification |
|---|---|
| Control redundancy | Supports 1:1 hot backup, active/standby switchover time <50ms |
| Switching fabric board redundancy | Supports N+M redundancy, supports hot-swap |
| Power supply redundancy | Supports 2+2, 1+1 redundancy modes, supports hot-swap |
| Fan redundancy | Supports N+1 redundancy, intelligent speed control, supports hot-swap |
| Mean Time Between Failures (MTBF) | ≥400000 hours |
| Mean Time To Repair (MTTR) | ≤30 minutes |
| Availability | ≥99.999% |
6.1.3 Functional and Protocol Parameters
| Functional Category | Supported Protocols and Features |
|---|---|
| Layer 2 Protocols | IEEE 802.1Q VLAN, STP/RSTP/MSTP, LACP static/dynamic aggregation, LLDP, IGMP Snooping v1/v2/v3, MLD Snooping, GVRP, port mirroring, flow mirroring |
| Layer 3 Routing | Static routing, RIP v1/v2, OSPF v2/v3, IS-IS, BGP v4/v4+, policy-based routing, ECMP equal-cost routing (up to 64 paths), VRRP v2/v3 |
| Multicast Protocols | PIM-SM, PIM-DM, PIM-SSM, MSDP, MBGP |
| MPLS Functions | MPLS L3VPN, MPLS L2VPN, VPLS, MPLS TE, LDP |
| Data Center Features | VXLAN, EVPN, TRILL, RDMA lossless network, PFC, ECN |
| QoS Functions | Supports SP, WRR, WFQ queue scheduling; supports CAR traffic rate limiting; supports WRED congestion avoidance; supports 802.1p/DSCP priority mapping |
| Security Functions | Standard/extended/expert-level ACL, time-based ACL, ARP anti-spoofing, DHCP Snooping, IP Source Guard, 802.1X authentication, MAC address authentication, Portal authentication, DoS/DDoS attack defense, port security |
| Management and O&M | CLI command line, Web graphical network management, SNMP v1/v2c/v3, Telnet, SSH v2, Syslog, NTP clock synchronization, NETCONF, sFlow traffic sampling, RMON, USB flash drive rapid deployment |
6.1.4 Power Supply and Environmental Parameters
| Parameter Item | Specific Specification |
|---|---|
| Input voltage | AC: 100-240V AC, 50/60Hz; DC: -36V ~ -72V DC |
| Maximum device power | ≤3200W (fully configured) |
| Operating temperature | 0°C ~ 45°C (long-term operation); -5°C ~ 55°C (short-term operation) |
| Storage temperature | -40°C ~ 70°C |
| Operating humidity | 10% ~ 90%, non-condensing |
| Heat dissipation method | Front-to-rear intelligent speed-controlled air cooling |
| Noise | ≤65dB (normal temperature, full load) |
| Protection rating | IP30 |
| Compliance certifications | CCC, CE, FCC, RoHS |
6.2 LA-Core 3248X Box-Type Core Switch Technical Parameters
| Parameter Category | Parameter Item | Specific Specification |
|---|---|---|
| Hardware Specifications | Port configuration | 48 × 10G SFP+ optical ports + 8 × 100G QSFP28 optical ports |
| Chassis height | 2U (standard 19-inch rack-mount) | |
| Dimensions | 442mm × 450mm × 88mm | |
| Weight | Approximately 12kg | |
| Performance Parameters | Switching capacity | 2.56Tbps |
| Packet forwarding rate | 1440 Mpps | |
| MAC address table | 256K | |
| IPv4 routing table | 128K | |
| Number of VLANs | 4094 | |
| Reliability | Power supply | Dual power supply redundancy, supports hot-swap |
| Fan | Intelligent speed-controlled fan, supports hot-swap | |
| MTBF | ≥200000 hours | |
| Functional Support | Routing protocols | Static routing, RIP, OSPF, BGP, VRRP |
| Layer 2 functions | VLAN, MSTP, LACP, IGMP Snooping | |
| Security functions | ACL, ARP protection, DHCP Snooping, 802.1X | |
| Management methods | CLI, Web, SNMP, SSH | |
| Environmental Parameters | Operating temperature | 0°C ~ 45°C |
| Power supply input | 100-240V AC | |
| Maximum power | ≤350W |
6.3 Optical Module Technical Parameters
6.3.1 Gigabit SFP Optical Module Parameters
| Model | Rate | Wavelength | Transmission Distance | Interface Type | Transmit Optical Power | Receive Sensitivity |
|---|---|---|---|---|---|---|
| LA-SFP-GE-SX | 1.25Gbps | 850nm | 550m (Multi-mode) | LC | -9.5 ~ -3dBm | ≤-17dBm |
| LA-SFP-GE-LX | 1.25Gbps | 1310nm | 10km (Single-mode) | LC | -9.5 ~ -3dBm | ≤-20dBm |
| LA-SFP-GE-LH40 | 1.25Gbps | 1310nm | 40km (Single-mode) | LC | -5 ~ 0dBm | ≤-24dBm |
6.3.2 10G SFP+ Optical Module Parameters
| Model | Rate | Wavelength | Transmission Distance | Interface Type | Transmit Optical Power | Receive Sensitivity |
|---|---|---|---|---|---|---|
| LA-SFP+-10G-SR | 10.3125Gbps | 850nm | 300m (Multi-mode) | LC | -7.3 ~ -1dBm | ≤-7.3dBm |
| LA-SFP+-10G-LR | 10.3125Gbps | 1310nm | 10km (Single-mode) | LC | -8.2 ~ 0.5dBm | ≤-11.1dBm |
| LA-SFP+-10G-ER | 10.3125Gbps | 1550nm | 40km (Single-mode) | LC | -4.7 ~ 4dBm | ≤-11.1dBm |
Chapter 7 Product Functions and Features
7.1 High-Performance Forwarding Capability
Wire-Speed Non-Blocking Forwarding
Utilizing a high-performance switching chip with CLOS architecture design, all ports support wire-speed forwarding of 64-byte small packets without port blocking, ensuring smooth network traffic flow during peak periods. Even during concurrent high-bandwidth services such as video conferencing, data backup, and large file transfers, low latency and zero packet loss are maintained.
Large Table Capacity
Equipped with high-capacity MAC address tables, ARP tables, and routing tables, capable of accommodating large-scale terminal access and complex network routing. Adaptable to massive terminal access requirements in large campuses and data centers, preventing network failures caused by table overflow.
Intelligent Traffic Scheduling
Supports refined QoS scheduling capabilities, enabling traffic classification based on multiple dimensions including port, VLAN, IP address, protocol type, and application port. Allocates differentiated bandwidth and priority to different service levels such as voice, video, and core business operations, ensuring priority forwarding for critical services. Supports congestion avoidance, traffic shaping, and port rate limiting to achieve rational allocation of network resources.
7.2 Carrier-Grade High Reliability
Full Hardware Redundancy Design
All critical components including main control engines, switch fabric boards, power modules, and fan modules support redundant configuration, with automatic switching upon critical component failure without affecting overall system operation. All replaceable modules support hot-swapping, enabling maintenance operations without service interruption, comprehensively ensuring 7×24-hour stable operation of the core network.
Multi-Layer Reliability Protocols
Supports VRRP gateway redundancy, LACP link redundancy, MSTP topology redundancy, and ECMP route redundancy, building an end-to-end redundancy protection system from the link layer to the network layer. Single-point failures achieve millisecond-level convergence with service-transparent operation. Supports GR (Graceful Restart) and NSF (Non-Stop Forwarding), ensuring uninterrupted data forwarding during device upgrades and active/standby switchovers.
Comprehensive Fault Detection Mechanism
Supports rapid fault detection technologies including BFD bidirectional forwarding detection, Ethernet OAM, and port status detection, capable of detecting link and device failures within milliseconds, triggering protection switching and significantly reducing fault recovery time.
7.3 Flexible Expansion and Compatibility
Modular Smooth Expansion
Chassis core switches support flexible expansion of service line cards. Users can progressively increase port count and upgrade port rates based on business growth without replacing the entire system, protecting initial investment. Supports mixed installation of Gigabit, 10G, 40G, 100G, and 400G rate line cards to accommodate bandwidth requirements of different services.
Comprehensive Standard Compatibility
Strictly adheres to international standard protocols including IEEE and IETF, fully compatible with mainstream vendor network equipment, enabling seamless integration into existing network architectures without large-scale modification. Supports standard optical modules and is compatible with compliant optical modules from various brands, reducing user accessory costs.
Multi-Scenario Adaptability
The same hardware platform can activate different function sets through software licenses, adapting to different scenario requirements including campus networks, data centers, and industrial networks. Multiple functions in one device, reducing user spare inventory and maintenance costs.
7.4 Comprehensive Security Protection
Access Security Protection
Supports multiple access authentication methods including 802.1X authentication, MAC address authentication, and Portal authentication, working with AAA servers to implement user identity management and prevent unauthorized terminal access to the network. Supports port security features, limiting the number of MAC addresses learned on ports to prevent MAC address flooding attacks.
Network Layer Security Protection
Supports rich Access Control Lists (ACL), enabling granular access control based on five-tuple, time periods, VLANs, and other dimensions to isolate different security domains. Supports Layer 2 security features including ARP anti-spoofing, DHCP Snooping, and IP Source Guard, effectively defending against common intranet threats such as ARP attacks and rogue DHCP servers.
Anti-Attack Capability
Built-in hardware-level attack defense engine capable of identifying and defending against common network attacks including DoS/DDoS attacks, SYN flooding, and ICMP flooding, ensuring stable CPU operation and preventing device paralysis from attacks. Supports control plane rate limiting to prevent illegal traffic from impacting the device control plane.
7.5 Intelligent Operations and Maintenance Management
Diversified Management Methods
Provides multiple management methods including CLI command line, Web graphical network management, SNMP, and NETCONF, accommodating different preferences of operations personnel. Supports SSH and Telnet remote management, combined with hierarchical privilege management for secure remote operations.
Automated Operations Capability
Supports zero-configuration deployment via USB drive, with devices automatically reading configuration files from USB upon power-on to complete initialization, significantly improving batch deployment efficiency. Supports automatic configuration backup and remote software version upgrade, reducing operations workload. Supports Python scripting and open APIs, enabling integration with third-party automated operations platforms for network automation management.
Visualized Operations Monitoring
Supports sFlow/NetStream traffic sampling for real-time monitoring of network traffic distribution and Top traffic, enabling rapid identification of network anomalies. Supports rich Syslog logging and alarm functions, with real-time reporting of device failures, port anomalies, and performance threshold breaches for rapid troubleshooting by operations personnel. Supports port mirroring and flow mirroring to provide data support for network fault diagnosis and traffic analysis.
7.6 Green Energy-Saving Design
Intelligent Power Management
Supports port sleep and dynamic power adjustment functions, with unconnected ports automatically entering low-power mode to reduce standby power consumption. The intelligent fan speed control system dynamically adjusts fan speed based on real-time device temperature, reducing energy consumption and noise while ensuring adequate heat dissipation.
High-Efficiency Power Supply Design
Utilizes high-efficiency power modules with conversion efficiency exceeding 92%, reducing electrical energy loss. Supports redundant power intelligent sleep mode, with some power supplies entering sleep mode under light load conditions to improve overall energy efficiency.
Environmentally Friendly Materials
The entire system uses lead-free processes and environmentally friendly materials, compliant with RoHS environmental standards, reducing the impact of hazardous substances on the environment and human health. Packaging materials use recyclable materials, practicing green environmental concepts.
Chapter 8 Product Application Scenarios
8.1 Large Enterprise Campus Network Core
Scenario Description
Large enterprise headquarters campuses typically include multiple office buildings, R&D buildings, and production workshops, with terminal counts ranging from thousands to tens of thousands. Business covers office OA, video conferencing, ERP systems, production control, and security surveillance. The network needs to carry concurrent multi-service traffic while ensuring stable operation of core services.
Deployment Solution
Deploy two LA-Core 7808 chassis core switches in the campus central equipment room, utilizing virtualization technology to build a dual-core architecture for load sharing and redundancy backup. Building aggregation switches uplink to the two core switches via 10G/40G dual links, using link aggregation and MSTP for link redundancy and load sharing. Core switches connect to egress routers and firewalls for Internet access and border security protection.
Value Proposition
Dual-core architecture ensures high network availability, with single core failure not affecting entire network operation; high-performance forwarding capability carries concurrent multi-service traffic; refined QoS ensures quality experience for core services such as video conferencing and ERP; unified network management platform enables centralized operations across the entire network, reducing management complexity.
8.2 Smart Campus Network Core
Scenario Description
University campus networks cover teaching buildings, libraries, dormitory areas, administrative buildings, and gymnasiums. Terminal scale is large with complex user groups. Services include multimedia teaching, online examinations, campus card systems, library resource access, dormitory Internet access, and security surveillance. Peak period traffic pressure is significant, while user authentication and behavior management are also required.
Deployment Solution
Deploy two LA-Core 7812 high-end core switches in the campus core equipment room as the entire network core, dividing into multiple logical areas including teaching, dormitory, and administrative office zones, with business isolation through VLANs and ACLs. Core switches connect to authentication and billing systems for student Internet access authentication and bandwidth management. 10G backbone links connect aggregation nodes in each area, with the data center area accessing the core via 100G high-speed links to ensure teaching resource access speed.
Value Proposition
Large table capacity carries access for tens of thousands of student terminals; powerful QoS capabilities ensure teaching business priority; comprehensive security authentication system achieves manageable and controllable campus network; high-reliability design ensures network stability during critical periods such as teaching and examinations.
8.3 Government External Network Core Node
Scenario Description
The government external network connects government departments at all levels, carrying government office operations, data sharing, and public service businesses. Network security, reliability, and compliance requirements are extremely high, requiring compliance with MLPS 2.0 (Multi-Level Protection Scheme) related requirements, while supporting multi-department business isolation and secure data transmission.
Deployment Solution
Deploy LA-Core 7808 Xinchuang (indigenous innovation) edition core switches as the government external network regional core, with dual-system redundant deployment. MPLS VPN technology is used to achieve logical isolation of different departments and different security level services, ensuring data security. Integration with government security platforms implements access control, behavior auditing, and security monitoring. Equipment fully adopts domestic chips and domestic operating systems, meeting Xinchuang compliance requirements.
Value Proposition
Self-controllable software and hardware platform meets government Xinchuang requirements; MPLS VPN achieves secure isolation across multiple departments; carrier-grade reliability ensures 7×24-hour availability of government services; comprehensive security functions meet MLPS compliance requirements.
8.4 Small and Medium Data Center Core
Scenario Description
Small and medium data centers carry enterprise private cloud, business server clusters, and storage backup systems. Server density is high with large traffic volumes and high east-west traffic ratio, requiring high network forwarding performance, low latency, and virtualization capabilities, while also supporting cloud computing and elastic business expansion.
Deployment Solution
Adopting Spine-Leaf architecture, deploying two LA-Core 7808 switches as Spine core nodes, connected downstream to multiple Leaf access switches. Servers access Leaf switches via 10G/25G connections, and Leaf switches dual-uplink to Spine cores via 100G high-speed links. Core switches support VXLAN EVPN large Layer 2 technology, enabling virtual machine cross-equipment-room migration and elastic business deployment. Supports RDMA lossless networks, adapted to storage and high-performance computing business requirements.
Value Proposition
CLOS non-blocking architecture ensures high-speed data exchange between servers; low-latency forwarding improves cloud computing business performance; large Layer 2 technology supports virtualization and cloud business deployment; intelligent traffic scheduling improves overall network resource utilization.
8.5 Industrial Plant Network Core
Scenario Description
Industrial scenarios including manufacturing plants, mines, and power utilities have harsh production environments with electromagnetic interference, large temperature fluctuations, and high dust levels. The network needs to carry industrial control, video surveillance, data acquisition, and office management services, placing extremely high demands on equipment environmental adaptability and reliability.
Deployment Solution
Deploy LA-Core 3000 series industrial-grade core switches in the plant central equipment room, featuring industrial-grade wide-temperature design and strong anti-interference capability. Workshops adopt industrial ring network access, with core switches supporting ring network protection protocols for millisecond-level link failure switchover. Production networks and office networks are isolated through VLANs and firewalls to ensure production network security.
Value Proposition
Industrial-grade hardware adapts to harsh plant environments; ring network redundancy ensures uninterrupted production operations; network isolation ensures industrial control system security and stability; unified operations platform enables centralized plant network management.
8.6 Branch Office Aggregation Core
Scenario Description
Municipal branch offices and county-level subsidiary companies of large enterprises have terminal scales of several hundred devices, requiring connection of headquarters and local business networks while ensuring stable dedicated line interconnection with headquarters. Equipment requires high cost-effectiveness and easy maintenance characteristics.
Deployment Solution
Deploy LA-Core 3248X box core switch as the branch core, with local access switches using Gigabit access and 10G uplink to the core. Core switches interconnect with headquarters core routers via dedicated lines, running OSPF/BGP routing protocols for headquarters-branch network connectivity. Dual power supply redundancy ensures stable equipment operation, and remote maintenance functions reduce on-site maintenance costs.
Value Proposition
High cost-effectiveness meets branch network budget requirements; Layer 3 routing functions achieve efficient headquarters-branch interconnection; compact structure adapts to branch equipment room space constraints; remote maintenance capability reduces headquarters maintenance pressure.
Chapter 9 Product Installation
9.1 Pre-Installation Preparation
9.1.1 Environment Inspection
Equipment Room Environment Requirements
- Equipment room temperature should be maintained between 10℃ and 35℃, with optimal working temperature of 22℃±2℃, avoiding prolonged equipment operation in high-temperature environments.
- Equipment room relative humidity maintained at 30%~80% without condensation. Dehumidification equipment is required in high-humidity areas, and anti-static precautions should be taken in dry areas.
- Equipment room must be kept clean, with dust concentration meeting equipment room standards, preventing dust from entering equipment and affecting heat dissipation and circuit safety.
- Equipment room must have good ventilation and heat dissipation conditions; cold/hot aisle design is preferred, with no obstructions at equipment air intakes.
- Equipment room must be located away from strong electromagnetic interference sources, strong vibration sources, flammable and explosive items, and corrosive gases.
Cabinet Installation Condition Inspection
| Item | Requirement |
|---|---|
| Cabinet specification | Standard 19-inch server cabinet, load-bearing capacity meeting fully-loaded equipment weight requirements (chassis equipment recommended cabinet load capacity ≥100kg/U) |
| Installation space | Sufficient space reserved inside cabinet, at least 1U heat dissipation space reserved above and below chassis equipment |
| Grounding | Cabinet properly grounded, grounding resistance ≤1Ω, compliant with equipment room grounding standards |
| Power supply | Cabinet PDU power capacity meeting equipment maximum power requirements, with sufficient power outlets reserved |
9.1.2 Tools and Materials Preparation
Installation Tools
| Tool Category | Tool Name | Purpose |
|---|---|---|
| Installation Tools | Phillips screwdriver (PH2) | Equipment fixing, screw installation |
| Flat-head screwdriver | Module removal, cover plate opening | |
| Hex wrench | Tightening certain chassis screws | |
| Torque wrench | Tightening fasteners to standard torque | |
| Anti-static wrist strap/gloves | Static protection, handling circuit boards and modules | |
| Tape measure/level | Cabinet installation position measurement and level calibration | |
| Auxiliary Tools | Label printer | Cable and port label production |
| Cable ties/cable management rack | Cable organization and fixing | |
| Flashlight | Cabinet interior lighting | |
| Diagonal pliers/scissors | Cable tie cutting | |
| Test Tools | Multimeter | Power supply voltage detection, continuity testing |
| Optical power meter | Optical link loss testing | |
| Laptop computer | Equipment configuration and debugging | |
| Console cable | Equipment local management |
9.1.3 Personnel and Safety Preparation
- Installation personnel must have network equipment installation experience, be familiar with equipment room operating procedures, and have read and understood the installation-related content in this manual.
- Anti-static wrist straps must be worn and properly grounded when operating equipment hardware. It is strictly prohibited to touch circuit board gold fingers and chips with bare hands to prevent static damage to components.
- Heavy equipment (fully-loaded chassis) requires at least 2-3 personnel for handling, using cabinet rails or lifting equipment to avoid personal injury or equipment drops from single-person handling.
- Confirm the power supply switch is OFF before power operations. It is strictly prohibited to hot-swap components other than power modules to prevent electric shock hazards.
9.2 Cabinet Installation Procedure
9.2.1 Installing Mounting Brackets and Rails
Remove the mounting brackets and screws from the accessory kit. Align the brackets with the mounting holes on both sides of the chassis and secure the brackets to the front of the chassis using the included screws. Some models support front/rear adjustable brackets, allowing installation position adjustment based on cabinet depth.
For heavy chassis equipment, sliding rails must first be installed in the cabinet. Adjust the rail length according to chassis depth, secure both ends of the rails to the square holes of the cabinet mounting rails, ensuring the left and right rails are level and at the same height.
Use a level to calibrate rail levelness to prevent equipment tilting, and tighten the rail mounting screws.
9.2.2 Equipment Rack Mounting
Two people coordinate to lift the chassis and place it smoothly onto the rails, then slowly push the equipment into the cabinet along the rails, being careful to avoid collision with the cabinet and equipment interfaces.
After pushing the equipment to the installation position, align the front mounting brackets with the cabinet mounting rail holes, insert M6 cabinet screws, and tighten the screws sequentially in a diagonal pattern to ensure the equipment is securely fixed.
Check equipment mounting firmness by gently pushing the equipment to verify no movement, and confirm the equipment is level without tilting.
9.2.3 Grounding Connection
Remove the grounding cable from the accessories, connect one end to the grounding terminal on the side of the chassis, and tighten the screw with a screwdriver.
Connect the other end of the grounding cable to the cabinet grounding busbar or equipment room grounding system, ensuring good contact and grounding resistance compliance with specifications.
The grounding cable must be a yellow-green dual-color dedicated grounding wire with a cross-sectional area of no less than 6mm² and appropriate length to avoid strain.
9.3 Module Installation Procedure
9.3.1 Main Control Board and Switch Fabric Board Installation
Wear the anti-static wrist strap, remove the main control board from the anti-static packaging, hold the handles on the top and bottom of the board, and align with the main control slot rails on the chassis.
Smoothly push the board along the rails into the slot until the board faceplate is flush with the chassis faceplate, then operate the levers on both sides of the board to fully insert the board into the backplane connector. A “click” sound indicates proper seating.
Tighten the mounting screws on both sides of the board faceplate with a Phillips screwdriver to ensure the board is firmly secured.
Follow the same procedure to install the standby main control board and switch fabric boards, noting the board slot markings and strictly avoiding incorrect slot insertion. Switch fabric boards should be evenly distributed to ensure balanced heat dissipation and traffic flow.
9.3.2 Service Line Card Installation
Confirm the service line card model matches the slot plan, remove the blank panel from the corresponding slot, and properly store the blank panel for future use.
Hold the handles on both sides of the service line card and smoothly push it in along the slot rails. After initial contact with the backplane, operate the levers to fully seat the card.
Tighten the faceplate mounting screws to ensure the card is properly installed.
Installation Precautions:
- It is strictly prohibited to forcibly insert or remove boards while powered on. Hot-swap operations must follow standard procedures.
- Keep the board level during installation to avoid tilting that could damage backplane connectors.
- Slots without installed boards must have blank panels installed to maintain airflow integrity and dust protection.
9.3.3 Power Module Installation
Remove the blank panel from the power slot and remove the power module from the anti-static packaging.
With the power module handle facing up, smoothly push it along the slot rails until fully inserted, at which point the internal latch automatically locks.
Gently pull the power module handle to confirm secure installation without looseness.
Install all redundant power modules according to the plan, ensuring the two power feeds are connected to different power supply circuits for true physical redundancy.
9.3.4 Fan Module Installation
Confirm the fan module airflow direction matches the system airflow direction, then insert into the fan slot.
Smoothly push the fan module in until the latch automatically locks, confirming proper installation.
Fan modules support hot-swapping. For replacement, first release the latch, then smoothly pull out the module.
9.3.5 Optical Module Installation
Wear anti-static gloves, remove the optical module from its packaging, and inspect the gold fingers for oxidation or scratches.
With the optical module pull ring facing down (some models face up per markings), align with the optical port slot and insert smoothly until a “click” sound is heard, confirming proper installation.
Installation Precautions:
- It is strictly prohibited to forcefully bend or knock optical modules to avoid damaging the internal optical path.
- Keep the dust plug on the optical module when no fiber is connected to prevent dust contamination of the end face.
- It is strictly prohibited to look directly into the optical module transmitter port to avoid laser eye injury.
- Optical modules must match the interface rate. It is strictly prohibited to force-insert into incompatible slots.
9.4 Post-Installation Inspection
- Physical Installation Inspection: Verify all boards and modules are properly installed with tightened screws; equipment is securely fixed without looseness or tilting; grounding connection is reliable.
- Cable Routing Inspection: Verify power cables and grounding cables are neatly routed without compression or damage; labels are clear and standardized.
- Power Supply Environment Inspection: Use a multimeter to measure supply voltage, confirming voltage is within the equipment rated input range; confirm power switch control functions normally.
- Airflow Inspection: Confirm equipment air intakes and exhausts have no obstructions, and cabinet ventilation is smooth.
- Documentation Verification: Record equipment serial numbers, module models and serial numbers, and organize installation documentation for archiving.
Chapter 10 Product Wiring
10.1 Power Cable Connection
10.1.1 AC Power Cable Connection
Confirm the equipment power switch is in the OFF position and the cabinet PDU power supply switch is in the OFF position.
Insert the equipment end plug of the AC power cable into the AC input interface of the power module, ensuring it is fully seated.
Use the power cable tie to secure the power cable to the fixing clip on the power module to prevent accidental cable disconnection.
Insert the other end of the power cable into the corresponding socket on the cabinet PDU, ensuring a secure connection.
Connect multiple power modules to different power supply circuits (e.g., mains 1, mains 2/UPS output) for physical redundancy.
After wiring is completed, verify the connections are correct, then close the PDU switches and equipment power switches in sequence and observe the power indicator status.
10.1.2 DC Power Cable Connection
Confirm the DC power supply circuit breaker is in the OFF position and verify zero voltage by measurement.
DC power cables typically include three conductors: positive, negative, and ground, corresponding to -48V (negative), RTN (positive), and PGND (protective ground) markings.
Strip the insulation from the cable ends, crimp cold-pressed terminals, connect the cables to the corresponding DC wiring terminals on the power module, and tighten screws to the required torque.
Cable color standards: typically blue for -48V negative, black for RTN positive, and yellow-green dual-color for protective ground.
Connect the other end to the equipment room DC power supply system. Strictly avoid reversing positive and negative polarity, as reverse connection will burn out the equipment.
After wiring is completed, re-verify polarity, and close the circuit breaker to power on after confirming correctness.
10.2 Management Cable Connection
10.2.1 Console Configuration Cable Connection
Remove the RJ45-to-DB9 Console configuration cable, insert the RJ45 end into the Console port on the core switch main control board.
Insert the DB9 end into the serial port of the debugging laptop. If the laptop has no serial port, use a USB-to-serial adapter and install the corresponding driver.
Start terminal emulation software (such as SecureCRT, PuTTY, Xshell) and configure the serial port parameters:
| Parameter | Value |
|---|---|
| Baud rate | 9600 |
| Data bits | 8 |
| Stop bits | 1 |
| Parity | None |
| Flow control | None |
After successful connection, system startup logs can be viewed on the terminal interface when the device powers on.
10.2.2 Management Network Port Connection
Use a standard Ethernet patch cable, inserting one end into the MGMT management Ethernet port on the main control board.
Connect the other end to the operations management network or the local debugging computer’s network port.
The default management port IP is typically 192.168.1.1/24, and device management can be performed via Web, Telnet, or SSH.
It is recommended to connect the management network port to a dedicated operations network, physically isolated from the business network, to enhance management security.
10.3 Service Cable Connection
10.3.1 Electrical Port Cable Connection
Use Cat5e/Cat6 shielded Ethernet patch cables with a maximum length of 100 meters.
Align the RJ45 connector with the electrical port slot and insert smoothly until a “click” sound indicates proper latching.
Connect the other end to the corresponding interface of the peer device, such as access switches, servers, or routers.
After connection, observe the port indicator light. A steady green light indicates normal physical connection, and blinking indicates data transmission.
Cabling Standards:
- Network cables should be routed away from high-voltage power cables to avoid electromagnetic interference.
- The cable bending radius should be no less than 8 times the cable diameter. Rigid 90-degree bending is strictly prohibited.
- Labels should be affixed at both ends of the cable, indicating the ports and purposes at both ends for ease of maintenance.
10.3.2 Fiber Optic Cable Connection
Prepare fiber jumpers of the appropriate specification (single-mode/multi-mode, LC/SC and other interface types), and check that the fiber end faces are free of stains and scratches, and that the fiber has no bends or damage.
Remove the dust plug from the optical module and the dust cap from one end of the fiber jumper.
Align with the optical module interface and insert the fiber jumper connector smoothly, ensuring it is securely latched.
Connect the other end to the optical module of the peer device, noting the transmit/receive correspondence: local transmit (TX) connects to peer receive (RX), and local receive (RX) connects to peer transmit (TX).
After connection, observe the port indicator light. The receive optical power can also be tested with an optical power meter to confirm it is within the normal range.
Fiber Cabling Standards:
- The fiber bending radius should be no less than 30mm. Small-angle bending is strictly prohibited to avoid fiber breakage.
- Fiber cables should be routed through protective conduits or fiber troughs to avoid compression and strain.
- Excess fiber length should be coiled neatly with a coil diameter of no less than 10cm.
- Labels should be affixed at both ends of the fiber, indicating the locations and fiber core numbers at both ends of the link.
10.3.3 Link Aggregation Wiring Standards
Multiple physical cables in an aggregation link must be connected to the ports of the corresponding aggregation group on the peer device. Port order is not strictly required, but rates and duplex modes must be consistent.
It is recommended that multiple cables use different physical paths to avoid all links going down due to a single route failure.
Fiber optic cables in the same aggregation group should preferably come from different fiber routes, and electrical ports should preferably come from different patch panels.
After wiring is completed, the corresponding aggregation group must be configured on the software side with the LACP protocol enabled.
10.4 Cable Organization and Labeling
- Cable Management Standards: All cables should be routed along the cabinet cable management rack and bundled neatly by category. Power cables and service cables should be routed separately with a spacing of ≥30cm. Fiber optics should use dedicated fiber troughs, avoiding mixed bundling with network cables that could cause compression.
- Bundling Requirements: Use nylon cable ties for bundling with appropriate tightness, avoiding over-tightening that could damage cable jackets. Cable tie directions should be consistent, with excess trimmed neatly and without burrs.
- Label Standards:
| Item | Requirement |
|---|---|
| Label placement | Labels affixed at both ends of cables, oriented for easy viewing |
| Label content | Clear, including local port number, peer device and port number, link number, etc. |
| Power labels | Indicate power supply circuit number |
| Management cable labels | Indicate management purpose |
- Cable Records: Create a port wiring table recording the connection object, cable number, and service type for each port, forming complete wiring documentation for subsequent operations and maintenance.
Chapter 11 Product Commissioning
11.1 Device Power-On Initialization
11.1.1 Final Pre-Power-On Inspection
- Re-confirm all boards and modules are properly installed with tightened screws.
- Confirm power cable connections are correct and supply voltage meets equipment requirements.
- Confirm Console cable connection is normal, and terminal software is open with correct parameter configuration.
- Confirm there is no short-circuit risk and no foreign objects such as tools or screws left inside the chassis.
11.1.2 Power-On Startup Procedure
Close the cabinet PDU power switch and equipment power module switches in sequence.
Observe the equipment indicators: the power indicator lights first, followed by fan startup, then the indicators on each board light up in sequence.
Observe the system startup process through the Console terminal:
1. Hardware self-test: CPU, memory, switching chips, and interface detection.
2. BootROM program loading and boot initiation.
3. System software image loading and operating system kernel startup.
4. Functional module initialization and configuration file reading.
The startup process takes approximately 3-10 minutes (longer for chassis equipment). Do not power off during this period to avoid system damage.
After startup is complete, a login prompt appears on the terminal, indicating successful system startup.
11.1.3 Startup Status Inspection
- Indicator Inspection: Power indicator steady green, system operation indicator blinking green, main control active indicator steady, standby indicator blinking, service board status indicators normal, no red alarms.
- Version Information Inspection: After logging in, check the system version and hardware version to confirm consistency with the ordered version.
- Board Status Inspection: Check the registration status of all boards, confirming all service boards, power supplies, and fans are online normally without abnormal offline status.
- Environmental Status Inspection: Check device temperature, fan speed, and power supply voltage to confirm environmental parameters are within normal ranges.
11.2 Basic Configuration
11.2.1 Device Basic Information Configuration
First Login: Refer to the product quick guide for default username and password. The administrator password must be changed upon first login.
<LA-Core> system-view [LA-Core] sysname Core-Switch-01 // Modify device name [Core-Switch-01] super password level 15 cipher Admin@123456 // Set super password
Management IP Configuration
[Core-Switch-01] interface M-GigabitEthernet 0/0/0 // Enter management port [Core-Switch-01-M-GigabitEthernet0/0/0] ip address 192.168.1.10 255.255.255.0 // Configure management IP [Core-Switch-01-M-GigabitEthernet0/0/0] quit
Remote Management Configuration
[Core-Switch-01] ssh server enable // Enable SSH service [Core-Switch-01] user-interface vty 0 4 // Enter virtual terminal configuration [Core-Switch-01-ui-vty0-4] authentication-mode aaa // Use AAA authentication [Core-Switch-01-ui-vty0-4] protocol inbound ssh // Allow SSH login only, disable Telnet for enhanced security [Core-Switch-01-ui-vty0-4] user privilege level 3 // Set privilege level [Core-Switch-01-ui-vty0-4] quit
Clock Configuration
[Core-Switch-01] clock timezone Beijing add 08:00:00 // Set time zone [Core-Switch-01] ntp server 192.168.1.254 // Configure NTP server for clock synchronization
11.2.2 VLAN Configuration
Batch VLAN Creation
[Core-Switch-01] vlan batch 10 20 30 100 200 // Batch create VLANs 10, 20, 30, 100, 200 [Core-Switch-01] vlan 10 [Core-Switch-01-vlan10] description Office_Building1 // Add VLAN description [Core-Switch-01-vlan10] quit
Trunk Port Configuration (for connecting aggregation switches)
[Core-Switch-01] interface Ten-GigabitEthernet 1/0/1 [Core-Switch-01-Ten-GigabitEthernet1/0/1] port link-type trunk // Set port type to Trunk [Core-Switch-01-Ten-GigabitEthernet1/0/1] port trunk allow-pass vlan 10 20 30 100 // Allow specified VLANs to pass [Core-Switch-01-Ten-GigabitEthernet1/0/1] undo port trunk allow-pass vlan 1 // Disallow default VLAN 1 [Core-Switch-01-Ten-GigabitEthernet1/0/1] description To-Agg-Switch-01-Port1 // Port description [Core-Switch-01-Ten-GigabitEthernet1/0/1] quit
11.2.3 Layer 3 Interface Configuration
VLANIF Interface Configuration (as gateways for VLANs)
[Core-Switch-01] interface Vlanif 10 [Core-Switch-01-Vlanif10] ip address 192.168.10.254 255.255.255.0 // Configure VLAN 10 gateway IP [Core-Switch-01-Vlanif10] description Gateway_Office1 // Interface description [Core-Switch-01-Vlanif10] quit
Layer 3 Physical Port Configuration (for connecting routers/firewalls)
[Core-Switch-01] interface Ten-GigabitEthernet 1/0/10 [Core-Switch-01-Ten-GigabitEthernet1/0/10] undo portswitch // Switch to Layer 3 routing port [Core-Switch-01-Ten-GigabitEthernet1/0/10] ip address 10.0.0.1 255.255.255.252 [Core-Switch-01-Ten-GigabitEthernet1/0/10] quit
11.3 Routing Configuration
11.3.1 Static Route Configuration
[Core-Switch-01] ip route-static 0.0.0.0 0.0.0.0 10.0.0.2 // Default route, next hop is egress firewall [Core-Switch-01] ip route-static 172.16.0.0 255.255.0.0 10.0.1.2 preference 60 // Detailed static route
11.3.2 OSPF Routing Configuration
[Core-Switch-01] ospf 1 router-id 10.0.0.1 // Create OSPF process 1, configure Router ID [Core-Switch-01-ospf-1] area 0 // Backbone area 0 [Core-Switch-01-ospf-1-area-0.0.0.0] network 192.168.10.0 0.0.0.255 // Advertise network segment [Core-Switch-01-ospf-1-area-0.0.0.0] network 10.0.0.0 0.0.0.3 [Core-Switch-01-ospf-1-area-0.0.0.0] quit [Core-Switch-01-ospf-1] quit
11.3.3 VRRP Gateway Redundancy Configuration
Configure VRRP in dual-core scenarios for gateway redundancy:
// Core switch 1 configuration [Core-Switch-01] interface Vlanif 10 [Core-Switch-01-Vlanif10] vrrp vrid 10 virtual-ip 192.168.10.1 // Virtual gateway IP [Core-Switch-01-Vlanif10] vrrp vrid 10 priority 120 // Set priority to 120, serving as primary gateway [Core-Switch-01-Vlanif10] vrrp vrid 10 preempt-mode timer delay 20 // Preempt mode with 20-second delay [Core-Switch-01-Vlanif10] quit // Core switch 2 configuration with priority 100, serving as standby gateway
11.4 Advanced Feature Configuration
11.4.1 Link Aggregation Configuration
[Core-Switch-01] interface Bridge-Aggregation 1 // Create aggregation interface 1 [Core-Switch-01-Bridge-Aggregation1] port link-type trunk [Core-Switch-01-Bridge-Aggregation1] port trunk allow-pass vlan 10 20 30 [Core-Switch-01-Bridge-Aggregation1] link-aggregation mode dynamic // Dynamic LACP mode [Core-Switch-01-Bridge-Aggregation1] quit // Add physical ports to the aggregation group [Core-Switch-01] interface range Ten-GigabitEthernet 1/0/1 to Ten-GigabitEthernet 1/0/2 [Core-Switch-01-if-range] port link-aggregation group 1 [Core-Switch-01-if-range] quit
11.4.2 MSTP Spanning Tree Configuration
[Core-Switch-01] stp mode mstp // Enable MSTP mode [Core-Switch-01] stp region-configuration // Enter MST region configuration [Core-Switch-01-mst-region] region-name LA-NETWORK // Region name [Core-Switch-01-mst-region] instance 1 vlan 10 20 // Instance 1 corresponds to VLANs 10, 20 [Core-Switch-01-mst-region] instance 2 vlan 30 100 // Instance 2 corresponds to VLANs 30, 100 [Core-Switch-01-mst-region] active // Activate configuration [Core-Switch-01-mst-region] quit [Core-Switch-01] stp instance 1 root primary // Set as primary root bridge for instance 1 [Core-Switch-01] stp instance 2 root secondary // Set as secondary root bridge for instance 2 [Core-Switch-01] stp enable // Enable spanning tree globally
11.4.3 ACL and Security Configuration
// Create advanced ACL to prohibit specified network segment from accessing servers [Core-Switch-01] acl number 3000 [Core-Switch-01-acl-adv-3000] rule deny ip source 192.168.20.0 0.0.0.255 destination 192.168.100.10 0 [Core-Switch-01-acl-adv-3000] rule permit ip [Core-Switch-01-acl-adv-3000] quit // Apply ACL on port inbound direction [Core-Switch-01] interface Ten-GigabitEthernet 1/0/5 [Core-Switch-01-Ten-GigabitEthernet1/0/5] packet-filter 3000 inbound [Core-Switch-01-Ten-GigabitEthernet1/0/5] quit // Enable ARP anti-spoofing [Core-Switch-01] arp anti-attack check user-bind enable
11.4.4 QoS Configuration
// Define traffic classifier to match voice traffic [Core-Switch-01] traffic classifier voice [Core-Switch-01-classifier-voice] if-match dscp ef [Core-Switch-01-classifier-voice] quit // Define traffic behavior to ensure high-priority scheduling [Core-Switch-01] traffic behavior voice [Core-Switch-01-behavior-voice] queue ef bandwidth pct 10 // Ensure 10% bandwidth [Core-Switch-01-behavior-voice] quit // Define QoS policy [Core-Switch-01] qos policy core-policy [Core-Switch-01-qospolicy-core-policy] classifier voice behavior voice [Core-Switch-01-qospolicy-core-policy] quit // Apply QoS policy on port [Core-Switch-01] interface Ten-GigabitEthernet 1/0/1 [Core-Switch-01-Ten-GigabitEthernet1/0/1] qos apply policy core-policy outbound [Core-Switch-01-Ten-GigabitEthernet1/0/1] quit
11.5 Functional Verification Tests
11.5.1 Connectivity Tests
- Same-VLAN connectivity: Ping tests between terminals within the same VLAN to verify Layer 2 forwarding functionality.
- Cross-VLAN connectivity: Terminals in different VLANs ping the gateway and terminals across subnets to verify Layer 3 routing functionality.
- External network connectivity: Terminals ping public addresses to verify outbound routing functionality.
- Redundancy switchover test: Disconnect the primary core device or primary link to test whether services automatically switch to the backup path and whether the service interruption time meets requirements.
11.5.2 Protocol Status Verification
- Check OSPF neighbor status to confirm neighbors are established correctly and route learning is complete.
- Check VRRP status to confirm master/backup roles are correct and the virtual gateway is pingable.
- Check link aggregation status to confirm all member ports in the aggregation group are operational and load balancing is effective.
- Check Spanning Tree status to confirm port roles are correct and there are no abnormal blocking states.
11.5.3 Performance and Security Testing
- Use a traffic generator to test port throughput and verify wire-speed forwarding capability.
- Simulate ARP attacks and port scans to verify that security protection functions are operative.
- Test QoS effectiveness by verifying that high-priority service latency and packet loss rates meet requirements under congestion scenarios.
11.6 Configuration Save and Backup
After all configuration and debugging is complete, execute the save command to store the configuration to the device flash memory:
<Core-Switch-01> save The current configuration will be written to the device. Are you sure? [Y/N]:Y Now saving current configuration to the device. Saving configuration successfully.
- Export and back up the configuration file to a local computer and file server via TFTP/FTP/SCP.
- Print the paper configuration documentation and archive it together with network topology diagrams, port tables, and other materials.
12.1 Installation Environment Precautions
- Temperature and humidity control: The device must operate within the specified temperature and humidity range. Prolonged exposure to high temperatures accelerates component aging and shortens device lifespan; excessive humidity can cause condensation and short circuits, while low humidity can generate static electricity that damages chips. The equipment room should be equipped with a temperature/humidity monitoring system with timely alarms for anomalies.
- Dust protection: The equipment room should be kept clean with regular dust removal. Dust accumulation can block cooling air ducts and reduce insulation performance, potentially causing short-circuit failures in severe cases. Install dust filters at device air intakes and clean them regularly.
- Electromagnetic environment: Keep devices away from strong electromagnetic interference sources such as high-power motors, transformers, and radio transmitters to prevent data transmission errors and abnormal device operation caused by EMI. The equipment room should have proper electromagnetic shielding and grounding.
- Space reservation: Reserve at least 80cm of operating space in front of and behind the device for maintenance operations and heat dissipation. Reserve ventilation space above and below racks to avoid poor heat dissipation from dense device stacking.
12.2 Hardware Operation Precautions
- Electrostatic protection: Always wear an anti-static wrist strap with reliable grounding when touching internal boards, modules, optical modules, or other components. Wear anti-static clothing and gloves when conditions permit. It is strictly forbidden to touch circuit board gold fingers and chips with bare hands without electrostatic protection.
- Module insertion/removal specifications: Insert and remove modules with steady force. Forcible or angled insertion/removal is strictly prohibited to avoid damaging connector pins. For hot-swap operations, wait for the device to confirm module power-off before removal. Never forcibly remove operating business boards.
- Fiber optic operation: Never look directly at the laser emitted from optical modules or fiber end faces, as this may cause irreversible eye damage. Handle fiber connectors gently during insertion/removal to avoid damaging end faces. Keep dust caps on unused optical modules and fiber connectors to prevent dust contamination.
- Power safety: Disconnect power and confirm de-energized status before device installation or repair. Avoid contact with live parts when replacing power modules. Never operate power equipment with wet hands to prevent electric shock.
- Load-bearing safety: Heavy chassis-type equipment must be moved and rack-mounted with multiple people or professional lifting equipment. Single-person handling is strictly prohibited to prevent device damage and personal injury. Verify rack load-bearing capacity before installation to prevent rack tipping.
12.3 Software Configuration Precautions
- Configuration backup: Always back up the current configuration file before making any configuration changes. After modifications are verified correct, promptly save the new configuration and back it up. Major configuration changes require a rollback plan for rapid recovery in case of anomalies.
- Permission management: Strictly manage device login accounts and permissions. Assign corresponding permission levels to different operations personnel. Sharing super administrator accounts is strictly prohibited. Change login passwords regularly using a complexity policy that includes uppercase/lowercase letters, numbers, and special characters.
- Remote management security: Disable the insecure Telnet protocol and use SSH for encrypted management. Restrict IP address ranges allowed for remote login to prevent unauthorized access. It is recommended that management ports connect to a dedicated operations network isolated from the business network.
- System upgrade: Before upgrading system software, verify version compatibility, read the version release notes, and back up configuration files and system software. Never cut power during the upgrade process. Verify normal functionality after the upgrade before putting it into production use.
- Broadcast storm prevention: Enable Spanning Tree Protocol in the network to prevent broadcast storms caused by physical loops. Plan VLANs reasonably to reduce broadcast domain sizes. Enable broadcast storm suppression on ports to limit broadcast traffic ratios.
12.4 Daily Operation and Maintenance Precautions
- Regular inspections: Establish a regular inspection schedule: check device operating status and alarm information daily, check environmental temperature, humidity, and cleanliness weekly, and perform performance statistics and analysis monthly to identify potential hidden faults early.
- Operation standards: Implement a two-person verification system for core device operations where one person operates and another verifies to prevent operational errors. Report and obtain approval before operations, and record operation logs afterward.
- Change management: Strictly follow change management processes for network configuration changes. Develop change plans and rollback plans, schedule operations during low business activity periods, and verify normal service after changes.
- Spare parts management: Maintain appropriate spare inventory for core components (power supplies, fans, main control boards, optical modules). Store spares in anti-static, temperature-controlled, dry environments to ensure rapid replacement during failures.
- Emergency response: Develop network fault emergency response plans defining fault levels, handling procedures, and responsible personnel. Conduct regular emergency drills to ensure rapid response and efficient handling during actual faults.
12.5 Security and Compliance Precautions
- MLPS compliance: Core switches carrying important business must comply with the requirements of Cybersecurity Classified Protection Level 2.0, implementing security control points including identity authentication, access control, security auditing, and intrusion prevention.
- Log retention: Enable device Syslog functionality and send logs to a dedicated log server. Retain logs for no less than 6 months to meet compliance audit requirements.
- Data security: Device configuration files and operations logs contain sensitive data including network topology and account information. Handle with care and strictly prohibit leakage. Thoroughly erase configuration data from decommissioned devices to prevent information disclosure.
- Vulnerability management: Regularly monitor device vendor security advisories and vulnerability warnings. Promptly assess vulnerability risks and apply patch upgrades when necessary to remediate security vulnerabilities.
13.1 Daily Maintenance Specifications
13.1.1 Daily Inspection Items
Perform routine daily inspections and record the following items:
- Indicator light status: Check whether power indicators, system indicators, business board indicators, and port indicators are normal, and whether any red alarms are present.
- Device operating sound: Check whether fan rotation sounds are normal, with no abnormal noise or friction sounds; check for high-frequency power supply whistling.
- Equipment room environment: Check whether equipment room temperature and humidity are within the normal range and whether the air conditioning is operating normally.
- Cable status: Verify that all cables are firmly connected with no looseness or disconnection; fiber optics have no excessive bending.
- Network management alarms: Check the network management system for device alarms or performance threshold alarms and promptly address any anomalies.
13.1.2 Monthly Maintenance Items
Perform in-depth maintenance and inspection monthly:
- Cleaning and dust removal: Use a dry soft brush to clean dust from the device surface and ventilation openings. Use compressed air to clean dust from cooling vents, being careful to avoid blowing dust into the device interior.
- Cable inspection: Check that all cables are securely bound, labels are clear, and cables show no aging or damage; re-tighten loose connectors.
- Performance check: Check device CPU utilization, memory utilization, port traffic, and bandwidth utilization. Track operating trends and identify performance bottlenecks.
- Log analysis: Analyze system logs, summarize alarms and abnormal events, and investigate potential hidden faults.
- Configuration verification: Verify whether the device’s running configuration matches the baseline configuration and investigate any unauthorized configuration changes.
13.1.3 Quarterly/Semi-Annual Maintenance Items
Perform comprehensive maintenance quarterly or semi-annually:
- Deep cleaning: Conduct overall equipment room dust removal, clean rack interiors and device air ducts; clean fan and filter dust where conditions permit.
- Redundancy testing: Test power redundancy, main control redundancy, and link redundancy switchover functions to verify high-availability mechanisms are operational.
- Optical link testing: Use an optical power meter to test transmit/receive optical power on all backbone fiber links, evaluate link loss, and clean contaminated fiber end faces.
- Configuration backup and optimization: Perform full configuration backups, clean up redundant configurations, and optimize unreasonable policies and parameters.
- Spare parts inspection: Check spare parts inventory status, test spare part usability, and ensure spare parts are complete and functional.
13.2 Scheduled Maintenance Operations
13.2.1 Fan Maintenance
- Regularly check fan speed and status. Use commands to verify fan speed is within the normal range.
- If abnormal noise or abnormal speed is detected, promptly replace the faulty fan module.
- Clean the fan dust filter every six months; shorten the cleaning cycle in dusty environments. To clean, remove the dust filter, rinse with clean water, air dry, and reinstall.
- Fan modules should be replaced using hot-swap procedures. Wear an anti-static wrist strap and insert/remove smoothly along the guide rails.
13.2.2 Power Supply Maintenance
- Regularly check power module indicator status to confirm normal power output.
- Regularly check that power cables are securely connected with no aging or damage.
- Perform a power redundancy switchover test every six months: disconnect one power source, verify normal device operation, then restore power.
- When a power module fails, first confirm the corresponding power circuit is de-energized, then remove the faulty module for replacement. Power modules supporting hot-swap can be replaced online directly.
13.2.3 Optical Interface and Fiber Maintenance
- Keep optical interfaces clean. Avoid dust contamination of end faces when inserting/removing fiber connectors.
- When fiber end faces are contaminated, use a dedicated fiber cleaning pen or lint-free alcohol swab. Wait for complete alcohol evaporation before reconnecting.
- Regularly test optical power. If received optical power continuously declines, investigate fiber link loss and optical module aging issues.
- Avoid stepping on or crushing fiber cabling. Fiber patch cord bend radius must comply with specifications to prevent fiber breakage.
13.3 Fault Repair Principles
- Software before hardware: For faults, first diagnose software issues including configuration errors, protocol faults, and software anomalies. Only after ruling out software issues should hardware faults be investigated.
- External before internal: First check external factors such as power supply, cables, peer devices, and environmental factors, then investigate device hardware failures.
- Overall before local: First determine whether the fault scope is whole-device, single-board, or single-port, then progressively narrow the fault location.
- Common before specific: If multiple services fail simultaneously, prioritize checking common components (power supply, main control, switching fabric). For single-service anomalies, check the corresponding board and links.
- Safety operating principle: Hardware repair must be performed with power disconnected (except for hot-swappable components). Take electrostatic precautions to prevent fault expansion and secondary damage.
13.4 Common Hardware Replacement Procedures
13.4.1 Power Module Replacement
1. Identify the faulty power module location and record its model and serial number.
2. For non-hot-swap power supplies, first disconnect the corresponding power circuit breaker; for hot-swap power supplies, this step can be skipped.
3. Press the power module latch and pull the handle steadily to remove the faulty power module.
4. Slide the new power module smoothly into the slot until the latch locks.
5. Connect power and observe the power indicator to confirm normal startup and device operation.
6. Record replacement information and return the faulty power supply for repair according to regulations.
13.4.2 Fan Module Replacement
1. Identify the faulty fan location and prepare a same-model spare fan.
2. Press the fan module latch and smoothly pull out the faulty fan.
3. Check that the fan slot is clear of foreign objects, insert the new fan in the correct orientation, and push until the latch locks.
4. Observe fan operation to confirm normal speed and no abnormal device temperature.
5. Complete the replacement quickly to prevent rapid internal temperature rise.
13.4.3 Business Board Replacement
1. Back up board configuration in advance and confirm the spare board model and version match.
2. Execute the board power-off command in the system and wait for safe power-off.
3. Loosen the board retaining screws, pull the ejector lever to disconnect the board from the backplane connector, and smoothly remove the board.
4. Slide the new board smoothly along the guide rails, operate the ejector lever to fully seat the board, and tighten the retaining screws.
5. Wait for the board to automatically power up and register. After confirming normal board status, load the configuration and verify service recovery.
6. Avoid touching other operating boards during replacement to prevent interference with other services.
13.5 Warranty and After-Sales Service
- Warranty policy: The LA-Core series core switches provide a 3-year factory warranty. Hardware faults not caused by human damage are repaired or replaced free of charge during the warranty period.
- Technical support: A 7×24-hour technical support hotline is available, with professional engineers providing remote assistance for fault diagnosis and configuration guidance.
- On-site service: Major faults during the warranty period may qualify for on-site repair service. Response times are implemented according to the Service Level Agreement.
- Advanced replacement: For core component faults, an advanced replacement service is available where spare parts are shipped first before return of the faulty components, minimizing business interruption time.
- Extended warranty: Extended warranty services may be purchased to extend device warranty coverage and ensure long-term stable operation.
14.1 Power Supply Faults
Fault Symptom 1: Device completely fails to power on; all indicators are off
Possible causes:
- External power supply interrupted; PDU outlet has no power.
- Power cable loose or damaged.
- Power module failure.
- Device main power switch not turned on.
- Backplane power supply failure.
Troubleshooting steps:
1. Use a multimeter to measure the PDU outlet voltage and confirm normal external power supply.
2. Check power cable connections, reconnect cables, and test with a spare power cable.
3. Confirm the device power switch is in the ON position.
4. For dual power supply configurations, check whether both paths have failed simultaneously; test with a known-good power module.
5. If the device still fails to power on after replacing the power supply, suspect chassis backplane or main board faults and contact the manufacturer for repair.
Fault Symptom 2: Power indicator shows red alarm
Possible causes:
- Input voltage too high or too low, outside the rated range.
- Power module overheating protection triggered.
- Internal power module failure.
- Power module overloaded.
Troubleshooting steps:
1. Measure input voltage to confirm it is within the device’s rated range.
2. Check device ventilation and heat dissipation, and whether ambient temperature is too high.
3. Review device power configuration and calculate whether total power consumption exceeds the power module’s rated capacity.
4. Replace with a spare power module for testing. If normal operation resumes after replacement, the original power module is faulty and should be replaced.
14.2 Port Faults
Fault Symptom 1: Port does not come up physically; indicator is off
Possible causes:
- Cable fault or poor contact.
- Optical module failure or incompatibility.
- Peer device port failure.
- Port manually shut down.
- Speed/duplex mode mismatch.
Troubleshooting steps:
1. Check port configuration to confirm the port is not shut down.
2. Reconnect cables and test with a spare cable.
3. For optical ports, replace the optical module for testing to isolate module faults; use an optical power meter to test transmit/receive power and confirm optical power is within the normal range.
4. Connect a known-good device to the peer port to isolate peer port failure.
5. Check speed and duplex configuration on both ends to ensure consistency; the recommendation is to configure both ends for auto-negotiation.
6. Test with another port on the device to isolate local port hardware faults.
Fault Symptom 2: Port flapping (frequent Up/Down oscillation)
Possible causes:
- Poor contact or damage in the cable.
- Optical power near the threshold; unstable optical link.
- Peer device port failure.
- Port negotiation anomaly.
- Severe electromagnetic interference.
Troubleshooting steps:
1. Reconnect cables at both ends, tighten connectors; replace with higher-quality cables.
2. For optical ports, clean fiber end faces and test optical power. Investigate link loss if optical power is too low.
3. Force port speed and duplex mode, disabling auto-negotiation for testing.
4. Check cable routing paths, keep away from power cables and interference sources, and use shielded cables.
5. Replace the peer device port for testing to rule out peer faults.
Fault Symptom 3: Severe packet loss on port
Possible causes:
- Link speed mismatch or duplex conflict.
- Poor cable quality or excessive distance.
- Port traffic overload causing congestion-related packet loss.
- Abnormal optical power with high bit error rate.
- Port hardware failure.
Troubleshooting steps:
1. View port statistics and check error packet and dropped packet counter growth.
2. Confirm speed and duplex consistency on both ends to avoid one end auto-negotiating while the other is forced, causing duplex mismatch.
3. Check port traffic utilization to determine whether bandwidth overload is causing congestion-related packet loss.
4. Test optical power for optical ports; both excessively low and excessively high receive power can cause bit errors and packet loss.
5. Replace cables and test on different ports to rule out cable and hardware faults.
14.3 Service Connectivity Faults
Fault Symptom 1: Terminals in the same VLAN cannot communicate with each other
Possible causes:
- Terminal IP addresses are not on the same subnet.
- Port VLAN misconfiguration; port not assigned to the correct VLAN.
- Port isolation configured on the port.
- Terminal firewall blocking traffic.
- Spanning Tree incorrectly blocking the port.
Troubleshooting steps:
1. Check terminal IP addresses and subnet masks to confirm they are on the same subnet.
2. View the switch port VLAN configuration to confirm both ports belong to the target VLAN and the Access port PVID is correct.
3. Check whether port isolation is configured; disable isolation for testing.
4. Disable the terminal firewall to rule out local blocking.
5. Check the Spanning Tree port status to confirm the port is in the forwarding state and not abnormally blocked.
6. View the switch MAC address table to confirm that MAC addresses from both terminals have been correctly learned.
Fault Symptom 2: Cross-VLAN communication failure
Possible causes:
- VLANIF interface not created or IP address not configured.
- Terminal gateway address not configured correctly.
- Layer 3 routing not configured or routes unreachable.
- ACL access control blocking traffic.
- Layer 3 forwarding not enabled on the core switch.
Troubleshooting steps:
1. Check whether the corresponding VLANIF interface exists, has the correct IP address, and is in the Up state.
2. Check whether terminal default gateway configuration matches the corresponding VLANIF IP address.
3. Test pinging the gateway from terminals. If the gateway cannot be reached, troubleshoot Layer 2 connectivity and gateway configuration.
4. View the device routing table to confirm a route exists for the destination subnet with a reachable next hop.
5. Check whether ACLs are applied to interfaces; review ACL rules for traffic blocking. Temporarily permit traffic for testing.
6. Confirm the device has the Layer 3 forwarding license activated and routing functionality enabled.
Fault Symptom 3: Unable to access the external network
Possible causes:
- Default route misconfiguration.
- Outbound router/firewall failure.
- NAT configuration anomaly.
- DNS server misconfiguration.
- Security policy blocking traffic.
Troubleshooting steps:
1. Ping a public address on the core switch to isolate core-to-outbound connectivity issues.
2. Check the core switch default route to confirm the next-hop address is correct and reachable.
3. Check outbound router and firewall operating status and configuration; troubleshoot NAT and routing configurations.
4. Test access using a public IP address. If IP access works but domain names do not, troubleshoot DNS configuration.
5. Check outbound security policies to confirm traffic is not blocked by security rules.
14.4 Network Performance Faults
Fault Symptom 1: Network lag and high latency
Possible causes:
- Insufficient backbone bandwidth causing congestion.
- Broadcast storm in the network.
- Network loop causing abnormal traffic patterns.
- Excessively high device CPU/memory utilization.
- High error rates and retransmissions on links.
Troubleshooting steps:
1. Check core switch port traffic utilization to determine whether bandwidth bottlenecks exist, particularly during peak hours.
2. Check the broadcast packet ratio. If broadcast packets are excessively high, investigate possible broadcast storms and locate loops.
3. Check device CPU and memory utilization. If excessively high, investigate possible attacks or protocol flapping.
4. Use traceroute to test path latency and identify high-latency nodes.
5. Check link packet loss conditions to identify link quality issues.
Fault Symptom 2: Intermittent network connectivity
Possible causes:
- Unstable links in the network causing frequent flapping.
- Routing protocol flapping with frequent route changes.
- Frequent Spanning Tree topology changes.
- Excessive device temperature causing unstable operation.
- Unstable power supply.
Troubleshooting steps:
1. Check port Up/Down logs to identify unstable links; replace cables and modules.
2. Check routing protocol neighbor status and route change logs to investigate causes of route flapping.
3. Check Spanning Tree topology change notifications to investigate causes of frequent topology changes.
4. Check device temperature and fan status to confirm normal heat dissipation with no thermal protection events.
5. Check power supply stability and investigate grid voltage fluctuations.
14.5 Device System Faults
Fault Symptom 1: Device restarts frequently
Possible causes:
- Unstable power supply with frequent power interruptions.
- Excessively high device temperature triggering thermal protection restart.
- Software system fault or kernel crash.
- Main control board hardware failure.
- Power module failure with unstable output.
Troubleshooting steps:
1. Check system restart logs to determine whether restarts are caused by power loss or software anomalies.
2. Check equipment room power supply and UPS operating status to identify power interruption issues.
3. Check device temperature and fan status; clean dust and improve heat dissipation.
4. Upgrade system software to the latest stable version to rule out software bugs.
5. For dual-main-control devices, observe whether a single main control board is restarting; replace the faulty main control board for testing.
Fault Symptom 2: Unable to log in for management
Possible causes:
- Management network unreachable.
- Management service not enabled.
- Incorrect login credentials.
- Access IP restricted.
- Excessively high device CPU preventing management request responses.
Troubleshooting steps:
1. Log in locally via the Console port to investigate remote management issues.
2. Test management network connectivity by pinging the device management IP.
3. Check whether SSH/Telnet services are enabled and configured correctly.
4. Check whether login IP restrictions are configured; test whether whitelisted IPs can log in.
5. Check device CPU utilization. If excessively high, wait or investigate the cause of high load.
6. Reset the administrator password and test login with the default account.
Q1: What is the difference between a core switch and a regular switch?
A: The main differences between core switches and regular access switches are as follows:
- Different positioning: Core switches are located at the network core layer, responsible for high-speed forwarding between aggregation devices; access switches are located at the access layer, responsible for terminal connections.
- Different performance: Core switches have much higher switching capacity and packet forwarding rates than access switches, supporting wire-speed forwarding with larger table capacities.
- Different reliability: Core switches generally adopt high-reliability designs including dual main control boards, multi-power redundancy, and hot-swap capabilities with higher MTBF; access switches typically have single-power designs with lower reliability.
- Different functionality: Core switches support complete Layer 3 routing protocols, MPLS, virtualization, QoS, and other advanced features; access switches primarily provide Layer 2 functionality with weaker Layer 3 capabilities.
- Different scalability: Chassis-type core switches support modular expansion with ports expandable as needed; access switches have fixed port configurations with limited expansion capability.
Q2: Is dual-switch redundancy mandatory for core switches?
A: Dual-switch redundant deployment at the core is recommended, but not mandatory. The decision should be based on business importance and budget:
- For production services, government, finance, healthcare, and other critical business networks, core switch failure would cause network-wide outage and severe losses. Dual-core redundant architecture is mandatory to ensure high availability.
- For small office and non-critical business scenarios with limited budgets, a single-core configuration may be acceptable, but redundant power supplies and critical link backups are recommended to reduce fault risk.
- For dual-core deployment, VRRP+MSTP or virtualization technologies are recommended to achieve load sharing and redundancy, improving overall network performance and reliability.
Q3: Can third-party optical modules be used in core switch ports?
A: LA-Core switches support compliant third-party optical modules that meet standard protocols, but the following should be noted:
- Only quality-certified optical modules that comply with IEEE standards should be selected. Inferior modules can cause link instability, bit errors, packet loss, and even damage to device interfaces.
- Some advanced features (such as digital diagnostics and precision optical power detection) may only support factory-original modules. Third-party modules may have compatibility issues.
- Device damage and link faults caused by third-party optical module quality issues are not covered under the factory warranty.
- Factory-original optical modules are recommended for guaranteed compatibility and stability with full warranty coverage.
Q4: Can a core switch connect directly to terminal computers?
A: Technically, core switches can connect directly to terminals, but such deployment is not recommended for the following reasons:
- Cost waste: Core switch port costs are significantly higher than access switch ports. Direct terminal connections cause cost waste.
- Security risk: Direct terminal access to the core lacks access-layer security controls, potentially introducing attacks and viruses to the core and affecting overall network stability.
- Management difficulties: With large numbers of terminals, direct core connections are not conducive to port management, VLAN segmentation, or user authentication.
- Unreasonable architecture: In a standard three-tier architecture, terminals should connect through the access layer and aggregation layer to the core. The core should focus on high-speed forwarding, following network design principles.
- Temporary connection of debugging terminals in special circumstances is acceptable, but long-term deployment should adopt a standard three-tier architecture.
Q5: Does a core switch system upgrade interrupt services?
A: This depends on the device architecture and upgrade method:
- Single main control devices: System upgrades require device restart, causing service interruption. The interruption time equals device startup time, typically several minutes.
- Dual main control high-end devices: Support ISSU (In-Service Software Upgrade) where main and backup control boards are upgraded alternately with smooth switchover, achieving zero-service-interruption upgrades with no user-perceptible impact.
- Upgrade recommendations: Regardless of the method, back up configurations and system files before upgrading, schedule operations during off-peak hours, and prepare rollback plans. Carefully read version documentation before upgrading to confirm version compatibility and precautions.
Q6: What is considered a normal temperature for a core switch?
A: The normal operating temperature ranges for core switches are as follows:
- Environmental temperature: Equipment room ambient temperature should ideally be maintained between 18℃-26℃, with device air intake temperature not exceeding 40℃.
- Internal device temperature: Normal chip operating temperature typically should not exceed 75℃. The specific value depends on device sensor readings.
- Alarm thresholds: Devices typically have two temperature alarm levels: a primary alarm (Warning) at approximately 60-70℃ and a secondary alarm (Critical) at approximately 80-85℃. Reaching the secondary alarm may trigger thermal protection.
- If device temperature remains elevated, check for blocked air ducts, fan malfunctions, and equipment room air conditioning issues, and take prompt cooling measures.
Q7: What is the typical service life of a core switch?
A: Core switch service life depends on operating environment, load conditions, and maintenance quality, typically 5-8 years:
- Hardware lifespan: The mean time between failures (MTBF) for electronic components is very long. Under normal conditions, device hardware can operate stably for 5-8 years without issues, with some devices lasting more than 10 years.
- Software lifecycle: Vendors typically provide software version maintenance and vulnerability fixes for 5-7 years. Devices beyond their lifecycle no longer receive version updates and face security risks.
- Upgrade cycle: With business bandwidth growth and technology evolution, enterprises typically upgrade core networks every 5 years or so to meet new business requirements.
- Good daily maintenance and a proper equipment room environment can effectively extend device service life.
Q8: How can a core switch defend against network attacks?
A: Core switches can defend against network attacks through multiple technical measures:
- Control plane protection: Enable CPP (Control Plane Protection) to rate-limit and filter packets destined for the CPU, preventing DoS attacks from saturating the CPU.
- Layer 2 security protection: Enable DHCP Snooping, ARP anti-spoofing, and IP Source Guard to protect against internal ARP attacks and address spoofing.
- Access control: Use ACLs to filter illegal traffic and block abnormal packets from entering the core network.
- Traffic monitoring: Enable sFlow/NetStream traffic analysis for real-time anomaly detection and rapid attack source location.
- Broadcast storm suppression: Configure broadcast, multicast, and unknown unicast storm suppression on ports to limit attack traffic propagation.
- Core switches focus on forwarding performance. For deep security protection, it is recommended to combine with dedicated firewalls, intrusion prevention systems, and other security devices to build a defense-in-depth architecture.
Q9: What should be done when core switch ports are insufficient?
A: The following port expansion options are available, selectable by requirement:
- Business board expansion: For chassis-type core switches with available slots, directly add business boards with the required specifications. This is the most direct expansion method.
- Tiered expansion: Add access-layer or aggregation-layer switches for terminal connections, uplinking to the core switch via high-speed links. This suits scenarios with insufficient terminal access ports.
- Port upgrade: Replace lower-speed ports with higher-speed ports (e.g., upgrading from 10G to 100G) to increase per-port bandwidth and indirectly relieve port pressure. This suits backbone link expansion.
- Device stacking/clustering: Use virtualization to consolidate multiple core switches into one logical device, expanding port count and overall performance while maintaining management simplicity.
- Before expansion, evaluate the core switch’s switching capacity and performance headroom to avoid forwarding bottlenecks after port addition.
Q10: What metrics should be monitored in daily core switch operations?
A: Daily operations should focus on the following core metrics:
- Hardware health metrics: Power supply status, fan status, board online status, and device temperature to ensure no hardware faults.
- Performance metrics: CPU utilization (normal <50%, peak <70%), memory utilization (normal <60%), switching chip utilization to avoid performance bottlenecks.
- Port metrics: Port bandwidth utilization, packet loss rate, error rate, and Up/Down status for timely detection of link anomalies.
- Protocol metrics: Routing neighbor states, Spanning Tree topology, VRRP status, and link aggregation status to ensure protocol stability.
- Security metrics: Attack packet counts, abnormal traffic alarms, and security logs for timely security threat detection.
- Environmental metrics: Equipment room temperature/humidity and power supply stability to guarantee the device operating environment.
16.1 Acceptance Basis and Standards
- National standards: “Code for Acceptance of Generic Cabling System Engineering” GB 50312, “Safety of Information Technology Equipment” GB 4943, “Code for Design of Lightning Protection and Earthing Engineering for Telecommunication Stations” GB 50689.
- Industry standards: YD/T related telecommunications equipment standards, IEEE 802.3 Ethernet standards.
- Project documentation: Project contracts, technical proposals, design drawings, and equipment technical specifications.
- Factory standards: Device factory inspection standards and the technical specifications in this manual.
16.2 Acceptance Procedures
16.2.1 Acceptance Preparation
- The contractor completes device installation, wiring, and commissioning, passes self-inspection, and submits acceptance applications with as-built documentation.
- The accepting party forms an acceptance team including client representatives, supervisors, and technical engineers.
- Prepare acceptance tools: laptop computers, Console cables, optical power meters, network cable testers, traffic generators, multimeters, etc.
- Organize acceptance documents: as-built drawings, configuration files, test reports, and equipment materials.
16.2.2 Visual and Installation Acceptance
- Device appearance inspection: Device appearance intact with no impact damage, paint damage, or deformation; all modules properly seated with no looseness; identification labels clear and complete.
- Installation craftsmanship inspection: Device securely and levelly installed; rack fixation reliable; grounding connections compliant with grounding resistance tests passed.
- Cable routing inspection: Cables neatly routed and properly bundled with clear and complete labels; power cables separated from business cables; fiber bend radius compliant with no crushing or damage.
- Environmental inspection: Equipment room temperature and humidity meet requirements; ventilation and heat dissipation adequate; no obstructions around devices; grounding and lightning protection facilities complete.
16.2.3 Functional Acceptance
- Basic device functions: Device powers on normally, system runs stably with no alarms; all boards, power supplies, and fans operate normally.
- Port function testing: All business ports pass connectivity tests; optical port power within normal range; port speed and duplex negotiation normal.
- VLAN functionality: VLAN segmentation correct; same-VLAN communication works and different-VLAN isolation defaults meet design requirements.
- Routing functionality: Static routes and dynamic routing protocols operate normally; route learning complete; cross-subnet access works.
- Redundancy functionality: Power redundancy switchover, main control redundancy switchover, and link redundancy switchover tests pass; service interruption time meets metric requirements.
- Security functionality: ACL access control, ARP protection, port security, and other features verified effective and compliant with design requirements.
- Management functionality: Local Console, remote SSH/Web, and SNMP network management all function properly for login and management; logging and alarm functions work normally.
16.2.4 Performance Acceptance
- Throughput testing: Use professional traffic generators to conduct throughput tests on backbone links, verifying wire-speed forwarding capability with zero packet loss.
- Forwarding latency testing: Test forwarding latency with different packet sizes including 64-byte and 1518-byte packets, meeting device technical specifications.
- Back-to-back testing: Verify device buffering capability with no packet loss under burst traffic.
- Stress testing: Run device under full load for 24 hours with stable operation, no abnormal restarts or packet loss; CPU and memory utilization within normal ranges.
- Business performance verification: Test real business scenarios including video conferencing, file transfer, and database access to confirm normal user experience with no lag or excessive latency.
16.2.5 Documentation Acceptance
- As-built documentation complete, including: project completion summary, network topology diagrams, port wiring tables, device configuration files, IP address planning tables, and VLAN planning tables.
- Equipment documentation complete, including: product manuals, warranty cards, certificates of conformity, and factory inspection reports.
- Test reports complete, including: functional test reports, performance test reports, and acceptance test records.
- All documents stamped with relevant organizational seals; paper and electronic versions delivered simultaneously.
16.3 Acceptance Determination Criteria
- Qualified determination: All acceptance items meet requirements with no major functional defects, performance metrics meet design requirements, and documentation is complete — the acceptance is judged as qualified.
- Rectification required: General quality issues or non-core functional defects exist that do not affect primary business operations — judged as requiring rectification within a time limit, with re-inspection after completion.
- Unqualified determination: Major hardware faults, core functional deficiencies, or seriously substandard performance exist that affect normal business operations — judged as unqualified acceptance, requiring comprehensive rectification and re-application for acceptance.
16.4 Acceptance Document Signing
After qualified acceptance, all acceptance parties jointly sign the “Equipment Acceptance Certificate,” specifying the acceptance conclusion, delivery date, warranty commencement date, and other information. Acceptance documents are executed in multiple copies, archived separately by both parties and the supervisor, serving as the basis for project delivery and warranty.
For issues found during acceptance, an “Acceptance Issue Rectification Record” is signed, specifying rectification content, deadlines, and responsible personnel. After rectification, re-inspection is conducted and re-inspection records are signed.
17.1 Search Keyword Classification Layout
Core Primary Keywords:
Core Switch, Core Switch Manufacturer, Core Switch Installation, Core Switch Commissioning, Core Switch Manual
High-Conversion Long-Tail Keywords:
Core Switch Installation and Wiring Tutorial, Core Switch Commissioning Steps, Chassis Core Switch Technical Parameters, Enterprise Core Switch Selection, Data Center Core Switch Deployment, Core Switch Fault Troubleshooting Methods, Core Switch Operation and Maintenance Manual
Industry Traffic Keywords:
Campus Network Core Switch, Data Center Core Switch, Industrial Core Switch, 10G Core Switch, 100G Core Switch, Layer 3 Core Switch, Modular Core Switch, Xinchuang Core Switch
Brand-Specific Keywords:
KITOZER Core Switch, Guangdong KITOZER Core Switch, LA-Core Core Switch, KITOZER Equipment Room Core Switch, KITOZER Network Switch
Dropdown/Related Search Keywords:
Differences Between Core Switches and Aggregation Switches, How to Configure a Core Switch, How Much Does a Core Switch Cost, Which Core Switch Brand is Best, Core Switch Working Principle, Core Switch Port Types, Core Switch Redundancy Configuration
17.2 SEO Optimization Tag System
Page Core Optimization Tags:
- Page theme: Core Switch Installation Wiring Commissioning Manual – Product Technical Parameters and Operation & Maintenance Guide
- Core keyword density: Core primary keywords evenly distributed throughout the document, density controlled at 2%-3%
- Content length: Ultra-long form in-depth technical content covering full-dimensional user search needs
Title Tag:
Core Switch Installation Wiring Commissioning Manual_Technical Parameters_Fault Troubleshooting_Operation Maintenance-KITOZER Intelligent Equipment Room Products
Meta Keywords:
Core Switch, Core Switch Installation, Core Switch Commissioning, Core Switch Technical Parameters, Core Switch Fault Troubleshooting, Chassis Core Switch, 10G Core Switch, KITOZER Core Switch
Meta Description:
KITOZER Intelligent Equipment Room Products provides a complete core switch installation wiring commissioning manual, covering core switch product introduction, principles, technical parameters, functional features, application scenarios, installation wiring steps, commissioning configuration, fault troubleshooting, operation maintenance, acceptance standards, and other full-process technical guidance, suitable for campus network, data center, and other multi-scenario core switch deployment.
H1 Tag:
Core Switch Installation Wiring Commissioning Manual
H2 Tags:
Product Introduction, Product Composition, Product Classification, Product List, Product Working Principle, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation, Product Wiring, Product Commissioning, Product Precautions, Product Maintenance and Repair, Product Common Problems and Solutions, Product QA, Product Acceptance
17.3 Internal Link Optimization Tags (Natural Anchor Text Embedding)
Core Anchor Text:
Core Switch, Core Switch Installation and Commissioning, Core Switch Technical Parameters
Long-Tail Anchor Text:
Chassis Core Switch Modular Configuration, 10G Core Switch Deployment Solution, Core Switch Common Fault Solutions, Core Switch Acceptance Standards and Specifications
Associated Anchor Text:
Aggregation Switch, Access Switch, Equipment Room Construction Solution, Generic Cabling System, Network Security Equipment, Server Rack
Copyright Notice
This manual is copyrighted by Guangzhou Lain Intelligent System Development Co., Ltd. and is protected by the Copyright Law of the People’s Republic of China and related international conventions. No entity or individual may use any portion of this manual for commercial purposes in any form (including but not limited to reproduction, reprinting, excerpting, alteration, translation, compilation, distribution, or sale) without the written authorization of the Company.
When reprinting or quoting content from this manual with authorization, the source must be attributed to “Guangzhou Lain Intelligent System Development Co., Ltd.” and the content may not be distorted, altered, or used for misleading promotional purposes.
The Company will pursue legal liability for copyright infringement to protect its legitimate rights and interests.
The content of this manual is subject to update without prior notice. The latest version shall be based on the official website publication.