Manufacturer: Guangzhou Lain Intelligent System Development Co., Ltd.
Document Version: V2.0
Release Date: July 2026
Table of Contents
TogglePreface

With the rapid development of the digital economy and artificial intelligence industry, the computing power density of data centers and intelligent computing centers continues to rise. The power density of a single cabinet has rapidly broken through from the traditional 5kW to 30kW, 50kW, and even above 100kW. Traditional air-cooling heat dissipation modes can no longer meet the heat dissipation requirements of high-density computing equipment, while also facing multiple pain points such as high energy consumption, high noise, and low space utilization. As a new generation of liquid-cooling heat dissipation infrastructure, the sealed water-cooled integrated cabinet has become the mainstream heat dissipation solution for high-density computing scenarios, leveraging its core advantages of high-efficiency heat exchange, low PUE, high reliability, and flexible deployment.
This manual provides a comprehensive and systematic description of the full lifecycle content of the sealed water-cooled integrated cabinet product independently developed and manufactured by Guangzhou Lain Intelligent System Development Co., Ltd., including the technical principles, structural composition, technical parameters, installation specifications, wiring standards, commissioning procedures, maintenance, troubleshooting, and acceptance criteria. It is designed to provide authoritative, detailed, and actionable operating guidelines for engineering construction personnel, operation and maintenance management personnel, and technical support personnel, ensuring safe, stable, and efficient equipment operation.
This manual is compiled in strict compliance with national and industry standards including the *Code for Design of Data Centers* (GB 50174), *Standard for Construction and Acceptance of Data Center Infrastructure* (GB 50462), *Operation and Maintenance Guide for Liquid Cooling System of Cold Plate Indirect Liquid Cooling Data Center* (T/CIE 342-2025), and *Technical Specification for Liquid Cooling System Engineering* (T/CAICI 131-2025). All operational procedures have been verified through extensive engineering practice. Relevant operating personnel must carefully read this manual before operations and strictly follow the standard procedures. Improper operation may result in equipment damage, water leakage accidents, electrical safety hazards, and other serious consequences.
If you encounter any technical issues during installation, commissioning, or operation and maintenance, please contact our technical support team promptly. We will provide full-process professional technical services.
Chapter 1 Product Introduction

1.1 Industry Development Background
Guided by the “Dual Carbon” strategic goals, the data center industry is accelerating its transformation toward green, low-carbon, high-density, and high-computing-power development. Traditional air-cooled data centers commonly suffer from high PUE values (typically between 1.4 and 1.8), large energy consumption proportions, and low heat dissipation capacity ceilings, making them increasingly unable to meet the computing power demands of emerging scenarios such as AI large model training, high-performance computing, and edge computing.
Liquid-cooling technology, leveraging the significantly higher specific heat capacity and heat exchange efficiency of water and other coolants compared to air, can increase single-cabinet heat dissipation capacity to 30kW–200kW while reducing data center PUE to below 1.1, substantially lowering cooling energy consumption. This has made it the core direction for data center heat dissipation technology upgrades. Among these solutions, the sealed water-cooled integrated cabinet serves as a cabinet-level integrated liquid-cooling solution that requires no large-scale renovation of the computer room, can be rapidly deployed and put into use immediately upon installation, and perfectly suits both the upgrade of existing computer rooms and the high-density deployment needs of new computer rooms. Market demand is experiencing explosive growth.
1.2 Product Definition
The sealed water-cooled integrated cabinet, also known as a cabinet-level closed cold-plate liquid-cooling cabinet, is an integrated heat dissipation device that highly integrates the cabinet enclosure, liquid cooling distribution unit (CDU), manifold, circulation pump, plate heat exchanger, intelligent control system, power distribution unit, and leak detection system within a standard cabinet. The product employs a closed-loop water circuit design: the secondary-side coolant circulates within a sealed piping system, exchanges heat with the IT equipment cold plates, and then transfers heat to the primary-side cooling water through the plate heat exchanger. The heat is ultimately carried away by an outdoor cold source, achieving efficient heat dissipation for IT equipment.
Unlike open water-cooling systems, the closed water-cooling system is fully sealed throughout and does not come into direct contact with ambient air, effectively preventing issues such as coolant oxidation, scaling, and impurity ingress. This substantially extends system service life and maintenance intervals while eliminating risks of pipeline corrosion and blockage, ensuring long-term stable system operation.
1.3 Product Technical Positioning
The sealed water-cooled integrated cabinet developed by Guangzhou Lain Intelligent System Development Co., Ltd. is positioned as a cabinet-level turnkey heat dissipation solution for high-density computing scenarios. It covers the full power range from 15kW to 120kW, is compatible with standard 19-inch IT equipment, and supports deployment of various computing devices including cold-plate liquid-cooled servers, GPU servers, storage devices, and network equipment. The product employs modular and standardized design, enabling factory prefabrication, complete-unit delivery, and rapid on-site installation, substantially shortening project construction cycles and reducing construction complexity and engineering risks.
The core technical route of the product is indirect cold-plate liquid cooling, which balances heat dissipation efficiency with equipment compatibility. It requires no modification to the internal structure of IT equipment—only replacement of the liquid-cooled cold plate is needed to achieve heat dissipation upgrades. The product is compatible with equipment from the majority of mainstream server manufacturers, offering exceptional universality and implementability. Additionally, the product reserves liquid-cooling upgrade interfaces, allowing smooth capacity expansion based on future computing power requirements and protecting user investment.
1.4 Product Core Value
Extreme Energy Efficiency, Low-Carbon and Eco-Friendly: Utilizing high-efficiency closed water-cooling heat exchange technology, the cooling system’s energy efficiency ratio far exceeds that of traditional air cooling. With support for free-cooling source integration, the annual PUE can be as low as 1.08, substantially reducing data center cooling energy consumption and helping users achieve carbon reduction goals.
Ultra-High Density, Space Saving: Single-cabinet heat dissipation capacity reaches up to 120kW—more than 10 times that of traditional air-cooled cabinets—significantly improving computer room space utilization and reducing floor area requirements and construction costs.
Silent Operation, Improved Environment: Completely eliminates the noise of high-speed cooling fans in the computer room. Cabinet operating noise is ≤55dB(A), significantly improving the computer room operation and maintenance environment and reducing the health impact of noise on maintenance personnel.
Stable and Reliable, Comprehensive Protection: Fully sealed water circuit design, combined with multi-level leak detection, emergency water cutoff, and fault alarm mechanisms, completely eliminates the risk of water leakage. All fluid circuit components are made of corrosion-resistant materials with a service life of over 15 years.
Intelligent Management, Simplified O&M: Built-in intelligent monitoring system enables real-time monitoring of flow rate, temperature, pressure, liquid level, and leak detection parameters, with support for remote monitoring, automatic adjustment, and fault prediction, significantly reducing O&M difficulty and labor costs.
Rapid Deployment, Flexible Adaptation: Integrated design means on-site work only requires connecting the primary-side supply/return water pipes and the power supply. No large-scale computer room renovation is needed, making it suitable for both new computer rooms and upgrades of existing ones.
1.5 Product Model Description
Lain sealed water-cooled integrated cabinets use a standardized naming convention with the model format: LA-SW-XXX-YY, where:
- LA: Represents the Lain (LaiAn) brand identifier of Guangzhou Lain
- SW: Represents the Sealed Water-cooled series
- XXX: Represents the rated heat dissipation power in kW, e.g., 30, 50, 80, 120
- YY: Represents the cabinet height specification in U, e.g., 42U, 47U, 52U
Example: LA-SW-50-42 represents a Lain sealed water-cooled integrated cabinet with a rated heat dissipation power of 50kW and a standard 42U cabinet height.
Chapter 2 Product Composition

The Lain sealed water-cooled integrated cabinet adopts a modular integrated design, comprising six core subsystems: the cabinet structure system, liquid-cooling circulation system, heat exchange system, power distribution system, intelligent monitoring system, and safety protection system. All subsystems work collaboratively to achieve efficient, stable, and safe heat dissipation for IT equipment.
2.1 Cabinet Structure System
The cabinet structure system serves as the load-bearing foundation of the entire device. It is fabricated from high-strength quality cold-rolled steel plates and undergoes pickling, phosphating, and electrostatic powder coating, providing excellent corrosion resistance, rust prevention, and wear resistance while meeting EMC electromagnetic shielding requirements.
2.1.1 Cabinet Enclosure
- Standard 19-inch rack structure, compliant with international standards including ANSI/EIA RS-310-D and IEC297-2, compatible with all standard 19-inch IT equipment installation;
- Cabinet plate thickness: 2.0mm upright posts, 1.5mm side panels and doors, 2.5mm base. Overall static load-bearing capacity ≥1500kg, meeting high-density equipment loading requirements;
- Surface treatment: degreasing, pickling, phosphating, electrostatic powder coating. Coating thickness 60–80μm, adhesion meeting Grade 0 of GB/T 9286-1998;
- Protection rating: IP20 for the cabinet body, IPX4 for the fluid circuit area, meeting computer room environmental usage requirements;
- Structural design: front and rear double-door design with ventilated observation windows on doors for convenient O&M operation and status observation; ample internal cable routing space reserved; separate routing channels for power and signal cables to avoid electromagnetic interference.
2.1.2 Mounting Racks and Upright Posts
- High-strength galvanized steel upright posts with standard U-position scale markings, positioning accuracy ±0.1mm, ensuring precise equipment installation;
- Front and rear adjustable upright posts, adaptable to IT equipment of different depths;
- Equipped with standard L-type mounting brackets, cage nuts, and other installation accessories to meet the mounting and fastening requirements of servers, switches, storage devices, and other equipment.
2.1.3 Base and Support Structure
- Integrated welded base equipped with heavy-duty adjustable leveling feet, adjustable height range ±20mm, adaptable to uneven floors;
- Base is pre-drilled with forklift slots and lifting holes for convenient equipment transport and positioning;
- Bottom is configured with a water-retention containment berm structure, capable of containing small amounts of accidental overflow, working with leak detection for early warning.
2.1.4 Cable Routing and Wiring Structure
- Cable routing channels are reserved at both the top and bottom of the cabinet, equipped with rubber grommets to protect cable jackets from abrasion;
- Internal segregated cable channels for power and signal cables, with physical separation of power cables and signal cables at a spacing of ≥200mm to reduce electromagnetic interference;
- Equipped with cable management bars, cable lacing bars, cable fasteners, and other accessories to ensure neat and standardized wiring.
2.2 Liquid-Cooling Circulation System
The liquid-cooling circulation system is the core functional unit of the product, responsible for circulating and distributing coolant within the cabinet to meet the heat dissipation requirements of IT equipment cold plates. The system employs a closed-loop circulation design and primarily consists of circulation pump assemblies, manifolds, fluid piping, quick couplings, filter assemblies, expansion tanks, and air venting devices.
2.2.1 Circulation Pump Assembly
- Utilizes imported brand variable-frequency centrifugal pumps featuring high efficiency, silent operation, and long service life;
- Adopts 1+1 redundant design; when the primary pump fails, the standby pump automatically switches over to ensure uninterrupted system operation;
- Pumps support 0–100% stepless speed regulation, intelligently adjusting flow based on load demand for energy-saving operation;
- Pumps are equipped with mechanical seals and use corrosion-resistant materials, capable of withstanding 0.6MPa working pressure, with a leak-free service life of ≥50,000 hours;
- Includes pump vibration-damping bases and flexible connection joints to reduce vibration transmission and operating noise.
2.2.2 Manifold (Water Collector/Distributor)
- Manufactured from 304 stainless steel in an integrated forming process, corrosion-resistant and rust-free, with pressure-bearing capacity ≥1.0MPa;
- Supply manifold and return manifold are symmetrically arranged; each port is equipped with an independent valve and flow indicator, allowing individual adjustment of each circuit’s flow rate;
- Number of ports can be configured based on the quantity of IT equipment in the cabinet, supporting 8–24 liquid-cooling ports, adaptable to different equipment deployment densities;
- Equipped with pressure and temperature sensors for real-time monitoring of supply/return water pressure and temperature data;
- Bottom is fitted with a drain valve to periodically discharge impurities from the piping, maintaining system cleanliness.
2.2.3 Fluid Piping System
- Main pipes use 304 stainless steel seamless steel tubes with polished inner surfaces, offering low flow resistance and resistance to scaling;
- Branch pipes use food-grade PFA hoses or stainless steel corrugated pipes, offering excellent flexibility and corrosion resistance;
- Pipe connections use welding, press-fitting, or flanged connections; all connection points undergo strict pressure testing to eliminate leakage;
- Pipe exteriors are wrapped with rubber-plastic insulation, thickness ≥20mm, to prevent condensation on pipe surfaces and reduce cooling capacity loss;
- Piping design follows hydraulic balance principles with flow resistance variation across branches of ≤10%, ensuring uniform heat dissipation across all IT equipment.
2.2.4 Quick Couplings
- Use double self-sealing quick couplings; both male and female ends automatically seal during connection and disconnection, achieving zero leakage during coupling/uncoupling;
- Material: 316L stainless steel, corrosion-resistant and wear-resistant, with mechanical coupling/uncoupling life of ≥1000 cycles;
- Equipped with anti-misconnection structure to prevent reversed supply/return piping connections;
- Supports blind-mating design—IT equipment automatically completes fluid connection upon being pushed into the cabinet, greatly improving O&M efficiency;
- Rated working pressure 0.6MPa, burst pressure ≥2.0MPa, with high safety factor.
2.2.5 Filter Assembly
- Y-type precision filter configured at the water inlet with a filtration accuracy of 50μm, effectively intercepting impurities in the piping and preventing blockage of cold plate micro-channels;
- Filter is equipped with a differential pressure sensor; when filter element blockage causes the differential pressure to exceed the limit, an automatic alarm is triggered to remind replacement of the filter element;
- Filter features a quick-release structure, allowing filter element replacement without disassembling the piping, for convenient maintenance.
2.2.6 Expansion Tank
- Uses a sealed pressurized expansion tank to accommodate the volume expansion of system coolant due to temperature changes and stabilize system pressure;
- Tank body is made of 304 stainless steel with an internal food-grade rubber diaphragm separating gas and liquid phases, preventing coolant oxidation;
- Equipped with a pressure gauge and inflation valve for real-time monitoring of bladder pressure, allowing nitrogen replenishment as needed;
- Tank volume is configured according to system water capacity, meeting the expansion volume requirements under maximum system temperature rise.
2.2.7 Automatic Air Venting Device
- Automatic air vent valves are installed at the highest point of the system to automatically discharge accumulated air from the piping, preventing cavitation from affecting pump life and heat exchange efficiency;
- Equipped with manual air vent valves for forced manual venting during commissioning and maintenance;
- Vent valve outlets are routed to the drip tray at the cabinet bottom to prevent coolant droplets from falling during venting.
2.3 Heat Exchange System
The heat exchange system is responsible for transferring heat between the primary-side cooling water and the secondary-side coolant, serving as the core of heat exchange in the closed water-cooling system. It primarily consists of a plate heat exchanger, primary-side control valve group, and temperature regulating valves.
2.3.1 Plate Heat Exchanger
- Uses brazed plate heat exchangers with 316L stainless steel plates and copper brazing, offering high heat exchange efficiency, compact size, and light weight;
- Plates feature herringbone corrugation design with excellent turbulence effects; heat transfer coefficient reaches up to 6000W/(㎡·℃) with heat exchange efficiency ≥95%;
- Rated pressure capacity 1.0MPa, design temperature range -10℃~120℃, adaptable to the vast majority of operating conditions;
- Primary side and secondary side are completely isolated, preventing cross-contamination between the two media and ensuring secondary-side coolant cleanliness;
- Detachable structure facilitates later cleaning and maintenance to restore heat exchange performance.
2.3.2 Primary-Side Control Valve Group
- Includes electric regulating valve, manual stop valve, filter, pressure gauge, thermometer, and other components;
- The electric regulating valve uses proportional-integral regulation, automatically adjusting primary-side water flow based on secondary-side supply water temperature, precisely controlling supply water temperature with control accuracy of ±0.5℃;
- The manual stop valve is used to isolate the water circuit during maintenance, facilitating heat exchanger and valve group servicing;
- The filter removes impurities from the primary-side water, preventing blockage of heat exchanger flow channels.
2.3.3 Temperature Regulation Unit
- Uses PID intelligent temperature control algorithm that automatically adjusts primary-side water flow and secondary-side pump speed based on IT load variations and secondary-side return water temperature;
- Supports multiple control modes including supply water temperature setpoint, return water temperature control, and dew point temperature interlock;
- Features anti-condensation control that monitors the computer room ambient dew point temperature in real time and automatically adjusts supply water temperature to prevent condensation on piping and IT equipment surfaces.
2.4 Power Distribution System
The power distribution system provides safe and reliable power supply to all liquid-cooling equipment, monitoring equipment, and IT equipment within the cabinet. It primarily consists of the cabinet power distribution unit, pump power supply circuits, control power supply circuits, IT equipment power distribution unit, and grounding protection unit.
2.4.1 Main Power Distribution Unit
- 380V three-phase five-wire input, with a standard molded case circuit breaker as the main switch, providing overload, short-circuit, and leakage protection;
- Equipped with surge protective device (SPD), protection class C, capable of withstanding lightning strikes and grid surge impacts;
- Configured with an energy metering module for real-time monitoring of voltage, current, power, energy, and other parameters, supporting energy consumption statistics;
- All power distribution components are from first-line brand products, meeting 3C certification standards, safe and reliable.
2.4.2 Pump Power Supply Circuit
- Primary and standby pumps are each powered by independent circuit breakers with overload, phase-loss, and short-circuit protection;
- Equipped with variable-frequency drives for soft start and stepless speed regulation of pumps, reducing grid impact while saving energy;
- Electrical interlocking and mechanical interlocking are provided to prevent simultaneous startup of both pumps, which could cause abnormal system pressure.
2.4.3 IT Equipment Power Distribution Unit
- Rack-mount PDU configured, supporting 10A/16A Chinese standard sockets or IEC C13/C19 sockets, with quantity configurable as required;
- Supports dual-circuit redundant input power supply to ensure IT equipment power supply reliability;
- Optional intelligent PDU providing per-circuit current and voltage monitoring and remote on/off control.
2.4.4 Control and Monitoring Power Supply Circuit
- Independent switching power supplies configured to provide 24V DC safe voltage for the control system, sensors, solenoid valves, and monitoring modules;
- UPS backup power interface configured to maintain monitoring system and alarm functions during mains power interruption;
- All control circuits are equipped with fuses to prevent short-circuit fault escalation.
2.4.5 Grounding Protection Unit
- Dedicated grounding copper busbar provided in the cabinet with cross-sectional area ≥35mm²; all metal components and electrical equipment enclosures are reliably connected to the grounding busbar;
- Cabinet doors and cabinet body are bridged with multi-strand copper braided straps to ensure grounding continuity, with bridging resistance ≤0.1Ω;
- Grounding resistance ≤4Ω, compliant with national electrical safety standards.
2.5 Intelligent Monitoring System
The intelligent monitoring system serves as the “brain” of the equipment, responsible for full-system operational status monitoring, logic control, data acquisition, fault alarm, and remote management. It primarily consists of the main controller, sensor group, human-machine interface, communication module, and alarm module.
2.5.1 Main Controller
- Industrial-grade PLC controller with fast processing speed, strong anti-interference capability, and stable operation, suitable for complex electromagnetic environments in computer rooms;
- Built-in complete control logic program supporting full-function control including pump start/stop, temperature regulation, fault protection, and automatic switchover;
- Program supports online upgrade, with customizable control logic based on user requirements.
2.5.2 Sensor Group
The system is equipped with a full range of sensors for real-time monitoring of system operating parameters, including:
- Temperature sensors: Secondary-side supply water temperature, secondary-side return water temperature, primary-side supply/return water temperature, ambient temperature, dew point temperature, etc., with accuracy of ±0.2℃;
- Pressure sensors: Secondary-side supply/return water pressure, system differential pressure, primary-side supply/return water pressure, etc., with accuracy of ±0.5% FS;
- Flow sensors: Secondary-side total flow rate, branch flow rate, etc., with accuracy of ±1% FS;
- Level sensors: Expansion tank liquid level, drip tray liquid level, etc., monitoring water shortage and overflow conditions;
- Water quality sensor: Optional conductivity sensor for real-time monitoring of coolant conductivity to assess water quality status.
2.5.3 Human-Machine Interface
- 7-inch color touchscreen display configured on the cabinet front door with a full Chinese-language operation interface, intuitively displaying system operating status;
- All operating parameters, fault information, and operating records can be viewed in real time;
- Supports parameter settings, manual operation, mode switching, and other operations with hierarchical permission management to prevent incorrect operation;
- Historical data storage function capable of storing more than 1 year of operating data, with data export support.
2.5.4 Communication Module
- Standard RS485 and Ethernet communication interfaces, supporting standard communication protocols including Modbus-RTU, Modbus-TCP, and SNMP;
- Can be integrated into computer room environmental monitoring systems and BMS building management systems for centralized monitoring;
- Optional 4G/5G wireless communication module for cloud-based remote monitoring and mobile APP status viewing.
2.5.5 Alarm Module
- Supports multiple alarm methods including audible/visual alarm, SMS alarm, email alarm, and platform alarm;
- Hierarchical alarm management classified into three levels: emergency alarm, critical alarm, and general alarm;
- Alarm content includes fault location, fault cause, and handling recommendations to facilitate rapid troubleshooting by O&M personnel;
- Alarm logging function where all alarm information is automatically archived for traceability and query.
2.6 Safety Protection System
The safety protection system serves as an important barrier ensuring safe equipment operation, building a comprehensive safety protection framework from multiple dimensions including leak protection, overpressure protection, overload protection, and anti-condensation.
2.6.1 Leak Detection System
- Locating-type leak detection cables deployed at all leak-prone locations including the cabinet bottom, pipe connections, and manifolds;
- Detection accuracy up to 1cm, enabling precise leak location identification, with leak response time ≤2s;
- Upon leak detection, an audible/visual alarm is immediately triggered while the inlet solenoid valve is closed and pumps are stopped to prevent leak escalation;
- Equipped with a leak detection controller supporting self-test functionality with periodic automatic sensor status verification, ensuring detection reliability.
2.6.2 Overpressure and Overcurrent Protection
- Safety valves fitted to the system that automatically relieve pressure when system pressure exceeds the set value, protecting piping and equipment;
- Electrical circuits are equipped with circuit breakers, fuses, thermal relays, and other protective components for overload, short-circuit, and phase-loss protection;
- Pumps are provided with pressure protection that automatically shuts down on water shortage or low pressure, preventing pump dry-run damage.
2.6.3 Anti-Condensation Protection System
- Built-in high-precision temperature and humidity sensors for real-time calculation of ambient dew point temperature;
- Intelligent control maintains supply water temperature always 1–2℃ above the dew point temperature, fundamentally preventing condensation;
- Condensation sensors are fitted at critical locations; upon detection of condensation risk, supply water temperature is automatically raised while optional heating devices are activated;
- All chilled water pipes and valves are wrapped with thickened insulation to reduce the probability of surface condensation.
2.6.4 Power Failure Protection and Auto-Restart on Power Recovery
- System supports power failure memory function—all operating parameters and statuses are automatically saved upon power loss;
- Automatic resumption of operation upon power recovery without manual intervention, ensuring system reliability in unattended scenarios;
- Time-delayed staggered startup is used upon power recovery to prevent grid impact from simultaneous startup of multiple devices.
Chapter 3 Product Checklist
3.1 Standard Complete Unit Checklist
| No. | Component Name | Specification/Model | Qty | Unit | Remarks |
|---|---|---|---|---|---|
| 1 | Cabinet enclosure | 42U/47U/52U standard 19-inch | 1 | set | Includes front/rear doors, side panels, base, adjustable leveling feet |
| 2 | Mounting upright posts | 19-inch standard galvanized posts | 4 | pcs | With U-position markings, front/rear adjustable |
| 3 | Circulation pump assembly | Variable-frequency centrifugal pump, 1+1 redundant | 1 | set | Includes VFD, vibration-damping base, flexible connections |
| 4 | Plate heat exchanger | Brazed type, 316L stainless steel | 1 | unit | Heat exchange power matched to model |
| 5 | Manifold | 304 stainless steel, with valves | 1 | set | Supply manifold + return manifold, port quantity configured as required |
| 6 | Expansion tank | Sealed pressurized stainless steel | 1 | unit | Volume matched to system water capacity |
| 7 | Fluid piping system | 304 stainless steel pipe + insulation | 1 | set | Includes main pipes, branch pipes, fittings, valves |
| 8 | Quick couplings | Double self-sealing 316L stainless steel | As required | pairs | Matched to IT equipment cold plate interfaces |
| 9 | Y-type filter | 50μm accuracy, stainless steel | 2 | pcs | 1 each for primary side and secondary side |
| 10 | Automatic air vent valve | Stainless steel, vertical type | 2 | pcs | Installed at system highest points |
| 11 | Main power distribution unit | 380V three-phase MCCB + SPD | 1 | set | Includes main switch, surge protector, energy meter |
| 12 | Rack-mount PDU | 16A/32A, IEC sockets | 2 | pcs | Dual-circuit redundancy, quantity customizable |
| 13 | Intelligent controller | Industrial-grade PLC | 1 | set | Includes control program |
| 14 | Touchscreen display | 7-inch color touchscreen | 1 | unit | Flush-mounted on front door |
| 15 | Sensor group | Temperature, pressure, flow, level | 1 | set | Includes all standard sensors |
| 16 | Leak detection system | Locating-type leak cable + controller | 1 | set | Covers all leak-prone areas of the cabinet |
| 17 | Grounding copper busbar | 35mm² pure copper | 1 | bar | Includes grounding terminals |
| 18 | Installation accessory kit | Screws, nuts, cable ties, seals, etc. | 1 | pack | Standard installation accessories |
| 19 | Product manual | Printed version | 1 | copy | Includes full installation, commissioning, and O&M content |
| 20 | Product certificate of conformity | Issued by manufacturer | 1 | copy | Includes factory inspection report |
3.2 Optional Accessories Checklist
| No. | Accessory Name | Function Description | Compatible Models |
|---|---|---|---|
| 1 | Intelligent PDU | Supports per-circuit current monitoring, remote on/off, energy statistics | All series |
| 2 | Conductivity sensor | Real-time monitoring of coolant conductivity, assessing water quality status | All series |
| 3 | 4G wireless communication module | Supports cloud-based remote monitoring, mobile APP alarms | All series |
| 4 | Emergency drainage pump | Automatic drainage upon leakage, reducing leak impact | All series |
| 5 | Antifreeze filling kit | For low-temperature environments, preventing winter pipe freezing | Northern region models |
| 6 | Spare filter element kit | Spare filter elements for Y-type filters, for maintenance replacement | All series |
| 7 | Spare quick couplings | O&M spare parts, in case of coupling damage | All series |
| 8 | UPS backup power supply | Ensures monitoring and alarm system operation during mains power interruption | All series |
| 9 | Cabinet top cable tray | Optimizes top cable routing for easier cable management | All series |
| 10 | Firestop sealing kit | Firestop sealing of cable openings at cabinet bottom | All series |
3.3 Tool Checklist Included with Equipment
| No. | Tool Name | Specification | Qty | Purpose |
|---|---|---|---|---|
| 1 | Hex wrench set | Metric 1.5–10mm | 1 | set |
| 2 | Adjustable wrench | 8-inch, 12-inch | 1 each | set |
| 3 | Phillips/flathead screwdrivers | PH1/PH2, 3mm/6mm | 1 each | set |
| 4 | Digital multimeter | Digital type | 1 | unit |
| 5 | Water pressure gauge | 0–1.0MPa | 1 | unit |
| 6 | Spirit level | 600mm | 1 | unit |
| 7 | Tape measure | 5m | 1 | unit |
| 8 | Wire stripper/crimping tool | 0.5–6mm² | 1 | set |
3.4 Unpacking and Acceptance Instructions
- Upon equipment arrival, unpacking and acceptance inspection must be conducted jointly by representatives of both the supplier and the buyer, verifying that the packing list matches the actual items;
- Inspect the equipment exterior for transport damage such as impact marks, deformation, or paint peeling; check whether glass panels and displays are cracked;
- Check that all interfaces and valves have protective covers and show no signs of leakage;
- Verify that the product model and specifications match the purchase contract;
- After unpacking and acceptance is completed, sign the unpacking acceptance form; if missing parts, damage, or other issues are found, they must be recorded on-site and the manufacturer contacted for resolution;
- After acceptance is completed, properly store equipment accessories, manuals, certificates of conformity, and other documentation for later O&M use.
Chapter 4 Product Operating Principle
4.1 Overall System Operating Principle
The Lain sealed water-cooled integrated cabinet employs the indirect closed-loop circulation principle. The entire system is divided into a primary-side cooling water circuit and a secondary-side coolant circuit, with the two circuits exchanging heat through the plate heat exchanger while remaining independent and non-contacting.
During system operation, the coolant in the secondary-side closed-loop piping is driven by the circulation pump, distributed through the supply manifold to the liquid-cooled cold plates of each IT device, absorbing heat generated by CPU, GPU, memory, and other heat-generating components. The heated coolant is collected through the return manifold and flows into the secondary-side channels of the plate heat exchanger. Simultaneously, primary-side cooling water (supplied by outdoor chillers, cooling towers, or free-cooling sources) flows into the primary-side channels of the plate heat exchanger, exchanging heat with the secondary-side coolant through the plate walls and carrying the heat away. The cooled secondary-side coolant is again delivered by the pump to the IT equipment cold plates, completing one cooling cycle.
The intelligent control system monitors parameters such as secondary-side supply water temperature, return water temperature, flow rate, and pressure in real time. Using a PID algorithm, it automatically regulates the opening of the primary-side electric regulating valve and the secondary-side pump speed, precisely maintaining the secondary-side supply water temperature stable at the setpoint and ensuring IT equipment always operates in the optimal temperature range.
4.2 Core Principles of Closed-Loop Circulation
The defining feature of the closed water-cooling system is that the secondary-side coolant circulates within a completely sealed piping system without direct contact with the atmosphere. Compared to open systems, it offers significant technical advantages:
- Elimination of oxidative corrosion: In the sealed environment, the coolant does not come into contact with atmospheric oxygen, greatly slowing the oxidative corrosion rate of piping and equipment and extending system service life;
- Reduced evaporative loss: With no surface evaporation, coolant loss is extremely low, with annual replenishment of ≤5% under normal operation, substantially reducing maintenance workload;
- Prevention of impurity ingress: The fully sealed system prevents external dust, debris, and microorganisms from entering, avoiding pipe blockage and biological growth and reducing cleaning and maintenance frequency;
- Stable system pressure: Working with the expansion tank, system pressure is stabilized, avoiding pump cavitation and improving operating stability and pump life;
- Suitable for high-floor deployment: Not constrained by open-tank height limitations, enabling deployment on any floor with enhanced adaptability.
4.3 Heat Transfer Process
The entire heat dissipation process comprises three stages of heat transfer, each following thermodynamic heat exchange laws, achieving progressive heat transfer from the IT chip to the outdoor environment:
Stage 1: Chip to Cold Plate (Conduction + Convective Heat Exchange)
Heat from the IT equipment chip surface is conducted through thermal interface material (TIM) to the liquid-cooled cold plate base. The coolant flowing through the micro-channels inside the cold plate carries the heat away through convective heat exchange, achieving chip cooling. The cold plate employs a micro-channel design that increases heat exchange area and turbulence intensity, enhancing heat exchange efficiency and ensuring chip junction temperature is controlled within the design range.
Stage 2: Secondary Side to Primary Side (Indirect Heat Exchange)
The heat-laden secondary-side coolant flows through the plate heat exchanger, transferring heat to the primary-side cooling water through the walls of the stainless steel plates. The herringbone corrugation structure of the plate heat exchanger generates strong turbulence in the fluid even at low flow velocities, greatly enhancing the heat transfer coefficient and achieving efficient indirect heat exchange, with heat exchange terminal temperature difference as low as 1℃.
Stage 3: Primary Side to Outdoor Environment (Heat Rejection)
The heated primary-side cooling water is delivered through piping to the outdoor cold source—such as cooling towers, dry coolers, or chillers—where the heat is released to the outdoor atmosphere. The cooled water then returns to the plate heat exchanger to complete the primary-side cycle. During low-temperature seasons, natural cooling sources can be used directly without operating chillers, achieving ultimate energy savings.
4.4 Intelligent Control Principle
The system uses an industrial-grade PLC as the control core, implementing closed-loop intelligent control of the entire system based on a multi-input multi-output PID control algorithm. Core control logic includes:
Supply Water Temperature Control: Using the secondary-side supply water temperature as the control target, the deviation between measured supply temperature and setpoint is collected, and PID calculations output control signals to regulate the opening of the primary-side electric regulating valve, changing the primary-side cooling water flow rate, thereby keeping the secondary-side supply water temperature stable at the setpoint with control accuracy of ±0.5℃.
Pump Variable-Frequency Control: Using system supply/return differential pressure or total flow as the control target, pump speed is automatically adjusted according to IT load variations. Pump speed is reduced while meeting heat dissipation requirements to reduce pump energy consumption. When load is low, the pump operates at low speed with significant energy savings; when load increases, the pump automatically speeds up to ensure adequate flow.
Pump Redundant Switchover Control: The system monitors the primary pump operating status in real time. When the primary pump experiences faults, overload, dry-running, or other abnormalities, the control system immediately cuts off the primary pump power and starts the standby pump, with switchover time ≤3s, ensuring uninterrupted heat dissipation. After switchover, an alarm is triggered to notify O&M personnel to service the primary pump.
Anti-Condensation Control: The system collects computer room ambient temperature and relative humidity in real time and automatically calculates the dew point temperature. When the supply water temperature approaches the dew point temperature, the supply water temperature setpoint is automatically raised to ensure the supply water temperature always remains more than 1℃ above the dew point temperature, fundamentally preventing condensation on piping and IT equipment surfaces.
Fault Protection Control: The system incorporates multiple layers of fault protection logic. When abnormalities such as leakage, overpressure, low pressure, water shortage, overtemperature, or electrical faults are detected, corresponding protective actions are executed according to fault severity—such as alarm, load reduction, shutdown, valve closure, etc.—preventing fault escalation and ensuring equipment and personnel safety.
4.5 Leak Protection Operating Principle
The system establishes a three-tier leak protection framework of “Prevention – Detection – Response” to comprehensively safeguard fluid circuit safety:
Prevention Tier: All fluid connectors use double-seal design; pipe welding and connections undergo strict pressure testing; high-reliability brand components are selected to reduce leakage probability at the source; piping layout is kept away from electrical equipment; a water-retention containment berm is provided at the bottom so that even minor leakage will not spread.
Detection Tier: Locating-type leak detection cables are deployed at all leak-prone points. In the event of a leak, the detection cable sends a signal to the controller immediately upon liquid contact, precisely locating the leak position with a response time of ≤2 seconds. Additionally, the drip tray is equipped with a level sensor as a backup detection measure.
Response Tier: Upon leak detection, the system immediately triggers audible/visual and remote alarms while automatically executing protective actions: closing the primary-side inlet solenoid valve, stopping the circulation pump, and cutting power to affected areas (optional). This maximally contains the leak scope and prevents damage to IT equipment.
Chapter 5 Product Technical Parameters
5.1 Basic Parameters
| Parameter | LA-SW-30-42 | LA-SW-50-42 | LA-SW-80-47 | LA-SW-120-52 |
|---|---|---|---|---|
| Rated heat dissipation power | 30kW | 50kW | 80kW | 120kW |
| Cabinet specification | 42U standard 19-inch | 42U standard 19-inch | 47U standard 19-inch | 52U standard 19-inch |
| Dimensions (W×D×H) | 600×1200×2000mm | 600×1200×2000mm | 600×1300×2200mm | 800×1300×2400mm |
| Net weight (complete unit) | Approx. 380kg | Approx. 450kg | Approx. 580kg | Approx. 750kg |
| Full-load weight | ≤1500kg | ≤1500kg | ≤1800kg | ≤2200kg |
| Cabinet material | Quality cold-rolled steel plate, electrostatic powder coated | Quality cold-rolled steel plate, electrostatic powder coated | Quality cold-rolled steel plate, electrostatic powder coated | Quality cold-rolled steel plate, electrostatic powder coated |
| Surface treatment | Pickling/phosphating + electrostatic powder coating | Pickling/phosphating + electrostatic powder coating | Pickling/phosphating + electrostatic powder coating | Pickling/phosphating + electrostatic powder coating |
| Protection rating | IP20 (cabinet) / IPX4 (fluid area) | IP20 (cabinet) / IPX4 (fluid area) | IP20 (cabinet) / IPX4 (fluid area) | IP20 (cabinet) / IPX4 (fluid area) |
| Installation method | Floor-standing fixed | Floor-standing fixed | Floor-standing fixed | Floor-standing fixed |
| Color | International gray RAL7035 (customizable) | International gray RAL7035 (customizable) | International gray RAL7035 (customizable) | International gray RAL7035 (customizable) |
5.2 Liquid-Cooling System Parameters
| Parameter | LA-SW-30-42 | LA-SW-50-42 | LA-SW-80-47 | LA-SW-120-52 |
|---|---|---|---|---|
| Cooling method | Closed indirect cold plate | Closed indirect cold plate | Closed indirect cold plate | Closed indirect cold plate |
| Circulation type | Closed forced circulation | Closed forced circulation | Closed forced circulation | Closed forced circulation |
| Secondary-side rated flow rate | 5.2m³/h | 8.6m³/h | 13.8m³/h | 20.7m³/h |
| Secondary-side rated supply/return temperature difference | 5℃ | 5℃ | 5℃ | 5℃ |
| Secondary-side rated supply water temperature | 25–35℃ adjustable | 25–35℃ adjustable | 25–35℃ adjustable | 25–35℃ adjustable |
| Secondary-side working pressure | 0.15–0.35MPa | 0.15–0.35MPa | 0.15–0.35MPa | 0.15–0.35MPa |
| Secondary-side pressure-bearing capacity | 1.0MPa | 1.0MPa | 1.0MPa | 1.0MPa |
| Primary-side rated supply water temperature | 18–30℃ | 18–30℃ | 18–30℃ | 18–30℃ |
| Primary-side rated flow rate | 6.0m³/h | 10.0m³/h | 16.0m³/h | 24.0m³/h |
| Primary-side working pressure | 0.2–0.4MPa | 0.2–0.4MPa | 0.2–0.4MPa | 0.2–0.4MPa |
| Temperature control accuracy | ±0.5℃ | ±0.5℃ | ±0.5℃ | ±0.5℃ |
| Pump configuration | 1+1 redundant, variable-frequency | 1+1 redundant, variable-frequency | 1+1 redundant, variable-frequency | 1+1 redundant, variable-frequency |
| Pump head | 25m | 30m | 35m | 40m |
| Pump power | 0.75kW×2 | 1.5kW×2 | 2.2kW×2 | 3.0kW×2 |
| Heat exchanger type | Brazed plate heat exchanger | Brazed plate heat exchanger | Brazed plate heat exchanger | Brazed plate heat exchanger |
| Heat exchanger material | 316L stainless steel | 316L stainless steel | 316L stainless steel | 316L stainless steel |
| Fluid circuit interface specification | DN25 female thread | DN32 female thread | DN40 female thread | DN50 female thread |
| System water capacity | Approx. 40L | Approx. 60L | Approx. 90L | Approx. 130L |
| Number of branch ports | 12 circuits | 16 circuits | 20 circuits | 24 circuits |
| Branch port specification | G1/2 quick coupling | G1/2 quick coupling | G3/4 quick coupling | G3/4 quick coupling |
5.3 Electrical System Parameters
| Parameter | Technical Specification |
|---|---|
| Rated input voltage | 380V AC ±15%, three-phase five-wire |
| Rated frequency | 50Hz ±5% |
| Total input power | 1.5kW–6.5kW (depending on model) |
| Control circuit voltage | 24V DC |
| Insulation resistance | ≥10MΩ (cold state) |
| Grounding resistance | ≤4Ω |
| Dielectric strength | 1500V AC, no breakdown or flashover for 1min |
| Surge protection | Class C lightning protection, nominal discharge current 20kA |
| PDU rated current | 32A/63A optional |
| PDU socket type | IEC C13/C19 or Chinese standard 10A/16A |
| Power supply redundancy | Supports dual-circuit mains input |
5.4 Monitoring and Alarm Parameters
| Parameter | Technical Specification |
|---|---|
| Controller type | Industrial-grade PLC |
| Display interface | 7-inch color touchscreen |
| Temperature measurement range | -20℃~100℃ |
| Temperature measurement accuracy | ±0.2℃ |
| Pressure measurement range | 0~1.0MPa |
| Pressure measurement accuracy | ±0.5% FS |
| Flow measurement accuracy | ±1% FS |
| Leak detection accuracy | Positioning accuracy ≤1cm, response time ≤2s |
| Communication interfaces | RS485, Ethernet |
| Communication protocols | Modbus-RTU, Modbus-TCP, SNMP |
| Alarm methods | Audible/visual alarm, dry contact alarm, remote alarm |
| Data storage period | ≥12 months |
| Power supply method | Mains powered, supports UPS backup power |
5.5 Environmental Adaptability Parameters
| Parameter | Technical Specification |
|---|---|
| Operating ambient temperature | 5℃~45℃ |
| Storage ambient temperature | -20℃~60℃ |
| Operating ambient humidity | 20%~80% RH (non-condensing) |
| Operating noise | ≤55dB(A) (at 1m from cabinet) |
| Altitude | ≤2000m (derating required above 2000m) |
| Seismic resistance | Intensity level 8 |
| Corrosion protection rating | Class C3 (indoor environment) |
5.6 Performance Specifications
| Parameter | Specification |
|---|---|
| Heat Exchange Efficiency | Plate heat exchanger efficiency ≥95%, system overall heat exchange efficiency ≥90% |
| Temperature Control Accuracy | Secondary side supply water temperature control accuracy ±0.5°C, temperature fluctuation ≤±0.3°C |
| Flow Uniformity | Flow deviation between branches ≤10%, ensuring uniform heat dissipation for all IT equipment |
| Energy Efficiency Ratio | Cooling system COP ≥25, far exceeding traditional air-cooled precision air conditioners |
| Reliability | System Mean Time Between Failures (MTBF) ≥100,000 hours |
| Service Life | Overall equipment design life ≥15 years, pump service life ≥50,000 hours |
6.1 Core Functions
6.1.1 High-Efficiency Liquid Cooling Function
The core function of the product is to provide efficient liquid cooling for high-density IT equipment. A closed-loop water cooling cycle removes heat generated by IT equipment, with single-cabinet cooling capacity covering 30kW–120kW, meeting the heat dissipation requirements of ultra-high-density equipment such as AI servers, GPU clusters, and high-performance computing nodes. Compared to traditional air cooling, heat exchange efficiency is improved by more than 10 times, chip junction temperature is lower, equipment operates more stably, and service life is extended.
6.1.2 Intelligent Temperature Regulation Function
Utilizing a PID intelligent temperature control algorithm, the system automatically adjusts cooling capacity based on IT load variations, precisely controlling supply water temperature. Multiple temperature control modes are supported, including constant supply water temperature mode, constant return water temperature mode, and dew point following mode. Users can select the optimal mode according to actual scenarios. Temperature control accuracy can reach ±0.5°C, preventing temperature fluctuations from affecting IT equipment.
6.1.3 Variable Frequency Pump Energy-Saving Function
The circulating pump adopts variable frequency control and can automatically adjust rotation speed based on system flow requirements, significantly reducing pump energy consumption under low load conditions, saving more than 30% energy compared to fixed-speed pumps. Pump sleep function is also supported — when water temperature falls below the set value, the pump runs at low speed, further reducing energy consumption. Combined with natural cold source utilization, annual cooling energy consumption can be reduced by more than 70%.
6.1.4 Full-Status Monitoring Function
The system is equipped with dozens of sensors, comprehensively monitoring operating parameters including temperature, pressure, flow, liquid level, voltage, current, and liquid leakage. All parameters are displayed in real-time on the touchscreen, allowing operations and maintenance personnel to intuitively grasp the system operating status. Historical data query and trend curve display are supported, facilitating analysis of system operating patterns and identification of potential issues.
6.1.5 Multiple Safety Protection Functions
More than ten safety protection functions are built in, including leak protection, overpressure protection, low-pressure protection, water deficiency protection, overtemperature protection, overload protection, short-circuit protection, lightning protection, and anti-condensation protection, constructing a comprehensive safety protection system to ensure safe operation of the system and IT equipment. Any abnormal condition triggers a timely alarm, and serious faults automatically execute protection actions to prevent accident escalation.
6.1.6 Remote Centralized Monitoring Function
Standard communication protocols are supported, enabling seamless integration with equipment room environment monitoring systems and Data Center Infrastructure Management (DCIM) platforms, realizing centralized monitoring and management of multiple cabinets. Optional cloud monitoring functionality allows real-time viewing of equipment operating status and receiving fault alarms through mobile APP and Web interfaces, enabling unattended operation and maintenance.
6.1.7 Automatic Fault Diagnosis Function
The system includes a built-in fault diagnosis expert database that automatically determines fault type and fault location based on sensor data, displaying fault causes and handling recommendations on the display screen. This helps operations and maintenance personnel quickly locate and resolve issues, reducing fault handling time and lowering maintenance difficulty.
6.1.8 Power-On Auto-Start Function
Equipped with power-loss memory and power-on auto-start functions, all operating parameters and statuses are automatically saved upon utility power interruption. When utility power is restored, the equipment automatically starts according to the set program and resumes normal operation without manual intervention, making it particularly suitable for unattended equipment room scenarios.
6.2 Product Features
6.2.1 Integrated Design, Minimal Deployment
All functional units including the cabinet, CDU, heat exchange, power distribution, and monitoring are highly integrated within a standard cabinet. Factory pre-fabricated and fully tested before shipment, on-site installation only requires connecting the primary side supply/return water pipes and power supply before commissioning. Installation cycle time is reduced by more than 80%. No large-scale equipment room modification is required — the cabinet can directly replace traditional air-cooled cabinets, making it particularly suitable for existing equipment room upgrades.
6.2.2 Fully Closed Loop, Stable and Reliable
The secondary side adopts a completely closed circulation design where coolant does not contact air, fundamentally eliminating oxidation, scaling, and impurity contamination issues. The system maintenance interval is extended to more than 1 year, with a service life of up to 15 years. All liquid path components are manufactured from 304/316L stainless steel, providing corrosion resistance and rust-free operation with stable long-term performance.
6.2.3 Active/Standby Redundancy, High Availability
The circulating pump adopts an active/standby redundant configuration. When the primary pump fails, the standby pump automatically switches over seamlessly in less than 3 seconds, ensuring uninterrupted cooling system operation. Critical sensors and power supply circuits also employ redundant design, so single-point failures do not affect overall system operation. Overall equipment availability reaches 99.99%.
6.2.4 Ultimate Energy Savings, Green and Low Carbon
High-efficiency heat exchange technology combined with variable frequency pumps and natural cold source utilization enables an annual PUE as low as 1.08, reducing cooling energy consumption by more than 70% compared to traditional air cooling. This significantly lowers data center operating costs and supports users in achieving dual-carbon goals. High supply water temperature design is supported to maximize natural cold source utilization and extend natural cooling duration.
6.2.5 Ultra-Low Noise, Environmentally Friendly
IT equipment cooling fans and equipment room air conditioner indoor units are completely eliminated. Cabinet operating noise is below 55dB(A), reducing overall equipment room noise by more than 20dB. This significantly improves the operations and maintenance work environment and reduces occupational health risks from noise, while eliminating the need for dedicated noise reduction facilities, saving construction costs.
6.2.6 Full-Chain Leak Prevention, Worry-Free Safety
A full-chain leak prevention system is constructed from three dimensions: component selection, structural design, and detection protection. Dual-seal quick connectors, full pipeline pressure testing, localized leak detection, and automatic valve shutoff with water cutoff provide multiple safeguards, completely addressing user concerns about water cooling leak risks and enabling confident deployment in core equipment room environments.
6.2.7 Standardized Compatibility, Strong Adaptability
The product adopts a standard 19-inch cabinet structure, compatible with all mainstream brands of cold plate liquid-cooled servers, storage, and network equipment without custom modification. Mixed installation of equipment with different power densities is supported, allowing flexible configuration based on business requirements and protecting user investment. Liquid path interfaces adopt industry standard specifications with strong universality.
6.2.8 Intelligent Operations, Cost Reduction and Efficiency Improvement
Full-parameter intelligent monitoring, automatic fault diagnosis, and remote centralized management significantly reduce operations and maintenance workload and technical barriers, reducing the need for O&M personnel. The system supports predictive maintenance, enabling component life prediction based on operating data, advance maintenance scheduling, avoidance of sudden failures, and reduced maintenance costs.
The Lain closed-loop water-cooled integrated cabinet, with its advantages of high-density heat dissipation, high efficiency, energy savings, and flexible deployment, is widely applied in scenarios requiring high computing power density and high energy efficiency. Core application scenarios are as follows:
7.1 AI Computing Centers
AI large model training and AI inference services require deployment of large numbers of GPU servers, typically with single-cabinet power exceeding 50kW, with some high-density clusters reaching 100kW. Traditional air cooling is completely unable to meet heat dissipation requirements. The closed-loop water-cooled integrated cabinet provides cooling capacity of up to 120kW, perfectly matching high-density GPU cluster deployment, while low PUE characteristics significantly reduce computing center cooling energy consumption and operating costs. It is the preferred cooling solution for AI computing centers.
7.2 High-Performance Computing (HPC) Centers
High-performance computing centers in universities, research institutes, meteorology, petroleum, aerospace, and other fields have high single-cabinet power density with extremely high requirements for equipment operating stability. The closed-loop water-cooled integrated cabinet features strong heat dissipation capability, high temperature control accuracy, and stable operation, ensuring computing nodes can operate at full load for extended periods while reducing cooling system energy consumption, aligned with the green and energy-efficient construction philosophy of research institutions.
7.3 Telecom Operator Data Centers
Core data centers and edge data centers of the three major telecom operators face dual pressures of computing power upgrades and energy saving and carbon reduction. The closed-loop water-cooled integrated cabinet enables rapid upgrades of existing equipment rooms, improving computing power density without modifying the equipment room building structure, while meeting national PUE control requirements for data centers, assisting operators in completing low-carbon transformation.
7.4 Financial Data Centers
Data centers of banks, securities, and insurance companies have extremely high requirements for reliability and security, while facing heat dissipation pressure from growing computing power. The closed-loop water-cooled integrated cabinet’s full-chain leak prevention design, multiple safety protections, and high redundancy configuration meet financial-grade reliability requirements, while improving equipment room computing power density to support fintech business development.
7.5 Enterprise Data Centers
Self-built data centers of large internet companies, manufacturing, and energy enterprises need to balance performance, cost, and deployment efficiency. The closed-loop water-cooled integrated cabinet’s integrated delivery and rapid deployment characteristics significantly shorten project construction cycles, enabling rapid response to business needs, while low long-term operating energy consumption significantly reduces TCO (Total Cost of Ownership).
7.6 Edge Computing Nodes
Edge scenarios such as edge data centers, 5G core equipment rooms, and ETC equipment rooms typically have limited space, no dedicated equipment room air conditioning, and constrained maintenance conditions. The closed-loop water-cooled integrated cabinet features high integration, small footprint, and independent operation capability without requiring room-level air conditioning systems — a complete cooling solution can be achieved with an outdoor dry cooler. This makes it particularly suitable for edge computing node deployment. Additionally, low noise characteristics make it adaptable to edge sites near office environments and residential areas.
7.7 High-Density Server Rooms
In IDC and cloud service provider equipment rooms, the closed-loop water-cooled integrated cabinet can be deployed for high-density server hosting requirements of high-value customers, providing differentiated high-power hosting services and increasing cabinet rental rates and equipment room revenue. Standardized design is compatible with equipment from different customers, allowing flexible scheduling and utilization.
7.8 Special Environment Equipment Rooms
For equipment rooms with strict noise requirements, such as those located within office buildings or research laboratory equipment rooms, the high noise of traditional air cooling can affect office and research environments. The closed-loop water-cooled integrated cabinet operates at ultra-low noise levels, significantly reducing equipment room noise to meet special environmental requirements. Furthermore, for dust-free equipment rooms with high cleanliness requirements, the closed-loop water cooling creates no airflow disturbance, preventing dust from being raised and maintaining equipment room cleanliness.
8.1 Pre-Installation Preparation
8.1.1 Technical Preparation
- Organize construction personnel to become familiar with this manual, construction drawings, and product technical documentation; clarify installation requirements, quality standards, and safety specifications;
- Conduct technical disclosure, explaining construction procedures, key milestones, risk points, and precautions to construction personnel;
- Verify equipment model and specifications match the design plan; confirm site conditions meet installation requirements;
- Prepare construction schedule plan, clarifying time nodes and responsible persons for each process.
8.1.2 Site Preparation
- Equipment room floor must be level and solid, with floor load capacity meeting the full-load weight of the cabinet; floor load-bearing capacity ≥1000kg/m²;
- Equipment room floor must be clean, free of dust, debris, and standing water; decoration work must be completed to prevent dust from entering equipment;
- Confirm cabinet installation position, mark installation reference lines, and reserve sufficient maintenance access: front access ≥1200mm, rear access ≥1000mm, side access ≥600mm;
- Equipment room ambient temperature should be maintained between 5°C and 45°C, humidity 20%–80% RH, no condensation;
- Confirm primary side supply/return water piping has been routed to the vicinity of the cabinet installation position, with interface specifications matching the equipment;
- Confirm power supply has been routed in place, with power capacity, voltage, and phase sequence meeting equipment requirements;
- Confirm grounding system is completed, grounding resistance ≤4Ω, with grounding terminals reserved near the cabinet.
8.1.3 Tools and Materials Preparation
- Installation tools: Forklift, manual hydraulic pallet truck, spirit level, tape measure, plumb bob, wrench set, hex key set, screwdriver set, torque wrench, electric drill, rotary hammer drill, multimeter, megohmmeter, water pressure gauge, pressure test pump, pipe wrench, pipe cutter, deburring tool, etc.;
- Installation materials: Expansion bolts, vibration isolation pads, sealant, PTFE tape, stainless steel pipe fittings, insulation cotton, cable ties, wire number tubes, grounding copper wire, copper lugs, fire-stop putty, etc.;
- Safety protective equipment: Safety helmet, insulated gloves, anti-slip shoes, safety goggles, warning signs, etc.
8.1.4 Equipment Incoming Inspection
- Upon equipment arrival, re-check whether the outer packaging is intact, with no signs of rain exposure or impact damage;
- Upon unboxing, verify equipment model, accessories, and spare parts match the packing list;
- Inspect equipment appearance for dents, deformation, or paint loss; check whether pipe interfaces have protective caps and whether there are any signs of leakage;
- Inspect electrical components and display screen for damage;
- Equipment temporary storage should be placed indoors in a dry, ventilated area free of corrosive gases, avoiding direct sunlight and rain; storage temperature -20°C to 60°C.
8.2 Cabinet Positioning and Securing
8.2.1 Equipment Handling
- Prioritize forklift handling; insert forklift arms into the cabinet base fork pockets, lift and lower slowly, avoiding jolts;
- When a forklift is unavailable, use a manual hydraulic pallet truck, placing wooden boards underneath to distribute pressure;
- Keep the cabinet upright during handling; tilt angle must not exceed 15°; tipping over or laying flat is strictly prohibited;
- Pay attention to avoiding walls, door frames, and other obstacles during handling to prevent equipment collision damage;
- When multiple personnel handle the cabinet collaboratively, unified command and synchronized actions are required to prevent personal injury and equipment damage.
8.2.2 Positioning and Alignment
- Push the cabinet to the predetermined installation position, adjust position against the installation reference lines to ensure cabinets are neatly arranged and aligned with other cabinets;
- Adjust the adjustable leveling feet at the cabinet base, using a spirit level to calibrate cabinet levelness and plumbness:
- Levelness deviation ≤1mm/m;
- Verticality deviation ≤1.5mm/m;
- When installing multiple cabinets side by side, adjust cabinet spacing to ensure uniform gaps between cabinets, gap ≤2mm, with tops and fronts flush;
- After adjustment, lock the leveling feet nuts to ensure the cabinet is stable and free of wobble.
8.2.3 Cabinet Securing
- For equipment rooms with seismic requirements, use expansion bolts to secure the cabinet base to the floor;
- Mark drilling positions at the base mounting holes, move the cabinet aside, then drill holes using a rotary hammer drill; hole diameter and depth must match expansion bolt specifications;
- Insert expansion bolts, reposition the cabinet, insert bolts and tighten; tightening torque must comply with specification requirements;
- When multiple cabinets are installed side by side, use cabinet connecting bolts to secure adjacent cabinet columns together, ensuring overall stability;
- After securing, re-check levelness and verticality to confirm no changes have occurred.
8.3 Primary Side Water Pipeline Connection
8.3.1 Pipeline Connection Requirements
- Primary side supply and return water piping should use galvanized steel pipe, 304 stainless steel pipe, or PPR pipe; pipeline specifications must match equipment interfaces;
- Before pipeline installation, clean internal debris and rust from piping to ensure cleanliness;
- Pipeline connections must be secure and sealed with no leakage; wrap PTFE tape for threaded connections, install sealing gaskets for flange connections;
- Piping should be independently supported; piping weight must not be borne by equipment interfaces to avoid interface stress damage;
- Install air vent valves at the highest points of piping and drain valves at the lowest points;
- Wrap insulation cotton around the external surface of piping, thickness ≥20mm, with well-sealed joints to prevent condensation and cooling capacity loss.
8.3.2 Connection Procedure
1. Remove protective caps from equipment primary side supply and return water interfaces; inspect threads for integrity and foreign matter;
2. Install unions or flexible connections at equipment interfaces for ease of later maintenance and disassembly;
3. Sequentially connect valve group components including valves, filters, electric regulating valves, pressure gauges, and thermometers;
4. Connect to the equipment room main supply and return water piping; route piping level and vertical, secure firmly;
5. Supply and return water piping should be clearly labeled to prevent reversed connection;
6. Wrap PTFE tape on all threaded connections; tighten with moderate force to avoid thread stripping and interface cracking.
8.3.3 Pipeline Pressure Testing
1. After pipeline connection is complete, close equipment-side valves and conduct hydrostatic pressure testing on the primary side external piping;
2. Test pressure is 1.5 times the working pressure, and not less than 0.6MPa;
3. Slowly raise pressure to the test pressure, hold for 24 hours; pressure drop ≤1% is acceptable;
4. Inspect all interfaces, welds, and valves for leakage; if leakage is found, relieve pressure, address the issue, and re-test;
5. After successful pressure testing, reduce pressure to working pressure and maintain this state pending subsequent system commissioning.
8.4 Secondary Side Liquid Path System Inspection and Connection
8.4.1 Internal Liquid Path Inspection
1. Open the cabinet door and inspect internal piping, valves, pumps, heat exchangers, manifolds, and other components for integrity and transport loosening;
2. Inspect all joints and flanges for tightness and signs of leakage;
3. Inspect valve positions, confirming air vent valves and drain valves are in the closed position and system main valves are in the open position;
4. Inspect quick connectors for integrity and verify dust caps are complete.
8.4.2 IT Equipment Liquid Path Connection
1. After IT equipment is installed in position, connect liquid cooling quick connectors;
2. Before connection, inspect male and female connectors for foreign matter or damage, and verify sealing rings are intact;
3. Align connectors and insert smoothly; a “click” sound indicates full engagement; gently pull to confirm connector will not detach;
4. Strictly connect supply and return water according to labels; reversed connection is prohibited;
5. After connection, inspect joint areas for leakage; if leakage is found, disconnect, reconnect, and replace sealing rings;
6. After all branch connections are complete, open branch valves one by one and observe for any abnormalities.
8.5 Grounding System Installation
8.5.1 Grounding Requirements
- Cabinet grounding must be reliable, with grounding resistance ≤4Ω, complying with GB 50174 “Data Center Design Specification”;
- All metal components, electrical equipment enclosures, and shielding layers of the cabinet must be reliably grounded;
- Grounding wire shall be stranded copper-core insulated wire, cross-sectional area ≥35mm², yellow-green dual color;
- Grounding connections must be secure with good contact; daisy-chain grounding is prohibited;
- Grounding wire must not be connected to water pipes, air ducts, or other piping, and must not be mixed with lightning protection grounding.
8.5.2 Installation Procedure
1. Securely fix the grounding copper busbar to the cabinet base columns;
2. Use yellow-green dual color grounding copper wire to connect all cabinet metal components and electrical equipment enclosures to the grounding copper busbar;
3. Bridge cabinet doors and cabinet body with copper braided straps to ensure grounding continuity;
4. Use a grounding cable to connect the cabinet grounding copper busbar to the equipment room grounding busbar; terminal connections use copper lugs crimped and secured with bolts;
5. After installation, measure grounding resistance with a grounding resistance tester, confirming ≤4Ω;
6. Use a multimeter to measure continuity between each metal component and the grounding copper busbar, confirming no open circuits.
8.6 Pipeline Insulation and Protection
- All exposed cold water piping, valves, and heat exchanger surfaces must be wrapped with insulation cotton;
- Insulation cotton shall be closed-cell rubber-plastic material, thickness ≥20mm, thermal conductivity ≤0.034W/(m·K);
- Insulation cotton joints shall be bonded with specialized adhesive and sealed externally with aluminum foil tape, ensuring no exposed areas;
- Thermal bridge treatment shall be applied at pipeline support locations to prevent condensation from cold bridges;
- The cabinet base water collection pan shall be installed in position, with leak detection cable laid flat, covering all leakage-prone points.
8.7 Installation Quality Inspection
After installation, perform installation quality self-inspection according to the following items. Only after all items pass may the wiring and commissioning phase begin:
| Inspection Item | Requirement |
|---|---|
| Cabinet position, levelness, verticality | Meet requirements, securely fixed, no wobble |
| Pipeline connections | Correct, no reversed connections, supports secure, no interface leakage |
| Valves | Operate smoothly, clearly labeled, correct position |
| Insulation | Complete, no exposed areas, neat appearance |
| Grounding system | Reliable, grounding resistance meets requirements |
| Leak detection system | Laid in position, connections normal |
| Equipment appearance | Intact, no impact damage, no debris inside |
| Safety protection devices | All installed in position, functional |
9.1 General Wiring Requirements
- All wiring work must be performed by certified electricians, strictly following electrical safety operating procedures; work with power disconnected; live wiring is strictly prohibited;
- Before wiring, carefully verify electrical schematic diagrams and wiring diagrams, confirming wire numbers, terminals, and voltage levels match;
- Cable selection must meet design requirements; power cables, control cables, and signal cables must be routed separately to avoid electromagnetic interference;
- Terminal connections must be crimped securely with good contact, no loose or false connections; stranded wires must be terminated with ferrules before connecting to terminal blocks;
- Wiring shall be neat and organized, level and vertical, tied and secured, clearly labeled; wire number tube specifications uniform with legible, fade-resistant markings;
- Power (high voltage) and weak current (low voltage) circuits must maintain spacing ≥200mm; when crossing, cross at right angles; parallel routing is prohibited;
- All exposed live parts must have insulation protection to prevent electric shock hazards;
- After wiring is complete, continuity testing and insulation testing must be performed; power may only be applied after confirmation of no errors.
9.2 Main Power Supply Wiring
9.2.1 Cable Selection
- Three-phase five-wire input; cables shall be copper-core PVC insulated power cables;
- Cable cross-sectional area calculated based on total equipment power, ensuring cable temperature rise does not exceed allowable limits at full load, voltage drop ≤5%;
- LA-SW-30 model: Main cable ≥4mm² × 5 cores;
- LA-SW-50 model: Main cable ≥6mm² × 5 cores;
- LA-SW-80 model: Main cable ≥10mm² × 5 cores;
- LA-SW-120 model: Main cable ≥16mm² × 5 cores.
9.2.2 Wiring Procedure
1. Confirm the equipment room main power supply is in the OFF position; verify no voltage with a voltage tester;
2. Route the main power cable through the cable entry hole at the cabinet base, installing a rubber grommet to protect the cable;
3. Connect cable phase conductors (L1, L2, L3), neutral (N), and ground (PE) to the corresponding incoming terminals of the main circuit breaker;
4. Tighten terminal bolts to the required torque, ensuring good contact;
5. Leave appropriate excess cable length inside the cabinet, secure with ties, and label clearly;
6. Verify phase sequence to ensure correct three-phase rotation; a phase sequence meter may be used.
9.2.3 Precautions
- Power supply voltage must match the equipment rated voltage, with fluctuation range within ±15%;
- Neutral and ground wires must be strictly separated; they must not be mixed; the ground wire must not be connected to neutral;
- Incoming cables must be securely fixed to prevent cable tension from pulling terminals loose;
- When multiple devices share a power source, each device must have its own dedicated switch; series connection is prohibited;
- After power wiring is complete, measure insulation resistance at the incoming terminals; insulation resistance between phases and between phases to ground ≥10MΩ is acceptable.
9.3 Pump Circuit Wiring
9.3.1 Main Circuit Wiring
- Route wiring from the main circuit breaker output terminals to the variable frequency drive (VFD) input terminals; cable cross-sectional area must match pump power;
- Connect VFD outputs to the primary pump and standby pump motors respectively; interlock the electrical circuits to prevent both pumps from starting simultaneously;
- Pump motor enclosures must be reliably grounded;
- Pay attention to motor rotation direction during wiring, ensuring pump rotation matches the direction indicated by the label.
9.3.2 Control Circuit Wiring
- Connect VFD control terminals to the PLC controller for receiving start/stop and speed regulation signals, and feeding back running and fault signals;
- Connect pump outlet pressure sensor signals to PLC analog input modules;
- Connect pump thermal relay normally-closed contacts into the control circuit for automatic shutdown on overload;
- All control cables shall be shielded cable with shielding layer grounded at one end only.
9.4 Sensor and Actuator Wiring
9.4.1 Temperature Sensor Wiring
- Temperature sensors use PT100 platinum resistance, three-wire connection;
- Connect the three sensor wires to the corresponding PLC analog module terminals, with correct wire color correspondence;
- For long cable runs, compensation wire shall be used to reduce measurement error;
- Sensor probes must be installed in position, in full contact with the measured medium, and securely fastened.
9.4.2 Pressure/Flow Sensor Wiring
- Power supply: 24V DC; two-wire or three-wire configuration;
- Connect power positive, signal positive, and power negative to corresponding terminals; positive and negative must not be reversed;
- Sensor shielding layer must be reliably grounded to avoid signal interference;
- Pay attention to flow direction labels during installation; reverse installation is prohibited.
9.4.3 Electric Regulating Valve Wiring
- Connect electric actuator power, control signal, and feedback signal to corresponding terminals;
- Analog control signals shall use shielded cable to reduce interference;
- After wiring, manually test valve opening/closing action to confirm correct direction and accurate feedback.
9.4.4 Leak Detection Wiring
- Leak controller power supply: 24V DC, connected to control power supply;
- Connect both ends of the leak detection cable to the controller input terminals; extension cables shall use dedicated connection cables;
- Connect alarm output dry contacts to PLC alarm inputs;
- Detection cable must be laid flat, must not be submerged in water, and must not contact metal directly.
9.5 Monitoring and Communication Wiring
9.5.1 Touchscreen Wiring
- Touchscreen power supply: 24V DC, connected to the switching power supply output;
- Communication cable shall use shielded network cable or RS485 bus, connected to the PLC communication port;
- Communication A and B wires must be correctly matched; shielding layer grounded at one end only;
- Mount the touchscreen on the cabinet front door; organize wiring neatly to avoid affecting door operation.
9.5.2 Remote Communication Wiring
- Connect Ethernet interface to the equipment room LAN; use shielded network cable of Cat5e or higher;
- Connect RS485 bus to the environment monitoring system; bus shall be daisy-chained with terminating resistors;
- Communication cables and power cables must be routed separately to avoid interference;
- After wiring, test communication connectivity to ensure normal data transmission.
9.6 PDU and IT Equipment Power Distribution Wiring
- PDU power is drawn from the main power distribution unit, controlled by an independent circuit breaker;
- Mount PDUs on the rear columns of the cabinet at appropriate heights for convenient equipment plug-in;
- Dual-circuit PDUs shall be connected to different power supply circuits for redundant power supply;
- IT equipment power cables plug into PDU outlets, secured neatly with excess cable slack for plugging/unplugging;
- All outlets shall be clearly labeled with corresponding equipment numbers for operations and maintenance management.
9.7 Alarm System Wiring
- Install the audible and visual alarm at a prominent position on top of the cabinet; connect power and alarm signals to the PLC;
- Route remote alarm dry contacts to the equipment room monitoring system;
- Optional SMS alarm module: insert SIM card and connect to the controller communication port;
- Test alarm functions to confirm audible, visual, and signal outputs are normal.
9.8 Wiring Inspection and Testing
9.8.1 Visual and Continuity Inspection
- Check all wiring for firmness, terminal tightness, and clarity/correctness of wire numbers;
- Check wiring neatness, separation of high and low voltage circuits, and completeness of labeling;
- Verify wiring against drawings circuit by circuit, confirming no incorrect or missing connections;
- Check all exposed live parts for insulation protection and grounding reliability.
9.8.2 Insulation Resistance Testing
1. Disconnect power to all low-voltage modules and sensors to prevent test voltage from damaging electronic components;
2. Use a 500V megohmmeter to measure power circuit insulation resistance; insulation resistance between phases, phase-to-ground, and phase-to-neutral ≥10MΩ;
3. Control circuit insulation resistance ≥2MΩ;
4. If insulation test fails, investigate section by section to identify the cause; power may only be applied after passing.
9.8.3 Grounding Continuity Testing
- Measure resistance between cabinet metal components, electrical equipment enclosures, and the grounding terminal: should be ≤0.1Ω;
- Measure resistance between the cabinet grounding terminal and the equipment room grounding busbar: should be ≤0.5Ω;
- Confirm the grounding system conducts properly with no open circuits or loose connections.
10.1 Pre-Commissioning Preparation
10.1.1 Condition Confirmation
- Installation and wiring work fully completed, self-inspection passed;
- Equipment room environment meets operating requirements: temperature 5–45°C, humidity 20–80% RH, no condensation;
- Primary side cooling water supply is normal; supply water temperature, pressure, and flow meet equipment requirements;
- Power supply is normal; voltage, phase sequence, and frequency meet requirements;
- Grounding system passes inspection; grounding resistance ≤4Ω;
- Commissioning tools are complete: multimeter, clamp ammeter, water pressure gauge, thermometer, laptop computer, etc.;
- Commissioning personnel are familiar with equipment principles and operating procedures, equipped with safety protective equipment;
- Emergency supplies are available on site: towels, water buckets, leak plugging tools, fire extinguishers, etc.
10.1.2 System Status Inspection
- Inspect all valve positions: main valves open, branch valves open according to connection status, drain valves and air vent valves closed;
- Inspect pumps, heat exchangers, and piping connections for integrity and any signs of leakage;
- Inspect electrical system — all switches in the OFF position, VFD and controller without alarms;
- Inspect expansion tank pressure; pre-charge pressure meets requirements;
- Clear debris from inside the cabinet, remove all tools, and close the cabinet door.
10.1.3 Safety Precautions
- Commissioning process strictly follows procedures; dedicated supervision with clear division of responsibilities;
- Live work requires a minimum of two people, one operator and one safety observer;
- During pressurization and water flow operations, closely monitor pipeline status; stop immediately and relieve pressure for handling if leakage is found;
- Pumps must be vented before startup to prevent dry running that could damage mechanical seals;
- Maintain detailed records throughout commissioning, including parameters, times, abnormal conditions, and corrective actions taken.
10.2 Electrical System No-Load Commissioning
10.2.1 Control Circuit Power-On
1. Disconnect all power circuit switches; close only the control power switch;
2. Check controller, touchscreen, and sensor power supply — verify indicator lights illuminate;
3. Check touchscreen display for normal operation and absence of fault alarms;
4. Check sensor readings for reasonable values and absence of abnormal fluctuations;
5. Test all switches and buttons for functionality and correct response.
10.2.2 Single-Point Function Testing
- Manually test electric regulating valve opening/closing action, confirming correct direction, smooth operation, no sticking, and accurate feedback signals;
- Manually test pump contactor pickup and dropout actions, confirming interlock function operates normally;
- Test audible/visual alarm function by simulating fault signals, confirming alarms trigger correctly;
- Test leak detection function by touching the detection cable with a damp tissue, confirming alarm and interlock actions operate normally;
- Test protection functions by simulating overload, overtemperature, low-pressure, and other signals, confirming protection actions operate correctly.
10.2.3 Parameter Setting
1. Set secondary side supply water temperature setpoint according to design requirements, typically 28–32°C;
2. Set pump pressure/flow setpoints and PID parameters;
3. Set temperature, pressure, and flow alarm thresholds;
4. Set pump switching time and rotation cycle;
5. Set communication parameters, address, baud rate, etc.;
6. Record and archive all parameter settings after completion.
10.3 Liquid Path System Filling and Venting
10.3.1 Coolant Preparation
- Recommended secondary side coolant: high-purity deionized water, conductivity ≤10μS/cm;
- For low-temperature environments, antifreeze must be added: use ethylene glycol type antifreeze; mixing ratio determined by minimum ambient temperature;
- Use of untreated water such as tap water or well water is prohibited to prevent scaling, corrosion, and microbial growth;
- Coolant quantity based on system water capacity, with an additional 10% margin prepared.
10.3.2 System Filling
1. Close secondary side branch valves, open main pipeline valves;
2. Slowly inject coolant from the system fill port while opening the highest-point air vent valve to release air;
3. Fill slowly to avoid introducing large amounts of air with fast water flow;
4. Observe the expansion tank liquid level; stop filling when the level reaches the normal level;
5. Close the air vent valve and let the system stand for 30 minutes to allow air to fully rise.
10.3.3 System Venting
1. Jog the pump — run for 5–10 seconds, then stop — to promote air flow to high points within the piping;
2. Open the air vent valve again to vent until continuous liquid flow with no bubbles is observed;
3. Repeat the jog-and-vent operation 3–5 times to completely remove air from the system;
4. Observe the expansion tank liquid level; replenish coolant promptly when the level drops;
5. After venting is complete, confirm system pressure is stable between 0.15–0.35MPa.
10.4 Individual Pump System Commissioning
10.4.1 Primary Pump Commissioning
1. Confirm the system is fully filled with water and venting is complete;
2. Manually start the primary pump; observe whether pump rotation direction is correct and whether there is abnormal noise or vibration;
3. Measure pump current and voltage, confirming they are within rated range;
4. Observe system pressure and flow values, confirming they reach design values;
5. Adjust pump speed and observe whether pressure and flow changes are smooth and responsive;
6. Run the pump continuously for 30 minutes; check for leakage and verify bearing temperature is normal (≤70°C); operation should be smooth without abnormalities.
10.4.2 Standby Pump Commissioning
1. Stop the primary pump and switch to standby pump operation;
2. Repeat the above primary pump test items to confirm normal standby pump operation;
3. Test automatic switching function: simulate primary pump failure, confirm standby pump starts automatically, switching time ≤3s;
4. Test pump rotation function: set rotation time, verify timed automatic switching operates correctly;
5. Both pumps operated individually; parameter deviation ≤5% is acceptable.
10.5 Heat Exchange System Commissioning
10.5.1 Primary Side Water Flow
1. Slowly open the primary side supply water valve to fill and vent the primary side piping;
2. After venting is complete, fully open supply and return water valves;
3. Check primary side pressure and temperature for normal values and inspect piping for leakage;
4. Confirm primary side supply water temperature meets design requirements.
10.5.2 Temperature Control Commissioning
1. After the system is operating stably, observe secondary side supply water temperature changes;
2. Check whether the electric regulating valve automatically adjusts opening based on temperature, with smooth action;
3. When temperature approaches the setpoint, observe temperature control accuracy, confirming fluctuation ≤±0.5°C;
4. Modify the temperature setpoint and observe system response speed and regulation performance;
5. Fine-tune PID parameters for optimal temperature control without overshoot or oscillation.
10.5.3 Anti-Condensation Function Commissioning
1. Verify ambient temperature/humidity and dew point temperature calculations are accurate;
2. Simulate high-humidity low-temperature conditions by lowering supply water temperature to verify anti-condensation protection triggers;
3. Confirm supply water temperature automatically raises, always remaining more than 1°C above dew point temperature;
4. Inspect pipeline surfaces for any condensation phenomena.
10.6 Branch Flow Balancing Commissioning
- Open each branch valve one by one, observing flow indicators on each branch;
- Adjust branch valve openings to achieve uniform flow across all branches, flow deviation ≤10%;
- For branches with different loads, adjust flow according to equipment heat dissipation requirements;
- After flow balancing is complete, mark valve openings and prohibit unauthorized adjustment;
- Inspect all branch joints for leakage and confirm IT equipment cold plates operate normally.
10.7 System Integrated Commissioning
1. After all subsystem commissioning is complete, conduct whole-machine integrated operation testing;
2. Set to automatic operation mode and observe whether system automatic control logic is correct;
3. Simulate load changes and observe whether pump speed and valve openings automatically follow adjustments;
4. Run continuously for 2 hours, recording all operating parameters including supply/return water temperature, pressure, flow, pump current, and ambient temperature;
5. Inspect all components for operating status — no abnormal noise, vibration, leakage, or overtemperature;
6. Verify alarm protection functions by simulating various faults and confirming correct alarm and protection actions.
10.8 Full-Load Testing
1. Power on all IT equipment and operate at full load, bringing heat dissipation load to rated value;
2. Run the system continuously for 72 hours, recording operating parameters every 2 hours;
3. Test criteria:
| Test Item | Requirement |
|---|---|
| Secondary side supply water temperature | Stable at setpoint, accuracy ±0.5°C |
| IT equipment chip temperature | Within normal range, no overtemperature alarms |
| System pressure | Stable, no significant fluctuation |
| Pump operation | Smooth, no abnormal noise, bearing temperature normal |
| All piping and joints | No leakage |
| Condensation | No condensation phenomenon |
| Equipment operating noise | ≤55dB(A) |
4. No abnormalities during 72-hour full-load testing with all indicators meeting standards — commissioning is deemed qualified.
10.9 Monitoring System Integrated Commissioning
- Commission communication connection between equipment and equipment room environment monitoring system;
- Confirm all monitoring data uploads correctly with accurate, real-time data;
- Confirm remote alarm functions operate normally; alarm information synchronizes to the monitoring platform;
- Test remote control functions (if authorized), confirming command response is normal;
- Save communication configuration parameters and hand over to operations and maintenance personnel.
11.1 Installation Precautions
- Equipment installation must be performed by professional personnel, strictly following this manual and applicable specifications; non-compliant construction is strictly prohibited;
- Equipment must not be installed in environments with corrosive gases, flammable/explosive gases, excessive dust, or damp/water-logged conditions;
- Installation location must reserve sufficient maintenance space; operating panels and maintenance areas must not be obstructed;
- During pipeline welding operations, protective measures must be taken to prevent weld spatter from reaching equipment components and electrical elements;
- Forced connection of equipment interfaces is strictly prohibited; piping must not bear additional stress to prevent interface cracking and leakage;
- During insulation work, open flames are strictly prohibited, keep away from electrical equipment, and take fire prevention measures;
- During installation, all liquid path interfaces must remain capped to prevent foreign matter from entering the system;
- When winter construction ambient temperature is below 5°C, anti-freeze measures must be taken; after construction, promptly drain pipeline water to prevent freezing damage.
11.2 Wiring Precautions
- Electrical wiring must be performed by certified electricians, strictly following electrical safety regulations; work with power disconnected and warning signs posted;
- Before wiring, confirm power supply voltage matches equipment rated voltage to avoid burning out equipment from incorrect voltage connection;
- Cables must match load current; using undersized cable for large loads is strictly prohibited to prevent overheating and fire;
- Terminal crimping must be secure; inserting stranded wires directly into terminals without ferrules is strictly prohibited to prevent loose connections and overheating;
- High-voltage and low-voltage circuits must be routed separately; sharing the same conduit or duct is prohibited to prevent electromagnetic interference causing control failure;
- Grounding must be reliable; failure to ground or false grounding is strictly prohibited to prevent electric shock hazards and static damage to electronic components;
- Insulation testing must be performed before power-on; powering on with failed insulation is strictly prohibited;
- Unauthorized modification of electrical circuits or replacement of component specifications is strictly prohibited; contact the manufacturer’s technical support if changes are needed.
11.3 Commissioning Precautions
- Before commissioning, confirm installation and wiring are fully complete and self-inspection has passed; commissioning during installation is strictly prohibited;
- Before pump startup, confirm the system is fully filled with water and air is vented; dry running is strictly prohibited as it will damage mechanical seals;
- During hydrostatic pressure testing, pressure must be raised slowly; overpressure is strictly prohibited; personnel must not stand directly facing interfaces or welds during testing;
- System filling must use qualified coolant; use of tap water or wastewater is strictly prohibited to prevent blockage and system corrosion;
- If abnormal conditions such as leakage, abnormal noise, or unusual odors are found during commissioning, stop immediately for inspection; continue only after fault resolution;
- Parameter setting must be performed by professional personnel; unauthorized modification of protection thresholds or control parameters is strictly prohibited to prevent protection failure;
- During full-load testing, personnel must be on duty with periodic inspections; unattended long-duration operation is not permitted;
- After commissioning is complete, all parameters should be locked with operation permission levels set to prevent unauthorized personnel from making operational errors.
11.4 Safety Notes for Operation
- During equipment operation, the equipment room environment should be maintained within the specified range, avoiding operation in high-temperature or high-humidity environments.
- The system operating pressure should be maintained between 0.15-0.35MPa. If abnormal pressure occurs, inspect and address it promptly.
- Regularly observe the expansion tank liquid level. If the liquid level is too low, promptly replenish with the same type of coolant.
- Strictly avoid frequent starting and stopping of the water pump. The interval between starts and stops should be no less than 5 minutes to prevent impact damage to components.
- If there is a sudden water supply interruption during operation, immediately stop the water pump, close the primary side valves, and restart gradually after water supply is restored.
- When the equipment room is unattended for a long time, remote alarms should be set up to ensure that faults can be promptly notified to operation and maintenance personnel.
- During hot and humid summer seasons, strengthen condensation checks and appropriately increase the supply water temperature to prevent condensation.
- Do not open the cabinet door arbitrarily during equipment operation to avoid affecting airflow, temperature, and humidity, and also to prevent electric shock risks.
11.5 Safety Notes for Maintenance
- Maintenance must be carried out after the equipment is stopped, powered off, water supply is cut off, and pressure is released. Repair work with power or pressure applied is strictly prohibited.
- Maintenance operations must be performed by trained professionals familiar with the equipment structure and operating methods.
- Before disassembling liquid circuit components, the coolant in the corresponding pipeline must be drained, and preparations should be made to collect water to prevent coolant from splashing onto electrical equipment.
- When replacing spare parts such as filter cartridges and sealing rings, genuine original spare parts must be used. Using unqualified substitutes is prohibited.
- After disassembling liquid circuit components, seal the interfaces promptly to prevent foreign matter from entering the system.
- During electrical maintenance, verify that the power is disconnected using a voltage tester, and wear insulating protective equipment.
- Calibrate sensors regularly to ensure accurate monitoring data and avoid false alarms or missed alarms.
- After maintenance work is completed, a comprehensive inspection must be conducted to confirm that no tools or debris are left inside the equipment before powering on and running water for a trial operation.
11.6 Safety Precautions
- It is strictly forbidden to pile flammable and explosive items near the equipment. Fire-fighting equipment must be provided, complying with fire safety requirements.
- It is strictly forbidden to operate electrical equipment with wet hands to prevent electric shock.
- In the event of an electrical fire in the equipment, first cut off the power supply, and use a dry powder fire extinguisher. Using water to extinguish the fire is strictly prohibited.
- In the event of a coolant leakage accident, first cut off the water source and power supply before cleaning up to prevent liquid from contacting live parts.
- Avoid coolant contact with skin and eyes. If accidental contact occurs, immediately rinse thoroughly with plenty of clean water. Seek medical attention if severe.
- It is strictly forbidden to stand on or place heavy objects on the equipment to prevent cabinet deformation and component detachment.
- In case of equipment failure, promptly contact professionals for repair. It is strictly forbidden to disassemble core components without authorization.
- Conduct regular safety inspections, promptly eliminate safety hazards, and ensure the safe operation of the equipment.
12.1 General Principles of Maintenance
- To ensure the long-term stable and reliable operation of the closed-loop water-cooling integrated cabinet and extend the equipment’s service life, a comprehensive maintenance system must be established, and preventive maintenance must be carried out regularly.
- Maintenance work should follow the principle of “prevention first, combining prevention and remedy,” with daily inspections as the foundation, regular maintenance as the focus, and fault repair as a supplement.
- All maintenance work must be strictly carried out in accordance with these procedures. Maintenance records should be kept, and equipment operation and maintenance archives should be established.
- Maintenance personnel must receive professional training and be familiar with the equipment structure, principles, operating methods, and safety regulations.
- Spare parts should be stocked as required, and wearing parts should be procured in advance to shorten fault repair time.
12.2 Daily Inspection (Daily)
Daily routine inspections are carried out by operation and maintenance personnel once a day, checking and recording the following:
- Operating Status Check: Check if the touchscreen display is normal, if there are any alarm messages, and if the system operation mode is correct.
- Parameter Check: Record secondary side supply/return water temperature, pressure, flow, primary side supply/return water temperature, ambient temperature and humidity, confirming parameters are within the normal range.
- Water Pump Check: Listen to the water pump operating sound for any abnormalities, check for unusual noise or vibration, and touch the motor housing to check if the temperature is normal.
- Leak Check: Inspect pipelines, valves, joints, heat exchangers, water pumps, etc., for any signs of leakage, and check for water accumulation at the bottom of the cabinet.
- Leak Detection Check: Verify that the leak detection system status is normal, with no alarms.
- Electrical Distribution Check: Inspect the electrical distribution cabinet for any unusual smells or sounds, ensure indicator lights are normal, and current and voltage are within normal ranges.
- Environment Check: Ensure the computer room temperature and humidity are normal, free from water accumulation and debris, and well-ventilated.
12.3 Monthly Maintenance
A comprehensive maintenance is performed once a month, including:
- Cleaning and Dust Removal:
- Clean the external surface of the cabinet and the display screen to keep them neat and tidy.
- Clean the dust inside the cabinet, focusing on electrical components, controllers, and cooling fans.
- Clean debris from the surface of the filter cartridge and check the pressure differential value.
- Clean debris and water accumulation at the bottom of the cabinet to keep it dry and clean.
- Tightening Inspection:
- Check and tighten all electrical wiring terminals to prevent loosening and overheating.
- Check the tightness of pipeline joints, flange bolts for any loosening or leakage.
- Check the cabinet fixing bolts and component mounting screws to ensure they are secure.
- Functional Check:
- Test whether the audible and visual alarm functions are working correctly.
- Check the automatic water pump switching function by manually switching the main and standby pumps to ensure the standby pump is operational.
- Check whether the electric control valve operates smoothly without sticking.
- Check the leak detection function by simulating a leak to test if the alarm is triggered correctly.
- Verify sensor values against on-site instruments to confirm data accuracy.
- Liquid Circuit Check:
- Check the expansion tank liquid level, replenish with qualified coolant if insufficient.
- Check if the system pressure is normal. If low, investigate the cause and address it.
- Open the vent valve for one manual venting operation to remove accumulated air from the system.
- Check the insulation layer for any damage or detachment, and repair promptly.
- Record Filing: Record all maintenance items and parameters for archival purposes.
12.4 Quarterly Maintenance
An in-depth maintenance is performed quarterly, adding the following to the monthly maintenance items:
- Water Pump Maintenance:
- Check the water pump mechanical seal for leakage. If leakage exceeds the limit, replace the seal.
- Check the water pump vibration dampeners for aging or damage, replace if necessary.
- Measure the three-phase current of the water pump to confirm balance, with deviation ≤5%.
- Apply lubricating grease to the water pump bearings (according to manufacturer requirements).
- Filter Maintenance:
- Disassemble the Y-type filter cartridge and thoroughly clean internal impurities.
- Check the filter cartridge for damage or blockage, replace if damaged.
- After cleaning, reassemble and check that the seal is good and there is no leakage.
- Valve Maintenance:
- Operate all valves (open/close) to check flexibility, and apply lubricating grease to valve stems.
- Check valve sealing performance. If internal leakage is severe, replace the valve core or the entire valve.
- Check if the safety valve’s actuation pressure is accurate and calibrate regularly.
- Electrical Maintenance:
- Check the surge protector status, replace promptly if failed.
- Check circuit breakers and contactor contacts for burning or pitting. Address or replace if poor contact.
- Check the grounding system, test ground resistance, and ensure reliability.
- Tighten the wiring terminals on the frequency converter and clean dust from its heat sink.
- Water Quality Check:
- Extract a coolant sample to test conductivity and pH value.
- If conductivity exceeds the standard, analyze the cause and replace the coolant if necessary.
- Check for signs of microbial growth or scaling.
12.5 Annual Maintenance
A comprehensive overhaul and maintenance is performed annually by professional technical personnel, including:
- Heat Exchanger Cleaning:
- Disassemble the plate heat exchanger for chemical or physical cleaning to remove scale and impurities, restoring heat exchange performance.
- Check plates for corrosion, deformation, cracks, and check gaskets for aging or failure.
- After reassembly, perform a pressure test to confirm there is no leakage.
- System Comprehensive Cleaning:
- Drain the system coolant, add cleaning solution for circulation cleaning to remove dirt from the inner walls of the pipelines.
- Rinse repeatedly with clean water until the discharged water is clean.
- Refill with new qualified coolant, and re-prime and vent the system.
- Wearing Parts Replacement:
- Replace water pump mechanical seals.
- Replace all O-rings and sealing gaskets.
- Replace quick coupling sealing rings.
- Inspect and replace aged pipelines and hoses.
- Sensor Calibration:
- Perform metrological calibration on all temperature, pressure, and flow sensors.
- Repair or replace sensors that fail calibration.
- Calibrate the sensitivity of the leak detection system.
- Electrical System Comprehensive Test:
- Conduct comprehensive insulation testing and inspect cables for aging.
- Test all protection functions to ensure accurate protection thresholds and reliable operation.
- Upgrade the controller program to the latest version to optimize control logic.
- Back up system parameters and programs.
- Overall Performance Test:
- Conduct full-load operation tests to detect performance indicators such as system cooling capacity, temperature control accuracy, and energy efficiency ratio (COP/EER).
- Evaluate equipment operation status and provide maintenance suggestions and lifespan assessment.
- Issue an annual maintenance report with recommendations for the next year’s operation and maintenance.
12.6 Long-Term Shutdown Maintenance
When the equipment is shut down for a long period (more than 1 month):
- Drain the coolant from the system to prevent freezing and corrosion.
- Cut off power and water supply, and close all valves.
- Clean the inside and outside of the equipment and perform drying treatment to prevent moisture and mold.
- Cover all interfaces with protective caps to prevent dust and debris from entering.
- Cover with a dust cover to avoid dust accumulation.
- Run the equipment with power for 2 hours monthly to expel moisture and check the status of electrical components.
- When the ambient temperature is below 0°C, freezing prevention measures must be taken to ensure no residual water remains in the pipelines.
12.7 Common Component Repair Methods
12.7.1 Water Pump Repair
- Common Faults: Leakage, abnormal noise, insufficient flow, failure to start.
- Leakage Treatment: Usually caused by worn mechanical seal. Drain the water from the corresponding pipeline, disassemble the pump, replace the mechanical seal, and perform a pressure test ensuring no leakage after replacement.
- Abnormal Noise Treatment: Check if the bearings are damaged, if the impeller is stuck, or if the base is loose. Correspondingly replace bearings, clean debris, or tighten the base.
- Insufficient Flow: Check if the impeller is worn, if the pipeline is blocked, or if the speed is normal, and address accordingly.
- Failure to Start: Check the power supply, frequency converter, motor windings, and capacitors; replace faulty components.
12.7.2 Valve Repair
- Internal Leakage Treatment: Disassemble the valve core, check the sealing surface for damage or debris, clean or lap the sealing surface, and replace the valve core if severely damaged.
- External Leakage Treatment: Replace the valve stem packing or flange gasket.
- Sticking Treatment: Disassemble and clean the valve stem and core, remove rust and scale, and apply lubricating grease.
12.7.3 Sensor Repair
- When the reading is inaccurate, first check if the wiring is loose or if the shielding is good.
- Perform calibration. If calibration fails, replace the sensor.
- When replacing, pay attention to the interface seal to prevent leakage.
12.7.4 Controller Repair
- In case of program anomalies, restart the controller, restore factory settings, and then re-download the program.
- In case of hardware failure, replace the corresponding module. Programs and parameters can be restored from backup.
- It is strictly forbidden to disassemble the controller’s core chips without authorization to prevent damage.
12.7 Recommended Spare Parts
To ensure operation and maintenance efficiency, it is recommended to stock the following wearing parts:
| No. | Spare Part Name | Recommended Stock Quantity | Replacement Cycle |
|---|---|---|---|
| 1 | Y-type filter cartridge | 2 pieces/unit | 6-12 months |
| 2 | Quick coupling sealing ring | 10 pieces/unit | 1-2 years |
| 3 | Water pump mechanical seal | 1 set/unit | 2-3 years |
| 4 | Temperature sensor | 2 pieces/batch | 3-5 years |
| 5 | Pressure sensor | 1 piece/batch | 3-5 years |
| 6 | Solenoid valve coil | 1 piece/batch | 3-5 years |
| 7 | Relays, Contactors | Several | 5 years |
| 8 | Sealing gaskets | 1 set/unit | 1-2 years |
13.1 Common Liquid Circuit System Faults
13.1.1 Low System Pressure
- Possible Causes:
- System leakage, coolant loss.
- Insufficient air pressure in the expansion tank.
- Air accumulation in the system, large air volume.
- Untimely water replenishment, too low liquid level.
- Pressure sensor failure or zero drift.
- Solutions:
- Comprehensively check pipelines, joints, valves, water pumps, and heat exchangers for leaks, find the leak point and address it.
- Check the pre-charge pressure of the expansion tank. If insufficient, add nitrogen to the specified value.
- Open the high-point vent valve to thoroughly expel air from the system.
- Replenish coolant to the normal level.
- Calibrate the pressure sensor; replace it if damaged.
13.1.2 High System Pressure
- Possible Causes:
- Expansion tank undersized or bladder damaged.
- System temperature too high, excessive coolant expansion.
- Pipeline blockage, excessive flow resistance.
- Return water valve not fully open or blocked.
- Pressure sensor failure.
- Solutions:
- Check the expansion tank status. Replace if the bladder is damaged; expand capacity if undersized.
- Investigate the cause of high temperature, lower the supply water temperature, and increase flow.
- Clean the filter, check pipelines for blockages, and clear the flow path.
- Fully open the return water valve and check if the valve disc is detached.
- Calibrate or replace the pressure sensor.
13.1.3 Pipeline Joint Leakage
- Possible Causes:
- Loose joints, insufficient tightening.
- Sealing ring aged, damaged, or improperly installed.
- Damaged threads, presence of impurities.
- Pipeline stress pulling on the joint.
- System pressure exceeding the rated value.
- Solutions:
- Tighten the joint appropriately, being careful to avoid stripping the threads.
- Replace the sealing ring, aligning and placing it correctly during installation.
- Clean impurities from the threads, replace the joint if threads are damaged.
- Adjust pipeline supports to eliminate pipeline stress.
- Investigate the cause of high pressure and reduce the pressure to the normal range.
13.1.4 Insufficient Flow, Poor Heat Dissipation
- Possible Causes:
- Water pump speed insufficient, frequency setting too low.
- Water pump impeller worn, performance degraded.
- Filter blocked, high flow resistance.
- Pipeline valves not fully open, or blockage.
- Air in the system causing cavitation.
- Cold plate flow channel blocked.
- Water pump rotation direction reversed.
- Solutions:
- Increase the water pump speed setting, check the frequency converter output frequency.
- Disassemble the pump to inspect the impeller, replace if severely worn.
- Clean the filter cartridge.
- Fully open all valves, check pipelines for blockages and clear them.
- Thoroughly vent the system to expel air.
- Clean the cold plate flow channels to remove scale and impurities.
- Adjust the motor phase sequence to correct the rotation direction.
13.1.5 Abnormal Water Pump Noise, Excessive Vibration
- Possible Causes:
- Loose pump base, aged vibration dampeners.
- Water pump bearing damage.
- Impeller stuck, presence of debris.
- Air intake into the system, pump cavitation.
- Pump shaft concentricity deviation.
- Pipeline resonance.
- Solutions:
- Tighten base bolts, replace aged vibration dampeners.
- Replace bearings, apply lubricating grease.
- Disassemble and clean debris from the impeller.
- Vent the system to eliminate cavitation.
- Adjust the concentricity of the pump and motor.
- Change pipeline fixing methods to eliminate resonance points.
13.1.6 System Leak Alarm
- Possible Causes:
- Actual leakage from pipelines, joints, or components.
- Condensation on the pipeline surface, water droplets falling onto the detection cable.
- Leak detection cable damp, dusty, or contaminated causing false alarms.
- Leak controller failure.
- Detection cable damaged or short-circuited.
- Solutions:
- Locate the leak point based on positioning information and address the leakage.
- Check if the insulation is intact, increase the supply water temperature to eliminate condensation.
- Clean and dry the detection cable, reset after drying.
- Repair or replace the leak controller.
- Replace the damaged detection cable.
13.2 Common Cooling Effect Problems
13.2.1 High Supply Water Temperature, Insufficient Cooling
- Possible Causes:
- Excessive primary side supply water temperature.
- Insufficient primary side flow, valve opening not enough.
- Heat exchanger scaling, reduced heat exchange efficiency.
- Electric control valve fault, unable to open fully.
- IT load exceeding rated heat dissipation power.
- Insufficient secondary side flow.
- Temperature sensor fault, display deviation.
- Solutions:
- Check the primary side cooling source, lower the supply water temperature.
- Fully open primary side valves, check if the filter is blocked, and increase flow.
- Clean the heat exchanger to remove scale.
- Repair the electric control valve, eliminating sticking and control faults.
- Reduce IT load or add cooling equipment.
- Increase the secondary side pump speed to increase flow.
- Calibrate or replace the temperature sensor.
13.2.2 Large Fluctuations in Supply Water Temperature
- Possible Causes:
- Unreasonable PID parameter settings, control oscillation.
- Violent IT load fluctuations.
- Large fluctuations in primary side water pressure and temperature.
- Electric control valve operating too frequently.
- Air in the system, unstable flow.
- Solutions:
- Re-tune PID parameters, reduce proportional gain, increase integral time.
- Enable pump variable frequency regulation to stabilize system flow and pressure.
- Install pressure and temperature stabilization devices on the primary side.
- Adjust the control valve dead zone to reduce frequent operation.
- Thoroughly vent the system.
13.2.3 Condensation on Pipeline Surface
- Possible Causes:
- Supply water temperature too low, below the ambient dew point.
- Insulation layer damaged, insufficient thickness, or poor sealing at joints.
- High humidity in the computer room environment.
- Cold bridge treatment not proper, heat transfer at supports and interfaces.
- Solutions:
- Enable the anti-condensation function, increase supply water temperature, maintaining it at least 1°C above the dew point.
- Repair the insulation layer, thicken the insulation cotton, and seal joints with tape.
- Dehumidify the computer room to lower ambient humidity.
- Add thermal insulation pads at supports to eliminate cold bridges.
13.3 Common Electrical System Faults
13.3.1 Equipment Cannot Power On
- Possible Causes:
- External power outage, phase loss, or abnormal voltage.
- Main circuit breaker tripped, fuse blown.
- Emergency stop button pressed.
- Power cord loose or disconnected.
- Surge protector short-circuited.
- Solutions:
- Check external power supply, restore normal power.
- Investigate the cause of the circuit breaker trip, clear the fault, and close the breaker.
- Reset the emergency stop button.
- Check wiring terminals, tighten or replace cables.
- Replace the damaged surge protector.
13.3.2 Water Pump Cannot Start
- Possible Causes:
- Water pump power not connected, circuit breaker tripped.
- Frequency converter fault, alarm protection active.
- Control circuit fault, no start signal.
- Water pump motor burnt out, winding open circuit.
- Water pump impeller seized.
- Water shortage, low pressure protection triggered.
- Solutions:
- Check the power supply circuit, close the breaker to supply power.
- View the fault code on the frequency converter, clear the fault, and reset.
- Check the control wiring, PLC output, and relay contacts.
- Measure the motor winding resistance. If burnt, replace the motor.
- Disassemble the pump and clean blocked debris.
- Replenish coolant and clear the low-pressure fault.
13.3.3 Frequent Water Pump Start/Stop
- Possible Causes:
- Unreasonable pressure setpoints, pressure differential too small.
- System leakage, rapid pressure drop.
- Pressure sensor signal unstable.
- Improper frequency converter parameter settings.
- Check valve failure, pressure backflow.
- Solutions:
- Set a reasonable start/stop pressure differential, increase the hysteresis.
- Find and address system leaks.
- Check the sensor wiring, shield against interference, replace if damaged.
- Adjust frequency converter PID parameters, increase filtering time.
- Repair or replace the check valve.
13.3.4 Display Screen Not Working
- Possible Causes:
- Control power supply fault, no 24V output.
- Display screen power wiring loose.
- Display screen damaged.
- Communication cable disconnected, no signal.
- Controller fault.
- Solutions:
- Check the switch-mode power supply, output normal voltage, replace if damaged.
- Tighten the display screen power wiring.
- Replace the display screen.
- Check the communication cable, repair broken points.
- Repair the PLC controller.
13.3.5 Abnormal Sensor Values
- Possible Causes:
- Sensor wiring loose or disconnected.
- Abnormal sensor power supply.
- Sensor damaged or drifted.
- Signal interference, fluctuating values.
- Analog module fault.
- Solutions:
- Check wiring, tighten terminals.
- Measure supply voltage, restore normal power.
- Calibrate or replace the sensor.
- Check shield grounding, keep away from power lines to eliminate interference.
- Replace the PLC analog module.
13.4 Common Control System Problems
13.4.1 Temperature Control Failure
- Possible Causes:
- Temperature sensor fault, inaccurate detection.
- Electric control valve stuck, unable to operate.
- Controller PID parameters lost or incorrect.
- Primary side water supply cut off, no cooling source.
- Incorrect control mode setting.
- Solutions:
- Calibrate or replace the temperature sensor.
- Repair the electric control valve, clean blockages, replace damaged parts.
- Reset PID parameters, download the correct program.
- Restore primary side water supply.
- Switch to the correct control mode.
13.4.2 False Alarms
- Possible Causes:
- Unreasonable alarm threshold settings.
- Sensor value drift.
- Electromagnetic interference, signal fluctuation.
- Controller program fault.
- Solutions:
- Set reasonable alarm thresholds, avoid being overly sensitive.
- Calibrate sensors to ensure accurate values.
- Ensure proper shielding and grounding to eliminate electromagnetic interference.
- Restart the controller, update the program.
13.4.3 Remote Communication Failure
- Possible Causes:
- Communication cable disconnected, wiring error.
- Mismatched communication parameter settings (address, baud rate, protocol).
- Communication module damaged.
- Network fault, IP conflict.
- Firewall blocking, port not opened.
- Solutions:
- Check the communication line, correct wiring errors.
- Verify communication parameters at both ends to ensure consistency.
- Replace the communication module.
- Troubleshoot network faults, resolve IP conflicts.
- Configure the firewall to open the corresponding port.
14.1 Basic Concepts
Q1: What is the difference between closed-loop and open-loop liquid cooling? Which is better?
A: The core difference is whether the secondary side coolant contacts the atmosphere. A closed-loop system is completely sealed, preventing coolant-air contact. Its advantages include slower oxidation/corrosion, less scaling, longer maintenance cycles, stable pressure, and no evaporative loss. An open system has an open reservoir, exposing coolant to air, which leads to oxidation, scaling, microbial growth, and frequent maintenance, but its structure is simpler and cheaper.
For high-reliability applications like data centers, closed-loop liquid cooling offers superior overall performance, longer lifespan, and lower operational costs, making it the current mainstream technology.
Q2: What is the difference between cold plate liquid cooling and immersion cooling?
A: Cold plate liquid cooling uses coolant flowing through cold plates that indirectly contact the chips, not the electronic components directly. Advantages include good compatibility with standard servers, easy maintenance, and high safety. Immersion cooling completely submerges servers in dielectric coolant, offering higher heat dissipation density, but requires specialized servers, high retrofitting costs, complex maintenance, and expensive coolant.
The closed-loop water-cooling integrated cabinet uses the cold plate approach, balancing performance and practicality, suitable for most high-density computing scenarios.
Q3: Will water cooling leak? Is it safe?
A: Closed-loop products from reputable manufacturers incorporate multiple anti-leak designs, making them extremely safe. KITOZER products ensure safety from three dimensions: 1) Component level – using double-sealed quick couplings, all-stainless-steel piping, and strict factory pressure tests to minimize leakage probability at the source; 2) Detection level – full-chain locating leak detection with response within 2 seconds; 3) Protection level – automatic valve closure, pump stop, and alarm upon leak detection to control the leakage scope.
With proper installation and regular maintenance, the risk of leakage is very low, far lower than the probability of leakage in traditional air conditioning water pipes.
14.2 Installation and Deployment
Q4: Can a traditional air-cooled data center be directly retrofitted for water cooling? Does it require building modifications?
A: Yes, direct retrofitting is possible without large-scale building modifications. The closed-loop water-cooling integrated cabinet is a cabinet-level integrated device, sized the same as standard racks, allowing direct replacement of existing air-cooled racks. On-site, only the primary side chilled water pipes and power supply need to be connected. The data center only needs to support the outdoor cooling source and main water pipes; no changes to building structure, load-bearing capacity, or decoration are required. The retrofit cycle is short with minimal impact on operations.
Q5: What are the options for the primary-side cooling source? Is a chiller mandatory?
A: The primary-side cooling source can be flexibly selected based on the scenario:
- Northern regions: Prioritize dry coolers + free cooling, leveraging natural cooling for most of the year for optimal energy efficiency.
- Central and southern regions: Can use closed-circuit cooling towers, free cooling in winter, evaporative cooling in summer.
- High-temperature areas or sites with existing chillers: Can directly connect to the existing chilled water system.
- Low-power scenarios: Can also use an integrated chiller for plug-and-play operation.
A chiller is not strictly necessary; prioritizing natural cooling sources is more energy-efficient.
Q6: What size water pipes are needed for a single cabinet? Are there water pressure requirements?
A: The interface size varies with power: 30kW uses DN25, 50kW uses DN32, 80kW uses DN40, 120kW uses DN50. The primary side supply water pressure requirement is 0.2-0.4MPa. Too low pressure leads to insufficient flow, while too high pressure can damage equipment.
14.3 Operation and Maintenance
Q7: How often should the coolant be changed? What type of water is used?
A: Closed-loop systems have minimal coolant loss, typically requiring only about 5% replenishment annually. High-purity deionized water is recommended, with conductivity ≤10μS/cm. Test water quality every 1-2 years and replace the coolant if conductivity exceeds standards. Usually, a complete replacement is done every 2-3 years. In low-temperature environments, an ethylene-glycol type antifreeze coolant must be added.
Q8: Is the equipment noisy? Will it affect the data center environment?
A: The closed-loop water-cooling cabinet operates at ≤55dB(A), equivalent to a normal office environment, far lower than the 70-80dB of traditional air-cooled racks. By eliminating server fans and CRAC indoor units, overall data center noise is significantly reduced, greatly improving the maintenance environment.
Q9: How many people are needed for daily maintenance? Is it difficult?
A: Daily maintenance is straightforward. Ordinary data center personnel can handle it after basic training. For deployments of up to 10 cabinets, one maintenance person can typically manage. Daily tasks involve checking parameters during inspections, and monthly simple maintenance. Core maintenance is recommended to be performed by manufacturer professionals.
Q10: Will the pipes freeze and get damaged in winter?
A: Indoor data center temperatures are usually above 5°C, preventing freezing. For edge sites subject to low winter temperatures, antifreeze solution can be added, selecting the appropriate concentration based on local minimum temperatures, withstanding temperatures as low as -35°C. For long-term shutdown, drain the water from the pipelines to prevent freezing cracks.
14.4 Performance Parameters
Q11: What PUE can be achieved? How much power does it save compared to air cooling?
A: With closed-loop water cooling + natural cooling sources, the annual average PUE can be reduced to 1.08-1.15. Compared to a traditional air-cooled data center’s PUE of 1.5-1.8, cooling energy consumption can be reduced by 60%-70%. For a single cabinet with a 50kW load, this translates to approximate annual electricity cost savings of ¥150,000-200,000, demonstrating significant energy-saving benefits.
Q12: What is the typical supply water temperature setting? Is higher always better for energy efficiency?
A: The typical setting is 28-32°C, adjusted based on the heat tolerance of the IT equipment. Within permissible equipment limits, a higher supply water temperature extends the duration of free cooling and increases energy efficiency. KITOZER products support supply water temperatures up to 35°C, maximizing the use of natural cooling sources. However, it must not be set below the ambient dew point to prevent condensation.
Q13: Is the one-primary-one-standby pump configuration necessary? Is it wasteful?
A: It is highly necessary for critical business scenarios. The pump is a core moving part with a potential for failure. The 1+1 configuration enables seamless switchover, ensuring uninterrupted heat dissipation and preventing IT equipment overheating and downtime due to pump failure. Pumps have low power consumption themselves, and the standby pump uses no power, thus not wasteful, but significantly enhancing system reliability.
14.5 After-Sales Support
Q14: What is the product warranty period? How fast is after-sales response?
A: The entire KITOZER closed-loop water-cooling integrated cabinet carries a 2-year warranty, with a 3-year warranty on core components, and lifetime technical support. After-sales response time is within 4 hours in the Guangdong area, 24-hour on-site service in major cities nationwide, and 7×24-hour technical hotline support.
Q15: Are customization options available? (e.g., size, power, interfaces)
A: Yes, customization services are supported. We can adjust cabinet dimensions, power capacity, number of interfaces, power distribution configuration, functional modules, etc., based on user requirements to suit different scenarios. Please contact our sales and technical team to discuss specific customization plans.
15.1 Acceptance Basis
- Purchase contract, technical agreement, design drawings.
- This product manual, factory inspection standards.
- National and industry standards:
- GB 50462 – Standard for construction and acceptance of data center infrastructure
- GB 50174 – Code for design of data centers
- T/CAICI 131-2025 – Technical specification for liquid cooling system engineering
- T/CIE 342—2025 – Operation and maintenance guide for liquid cooling system in cold plate indirect liquid-cooled data center
- GB 50303 – Code for acceptance of construction quality of building electrical engineering
- GB 50235 – Code for construction of industrial metallic piping engineering
15.2 Acceptance Stages
Acceptance is divided into three stages: unpacking acceptance, installation acceptance, and completion acceptance.
15.2.1 Unpacking Acceptance
- After equipment arrival, both supply and demand parties conduct unpacking acceptance together.
- Verify that the equipment model, specification, and quantity are consistent with the contract.
- Check the equipment appearance is intact, without transportation damage, rust, or deformation.
- Verify the packing list, ensuring accessories, spare parts, and documentation are complete.
- Sign the unpacking acceptance form. Raise any objections on the spot and negotiate a solution.
15.2.2 Installation Acceptance
After installation is completed and before commissioning, an installation quality acceptance is performed. Content includes:
- Cabinet Installation: Correct position, levelness and verticality meet requirements, securely fixed, reliable grounding.
- Pipeline Installation: Correct connections, level and vertical alignment, secure fixing, clear labeling, successful pressure test, no leakage.
- Electrical Installation: Neat wiring, clear labeling, qualified insulation, reliable grounding, complying with electrical codes.
- Safety Protection: Leak detection installed correctly, insulation complete, fire stopping pass.
- Documentation Check: Construction records, test records, concealed works records are complete.
The commissioning phase can only begin after installation acceptance is passed.
15.2.3 Completion Acceptance
After the system commissioning is completed and the 72-hour full-load test passes, completion acceptance is carried out, involving the construction party, the building owner, and the supervision party (if applicable).
15.3 Completion Acceptance Items and Criteria
15.3.1 Appearance and Structure Acceptance
- Equipment appearance is intact, free from scratches, paint peeling, deformation; labels are clear and complete.
- Cabinet doors open and close flexibly, locks are intact, and sealing is good.
- Cabinets are arranged neatly with uniform gaps and horizontally aligned.
- Pipes and cables are arranged neatly, firmly fixed, and clearly labeled.
- Insulation layer is complete and aesthetically pleasing, without damage or exposure.
15.3.2 Performance Indicator Acceptance
- Heat Dissipation Performance: During full-load operation, the secondary side supply/return temperature differential reaches the design value; IT equipment operating temperatures are within normal range without overheating.
- Temperature Control Accuracy: Secondary side supply water temperature is stable at the set point, with fluctuation ≤±0.5°C.
- Flow Indicators: Total system flow reaches the design value; flow deviation in each branch ≤10%.
- Pressure Indicators: System operating pressure is stable at 0.15-0.35MPa, with pressure fluctuation ≤0.02MPa.
- Noise Indicator: Noise ≤55dB(A) at 1 meter from the cabinet.
- Energy Efficiency: System cooling COP meets design requirements; single-cabinet PUE meets the target.
15.3.3 Functional Acceptance
- Pump Function: Main/standby pump switchover operates normally; variable frequency regulation is smooth; protection functions are effective.
- Temperature Control Function: Automatic temperature control works normally; control is responsive; anti-condensation function is effective.
- Monitoring Function: All parameter monitoring is accurate, display is normal, historical data storage is complete.
- Alarm Function: Audible/visual alarms and remote alarms work normally; alarm levels are accurate; protection actions are correct.
- Leak Protection: Simulate leak – alarm is timely, linked valve closure and pump stop actions are correct.
- Communication Function: Communication with the environmental monitoring system (DCIM/BMS) is normal; data upload is accurate; remote monitoring function works.
- Auto-Start: After power outage, automatically restores operation upon power return, with correct status.
15.3.4 Safety Acceptance
- Electrical insulation resistance is qualified: power circuit ≥10MΩ, control circuit ≥2MΩ.
- Grounding resistance ≤4Ω, all metal parts are continuously and reliably grounded.
- All protection devices are complete and effective, with reliable operation.
- Pipeline pressure test is passed, without leakage.
- No safety hazards around the equipment; fire-fighting facilities are complete.
15.3.5 Documentation Acceptance
Completion documents should be comprehensive and complete, including at least:
- Unpacking acceptance form.
- Installation construction records.
- Hydrostatic test records.
- Insulation test, grounding test records.
- Commissioning records, 72-hour full-load test records.
- Product manual, certificate of conformity, factory inspection report.
- As-built drawings, system schematic diagram, wiring diagram.
- Training records, operation and maintenance manual.
15.4 Acceptance Process
1. The construction party completes all installation and commissioning work, passes its own inspection, and submits the acceptance application and completion documents to the building owner.
2. The building owner organizes an acceptance team within 3 working days of receiving the application and determines the acceptance time.
3. The acceptance team inspects and tests item by item according to the acceptance criteria, filling out the acceptance record form.
4. For issues found during acceptance, the construction party makes corrections within a specified deadline and undergoes re-acceptance after completion.
5. After all items pass acceptance, all parties sign the completion acceptance report, and the equipment is officially handed over to the building owner.
6. Equipment that fails acceptance must not be put into use; re-acceptance must be organized after corrections are made.
15.5 Acceptance Criteria Table
| Acceptance Category | Acceptance Item | Acceptance Criteria | Result | Remark |
|---|---|---|---|---|
| Appearance/Structure | Cabinet appearance | Intact, no damage, clear labels | ||
| Cabinet installation | Levelness ≤1mm/m, Verticality ≤1.5mm/m | |||
| Pipeline layout | Level/vertical, secure fixing, clear labels | |||
| Wiring workmanship | Neat/standardized, power/data separation, clear labels | |||
| Liquid Circuit | Pressure test | 1.5x working pressure for 24h, pressure drop ≤1% | ||
| Leak check | No leakage at interfaces, welds, components | |||
| Rated flow | Meets design flow value | |||
| Pump switchover | Automatic switch time ≤3s, functions normal | |||
| Cooling Performance | Temperature control | ±0.5°C | ||
| Full-load cooling | IT equipment temperature normal, no overheating | |||
| Heat exchange rate | ≥90% | |||
| Electrical System | Insulation resistance | Power circuit ≥10MΩ | ||
| Grounding resistance | ≤4Ω | |||
| Protection functions | Overload, short circuit, phase loss protection works | |||
| Monitoring/Alarm | Parameter monitoring | All parameters displayed accurately | ||
| Alarm function | Audible/visual, remote alarms normal | |||
| Leak detection | Response ≤2s, linked protection normal | |||
| Remote communication | Data upload normal, stable communication | |||
| Safety/Environment | Operating noise | ≤55dB(A) | ||
| Anti-condensation | No condensation on pipelines | |||
| Safety protection | Complete, no hidden hazards | |||
| Documentation | Documentation completeness | Complete, accurate, standardized |
15.6 Handover and Training
After acceptance, the equipment handover procedures are carried out, including the handover of equipment, spare parts, tools, and documentation.
- The manufacturer provides on-site technical training to the operation and maintenance personnel, covering equipment principles, operating methods, daily inspections, common fault handling, safety precautions, etc.
- After training, an assessment is conducted to ensure personnel have mastered basic operation and emergency response capabilities.
- After the handover is complete, the equipment enters the warranty period, with warranty services provided according to the contract terms.
Appendix A: System Schematic Diagram
(Attach the system schematic diagram of the closed-loop water-cooling integrated cabinet here, showing the primary and secondary side water flow paths, positions of pumps, heat exchangers, manifolds, valves, sensors, and other components.)
Appendix B: Electrical Schematic Diagram
(Attach the main electrical schematic, control circuit diagram, and terminal wiring diagram here.)
Appendix C: Common Fault Code Table
| Fault Code | Fault Name | Fault Level | Handling Suggestions |
|---|---|---|---|
| E01 | Secondary supply over-temp | Emergency | Check cooling source, pump; reduce load |
| E02 | Secondary low pressure | Important | Check for leaks, replenish coolant, vent air |
| E03 | System leak | Emergency | Stop equipment immediately, find leak point and address |
| E04 | Pump overload | Important | Check pump, frequency converter; clear fault |
| E05 | Low flow rate | Important | Clean filter, check valves, vent air |
| E06 | Sensor fault | General | Check wiring, replace sensor |
| E07 | Power phase loss | Emergency | Check three-phase power supply |
| E08 | Communication fault | General | Check communication cable and parameters |
Appendix D: Maintenance Record Form Template
(Includes columns for date, inspection items, parameter records, abnormal conditions, corrective actions, maintenance personnel signature, etc.)
I. Search Keyword System
1. Core Primary Keywords
Closed-loop water-cooling integrated cabinet, Water-cooling integrated cabinet, Closed-loop liquid-cooling cabinet, Cold plate liquid-cooling cabinet, Cabinet-type water cooling system.
2. High-Conversion Long-Tail Keywords
Closed-loop water-cooling integrated cabinet manufacturer, Closed-loop water-cooling integrated cabinet price, Closed-loop water-cooling integrated cabinet installation, 50kW closed-loop water-cooling cabinet, High-density water-cooling cabinet, Data center closed-loop water-cooling cabinet, Cabinet-level liquid cooling solution, Integrated water-cooling cabinet customization, Data center water-cooling cabinet retrofitting, Closed-loop water-cooling cabinet operation and maintenance.
3. Industry Traffic Keywords
Data center liquid cooling technology, Cold plate liquid cooling solution, High-density server heat dissipation, Data center water cooling system, Liquid-cooled cabinet installation specification, Water-cooled cabinet commissioning method, Liquid-cooled data center PUE, Indirect liquid cooling system, Closed-loop circulating water cooling unit, Liquid-cooled cabinet acceptance standard.
4. Brand-Specific Keywords
KITOZER water-cooled cabinet, Guangdong KITOZER liquid cooling, KITOZER closed-loop water-cooling integrated cabinet, LA-SW water-cooled cabinet, KITOZER smart data center equipment, Guangzhou water-cooled cabinet manufacturer.
5. Dropdown/Related Search Keywords
Water-cooling integrated cabinet principle, Water-cooling integrated cabinet composition, Difference between closed-loop and open-loop water cooling, Liquid-cooled cabinet leakage risk, How to install a water-cooled cabinet, Liquid-cooled cabinet technical parameters, Integrated water-cooled cabinet application scenarios, Water-cooled cabinet maintenance methods.
II. SEO Optimization Tag System
1. Page Core Optimization Tags
- Page Theme: Closed-loop water-cooling integrated cabinet installation, wiring, and commissioning manual.
- Core Keyword Layout: Naturally integrate core keywords in the first paragraph, chapter titles, beginning and end of the main text. Keyword density controlled at 2%-3%.
- Content Length: Long-form, in-depth content covering the entire product lifecycle knowledge points to meet users’ comprehensive information needs.
2. Title Tag
Closed-Loop Water-Cooling Integrated Cabinet Installation, Wiring & Commissioning Manual | Product Parameters | O&M Guide – KITOZER Smart Data Center Equipment
3. Meta Keywords
Closed-loop water-cooling integrated cabinet, water-cooling integrated cabinet, cold plate liquid-cooling cabinet, liquid-cooled cabinet installation and commissioning, data center water-cooled cabinet, closed-loop water-cooling system, KITOZER water-cooled cabinet.
4. Meta Description
KITOZER provides professional closed-loop water-cooling integrated cabinets. This manual details the product introduction, components, principles, technical parameters, installation, wiring, commissioning processes, maintenance, troubleshooting, and acceptance standards, facilitating efficient heat dissipation and low-carbon energy saving for high-density data centers.
5. H1 Tag
Closed-Loop Water-Cooling Integrated Cabinet Installation, Wiring & Commissioning Manual
6. H2 Tags
Product Introduction, Product Composition, Product List, Product Working Principle, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation, Product Wiring, Product Commissioning, Product Safety & Precautions, Product Repair & Maintenance, Common Problems & Solutions, Product FAQ, Product Acceptance.
III. Internal Link Optimization Tags (Anchor Text · Natural Placement)
1. Core Anchor Text
Closed-loop water-cooling integrated cabinet, Water-cooling integrated cabinet, Cold plate liquid-cooling cabinet.
2. Long-tail Anchor Text
Closed-loop water-cooling integrated cabinet installation and commissioning, High-density server water-cooling solution, Data center liquid cooling system solution.
3. Related Anchor Text
Precision air conditioning for data centers, Micro-module data center, Shielded room construction, Intelligent environment monitoring system.
The copyright of this document belongs to Guangdong Lain Intelligent System Development Co., Ltd. and is protected by national copyright laws. Any unit or individual is prohibited from reproducing, reprinting, adapting, excerpting, disseminating, or using this document commercially in any form without the written authorization of the company. Violators will be held legally responsible.
If reprinting or citing content from this document, please indicate the source as “Source: Guangdong Lain Intelligent System Development Co., Ltd.” and maintain content integrity without altering or distorting the original meaning.
The content of this document is subject to periodic updates due to product technology upgrades without prior notice. Please refer to the official release for the latest version.