Table of Contents
ToggleTwo Ways to Cool a Sealed Outdoor Rack
An outdoor rack is sealed against rain and dust. You can’t bring outside air in. So you either recirculate internal air through a heat exchanger (no compressor) or use a vapor-compression AC unit.
| Feature | Heat Exchanger | Rack AC |
|---|---|---|
| Cooling principle | Air-to-air, no refrigerant | Vapor compression (refrigerant) |
| Min. internal-to-ambient delta | Requires outside 5C cooler than inside | Cools below ambient |
| Capacity range | 50-500W | 500-3000W |
| Power consumption | Low (just fans, 30-80W) | Higher (300-1500W) |
| Maintenance | Minimal (no compressor) | More (filter, refrigerant check) |
| Price | $300-800 | $600-2000 |
Choose Heat Exchanger When
Low heat load (under 300W) and the outside air is consistently cooler than inside.
Choose Rack AC When
High heat load or when outside temperature exceeds the target internal temperature.