Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32
KITOZER
KITOZER

Immersion Liquid Cooling Cabinet Water Circulation Accessories

Dedicated to Integrated Liquid Cooling Cabinets

Version: V2.0

Guangzhou Lain Intelligent System Development Co., Ltd.

Release Date: July 2026

Table of Contents

Preface

With the rapid development of the digital economy and artificial intelligence industry, the power density of data center cabinets has continued to rise. Traditional air-cooling heat dissipation technologies can no longer meet the heat dissipation requirements of ultra-high-density computing equipment above 80kW. Liquid cooling technology, leveraging its core advantages of high-efficiency heat exchange, low PUE, and low noise, has become the mainstream solution for thermal management in next-generation data centers. Among these, single-phase immersion liquid cooling technology achieves direct contact heat exchange across all components by fully immersing IT equipment in dielectric coolant, achieving heat dissipation efficiency far exceeding cold plate and air-cooling solutions. It is currently the preferred technical path for ultra-high-power-density computer rooms.

As the core power and heat exchange unit of the immersion liquid cooling cabinet, the water circulation system undertakes key functions including coolant circulation delivery, heat exchange, pressure stabilization, purification and filtration, intelligent regulation, and safety protection. The installation quality, wiring specifications, and commissioning accuracy directly determine the operational stability, heat exchange efficiency, and service life of the entire liquid cooling system.

This manual is compiled in accordance with national and industry standards including the “Design Specification for Single-phase Immersion Direct Liquid Cooling Data Centers,” “Technical Specification for Liquid Cooling Components for IT Servers and Storage Equipment,” and “Technical Specification for Liquid Cooling System Engineering,” combined with years of liquid cooling product R&D and engineering practice experience from Guangzhou Lain Intelligent System Development Co., Ltd. It provides a comprehensive, systematic, and detailed exposition of the product description, composition structure, technical parameters, installation procedures, wiring specifications, commissioning methods, operation and maintenance, fault diagnosis, and acceptance standards for immersion liquid cooling cabinet water circulation accessories. It aims to provide standardized operational guidance and technical references for engineering construction personnel, operation and maintenance management personnel, and technical support staff.

This manual applies to the installation, wiring, commissioning, operation and maintenance, and acceptance of the LA-YM series 30kW, 50kW, 80kW, and 120kW immersion liquid cooling cabinet supporting water circulation systems produced by Guangzhou Lain Intelligent System Development Co., Ltd. All relevant personnel are requested to carefully read this manual before operations and strictly follow the standardized procedures to ensure safe and stable system operation.

The content of this manual will be continuously updated with product technology iterations. For any questions, please contact our company’s technical support department.

Chapter 1 Product Introduction

1.1 Product Overview

This product is a dedicated integrated water circulation accessory system for immersion liquid cooling cabinets. It is a core supporting unit of the integrated liquid cooling cabinet, integrating six major functional modules: circulation power, heat exchange isolation, filtration and purification, pressure stabilization and liquid replenishment, intelligent control, and safety protection. It connects to the immersion liquid cooling chamber through sealed piping, driving the dielectric coolant to circulate between the chamber and the heat exchange unit, efficiently exporting the heat generated by IT equipment to the primary-side cold source system, achieving precise temperature control for ultra-high-power-density cabinets.

The product adopts a modular integrated design, integrating components such as pumps, heat exchangers, valves, sensors, and control cabinets into a standard cabinet. Pre-assembly and factory testing are completed before shipment. On-site work only requires connecting the inlet/outlet liquid piping, power supply, and communication wiring for rapid deployment, significantly shortening the engineering construction cycle and reducing on-site installation difficulty and error rates.

The product is compatible with single-phase immersion liquid cooling systems and supports various dielectric coolants including electronic fluorinated fluids, synthetic hydrocarbons, and mineral oils. It supports interfacing with multiple cold source systems such as cooling towers, dry coolers, chillers, and natural cold sources. It is widely used in AI computing rooms, high-performance computing centers, edge computing nodes, and other high-density heat dissipation scenarios.

1.2 Product Positioning and Technical Background

1.2.1 Industry Technical Background

Traditional data center air-cooling solutions are limited by air specific heat capacity and heat exchange efficiency, typically capable of dissipating no more than 30kW per cabinet. Facing AI computing clusters where single GPU card power consumption exceeds 700W and single-cabinet power density exceeds 100kW, air-cooling solutions have inherent bottlenecks including high PUE, high noise, low space utilization, and difficulty in resolving localized hot spots.

Liquid cooling technology leverages the physical characteristic that the specific heat capacity of liquids is approximately 3000 times that of air, enabling higher-efficiency heat transfer. Among these, immersion liquid cooling, as a representative of direct-contact liquid cooling, completely eliminates the interface thermal resistance between chips and the heat dissipation medium. Single-cabinet heat dissipation capacity can reach 30-200kW, and PUE can be reduced to below 1.1, making it the currently optimal technical solution in the field of high-density heat dissipation for data centers.

The water circulation system is the “heart” of the immersion liquid cooling system, responsible for driving coolant circulation and heat exchange. Its performance directly determines the heat dissipation capability, operational reliability, and energy efficiency level of the entire liquid cooling system. Early liquid cooling water circulation systems were mostly field-assembled, with issues such as low integration, long installation cycles, inconsistent control logic, and multiple failure points. Integrated water circulation units have become an inevitable industry development trend.

1.2.2 Product Market Positioning

This product is positioned as a core supporting equipment for mid-to-high-end immersion liquid cooling data centers. It targets data center customers with high requirements for heat dissipation density, operational reliability, and energy efficiency levels, providing standardized, integrated, and intelligent water circulation solutions. It can directly match our company’s full series of immersion liquid cooling cabinets and is also compatible with immersion liquid cooling chambers from third-party manufacturers that conform to interface standards.

The product covers the full power range from 30kW to 120kW, meeting different heat dissipation requirements from edge computing nodes to ultra-large-scale AI clusters. It supports independent single-unit operation and multi-unit cluster networking operation, with flexible expansion capability.

1.3 Development History of Immersion Liquid Cooling Technology

The development of immersion liquid cooling technology can be traced back to the 1960s, when it was first applied in military and supercomputing fields. Limited by coolant costs and system complexity, it was not widely adopted in commercial data centers for a long period. Entering the 21st century, with the continuous increase in IT equipment power density and the maturation of liquid cooling technology, immersion liquid cooling gradually entered the commercialization stage:

  • Germination Stage (2000-2010): Primarily used in laboratory and military special applications, mainly solving heat dissipation problems of specific ultra-high-density equipment. Coolant costs were high, and systems were highly customized.
  • Initial Stage (2010-2018): Internet companies began piloting immersion liquid cooling, mainly for high-performance computing clusters. Technical routes gradually diverged into single-phase immersion and two-phase immersion, the industry chain gradually matured, and coolant costs significantly decreased.
  • Rapid Development Stage (2018-2025): The AI computing boom drove rapid growth in liquid cooling demand. Immersion liquid cooling technology gradually became standardized, national and industry standards were successively released, integrated solutions became mainstream, deployment costs continued to decline, and large-scale commercial application cases increased rapidly.
  • Popularization and Application Stage (2025 to Present): Immersion liquid cooling has become the standard configuration for ultra-high-density data centers. Technology is developing toward higher energy efficiency, more intelligent operation and maintenance, and lower full-lifecycle costs. As a core component, the water circulation system continues to iterate toward integration, modularization, and intelligence.

Guangzhou Lain Intelligent System Development Co., Ltd. has been developing liquid cooling technology since 2018. Through five generations of product iteration, the company has accumulated deep technical experience in structural design, control algorithms, and reliability optimization of immersion liquid cooling water circulation systems. Products have been operating stably in dozens of domestic data center projects.

1.4 Company Profile of Guangzhou Lain Intelligent System Development Co., Ltd.

Guangzhou Lain Intelligent System Development Co., Ltd., headquartered at No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, Zhongrun Industrial Park, is a leading domestic provider of intelligent computer room overall solutions. The company specializes in the R&D, production, and sales of computer room cooling, liquid cooling technology, and computer room integrated equipment. It is a national high-tech enterprise with dozens of liquid cooling-related patents and software copyrights.

The company has established a standardized liquid cooling product production base, equipped with professional product testing laboratories, and possesses full-chain service capabilities from core component R&D to system integration, from manufacturing to engineering implementation, and from after-sales operation and maintenance to technical support. Core products cover immersion liquid cooling cabinets, cold plate liquid cooling cabinets, liquid cooling distribution units (CDU), computer room precision air conditioners, micro-module data centers, and computer room environment monitoring systems, and other full-series computer room equipment, widely used in government affairs, finance, communications, internet, education, healthcare, military, and other industries.

The company adheres to the business philosophy of “technological innovation, quality first, customer foremost,” driven by continuous technology R&D, continuously launching high-quality liquid cooling products and solutions that meet market demands, committed to becoming a leading domestic green data center infrastructure service provider.

1.5 Product R&D Philosophy and Design Standards

1.5.1 R&D Philosophy

1. Reliability First: All core components adopt redundant design, key components are sourced from internationally first-tier brands, and undergo strict environmental testing and life testing to ensure long-term stable system operation, with Mean Time Between Failures (MTBF) ≥ 100,000 hours.

2. High Energy Efficiency Design: Variable frequency speed control technology and intelligent temperature control algorithms dynamically adjust flow rate and cooling capacity based on load, maximize the utilization of natural cold sources, reduce system operating energy consumption, and help data centers achieve low-carbon operations.

3. Modular Integration: Standardized modular design with independently replaceable functional units, convenient installation and maintenance, and support for rapid on-site expansion and upgrades.

4. Intelligent Operation and Maintenance: Equipped with an intelligent control system supporting real-time monitoring of all parameters, automatic fault diagnosis, remote monitoring, and operation and maintenance, reducing manual O&M costs and improving fault response speed.

5. High Compatibility: Compatible with multiple coolant media and cold source types, supports interfacing with mainstream environment monitoring systems, and meets customized requirements of different scenarios.

1.5.2 Design Implementation Standards

Product design, production, and inspection strictly comply with the following national and industry standards:

  • GB/T 1.1-2020 “Directives for Standardization – Part 1: Structure and drafting rules for standardization documents”
  • “Technical Specification for Liquid Cooling Components for IT Servers and Storage Equipment”
  • T/CIE 093-2020 “Design Specification for Single-phase Immersion Direct Liquid Cooling Data Centers”
  • T/CAICI 131-2025 “Technical Specification for Liquid Cooling System Engineering”
  • YD/T 3979-2021 “Overall Technical Requirements and Test Methods for Data Center Liquid-cooled Server Systems”
  • GB 50236-2011 “Code for Construction of Field Equipment and Industrial Pipe Welding Engineering”
  • GB 50303-2015 “Code for Acceptance of Construction Quality of Building Electrical Engineering”
  • GB/T 13306-2011 “Nameplates”
  • GB/T 191-2008 “Packaging – Pictorial Marking for Handling of Goods”

1.6 Product Version and Model Description

This product is the LA-YM series immersion liquid cooling water circulation system. The model naming convention is as follows:

LA - YM - □□ - □
 |    |    |    |
 |    |    |    └─ Design version number (A/B/C...)
 |    |    └───── Rated heat exchange power (kW)
 |    └────────── Immersion liquid cooling
 └─────────────── Lain brand

For example: LA-YM-50-B represents Lain brand, immersion liquid cooling, rated heat exchange power 50kW, B-version water circulation system.

Product models covered in this manual include:

  • LA-YM-30-A/B: Rated heat exchange power 30kW, suitable for immersion cabinets with power density of 30kW and below
  • LA-YM-50-A/B: Rated heat exchange power 50kW, suitable for immersion cabinets with power density of 50kW and below
  • LA-YM-80-A/B: Rated heat exchange power 80kW, suitable for immersion cabinets with power density of 80kW and below
  • LA-YM-120-A/B: Rated heat exchange power 120kW, suitable for immersion cabinets with power density of 120kW and below

1.7 Applicable Scope and Reading Guide of This Manual

1.7.1 Applicable Scope

This manual applies to the installation construction, electrical wiring, system commissioning, routine operation and maintenance, fault repair, and engineering acceptance of the LA-YM series full-model immersion liquid cooling cabinet water circulation accessory systems produced by Guangzhou Lain Intelligent System Development Co., Ltd.

  • Construction personnel: Focus on Chapter 8 Product Installation, Chapter 9 Product Wiring, Chapter 11 Product Precautions
  • Commissioning personnel: Focus on Chapter 10 Product Commissioning, Chapter 13 Common Problems and Solutions
  • Operation and maintenance personnel: Focus on Chapter 12 Product Repair and Maintenance, Chapter 13 Common Problems and Solutions
  • Acceptance personnel: Focus on Chapter 15 Product Acceptance, Chapter 5 Product Technical Parameters

1.7.2 Precautions

  • The content of this manual is company technical confidential information and shall not be distributed, copied, or reproduced without authorization.
  • If product technical parameters and structure are upgraded or adjusted, the technical documents shipped with the product shall prevail; the content of this manual is for reference only.
  • It is strictly forbidden for personnel without professional training to perform installation, wiring, commissioning, and repair operations, which may result in equipment damage and safety accidents.
  • All operations must strictly comply with relevant safety regulations and implement safety protection measures.

Chapter 2 Product Composition

2.1 Overall Architecture of the Water Circulation System

The immersion liquid cooling cabinet water circulation system adopts a dual-loop isolation design, divided into a secondary-side (cabinet-side) coolant loop and a primary-side (cold source-side) cooling water loop. The two loops achieve heat isolation exchange through a plate heat exchanger, preventing cross-contamination of media on both sides and ensuring medium cleanliness and safety on the IT equipment side.

The system consists of six major functional units:

1. Circulation Power Unit: Consists of a primary/standby dual pump set that provides circulation power for the secondary-side coolant, driving coolant circulation between the immersion chamber and the heat exchanger.

2. Heat Exchange Isolation Unit: The core is a plate heat exchanger that achieves heat exchange between the high-temperature secondary-side coolant and the low-temperature primary-side cooling water, while also achieving physical isolation of media on both sides.

3. Filtration and Purification Unit: Composed of a main-line coarse filter and a bypass fine filter, removing particulate impurities from the coolant to protect IT equipment and heat exchange components and extend coolant service life.

4. Pressure Stabilization and Liquid Replenishment Unit: Composed of an expansion tank, liquid replenishment tank, safety valve, and automatic replenishment valve. It stabilizes system pressure, compensates for coolant volume changes caused by temperature variations, automatically replenishes system coolant losses, and automatically relieves pressure for protection when overpressure occurs.

5. Sensing and Detection Unit: Composed of various sensors for temperature, pressure, flow rate, liquid level, and conductivity, collecting system operating parameters in real time to provide data for intelligent control.

6. Intelligent Control Unit: Composed of a PLC controller, variable frequency drives, human-machine interface, and electrical components, implementing system operational logic control, parameter adjustment, fault protection, data display, and remote communication.

The system is fully integrated into a standard 19-inch cabinet. Piping connections, electrical wiring, and factory testing are completed before shipment. On-site, only connection of external inlet/outlet liquid piping, power supply, and communication cables is required for commissioning.

2.2 Main Circulation Pump Unit

The main circulation pump unit is the power core of the water circulation system, providing pressure and flow for coolant circulation. It adopts a one-duty-one-standby dual pump redundancy design. When the main pump fails, the standby pump automatically switches over to ensure continuous system operation.

2.2.1 Main Circulation Centrifugal Pump

A horizontal stainless steel centrifugal pump is used. All wetted components are made of 304/316L stainless steel, compatible with various dielectric coolant media. It features corrosion resistance, leak-free operation, high efficiency, and low noise.

  • Impeller: Closed impeller design with optimized hydraulic model, high hydraulic efficiency, and good anti-cavitation performance. The impeller undergoes dynamic balance testing for low operating vibration.
  • Pump Casing: Precision casting process with smooth flow channels, low hydraulic losses, and strong pressure-bearing capacity. Rated pressure rating: 1.6MPa.
  • Mechanical Seal: Silicon carbide-graphite paired mechanical seal with medium-compatible rubber sealing rings, achieving zero-leakage operation and long service life. Compatible with fluorinated liquids, synthetic hydrocarbons, and other media.
  • Motor: Three-phase asynchronous motor, protection class IP55, insulation class F, with overload and over-temperature protection capability. Motor energy efficiency level reaches IE3, providing high efficiency and energy conservation.
  • Base: Cast iron integral base with good rigidity and excellent vibration damping performance. Equipped with damping pads to reduce operating vibration and noise transmission.

2.2.2 Standby Circulation Pump

The standby pump uses the exact same model and specifications as the main pump to ensure consistent system performance after switchover. The standby pump remains in a hot standby state for extended periods. The control system monitors the main pump operating status in real time. When the main pump experiences faults, overload, insufficient flow, or other abnormalities, the control system automatically starts the standby pump within 3 seconds and simultaneously issues an alarm signal, ensuring uninterrupted system cooling capacity.

2.2.3 Pump Unit Base and Vibration Damping Components

  • The pump unit shares a carbon steel plastic-sprayed mounting base, secured to the cabinet frame with bolts to ensure overall structural stability.
  • Rubber vibration damping pads are installed between the pumps and the base. The pads are made of nitrile rubber, providing excellent vibration damping and oil resistance, capable of reducing more than 90% of vibration transmission.
  • Metal flexible connections are installed at both pump inlet and outlet to isolate vibration transmission between piping and pumps, preventing pipeline resonance and stress damage.

2.2.4 Pump Inlet/Outlet Valve Assemblies

Each pump is equipped with a complete valve assembly at both inlet and outlet for pump maintenance and flow regulation:

  • Inlet Side: Sequentially configured with flexible joint, manual butterfly valve, Y-type strainer, and vacuum pressure gauge. The manual butterfly valve is used to isolate the pipeline during pump maintenance. The Y-type strainer protects the pump impeller from damage by large particulate impurities. The vacuum pressure gauge monitors inlet pressure to determine whether the inlet is blocked or has insufficient liquid.
  • Outlet Side: Sequentially configured with check valve, manual butterfly valve, pressure transmitter, and flexible joint. The check valve prevents liquid backflow causing pump reverse rotation during shutdown. The manual butterfly valve is used for maintenance isolation and flow regulation. The pressure transmitter monitors outlet pressure. The flexible joint isolates vibration.

2.3 Heat Exchange Unit

The heat exchange unit is the core component for heat transfer, using a gasketed plate heat exchanger to achieve counter-current heat exchange between the secondary-side coolant and primary-side cooling water. It features high heat exchange efficiency, small footprint, and easy cleaning and maintenance.

2.3.1 Plate Heat Exchanger

  • Plates: 304/316L stainless steel plates formed by precision stamping. The plate surface features herringbone corrugation patterns that enhance fluid turbulence effects, significantly improving the heat transfer coefficient. Overall heat transfer coefficient can reach 3000-6000 W/(m²·℃).
  • Sealing Gaskets: Made of nitrile rubber or fluororubber, matched according to media type. Fixed in the plate sealing grooves by bonding or snap-fit methods, achieving sealing between plates and flow channel separation.
  • Frame: Composed of fixed pressure plate, movable pressure plate, upper and lower guide bars, and clamping bolts. Made of carbon steel with plastic spraying. The plate pack is compressed by clamping bolts to achieve sealing and fixation.
  • Connections: Standard flange connections with separate primary-side inlet/outlet and secondary-side inlet/outlet. All four connections are located on the fixed pressure plate for convenient piping connection.
  • Features: Counter-current heat exchange design with large logarithmic mean temperature difference and high heat exchange efficiency. Plates are disassemblable for easy cleaning and maintenance. Heat exchange area can be adjusted by adding or removing plates to flexibly adapt to different loads.

2.3.2 Heat Exchange Side Plate Circuit Regulation Components

The primary-side water inlet is equipped with an electric proportional regulating valve and manual regulating valve. The secondary side is equipped with temperature sensors. The control system automatically adjusts the primary-side electric valve opening based on the secondary-side outlet water temperature, controlling the primary-side cooling water flow rate to achieve precise control of the secondary-side outlet water temperature.

Both the primary and secondary sides are equipped with temperature sensors and pressure gauges to monitor temperature and pressure before and after heat exchange in real time, calculate heat exchange capacity and heat exchange temperature difference, and facilitate system energy efficiency analysis and fault diagnosis.

2.3.3 Primary/Secondary Side Isolation Structure

The plate heat exchanger itself achieves physical isolation of the primary and secondary side media. The flow channels on both sides are completely independent, and under normal operating conditions, media cross-contamination will not occur. The system is equipped with differential pressure monitoring and conductivity monitoring functions. When internal leakage occurs in the heat exchanger, abnormal changes in the pressure differential and medium conductivity on both sides will trigger automatic alarms from the control system, promptly reminding O&M personnel to handle the issue and preventing contamination of the IT equipment-side coolant.

2.4 Filtration and Purification Unit

Immersion coolant circulates in the system for long periods, gradually accumulating particles shed from piping, equipment wear debris, medium degradation products, and other impurities. These impurities can contaminate IT equipment, wear pump impellers, and block heat exchange channels. Therefore, a comprehensive filtration and purification system must be configured.

2.4.1 Main-Line Y-Type Strainer

Installed on the upstream side of the main circulation pump inlet, providing coarse filtration with a filtration precision of 80-100 mesh. It removes larger particulate impurities from the coolant, protecting the pump impeller and subsequent precision components. The strainer is made of 304 stainless steel and is equipped with a drain valve, allowing online blowdown and cleaning without shutdown or disassembly.

2.4.2 Bypass Precision Filter

Installed in a bypass configuration, diverting 10%-20% of the flow from the main line into the precision filter for deep purification filtration. Filtration precision is selectable at 1μm/5μm, progressively removing fine particles from the system and continuously improving coolant cleanliness. The bypass design does not affect the high-flow main-line circulation while achieving continuous purification, avoiding excessive resistance from the main-line filter that could impact system efficiency.

The precision filter uses a stainless steel housing with a built-in pleated filter cartridge. It has high dirt-holding capacity and long service life. It is equipped with inlet/outlet differential pressure transmitters that monitor the pressure differential across the filter in real time. When the differential pressure reaches a set threshold, an automatic alarm is triggered to remind the operator to replace the filter cartridge.

2.4.3 Filter Cartridge Assemblies

The precision filter cartridge uses a polypropylene pleated design with high dirt-holding capacity, stable filtration precision, and good chemical compatibility, suitable for various dielectric coolants. Both ends of the cartridge are sealed with rubber end caps for convenient installation. Replacement only requires opening the filter top cover to remove and replace the cartridge.

Three grades are available according to precision:

  • 5μm precision: For normal operating conditions, meeting cleanliness requirements of most scenarios
  • 1μm precision: For high-cleanliness requirement scenarios, suitable for high-precision IT equipment
  • 0.5μm precision: For ultra-high-cleanliness requirement scenarios, requires custom configuration

2.4.4 Differential Pressure Detection Devices

Both the main-line filter and bypass precision filter are equipped with differential pressure detection devices, consisting of two pressure transmitters and control logic that calculate the filter inlet/outlet differential pressure in real time.

  • When differential pressure reaches 0.08MPa, a pre-alarm signal is issued, indicating the filter cartridge is approaching blockage and replacement planning should be arranged.
  • When differential pressure reaches 0.12MPa, an alarm signal is issued, indicating the filter cartridge must be replaced as soon as possible to avoid affecting system flow.
  • Differential pressure data can be displayed in real time on the touchscreen, with support for historical data query and trend analysis.

2.5 Pressure Stabilization and Liquid Replenishment Unit

Coolant volume expands with heat and contracts with cold as temperature changes. The system also experiences minor losses during operation. The pressure stabilization and liquid replenishment unit is used to stabilize system pressure, compensate for volume changes, automatically replenish coolant losses, and provide overpressure relief protection.

2.5.1 Diaphragm-Type Expansion Tank

A diaphragm-type pneumatic expansion tank is used. The tank body is made of carbon steel, with an internal rubber diaphragm. One side of the diaphragm is pre-charged with nitrogen gas, and the other side is connected to the system piping.

  • Operating Principle: When system temperature rises and coolant volume expands, excess liquid enters the expansion tank, compressing the nitrogen and absorbing the expansion volume. When system temperature drops and coolant volume contracts, nitrogen pressure pushes the liquid in the diaphragm back into the system, compensating for the contraction volume and maintaining stable system pressure.
  • Features: Complete gas-liquid isolation; coolant does not come into contact with nitrogen, preventing gas from dissolving into the coolant. The tank body is corrosion-resistant with long service life. Pre-charge pressure can be adjusted according to system requirements.
  • Configuration Specifications: Expansion tank volume is matched to the system’s total water capacity. 30kW configures 24L, 50kW configures 50L, 80kW configures 100L, and 120kW configures 150L.

2.5.2 Automatic Liquid Replenishment Valve Assembly

Composed of a replenishment pump, solenoid valve, check valve, filter, and pressure sensor, connected to the replenishment tank, implementing automatic system liquid replenishment.

  • Operating Principle: The control system monitors system pressure in real time. When system pressure falls below the set lower limit, the liquid replenishment solenoid valve automatically opens and the replenishment pump starts, drawing coolant from the replenishment tank to replenish the system. When system pressure recovers to the set value, replenishment stops and the solenoid valve closes.
  • Functional Features: Fully automatic operation without manual intervention. Equipped with a check valve to prevent liquid backflow. Equipped with a filter to protect the solenoid valve and replenishment pump. Equipped with a replenishment timeout alarm function to prevent prolonged replenishment during major system leakage.

2.5.3 Liquid Replenishment Tank

Made of 304 stainless steel, used to store standby coolant and provide a medium source for system replenishment.

  • The tank is equipped with a level sensor and level indicator, displaying the remaining liquid volume in real time. A low level alarm is issued when the level is too low, reminding personnel to manually replenish coolant.
  • The tank has a sealed cover to prevent dust and debris from falling in and maintain coolant cleanliness.
  • Equipped with a replenishment connection port and drain port for convenient liquid filling and draining/cleaning.
  • Specifications: 30/50kW configures a 50L replenishment tank; 80/120kW configures a 100L replenishment tank.

2.5.4 Pressure Safety Valve

Installed at the highest point of the system main pipeline, this is a spring-loaded safety valve. When system pressure exceeds the set safety pressure value, the safety valve automatically opens, relieving excess liquid to the replenishment tank, reducing system pressure and preventing overpressure damage to piping and equipment.

  • Set Pressure: Configured according to the system rated working pressure, typically 1.1-1.2 times the working pressure.
  • Material: Valve body is 304 stainless steel; sealing elements are fluororubber, compatible with coolant media.
  • Features: Simple structure, reliable operation, can open and close repeatedly, opening pressure can be calibrated.

2.6 Valve and Piping Unit

Valves and piping form the vascular system of the system, responsible for coolant delivery, on/off control, regulation, and distribution. All components are made of stainless steel, compatible with dielectric coolant media.

2.6.1 Main Pipeline Fittings

  • Material: All made of 304/316L stainless steel with polished inner surfaces, low flow resistance, corrosion resistance, and not prone to scaling.
  • Connection Methods: Combination of argon arc welding, press-fit connection, and flange connection to ensure reliable sealing.
  • Specifications: Pipe diameters are matched to system flow rates. 30kW uses DN25, 50kW uses DN40, 80kW uses DN50, and 120kW uses DN65.
  • Fitting Types: Include straight pipes, elbows, tees, reducers, flanges, pipe caps, etc., all using standard components with good interchangeability.

2.6.2 Electric Regulating Valve

Installed at the primary-side water inlet, used to regulate the primary-side cooling water flow rate to achieve secondary-side outlet water temperature control.

  • Uses an electric proportional regulating valve. The valve body is stainless steel, the valve core has equal-percentage characteristics, and regulation precision is high.
  • The actuator is an electric actuator accepting 4-20mA analog control signals, outputting the corresponding valve opening with a regulation range of 0-100%.
  • Equipped with manual operation capability for manual valve opening adjustment during power failure or faults.
  • Protection class IP65, suitable for humid computer room environments.

2.6.3 Manual Stop Valves/Butterfly Valves

Multiple manual valves are configured throughout the system for maintenance, flow regulation, draining, and blowdown operations:

  • Butterfly Valves: Used for on/off control of large-diameter pipelines. Compact structure, convenient operation, and low fluid resistance.
  • Globe Valves: Used for precise flow regulation and shutdown of small-diameter pipelines. Excellent sealing performance.
  • Ball Valves: Used for blowdown, sampling, and draining connections. Quick switching and convenient operation.
  • All valves are made of 304 stainless steel with sealing elements compatible with coolant media.

2.6.4 Check Valves

Also known as one-way valves, installed at pump outlets and replenishment pump outlets to prevent liquid backflow, avoiding pump reverse rotation and medium backflow.

  • Lift-type or swing-type structure, stainless steel body, rubber sealing, good sealing performance, and low flow resistance.
  • Low opening pressure, sensitive action, and no sticking.

2.6.5 Quick Connectors

The system’s external connection ports can be optionally equipped with dry-break quick connectors, enabling rapid plug-and-unplug piping connections with zero leakage during connection/disconnection, significantly reducing on-site installation time.

  • Double self-sealing structure; both the plug and socket have built-in one-way valves that automatically seal upon disconnection, achieving zero leakage.
  • Made of 316 stainless steel, corrosion-resistant, long service life, with plug/unplug cycles ≥ 1000 times.
  • Matched to corresponding pipe diameters, firm connection, pressure rating consistent with the piping.

2.6.6 Flexible Connection Components

Installed at pump inlet/outlet and equipment-to-piping connections, used to absorb vibration, compensate for piping displacement, and reduce noise.

  • Stainless steel metal bellows flexible connections with high-temperature resistance, corrosion resistance, and strong pressure-bearing capability.
  • Both ends use flange or threaded connections for convenient installation.
  • Can absorb axial, lateral, and angular displacement, eliminating piping installation stress.

2.7 Sensing and Detection Unit

The sensing and detection unit serves as the “sensory organs” of the system, collecting operating parameters such as temperature, pressure, flow rate, liquid level, and conductivity in real time and transmitting them to the control system, providing data support for intelligent regulation and fault protection. All sensors undergo factory calibration, with high measurement precision and stable operation.

2.7.1 Temperature Sensors

Platinum resistance Pt100/Pt1000 temperature sensors are used, featuring high measurement precision, good stability, and long service life.

  • Installation Locations: Multiple points including secondary-side inlet, secondary-side outlet, primary-side inlet, primary-side outlet, pump body, and ambient.
  • Measurement Range: -20℃~120℃, covering the full operating temperature range of the liquid cooling system.
  • Measurement Precision: ±0.1℃ (Class A), meeting high-precision temperature control requirements.
  • Output Signal: 4-20mA analog signal or RS485 digital signal, long transmission distance, strong anti-interference capability.
  • Installation Method: Insertion type with protective thermowell, replaceable online without affecting system operation.

2.7.2 Pressure Sensors

Diffused silicon pressure transmitters are used, featuring stable performance and strong anti-interference capability.

  • Installation Locations: Pump inlet/outlet, filter inlet/outlet, system main pipeline, upstream of expansion tank, and other points.
  • Measurement Range: 0-1.6MPa, compatible with the system working pressure range.
  • Measurement Precision: ±0.25%FS, accurate and reliable pressure measurement.
  • Output Signal: 4-20mA two-wire analog signal, simple wiring, strong anti-interference capability.
  • Process Connection: External threaded connection with damping tube, reducing pressure impact and protecting the sensor element.

2.7.3 Flow Sensors

Electromagnetic flow meters or turbine flow meters are used to accurately measure instantaneous and cumulative coolant flow rates in the piping.

  • Installation Location: Secondary-side main return water pipeline, measuring the total system circulation flow rate.
  • Measurement Range: Range matched to system flow rate, with a measurable ratio up to 10:1.
  • Measurement Precision: ±0.5%FS, accurate flow measurement.
  • Output Signal: 4-20mA analog + pulse output, supporting instantaneous flow and cumulative flow measurement.
  • Features: Unobstructed flow channel, low pressure loss; corrosion-resistant, compatible with various media; no moving parts, long service life.

2.7.4 Liquid Level Sensors

Divided into contact and non-contact types, used to monitor the replenishment tank level and immersion chamber level.

  • Replenishment Tank Level: Uses a submersible level transmitter or magnetic flap level gauge, displaying remaining liquid volume in real time and providing high/low level alarms.
  • Immersion Chamber Level: Uses photoelectric level sensors or magnetostrictive level transmitters for high-precision monitoring of coolant level in the chamber. Low level triggers alarms and interlock protection.
  • High measurement precision, stable operation, compatible with dielectric coolant media.

2.7.5 Conductivity Sensors

Used to monitor the conductivity of the coolant, indirectly reflecting coolant purity and contamination level, and also capable of detecting internal leakage in the heat exchanger.

  • Installed in the secondary-side return water pipeline for real-time online conductivity monitoring.
  • When conductivity exceeds the set threshold, an automatic alarm is issued, indicating coolant contamination or heat exchanger internal leakage.
  • Measurement range adapted to media type, measurement precision ±2%FS.
  • Electrodes made of stainless steel or graphite, corrosion-resistant and easy to clean.

2.8 Electrical Control Unit

The electrical control unit is the “brain” of the system, responsible for the logical control, parameter regulation, fault protection, data display, and communication interaction of the entire water circulation system. It uses a PLC + touchscreen control architecture with powerful functionality, stable operation, and convenient operation.

2.8.1 Main Control Cabinet Enclosure

Uses a standard 19-inch cabinet-type installation, integrated with the water circulation mechanical portion in the same enclosure. Compact structure, protection class IP54, dustproof and waterproof, suitable for computer room environments.

  • Cabinet body formed from cold-rolled steel plate bending, with electrostatic powder coating on the surface for corrosion and wear resistance.
  • Internal mounting plates are layered, with power and low-voltage areas separated to reduce electromagnetic interference.
  • Cabinet is equipped with cooling fans and ventilation filters to ensure proper heat dissipation of internal electrical components.
  • Front door has a transparent window for direct observation of touchscreen display content and indicator light status.

2.8.2 PLC Control Module

A high-performance programmable logic controller (PLC) serves as the main control core, with stable and reliable operation, strong anti-interference capability, and suitability for industrial field environments.

  • Rich I/O interfaces supporting analog input/output and digital input/output, capable of connecting all sensor signals and actuator control signals.
  • Built-in intelligent control programs implementing all functions including pump control, temperature control, pressure control, fault protection, and logic interlocking.
  • Programs support online modification and upgrades, with control logic customizable according to customer requirements.
  • Power-off data retention capability; parameters and operating data are not lost after power failure.

2.8.3 Variable Frequency Drive Module

Configured with a high-performance vector-controlled variable frequency drive (VFD) to drive the circulation pump motor, achieving variable frequency speed control that dynamically adjusts pump speed and flow rate based on load requirements.

  • Wide speed regulation range, 0-50Hz stepless speed control, with significant energy-saving effects.
  • Soft-start capability, reducing starting current impact and extending pump motor service life.
  • Complete protection functions including overcurrent, overload, overvoltage, undervoltage, and over-temperature.
  • Supports PLC analog signal control for automatic flow and pressure regulation.

2.8.4 Human-Machine Interface Touchscreen

Uses a 7-inch/10-inch industrial-grade color touchscreen as the human-machine interface, providing intuitive and convenient operation.

  • Real-time display of system operating parameters: temperature, pressure, flow rate, liquid level, valve opening, pump frequency, etc.
  • Parameter settings support: temperature setpoints, pressure upper/lower limits, alarm thresholds, and other operating parameters.
  • Fault alarm display: real-time display of fault information and fault time for convenient troubleshooting.
  • Historical data query and curve display: query historical trend curves for parameters such as temperature, pressure, and flow rate.
  • Multi-level permission management: different operating permissions correspond to different operational ranges, preventing misoperation.

2.8.5 Relay and Contactor Assemblies

Includes AC contactors, intermediate relays, thermal relays, and other low-voltage electrical components, all from first-tier brands with reliable performance and long service life.

  • AC contactors used for power on/off control of loads such as pump motors and solenoid valves.
  • Thermal relays used for pump motor overload protection, automatically cutting power on overload to protect the motor.
  • Intermediate relays used for signal conversion and expansion, enabling low-voltage control of high-voltage circuits.
  • All components installed on standard DIN rails with standardized wiring for convenient maintenance and replacement.

2.8.6 Power Protection Modules

  • Configured with circuit breakers and residual current circuit breakers (RCCB) for short-circuit, overload, and leakage protection, ensuring electrical safety.
  • Configured with surge protective devices (SPD) to suppress grid surge impacts and protect precision electronic components such as PLCs and VFDs.
  • Optional dual power automatic transfer switch supporting dual power supply; automatic transfer to the other supply when one fails, ensuring continuous system power supply.
  • Configured with switching power supplies providing stable DC working power for PLCs, sensors, and touchscreens.

2.8.7 Communication Modules

  • Standard RS485 communication interface with Modbus-RTU protocol support, interfaceable with host computers and environment monitoring systems for remote monitoring.
  • Optional Ethernet module supporting TCP/IP protocol, connectable to LAN or internet for remote web monitoring and mobile APP monitoring.
  • Data upload support, uploading system operating parameters and alarm information to monitoring platforms.
  • Remote parameter settings and program upgrades supported, facilitating remote technical support maintenance.

2.9 Safety Protection Unit

To ensure safe and stable system operation and protect personnel and equipment safety, the system is equipped with multiple safety protection components.

2.9.1 Leak Detection Components

  • Leak detection cables are arranged at the cabinet base and key piping joints for real-time detection of coolant leakage.
  • When leakage is detected, the control system immediately issues audible and visual alarms. In severe cases, interlocked shutdown can be triggered to prevent leakage escalation.
  • High leak detection sensitivity, capable of detecting trace liquid leaks and locating the leak area.
  • Detection cables are reusable and automatically reset after drying.

2.9.2 Over-Temperature Alarm Devices

  • Multiple temperature monitoring points are set throughout the system. When the secondary-side outlet water temperature exceeds the set alarm value, an audible and visual alarm is issued.
  • When temperature continues rising to the shutdown threshold, the system automatically interlocks IT equipment frequency reduction or shutdown, protecting IT equipment from overheating damage.
  • Alarm thresholds can be flexibly set according to requirements.

2.9.3 Overload Protection Devices

  • Pump motors are configured with thermal relays and VFD overload protection. On motor overload, power is automatically cut to prevent motor burnout.
  • The system is configured with overcurrent, short-circuit, and leakage protection to ensure electrical safety.
  • On pressure over-limit, the safety valve automatically relieves pressure to protect piping and equipment.

2.9.4 Emergency Stop Button

Red mushroom-head emergency stop buttons are installed on the control cabinet panel and at easily accessible on-site locations. When an emergency occurs, pressing the button immediately cuts all power output and stops pump operation, ensuring personnel and equipment safety. The emergency stop button requires manual reset to prevent accidental restart.

2.10 Auxiliary Accessories Unit

2.10.1 Support and Hanger Components

  • Dedicated pipe clamps and brackets are configured for internal cabinet piping to secure piping and prevent vibration and stress deformation.
  • External piping is provided with support hangers, including expansion bolts, channel steel, pipe clamps, and damping pads for on-site piping installation and fixation.
  • All support hangers are corrosion-treated with long service life.

2.10.2 Sealing Kit

  • Includes various O-rings, gaskets, mechanical seals, and other sealing spare parts for routine maintenance and fault replacement.
  • Sealing material is matched to the coolant media to ensure reliable sealing and corrosion resistance.
  • A consumable sealing spare parts kit is shipped with the product for convenient on-site emergency replacement.

2.10.3 Insulation Material and Outer Protective Layer

  • Used for external piping insulation to prevent pipe condensation and cooling capacity loss.
  • Insulation material uses rubber-plastic insulation with low thermal conductivity and fire resistance rating Class B1.
  • Outer protective layer uses aluminum foil or color steel plate to protect the insulation layer, providing aesthetic appearance and durability.

2.10.4 Identification Labels and Nameplates

  • The system is configured with various identification labels and nameplates, including equipment nameplates, valve identification, piping flow direction labels, warning labels, and safety labels.
  • Clear and standardized identification for convenient identification and operation by O&M personnel.
  • Equipment nameplates indicate product model, parameters, factory serial number, manufacturer, and other information.

Chapter 3 Product List

3.1 List Compilation Instructions

1. This list is the standard configuration list for the LA-YM series immersion liquid cooling water circulation system. The list includes system