Floor Bolt-Down Quick Steps: Anchor It Securely

  1. Move rack to final position.
  2. Mark 4 hole locations through rack base.
  3. Drill 10mm hole, 60mm deep in concrete.
  4. Blow out dust.
  5. Insert M10 expansion bolt.
  6. Lower rack over bolts.
  7. Put washer and nut on each.
  8. Tighten diagonally (cross pattern) to 25 Nm.

KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – floor bolt, anchor. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.