Integrated Fire Linkage Solution for Computer Rooms

Table of Contents

1. System Overview

The integrated fire linkage system for computer rooms is an intelligent security system developed in accordance with GB 50116-2013 Code for Design of Automatic Fire Alarm System. It integrates fire detection, alarm transmission, linkage control, gas fire suppression and environmental monitoring, tailor-made for core IT scenarios including data centers, server rooms and network rooms.

The core value of the system lies in achieving “early detection, accurate alarm, rapid linkage and residue-free fire suppression”. Targeting the high incidence of electrical fires in computer rooms (caused by short circuits, overloads, line aging, etc.), the system adopts non-destructive fire suppression technology. It can link power cut-off, air conditioner shutdown, smoke exhaust activation, access control unlocking and video tracking to the maximum extent to protect core assets such as servers, switches and storage devices, prevent fire spread and data loss, and ensure 7×24-hour uninterrupted operation of computer rooms.

This solution takes the full range of KITOZER brand fire-fighting equipment as the core, adopting modular and redundant design, supporting dual modes of local linkage and remote monitoring. It is compatible with mainstream communication protocols including BACnet, Modbus and TCP/IP, and can seamlessly connect to computer room environment monitoring systems, BMS building management systems and security monitoring systems to build an integrated computer room safety protection network.

Featuring high reliability, low false alarm rate and easy maintenance, the system covers the whole-process protection from front-end detection to back-end disposal, and meets the hierarchical protection requirements of computer rooms of different scales (small single computer rooms, medium multi-computer rooms and large data centers).

2. System Composition

The integrated fire linkage system for computer rooms consists of six core components: front-end detection unit, core control unit, linkage execution unit, fire suppression disposal unit, auxiliary supporting unit and remote monitoring unit. All units realize signal interaction and coordinated operation through buses or network communication.

2.1 Front-end Detection Unit

It serves as the “perceptive nerve” of the system, responsible for real-time collection of computer room environmental parameters and fire characteristic signals to provide basis for early warning and fire alarm.

  • Smoke detectors: photoelectric/ion/aspirating types, monitoring early smoke with fast response and high sensitivity
  • Temperature detectors: fixed temperature/differential temperature/composite types, monitoring abnormal ambient temperature and high-temperature heat sources
  • Composite detectors: smoke-temperature integrated/smoke-temperature-gas integrated types, multi-parameter fusion to reduce false alarm rate
  • Manual alarm call points: manually triggered alarms in emergencies to link fire suppression activation
  • Fire telephones: two-way intercom between site and fire control room for fire confirmation and disposal command

2.2 Core Control Unit

Acting as the “brain” of the system, it receives detection signals, conducts logical operations, issues linkage instructions and feeds back equipment status to realize centralized management and intelligent control.

  • Fire alarm controller: receives detector signals, identifies alarm type and location, and triggers sound-light alarm display
  • Fire linkage controller: core hub that activates fire suppression, power supply, air conditioner, access control and other equipment in accordance with preset logic
  • Gas fire suppression controller: special control unit driving FM200/IG541 fire suppression devices to realize accurate zoned fire suppression
  • Graphic display device for fire control room: real-time display of computer room floor plan, equipment location, alarm status and linkage information

2.3 Linkage Execution Unit

It receives instructions from the core control unit and executes linkage actions on computer room environment and equipment to block fire spread and ensure evacuation safety.

  • Power cut-off device: cuts off non-fire-fighting power supply (servers, air conditioners, lighting, etc.) to prevent re-ignition caused by electrical short circuits
  • Air conditioning/fresh air control device: shuts down air conditioners and fresh air systems to block air circulation and inhibit fire spread
  • Smoke prevention and exhaust device: activates exhaust fans and opens exhaust valves to discharge smoke and guarantee visibility in evacuation passages
  • Fire door/shutter control device: closes fire doors and lowers fire shutters to divide fire compartments and isolate fire sources
  • Access control device: unlocks evacuation passage access control to enable rapid personnel evacuation
  • Sound-light alarm: emits high-decibel alarms and flashing lights to remind on-site personnel to evacuate
  • Emergency lighting/evacuation indicators: activates emergency lighting and lights evacuation indicators to guide escape routes
  • Security linkage device: triggers camera recording and PTZ positioning of alarm areas for remote fire viewing

2.4 Fire Suppression Disposal Unit

Core fire suppression equipment for computer rooms adopts a combined scheme of clean gas fire suppression supplemented by ultra-fine dry powder, leaving no residue, pollution or damage to electronic equipment.

  • FM200 fire suppression devices: pipe network/cabinet types, complete fire suppression within 30 seconds with good insulation and no corrosion
  • IG541 inert gas fire suppression devices: clean and environmentally friendly, suitable for manned computer rooms with zero residue after fire suppression
  • Ultra-fine dry powder fire suppression devices: suspended/cabinet types, low cost and fast fire suppression, applicable to power distribution rooms and cable interlayers
  • Pressure relief device: releases cabin pressure during fire suppression to protect computer room walls and doors/windows
  • Starting gas cylinders/solenoid valves: receive control signals to drive release of fire suppression agent

2.5 Auxiliary Supporting Unit

Supporting equipment to ensure stable system operation and improve protection integrity.

  • Fire power supply: UPS backup power and fire storage batteries to guarantee continuous system operation for ≥8 hours after power failure
  • Signal transmission equipment: fire buses, network switches and signal modules to ensure stable signal transmission
  • Earthing device: system earthing and lightning protection earthing to prevent static electricity and lightning interference
  • Protective sleeves: fire-resistant cable sleeves and bridge frames to protect lines from high-temperature damage

2.6 Remote Monitoring Unit

Realizes remote system management, early warning push and fault diagnosis, supporting unattended computer room operation and maintenance.

  • Remote monitoring host: connects to fire controllers to upload alarm, fault and linkage information in real time
  • Mobile APP/WEB platform: remotely views system status, receives alarm push and performs manual remote control
  • SMS/email alarm module: automatically pushes SMS and emails to operation and maintenance personnel in case of abnormalities
  • Data storage server: stores alarm records, linkage logs and equipment status for traceable query

3. System Classification

The integrated fire linkage system for computer rooms is classified into four dimensions by protection level, fire suppression medium, control mode and applicable scenarios, which can be flexibly selected according to computer room area, budget and protection requirements.

3.1 Classification by Protection Level (Basic/Standard/Enhanced)

  1. Basic Type (Low Configuration) Applicable to small single computer rooms (≤50㎡) and budget-limited scenarios. Core configuration: photoelectric smoke detectors + manual alarm call points + sound-light alarms + cabinet-type FM200 fire suppression device + simple linkage controller, realizing basic functions of “detection-alarm-manual linkage fire suppression”.
  2. Standard Type (Medium Configuration) Applicable to medium multi-computer rooms (50-200㎡) and conventional data centers. Configuration: smoke-temperature composite detectors + aspirating smoke detectors + fire telephones + linkage controller + pipe network FM200 fire suppression device + power/air conditioning/access control linkage devices + local graphic display device, realizing “automatic detection-intelligent alarm-full linkage-zoned fire suppression”.
  3. Enhanced Type (High Configuration) Applicable to large data centers (≥200㎡), high-end server rooms and core financial/government computer rooms. Configuration: multi-parameter composite detectors + ultra-early aspirating detectors + dual redundant linkage controllers + IG541 clean gas fire suppression device + full linkage of smoke prevention/exhaust and fire shutters + remote monitoring platform + integrated security/environment monitoring + redundant power supply + lightning protection earthing system, realizing “ultra-early warning-precise positioning-full automatic linkage-clean fire suppression-remote operation and maintenance-data traceability”.

3.2 Classification by Fire Suppression Medium

  • FM200 fire suppression system: mainstream preferred solution with high fire suppression efficiency, fast speed, good insulation and no residue, suitable for core computer rooms and server cabinet areas
  • IG541 inert gas fire suppression system: clean, environmentally friendly and non-toxic, suitable for manned computer rooms and scenarios with high environmental protection requirements
  • Ultra-fine dry powder fire suppression system: low cost and fast fire suppression, suitable for power distribution rooms, cable interlayers and auxiliary computer rooms
  • Hybrid fire suppression system: combination of FM200 and ultra-fine dry powder, adopting FM200 for core areas and ultra-fine dry powder for auxiliary areas to balance effect and cost

3.3 Classification by Control Mode

  • Centralized control system: all fire-fighting equipment is centrally controlled, displayed and managed in the fire control room, applicable to small and medium computer rooms with bus transmission and digital control
  • Decentralized & centralized hybrid control system: fire water pumps, smoke exhaust fans and gas fire suppression devices are centrally controlled, while terminal detectors and modules are managed in a decentralized manner, applicable to large data centers and multi-area computer rooms
  • IoT intelligent control system: based on TCP/IP network communication, supporting local control + remote monitoring + intelligent algorithms, realizing automatic fault diagnosis, automatic early warning push and automatic linkage optimization, applicable to high-end unattended computer rooms

3.4 Classification by Applicable Scenarios

  • Special system for server rooms: designed for high-density cabinets and abundant heat dissipation equipment, adopting ultra-early detection + zoned gas fire suppression + in-cabinet spray linkage
  • Special system for network rooms: focusing on protection of switches, routers and other network equipment, equipped with smoke-temperature composite detection + FM200 fire suppression + power/air conditioning linkage
  • Special system for power distribution/battery rooms: targeting high risks of electrical fires and battery thermal runaway, equipped with temperature + smoke + combustible gas composite detection + ultra-fine dry powder fire suppression + strong power cut-off linkage
  • Special system for data center parks: multi-computer room cluster protection, adopting distributed detection + zoned linkage + centralized monitoring + integrated park fire-fighting system

4. System Schematic Diagram

4.1 System Topology Principle

  1. Front-end detection: smoke, temperature and composite detectors collect computer room environmental signals in real time; manual alarm call points trigger artificial signals, which are transmitted to the fire alarm controller via fire buses
  2. Signal processing: the fire alarm controller identifies signal types, distinguishes early warning/fire alarm/fault, locates alarm equipment and uploads information to the fire linkage controller
  3. Logical linkage: the fire linkage controller sends instructions to all execution units in accordance with the preset “fire alarm-confirmation-linkage” logic:
    • After fire alarm confirmation: cut off non-fire-fighting power supply, shut down air conditioners/fresh air and close fire doors
    • Delay for 30 seconds (personnel evacuation): activate gas fire suppression devices and release fire suppression agent
    • Synchronous actions: activate sound-light alarms, emergency lighting, exhaust fans, unlock access control and trigger security recording
  4. Feedback monitoring: all execution units feed back status signals to the linkage controller after operation, which are displayed in real time on the graphic display device and uploaded to the remote monitoring platform
  5. Remote operation and maintenance: the remote monitoring platform receives system data, supporting remote viewing, manual control, alarm push and data storage & traceability

4.2 Core Linkage Logic (Special for Computer Rooms)

  • Single smoke detector alarm: early warning, sound-light prompt, upload to monitoring platform, no fire suppression activation
  • Smoke detector + temperature detector composite alarm: fire alarm confirmed, immediately cut off power supply, shut down air conditioners and activate sound-light alarms; delay 30 seconds to start gas fire suppression
  • Manual alarm call point trigger: direct fire alarm confirmation, link all equipment and activate fire suppression immediately
  • Post-fire-suppression linkage: after agent release, stop exhaust fans and close air vents to prevent agent leakage and maintain closed fire suppression environment

5. Complete System Configuration List (KITOZER Brand, Three Grades: Low/Medium/High)

5.1 Low Configuration List (Basic Type, ≤50㎡ Single Computer Room)

表格

No.Product NameModelTechnical ParametersQtyUnitBrandRemarks
1Photoelectric Smoke DetectorKITOZER-YG100Operating Voltage: DC24V; Standby Current ≤0.1mA, Alarm Current ≤20mA; Sensitivity: 0.15-0.3dB/m; Response Time ≤3s; Temp: -10℃~+50℃; IP30; Size Φ100×35mm, Weight 80g6PcsKITOZERCeiling mounted, 1 per 10㎡ computer room
2Manual Fire Alarm Call PointKITOZER-SB200DC24V; Standby ≤0.05mA, Alarm ≤15mA; Mechanical Press Trigger; Normally Open Feedback; Temp -10℃~+50℃; IP30; Size 86×86×30mm, Weight 120g2PcsKITOZER1 each at computer room entrance and cabinet area
3Fire Sound-Light AlarmKITOZER-SG300DC24V; Current ≤50mA; Sound ≥85dB@3m; Flash Frequency 1Hz; Red Light; Temp -10℃~+50℃; IP30; Φ120×40mm, 150g2PcsKITOZERInstalled at prominent positions in computer room
4Cabinet-type FM200 Fire Suppression DeviceKITOZER-QMP70Agent Volume 70L; FM200 Medium; Working Pressure 2.5MPa; Electromagnetic/Manual Emergency Start; Injection Time ≤10s; Protection Area ≤50㎡; Temp 0℃~+50℃; Size 600×500×1800mm, 220kg (with agent)1SetKITOZERFloor-mounted for computer room exclusive use
5Gas Fire Suppression ControllerKITOZER-QK400DC24V; 1 Loop, Max Load 30 Points; Auto/Manual Control; 0-30s Adjustable Delay; Output: Fire Suppression Start, Sound-Light, Power Cut-off; Feedback: Pressure, Start, Fault; RS485 Comm; Temp -10℃~+50℃; 400×300×100mm, 8kg1UnitKITOZERWall-mounted, connects to fire suppression device
6Simple Fire Linkage ControllerKITOZER-LK500DC24V; 1 Loop, Max Load 50 Points; 8 Preset Linkage Logics; Switch Output; RS485; Temp -10℃~+50℃; 400×300×100mm, 8kg1UnitKITOZERWall-mounted, connects to detectors and alarms
7Fire Backup Power SupplyKITOZER-DY600Input AC220V±10%; Output DC24V/5A; Backup Time ≥8h; Battery 12V/17Ah×2; Overvoltage/Overcurrent/Short Circuit/Undervoltage Protection; Temp -10℃~+50℃; 300×200×150mm, 15kg1SetKITOZERProvides backup power for the whole system
8Fire Bus CableKITOZER-XL7002×1.5mm² Copper Core; Flame Retardant PVC Insulation; Withstand Voltage ≥500V; Transmission Distance ≤1000m50MKITOZERSignal transmission between equipment
9Power Cut-off ModuleKITOZER-DQ800DC24V; Control Capacity AC220V/10A; Normally Open/Normally Closed Output; Response ≤1s; Temp -10℃~+50℃; 100×80×30mm, 200g1PcsKITOZERCuts off main non-fire-fighting power of computer room

5.2 Medium Configuration List (Standard Type, 50-200㎡ Multi-computer Room)

表格

No.Product NameModelTechnical ParametersQtyUnitBrandRemarks
1Smoke-Temperature Composite DetectorKITOZER-YW101DC24V; Standby ≤0.1mA, Alarm ≤25mA; Smoke Sensitivity 0.15-0.3dB/m; Temp Trigger 57℃±5℃; Dual Parameter Fusion; Response ≤3s; Temp -10℃~+50℃; IP40; Φ100×38mm, 85g15PcsKITOZERCeiling and cabinet interlayer installation
2Ultra-early Aspirating Smoke DetectorKITOZER-XQ201DC24V; Current ≤100mA; Sensitivity 0.005-0.2dB/m; Sampling Pipe ≤100m, Max 50 Sampling Holes; Response ≤1s; Temp -20℃~+60℃; IP50; 400×300×150mm, 12kg2SetKITOZERTop sampling for ultra-early warning
3Manual Fire Alarm Call PointKITOZER-SB201DC24V; Standby ≤0.05mA, Alarm ≤15mA; Mechanical Press + Key Reset; Fire Phone Jack; Temp -10℃~+50℃; IP40; 86×86×35mm, 130g4PcsKITOZEREntrance of each computer room and evacuation passage
4Fire Telephone ExtensionKITOZER-DH301DC24V; Max Call Distance ≤1000m; Clear Noise-free Audio; Temp -10℃~+50℃; IP30; 200×80×40mm, 300g2UnitKITOZER1 each in fire control room and computer room
5Fire Sound-Light AlarmKITOZER-SG301DC24V; Current ≤60mA; Sound ≥90dB@3m; Flash 1.5Hz; Self-Check Fault; Temp -10℃~+50℃; IP40; Φ130×45mm, 180g4PcsKITOZERInstalled inside each computer room
6Pipe Network FM200 Fire Suppression DeviceKITOZER-GMP120Agent Volume 120L; FM200 Medium; Working Pressure 4.2MPa; Electromagnetic/Manual Emergency Start; Injection ≤8s; Max 2 Zones, Protection Area ≤200㎡; Temp 0℃~+50℃; 800×600×2000mm, 350kg (with agent)1SetKITOZERFloor-mounted for multi-room zoned protection
7Multi-zone Gas Fire Suppression ControllerKITOZER-QK401DC24V; 2 Loops, Max Load 60 Points; Auto/Manual/Emergency Stop; 0-30s Delay Adjustable; Output: Fire Suppression, Sound-Light, Power Cut-off, AC Shutdown; Feedback: Pressure, Start, Fault, Zone Status; RS485+TCP/IP; Temp -10℃~+50℃; 500×400×120mm, 12kg1UnitKITOZERWall-mounted for multi-zone control
8Standard Fire Linkage ControllerKITOZER-LK501DC24V; 2 Loops, Max Load 120 Points; 16 Preset Linkage Logics, Custom Programming; Switch + Analog Output; RS485+TCP/IP+CAN Bus; Temp -10℃~+50℃; 500×400×120mm, 12kg1UnitKITOZERWall-mounted, full-system linkage control
9Fire Control Room Graphic Display DeviceKITOZER-TX60115.6-inch Screen, 1920×1080 Resolution; Embedded Linux; Displays Floor Plan, Equipment Position, Alarm Status, Linkage Log; 32G Storage; TCP/IP Comm; Temp -10℃~+50℃; 400×300×50mm, 5kg1UnitKITOZERWall/desktop mounted in fire control room
10Power Cut-off Control CabinetKITOZER-DQ801DC24V; Control Capacity AC220V/30A, 3 Circuits; Cuts Off Server/AC/Lighting Power; Overload Protection; Response ≤1s; Temp -10℃~+50℃; 400×300×150mm, 8kg1UnitKITOZERFloor-mounted, centralized non-fire power cut-off
11AC/Fresh Air Control ModuleKITOZER-KT901DC24V; Switch Control; Max 5 AC/Fresh Air Units; Response ≤1s; Temp -10℃~+50℃; 150×100×40mm, 300g2PcsKITOZERControls start/stop of computer room AC and fresh air
12Smoke Exhaust Fan Control ModuleKITOZER-PY1001DC24V; AC380V/20A Control Capacity; Max 2 Exhaust Fans; Auto/Manual Switch; Response ≤1s; Temp -10℃~+50℃; 200×150×50mm, 500g1PcsKITOZERControls start/stop of smoke exhaust fans
13Standard Fire Backup Power SupplyKITOZER-DY601Input AC220V±10%; Output DC24V/10A; Backup ≥12h; Battery 12V/38Ah×2; Overvoltage/Overcurrent/Short Circuit/Undervoltage/Lightning Protection; Temp -10℃~+50℃; 400×300×200mm, 25kg1SetKITOZERBackup power for full system
14Fire Communication Bus CableKITOZER-XL7012×2.5mm² Copper Core; Flame Retardant Fire-resistant PVC; Withstand Voltage ≥1000V; Transmission ≤2000m200MKITOZERSystem signal and communication transmission
15Emergency Lighting & Evacuation IndicatorKITOZER-YJ1101DC24V; 3W Power; Brightness ≥50cd/m²; Emergency Duration ≥90min; Temp -10℃~+50℃; IP40; 300×100×20mm, 200g8PcsKITOZERInstalled at evacuation passages and room entrances

5.3 High Configuration List (Enhanced Type, ≥200㎡ Large Data Center)

表格

No.Product NameModelTechnical ParametersQtyUnitBrandRemarks
1Multi-parameter Composite DetectorKITOZER-DF102DC24V; Standby ≤0.15mA, Alarm ≤30mA; Smoke + Temp + CO Detection; Smoke Sensitivity 0.1-0.3dB/m; Temp Trigger 55℃±3℃; CO Range 0-1000ppm, Accuracy ±5%; Response ≤2s; Temp -20℃~+60℃; IP50; Φ110×40mm, 90g30PcsKITOZERInstalled at cabinet interlayers, ceilings and cable trenches
2Ultra-high Sensitivity Ultra-early Aspirating DetectorKITOZER-XQ202DC24V; Current ≤150mA; Sensitivity 0.001-0.1dB/m; Sampling Pipe ≤200m, Max 100 Sampling Holes; Dual Sampling Chamber, Self-cleaning; Response ≤0.5s; Temp -20℃~+60℃; IP60; 500×400×180mm, 18kg5SetKITOZERFull-area ultra-early warning for data center
3Manual Fire Alarm Call Point (with Emergency Stop)KITOZER-SB202DC24V; Standby ≤0.05mA, Alarm ≤15mA; Mechanical Press + Key Reset + Emergency Stop; NO/NC Feedback, Fire Phone Jack; Temp -20℃~+60℃; IP50; 86×86×40mm, 150g8PcsKITOZEREntrance of each functional area and evacuation passage
4Fire Telephone Host + ExtensionsKITOZER-DH302Host DC24V, 16 Extension Interfaces; Extension DC24V, Max Call Distance ≤2000m; HD Noise-free Audio; Temp -20℃~+60℃; IP40; Host 300×200×80mm (5kg), Extension 200×80×45mm (350g)1+6SetKITOZER1 host in fire control room, 1 extension per computer room
5Explosion-proof Fire Sound-Light AlarmKITOZER-SG302DC24V; Current ≤70mA; Sound ≥95dB@3m; Flash 2Hz; Red Light; Explosion-proof Grade Exd II BT4; Self-check + Remote Monitoring; Temp -20℃~+60℃; IP65; Φ140×50mm, 220g8PcsKITOZERExplosion-proof installation in computer rooms and power distribution rooms
6IG541 Inert Gas Fire Suppression DeviceKITOZER-IG150Agent Volume 150L; IG541 Medium (52%N₂+40%Ar+8%CO₂, Purity ≥99.9%); Working Pressure 15MPa; Electromagnetic/Manual/Emergency Mechanical Start; Injection ≤60s; Max 4 Zones, Protection Area ≥200㎡; Non-toxic for manned areas; Temp 0℃~+50℃; 1000×800×2200mm, 500kg (with agent)2SetKITOZERFloor-mounted zoned protection for core computer rooms
7Dual Redundant Gas Fire Suppression ControllerKITOZER-QK402DC24V Dual Redundant Power; 4 Loops, Max Load 120 Points; Auto/Manual/Emergency Stop/Mechanical Emergency; 0-30s Delay Adjustable; Output: Fire Suppression, Sound-Light, Power Cut-off, AC Shutdown, Fire Door Close; Feedback: Pressure, Start, Fault, Zone Status, Agent Residual; RS485+TCP/IP+CAN Bus; Dual CPU Redundancy; Temp -20℃~+60℃; 600×500×150mm, 18kg2UnitKITOZERDual redundant backup to avoid single-point failure
8Dual Redundant Intelligent Fire Linkage ControllerKITOZER-LK502DC24V Dual Redundant Power; 4 Bus Loops, Max Load 240 Points; Custom Programmable Linkage Logic (AND/OR/NOT); Dual CPU Redundancy, Fault Self-diagnosis & Self-repair; Switch + Analog + Network Protocol Output; RS485+TCP/IP+CAN Bus+BACnet; Temp -20℃~+60℃; 600×500×150mm, 18kg2UnitKITOZERDual redundant backup for full-system intelligent linkage
9HD Touch Graphic Display Device for Fire Control RoomKITOZER-TX60221.5-inch Touch Screen, 1920×1080; Embedded Linux; Displays 3D Floor Plan, Real-time Equipment Status, Alarm Positioning, Linkage Process, Data Statistics; 128G SSD Storage; TCP/IP+BACnet, Remote Sync; Temp -20℃~+60℃; 500×400×60mm, 8kg1UnitKITOZERTouch operation in fire control room
10Intelligent Power Cut-off Control CabinetKITOZER-DQ802DC24V Dual Power; Control Capacity AC220V/60A, AC380V/40A, 6 Circuits; Intelligent Load Identification, Graded Cut-off; Overload/Short Circuit/Earth Leakage Protection; Remote Monitoring + Local Operation; Response ≤0.5s; Temp -20℃~+60℃; 600×500×250mm, 15kg2UnitKITOZERGraded cut-off of non-fire-fighting power supply
11Intelligent AC/Fresh Air Control CabinetKITOZER-KT902DC24V; AC220V/50A Control Capacity, 4 Circuits; Matches Central AC & Fresh Air; Linkage Temperature Control + Fire Signal; Remote Monitoring + Local Operation; Response ≤0.5s; Temp -20℃~+60℃; 500×400×200mm, 12kg2UnitKITOZERIntelligent control of AC and fresh air systems
12Smoke Prevention/Exhaust & Fire Shutter Linkage Control CabinetKITOZER-FP1102DC24V; AC380V/30A Control Capacity, 4 Circuits; Controls Exhaust Fans, Pressurized Air Fans & Fire Shutters; Programmable Linkage Logic; Remote Monitoring + Local Operation; Response ≤0.5s; Temp -20℃~+60℃; 500×400×200mm, 12kg2UnitKITOZERCentralized control of smoke exhaust and fire shutters
13Security Linkage ModuleKITOZER-AF1202DC24V; RJ45+RS485 Interface; Compatible with Hikvision/Dahua Cameras; Linkage Actions: Recording, PTZ Positioning, Snapshot; ONVIF Protocol; Temp -20℃~+60℃; 150×100×40mm, 350g4PcsKITOZERSeamless integration of fire-fighting and security systems
14Remote Monitoring Platform HostKITOZER-YC1302Quad-core Processor, 8G RAM, 512G SSD; Linux System; Functions: Data Receiving, Storage, Analysis, Alarm Push, Remote Control; RJ45×4, USB×2; Supports APP/WEB Access; Temp -20℃~+60℃; 400×300×150mm, 10kg1UnitKITOZERCore of data center remote monitoring
15Dual Redundant Industrial Fire Backup Power SupplyKITOZER-DY602Dual Input AC220V±15%; Dual Output DC24V/20A Redundant; Full Load Backup ≥24h; Battery 12V/100Ah×4 Lead-acid Maintenance-free; Overvoltage/Overcurrent/Short Circuit/Undervoltage/Lightning/Surge Protection; Temp -20℃~+60℃; 500×400×250mm, 45kg2SetKITOZERDual redundant backup power for extreme conditions
16Fire-resistant Fire Communication Bus CableKITOZER-XL7022×4mm² Oxygen-free Copper Core; Flame Retardant Fire-resistant PVC + Mica Tape Insulation; Withstand Voltage ≥1500V; Transmission ≤3000m; High Temperature Resistance ≥950℃500MKITOZERStable signal transmission under high temperature
17Intelligent Emergency Lighting & Evacuation IndicatorKITOZER-YJ1102DC24V; 5W Power; Brightness ≥80cd/m²; Emergency Duration ≥180min; Intelligent Dimming, Fault Reporting; Temp -20℃~+60℃; IP50; 350×120×25mm, 250g20PcsKITOZERInstalled at full-area evacuation passages and entrances
18Ultra-fine Dry Powder Fire Suppression Device (Auxiliary Area)KITOZER-CF502Agent Volume 5kg; Ultra-fine Dry Powder Medium (Particle Size ≤5μm, Fire Class A/B/C/E); Working Pressure 1.2MPa; Electromagnetic/Thermal Start (68℃); Injection ≤3s; Protection Area ≤20㎡; Suitable for Power Distribution Rooms & Cable Interlayers; Temp -20℃~+60℃; Φ250×400mm, 12kg10SetKITOZERSupplementary fire suppression for auxiliary areas

6. Full Product Technical Parameters

6.1 Detector Series

6.1.1 Photoelectric Smoke Detector (KITOZER-YG100)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: Standby ≤0.1mA, Alarm ≤20mA
  • Sensitivity: 0.15-0.3dB/m (adjustable)
  • Response Time: ≤3s
  • Ambient Temperature: -10℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP30
  • Output Mode: Normally Open/Normally Closed (Passive Contact)
  • Dimension: Φ100×35mm
  • Weight: 80g
  • Installation: Ceiling-mounted
  • Executive Standard: GB4715-2005

6.1.2 Smoke-Temperature Composite Detector (KITOZER-YW101)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: Standby ≤0.1mA, Alarm ≤25mA
  • Smoke Sensitivity: 0.15-0.3dB/m
  • Temperature Trigger: 57℃±5℃ (fixed temperature)
  • Response Time: ≤3s
  • Ambient Temperature: -10℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP40
  • Output Mode: Normally Open/Normally Closed (Passive Contact)
  • Dimension: Φ100×38mm
  • Weight: 85g
  • Installation: Ceiling-mounted
  • Executive Standard: GB4715-2005, GB4716-2005

6.1.3 Multi-parameter Composite Detector (KITOZER-DF102)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: Standby ≤0.15mA, Alarm ≤30mA
  • Detection Parameters: Smoke + Temperature + Carbon Monoxide (CO)
  • Smoke Sensitivity: 0.1-0.3dB/m
  • Temperature Trigger: 55℃±3℃ (fixed temperature)
  • CO Detection Range: 0-1000ppm, Accuracy ±5%
  • Response Time: ≤2s
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP50
  • Output Mode: RS485 + Passive Contact
  • Dimension: Φ110×40mm
  • Weight: 90g
  • Installation: Ceiling/Wall-mounted
  • Executive Standard: GB4715-2005, GB4716-2005, GB/T21281-2007

6.1.4 Ultra-early Aspirating Smoke Detector (KITOZER-XQ201/XQ202)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: ≤100mA (XQ201) / ≤150mA (XQ202)
  • Detection Sensitivity: 0.005-0.2dB/m (XQ201) / 0.001-0.1dB/m (XQ202)
  • Max Sampling Pipe Length: ≤100m (XQ201) / ≤200m (XQ202)
  • Max Sampling Holes: ≤50 pcs (XQ201) / ≤100 pcs (XQ202)
  • Response Time: ≤1s (XQ201) / ≤0.5s (XQ202)
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP50 (XQ201) / IP60 (XQ202)
  • Output Mode: RS485 + TCP/IP + Passive Contact
  • Dimension: 400×300×150mm (XQ201) / 500×400×180mm (XQ202)
  • Weight: 12kg (XQ201) / 18kg (XQ202)
  • Installation: Wall-mounted
  • Executive Standard: GB15631-2008

6.2 Manual Alarm Call Point Series

6.2.1 Manual Fire Alarm Call Point (KITOZER-SB200)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: Standby ≤0.05mA, Alarm ≤15mA
  • Trigger Mode: Mechanical Press
  • Reset Mode: Manual Reset
  • Feedback Signal: Normally Open (Passive Contact)
  • Ambient Temperature: -10℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP30
  • Dimension: 86×86×30mm
  • Weight: 120g
  • Installation: Wall-mounted (86 Junction Box)
  • Executive Standard: GB19880-2005

6.2.2 Manual Fire Alarm Call Point (with Emergency Stop, KITOZER-SB202)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: Standby ≤0.05mA, Alarm ≤15mA
  • Trigger Mode: Mechanical Press + Emergency Stop
  • Reset Mode: Key Reset
  • Feedback Signal: Normally Open/Normally Closed (Passive Contact)
  • Built-in Fire Phone Jack (RJ11)
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP50
  • Dimension: 86×86×40mm
  • Weight: 150g
  • Installation: Wall-mounted (86 Junction Box)
  • Executive Standard: GB19880-2005

6.3 Sound-Light Alarm Series

6.3.1 Fire Sound-Light Alarm (KITOZER-SG300)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: ≤50mA
  • Sound Pressure Level: ≥85dB (3m distance)
  • Flash Frequency: 1Hz
  • Light Color: Red
  • Ambient Temperature: -10℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP30
  • Dimension: Φ120×40mm
  • Weight: 150g
  • Installation: Wall/Ceiling-mounted
  • Executive Standard: GB4715-2005

6.3.2 Explosion-proof Fire Sound-Light Alarm (KITOZER-SG302)

  • Operating Voltage: DC24V (±10%)
  • Operating Current: ≤70mA
  • Sound Pressure Level: ≥95dB (3m distance)
  • Flash Frequency: 2Hz
  • Light Color: Red
  • Explosion-proof Grade: Exd II BT4
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Protection Grade: IP65
  • Dimension: Φ140×50mm
  • Weight: 220g
  • Installation: Wall-mounted
  • Executive Standard: GB4715-2005, GB3836.1-2010

6.4 Fire Suppression Device Series

6.4.1 Cabinet-type FM200 Fire Suppression Device (KITOZER-QMP70)

  • Agent Volume: 70L
  • Fire Suppression Medium: FM200 (Purity ≥99.9%)
  • Working Pressure: 2.5MPa (20℃)
  • Start Mode: Electromagnetic DC24V + Manual Emergency
  • Injection Time: ≤10s
  • Max Protection Area: ≤50㎡
  • Max Protection Height: ≤4m
  • Ambient Temperature: 0℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 600×500×1800mm
  • Weight: 220kg (with agent)
  • Installation: Floor-mounted
  • Executive Standard: GB18614-2012, GB50370-2005

6.4.2 Pipe Network FM200 Fire Suppression Device (KITOZER-GMP120)

  • Agent Volume: 120L
  • Fire Suppression Medium: FM200 (Purity ≥99.9%)
  • Working Pressure: 4.2MPa (20℃)
  • Start Mode: Electromagnetic DC24V + Manual Emergency
  • Injection Time: ≤8s
  • Max Protection Area: ≤200㎡
  • Max Zones: 2 Zones
  • Ambient Temperature: 0℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 800×600×2000mm
  • Weight: 350kg (with agent)
  • Installation: Floor-mounted
  • Executive Standard: GB18614-2012, GB50370-2005

6.4.3 IG541 Inert Gas Fire Suppression Device (KITOZER-IG150)

  • Agent Volume: 150L
  • Fire Suppression Medium: IG541 (52%N₂+40%Ar+8%CO₂, Purity ≥99.9%)
  • Working Pressure: 15MPa (20℃)
  • Start Mode: Electromagnetic DC24V + Manual Emergency + Mechanical Emergency
  • Injection Time: ≤60s
  • Min Protection Area: ≥200㎡
  • Max Zones: 4 Zones
  • Non-toxic, suitable for manned premises
  • Ambient Temperature: 0℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 1000×800×2200mm
  • Weight: 500kg (with agent)
  • Installation: Floor-mounted
  • Executive Standard: GB20128-2006, GB50370-2005

6.4.4 Ultra-fine Dry Powder Fire Suppression Device (KITOZER-CF502)

  • Agent Volume: 5kg
  • Fire Suppression Medium: Ultra-fine Dry Powder (Particle Size ≤5μm, Fire Class A/B/C/E)
  • Working Pressure: 1.2MPa (20℃)
  • Start Mode: Electromagnetic DC24V + Thermal Start (68℃)
  • Injection Time: ≤3s
  • Max Protection Area: ≤20㎡
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: Φ250×400mm
  • Weight: 12kg
  • Installation: Wall/Hanging-mounted
  • Executive Standard: GB16668-2010

6.5 Controller Series

6.5.1 Gas Fire Suppression Controller (KITOZER-QK400)

  • Operating Voltage: DC24V (±10%)
  • Loop Quantity: 1 Loop
  • Max Load Points: 30 (Detectors & Modules)
  • Control Mode: Auto/Manual
  • Delay Time: 0-30s Adjustable
  • Output: Fire Suppression Start (DC24V/1A), Sound-Light (DC24V/1A), Power Cut-off (Passive Contact)
  • Feedback: Pressure Switch, Start Feedback, Fault Feedback (Passive Contact)
  • Communication: RS485
  • Ambient Temperature: -10℃~+50℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 400×300×100mm
  • Weight: 8kg
  • Installation: Wall-mounted
  • Executive Standard: GB4717-2005, GB16806-2006

6.5.2 Dual Redundant Intelligent Fire Linkage Controller (KITOZER-LK502)

  • Operating Voltage: DC24V (±10%, Dual Redundant Power Supply)
  • Bus Loop Quantity: 4 Loops
  • Max Load Points: 240 (Detectors, Modules & Equipment)
  • Linkage Logic: Custom Programmable, Logical Operation (AND/OR/NOT)
  • Control Mode: Auto/Manual/Emergency Stop
  • Output: Passive Contact Switch + 4-20mA Analog + Network Protocols (TCP/IP/BACnet)
  • Feedback: Equipment Status, Fault, Alarm (Passive Contact + Network)
  • Communication: RS485 + TCP/IP + CAN Bus + BACnet
  • Dual CPU Redundancy, Fault Self-diagnosis & Self-repair
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 600×500×150mm
  • Weight: 18kg
  • Installation: Wall-mounted
  • Executive Standard: GB4717-2005, GB16806-2006

6.6 Auxiliary Equipment Series

6.6.1 Industrial Dual Redundant Fire Backup Power Supply (KITOZER-DY602)

  • Input: Dual AC220V±15% Mains Power
  • Output: Dual DC24V/20A Redundant Output
  • Full Load Backup Duration: ≥24h
  • Battery Specification: 12V/100Ah×4 Lead-acid Maintenance-free
  • Protection Functions: Overvoltage, Overcurrent, Short Circuit, Undervoltage, Lightning, Surge Protection
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 500×400×250mm
  • Weight: 45kg
  • Installation: Floor-mounted
  • Executive Standard: GB17945-2010

6.6.2 HD Touch Graphic Display Device for Fire Control Room (KITOZER-TX602)

  • Screen Size: 21.5-inch Touch Screen
  • Resolution: 1920×1080
  • Operating System: Embedded Linux
  • Display Content: 3D Computer Room Floor Plan, Real-time Equipment Status, Alarm Positioning, Linkage Flow, Data Statistics, Historical Records
  • Storage Capacity: 128G SSD
  • Communication Interfaces: RJ45×2 (TCP/IP), RS485×2, BACnet
  • Functions: Real-time Monitoring, Alarm Pop-up, Remote Sync, Data Export
  • Ambient Temperature: -20℃~+60℃
  • Relative Humidity: ≤95% (40℃, no condensation)
  • Dimension: 500×400×60mm
  • Weight: 8kg
  • Installation: Wall/Desktop-mounted
  • Executive Standard: GB17255-2009

7. Full Product Application Scope

7.1 Detector Series Application Scope

  • Photoelectric Smoke Detector (KITOZER-YG100): Small computer rooms, offices, corridors, power distribution rooms and other low-smoke/low-temperature premises for early smoldering fire monitoring
  • Smoke-Temperature Composite Detector (KITOZER-YW101): Medium computer rooms, server cabinet interlayers, network rooms and cable bridges with high electrical fire risks; multi-parameter fusion reduces false alarms
  • Multi-parameter Composite Detector (KITOZER-DF102): Large data centers, financial core computer rooms, government computer rooms and high-density cabinet areas with high asset value and fire risks; triple smoke/temp/CO detection for precise early warning
  • Ultra-early Aspirating Smoke Detector (KITOZER-XQ201/XQ202): High-end data centers, dust-free computer rooms, museums, archives and power rooms requiring ultra-early high-sensitivity warning; detects hidden hazards before smoke becomes visible

7.2 Manual Alarm Call Point Series Application Scope

  • Manual Fire Alarm Call Point (KITOZER-SB200): Small computer rooms, office areas and corridors accessible to personnel for manual emergency alarm trigger
  • Manual Fire Alarm Call Point with Emergency Stop (KITOZER-SB202): Medium & large data centers, computer room entrances, evacuation passages and areas near fire suppression devices; supports alarm trigger and emergency halt of linkage/fire suppression actions

7.3 Sound-Light Alarm Series Application Scope

  • Fire Sound-Light Alarm (KITOZER-SG300): Conventional indoor environments including all types of computer rooms, offices, corridors and stairwells; emits sound-light alerts to guide personnel evacuation during fires
  • Explosion-proof Fire Sound-Light Alarm (KITOZER-SG302): Power distribution rooms, battery rooms, oil generator rooms and flammable material storage areas with explosion-proof requirements; prevents electric sparks from triggering explosions

7.4 Fire Suppression Device Series Application Scope

  • Cabinet-type FM200 Fire Suppression Device (KITOZER-QMP70): ≤50㎡ small single computer rooms, server cabinet zones and network rooms; pipe-free design for easy installation and residue-free fire suppression
  • Pipe Network FM200 Fire Suppression Device (KITOZER-GMP120): 50-200㎡ medium multi-computer rooms and data room clusters; pipe network zoned design for precise multi-area fire suppression
  • IG541 Inert Gas Fire Suppression Device (KITOZER-IG150): ≥200㎡ large data centers, financial/government core computer rooms and manned high-end server rooms; clean, non-toxic and zero-residue with no damage to equipment
  • Ultra-fine Dry Powder Fire Suppression Device (KITOZER-CF502): Power distribution rooms, cable interlayers, battery rooms and auxiliary computer rooms; low cost and fast fire suppression as auxiliary fire-fighting equipment

7.5 Controller Series Application Scope

  • Gas Fire Suppression Controllers (KITOZER-QK400/QK401/QK402): Matches FM200, IG541 and other gas fire suppression systems; controls gas fire suppression in computer rooms, power distribution rooms and cabinet zones
  • Fire Linkage Controllers (KITOZER-LK500/LK501/LK502): All types of computer rooms, data centers, buildings and parks; core of fire-fighting systems to link fire suppression, power supply, AC, access control, security and all other fire-fighting equipment

7.6 Auxiliary Equipment Series Application Scope

  • Fire Backup Power Supplies (KITOZER-DY600/DY601/DY602): Supplies backup power for all fire-fighting equipment (detectors, controllers, alarms, fire suppression devices) in all computer rooms, data centers and building fire systems
  • Fire Communication Bus Cables (KITOZER-XL700/XL701/XL702): Signal and communication transmission between fire-fighting equipment for all computer rooms and data centers; XL702 fire-resistant cable for high-temperature high-risk environments
  • Emergency Lighting & Evacuation Indicators (KITOZER-YJ1101/YJ1102): Computer room evacuation passages, entrances, corridors and stairwells; provides emergency lighting and escape guidance during fires
  • Power Cut-off Modules/Cabinets (KITOZER-DQ800/DQ801/DQ802): Computer rooms, data centers and buildings; cuts off non-fire-fighting power to prevent re-ignition from electrical short circuits during fires
  • AC/Fresh Air Control Modules/Cabinets (KITOZER-KT901/KT902): Computer rooms, data centers and office buildings; shuts down AC and fresh air to block air circulation and inhibit fire spread during fires
  • Smoke Prevention/Exhaust & Fire Shutter Linkage Cabinets (KITOZER-FP1102): Large data centers, buildings and shopping malls; activates exhaust fans and closes fire shutters to discharge smoke and isolate fire sources during fires
  • Security Linkage Modules (KITOZER-AF1202): Computer rooms, data centers, parks and buildings; integrates fire-fighting and security systems to trigger camera recording and PTZ positioning for remote fire viewing during fires
  • Fire Telephone Host & Extensions (KITOZER-DH301/DH302): Medium & large computer rooms, data centers, buildings and parks; two-way intercom between fire control room and site for fire confirmation and disposal command
  • Remote Monitoring Platform Host (KITOZER-YC1302): Unattended computer rooms, large data centers and parks; realizes remote fire system monitoring, early warning push, fault diagnosis and data traceability

8. Full Product Advantages

8.1 Core Brand Advantages

  • Strong Customization Capacity: KITOZER has focused on computer room fire-fighting for 15 years, supporting full-series customization (size, parameters, functions, communication protocols, appearance). Tailored solutions available based on computer room area, layout, protection requirements and budget
  • OEM/ODM Processing Service: Supports customer private label production, providing technical support, production training and quality control to reduce customer production costs
  • Strict Confidentiality Agreements: Signs non-disclosure agreements with customers to protect customized solutions, technical parameters and project information against leakage
  • Sufficient Spot Inventory: Core products (detectors, controllers, alarms, fire suppression devices) kept in stock; standard models delivered within 3-7 days, customized models within 7-15 days to meet urgent project demands
  • Full-series Supporting Products: Complete integrated fire-fighting product line (detection, alarm, control, fire suppression, linkage, auxiliary, remote monitoring) for one-stop procurement with full compatibility and unified after-sales service, eliminating multi-brand adaptation issues
  • Leading Technical Parameters: Core product specifications exceed industry standards; detectors feature high sensitivity, fast response and low false alarm rate; fire suppression devices deliver high efficiency, fast speed and residue-free performance; controllers feature stable redundant design and complete functions
  • High-reliability Design: All products adopt industrial-grade components, redundant architecture and lightning/anti-static design, adapting to high-temperature, high-humidity and strong electromagnetic interference environments in computer rooms; stable continuous operation ≥10 years with failure rate ≤0.1%
  • Ultra-low False Alarm Rate: Detectors adopt multi-parameter fusion and intelligent algorithm threshold tracking technology to distinguish real fires from dust, water vapor and electromagnetic interference; false alarm rate ≤0.01%
  • Easy Maintenance: Modular design, automatic fault diagnosis and real-time status display; detectors maintenance-free ≥5 years, controllers maintenance-free ≥8 years to reduce operation and maintenance costs
  • Complete Compliance Certifications: All products hold national 3C fire product certification, ISO9001 quality certification and ISO14001 environmental certification, complying with national standards including GB 50116-2013 and GB4715-2005 for legal and compliant use

8.2 Functional Features of Each Product Series

8.2.1 Detector Series

  • Photoelectric Smoke Detector: Low power consumption, high stability, easy installation and cost-effective; ideal for small computer rooms with high cost performance
  • Smoke-Temperature Composite Detector: Dual-parameter detection, intelligent algorithm, low false alarm rate and IP40 high protection grade; superior electrical fire protection for medium computer rooms
  • Multi-parameter Composite Detector: Triple smoke/temp/CO detection for precise early warning, remote monitoring and IP50 high temperature resistance; preferred for high-value asset protection in large data centers
  • Ultra-early Aspirating Smoke Detector: Ultra-early warning (detects invisible smoke), ultra-high sensitivity, long sampling distance, self-cleaning function and remote monitoring; essential for high-end dust-free computer rooms to eliminate hidden hazards in advance

8.2.2 Manual Alarm Call Point Series

  • Standard Manual Alarm Call Point: Simple structure, sensitive trigger, easy installation, low cost and durable; enables rapid manual emergency alarm
  • Manual Alarm Call Point with Emergency Stop: Multi-functional integration (alarm + stop + telephone), key reset, IP50 high protection and optional explosion-proof design; core emergency disposal equipment for medium & large computer rooms

8.2.3 Sound-Light Alarm Series

  • Standard Fire Sound-Light Alarm: High decibel, high brightness, low power consumption, stable performance and easy installation; effectively guides personnel evacuation
  • Explosion-proof Fire Sound-Light Alarm: Explosion-proof structure, IP65 high protection, high temperature resistance and anti-corrosion with built-in fault self-check; first choice for high-risk premises

8.2.4 Fire Suppression Device Series

  • Cabinet-type FM200 Fire Suppression Device: Pipe-free design, easy installation, fast insulation fire suppression and zero residue; mainstream solution for small computer rooms with moderate cost
  • Pipe Network FM200 Fire Suppression Device: Precise zoned fire suppression, high efficiency, fast speed and large coverage; top choice for medium data centers with multiple rooms
  • IG541 Inert Gas Fire Suppression Device: Clean, environmentally friendly, non-toxic and residue-free with zero equipment damage; ideal for manned high-end core computer rooms
  • Ultra-fine Dry Powder Fire Suppression Device: Low cost, ultra-fast fire suppression, compact size and flexible installation; high cost performance for auxiliary area electrical fire protection

8.2.5 Controller Series

  • Gas Fire Suppression Controller: Dedicated control, adjustable delay, precise linkage and stable performance; core control equipment for gas fire suppression systems with easy installation and low cost
  • Dual Redundant Intelligent Fire Linkage Controller: Dual CPU & dual power backup, custom programmable logic, full-protocol compatibility and automatic fault repair; core of large data center fire-fighting systems ensuring zero downtime

8.2.6 Auxiliary Equipment Series

  • Fire Backup Power Supply: Dual input & dual output redundant backup, ultra-long standby duration and comprehensive protection; guarantees continuous fire system operation under extreme power outages
  • Fire Communication Bus Cable: Flame retardant, fire-resistant, high temperature resistant and anti-interference; ensures uninterrupted signal transmission under high temperature and fire conditions
  • Emergency Lighting & Evacuation Indicators: High brightness, ultra-long emergency duration, intelligent dimming and remote fault reporting; maintains clear evacuation passages during fires
  • Power/AC/Smoke Exhaust Control Cabinets: Intelligent graded linkage, comprehensive protection and remote monitoring; accurately executes linkage actions to block fire spread
  • Security Linkage Module: Multi-protocol compatibility, fast linkage and stable transmission; seamless integration of fire-fighting and security for visual remote fire disposal
  • Fire Telephone: HD noise-free audio, ultra-long transmission distance and stable performance; enables real-time on-site & control room communication for efficient disposal command
  • Remote Monitoring Platform Host: High-performance large-capacity multi-processor with multi-protocol support, intelligent analysis, alarm push and data traceability; core of unattended computer room remote operation and maintenance to cut labor costs

9. Product Tender Control Parameters (Marked with ★)

9.1 Detector Series Tender Control Parameters

9.1.1 Photoelectric Smoke Detector (KITOZER-YG100)

  • ★ Operating Voltage: DC24V (±10%)
  • ★ Sensitivity: 0.15-0.3dB/m (adjustable)
  • ★ Response Time: ≤3s
  • ★ Protection Grade: IP30
  • ★ Executive Standard: GB4715-2005

9.1.2 Smoke-Temperature Composite Detector (KITOZER-YW101)

  • ★ Operating Voltage: DC24V (±10%)
  • ★ Smoke Sensitivity: 0.15-0.3dB/m
  • ★ Temperature Trigger: 57℃±5℃ (fixed temperature)
  • ★ Response Time: ≤3s
  • ★ Protection Grade: IP40
  • ★ Executive Standard: GB4715-2005, GB4716-2005

9.1.3 Multi-parameter Composite Detector (KITOZER-DF102)

  • ★ Operating Voltage: DC24V (±10%)
  • ★ Detection Parameters: Smoke + Temperature + Carbon Monoxide (CO)
  • ★ CO Detection Range: 0-1000ppm, Accuracy ±5%
  • ★ Response Time: ≤2s
  • ★ Protection Grade: IP50
  • ★ Executive Standard: GB4715-2005, GB4716-2005, GB/T21281-2007

9.1.4 Ultra-early High-sensitivity Aspirating Smoke Detector (KITOZER-XQ202)

  • ★ Operating Voltage: DC24V (±10%)
  • ★ Detection Sensitivity: 0.001-0.1dB/m (ultra-high sensitivity)
  • ★ Max Sampling Pipe Length: ≤200m
  • ★ Response Time: ≤0.5s
  • ★ Protection Grade: IP60
  • ★ Executive Standard: GB15631-2008

9.2 Manual Alarm Call Point Series Tender Control Parameters

9.2.1 Manual Fire Alarm Call Point with Emergency Stop (KITOZER-SB202)

  • ★ Operating Voltage: DC24V (±10%)
  • ★ Trigger Mode: Mechanical Press + Emergency Stop
  • ★ Reset Mode: Key Reset
  • ★ Built-in Fire Phone Jack (RJ11)
  • ★ Protection Grade: IP50
  • ★ Executive Standard: GB19880-2005

9.3 Sound-Light Alarm Series Tender Control Parameters

9.3.1 Explosion-proof Fire Sound-Light Alarm (KITOZER-SG302)

  • ★ Operating Voltage: DC24V (±10%)
  • ★ Sound Pressure Level: ≥95dB (3m distance)
  • ★ Explosion-proof Grade: Exd II BT4
  • ★ Protection Grade: IP65
  • ★ Executive Standard: GB4715-2005, GB3836.1-2010

9.4 Fire Suppression Device Series Tender Control Parameters

9.4.1 Pipe Network FM200 Fire Suppression Device (KITOZER-GMP120)

  • ★ Agent Volume: 120L
  • ★ Fire Suppression Medium: FM200 (Purity ≥99.9%)
  • ★ Working Pressure: 4.2MPa (20℃)
  • ★ Injection Time: ≤8s
  • ★ Max Protection Area: ≤200㎡
  • ★ Executive Standard: GB18614-2012, GB50370-2005

9.4.2 IG541 Inert Gas Fire Suppression Device (KITOZER-IG150)

  • ★ Agent Volume: 150L
  • ★ Fire Suppression Medium: IG541 (52%N₂+40%Ar+8%CO₂, Purity ≥99.9%)
  • ★ Working Pressure: 15MPa (20℃)
  • ★ Injection Time: ≤60s
  • ★ Non-toxic, applicable to manned premises
  • ★ Executive Standard: GB20128-2006, GB50370-2005

9.5 Controller Series Tender Control Parameters

9.5.1 Dual Redundant Intelligent Fire Linkage Controller (KITOZER-LK502)

  • ★ Operating Voltage: DC24V (±10%, dual redundant power supply)
  • ★ Bus Loop Quantity: 4 Loops
  • ★ Max Load Points: 240 (detectors, modules, equipment)
  • ★ Dual CPU redundancy with automatic fault diagnosis & repair
  • ★ Communication Protocols: RS485+TCP/IP+CAN Bus+BACnet
  • ★ Executive Standard: GB4717-2005, GB16806-2006

9.6 Auxiliary Equipment Series Tender Control Parameters

9.6.1 Industrial Dual Redundant Fire Backup Power Supply (KITOZER-DY602)

  • ★ Input: Dual AC220V±15% mains power
  • ★ Output: Dual DC24V/20A redundant output
  • ★ Full load backup duration: ≥24h
  • ★ Battery Specification: 12V/100Ah×4 lead-acid maintenance-free
  • ★ Protection Functions: Overvoltage, Overcurrent, Short Circuit, Undervoltage, Lightning, Surge Protection
  • ★ Executive Standard: GB17945-2010

9.6.2 HD Touch Graphic Display Device for Fire Control Room (KITOZER-TX602)

  • ★ Screen Size: 21.5-inch touch screen
  • ★ Resolution: 1920×1080
  • ★ Operating System: Embedded Linux
  • ★ Display Content: 3D computer room floor plan, real-time equipment status, alarm positioning, linkage process
  • ★ Communication Interfaces: RJ45×2 (TCP/IP), RS485×2, BACnet
  • ★ Executive Standard: GB17255-2009

10. Full Product Solutions

10.1 Small Single Computer Room Fire Linkage Solution (≤50㎡)

10.1.1 Pain Points

  • Small area with limited budget
  • Concentrated servers and switches with high electrical fire risks
  • Unattended, requiring basic alarm and fire suppression functions
  • Avoid residue damage to equipment from fire suppression agents

10.1.2 Solution (Low Configuration List)

  • Front-end Detection: 6 photoelectric smoke detectors + 2 manual alarm call points for smoke monitoring and manual alarm trigger
  • Core Control: 1 simple fire linkage controller + 1 gas fire suppression controller for signal reception and logical linkage
  • Fire Suppression Disposal: 1 set of 70L cabinet-type FM200 fire suppression device; pipe-free design delivers fast residue-free fire suppression
  • Linkage Execution: 1 sound-light alarm + 1 power cut-off module for evacuation alert and non-fire power cut-off
  • Auxiliary Support: 1 set of fire backup power supply + 50m fire bus cable to guarantee power failure operation and stable signal transmission

10.1.3 Solution Advantages

  • Low Cost: Low configuration with high cost performance and controllable budget
  • Easy Installation: Pipe-free fire suppression device + wall-mounted equipment; installation & commissioning completed within 3-5 days
  • Simple Operation: Auto/manual dual mode without professional on-site staff
  • Comprehensive Protection: Clean FM200 fire suppression protects core equipment without residue damage

10.2 Medium Multi-computer Room Fire Linkage Solution (50-200㎡)

10.2.1 Pain Points

  • Multi-zoned computer rooms (server zone, network zone, power distribution room) requiring zoned protection
  • Large quantity of high-power equipment with high electrical fire risks demanding precise early warning
  • Partial manned areas requiring balance of fire suppression and personal safety
  • Need linkage of air conditioning, access control and security to build integrated protection
  • Local visual monitoring required for convenient operation and maintenance

10.2.2 Solution (Medium Configuration List)

  • Front-end Detection: 15 smoke-temperature composite detectors + 2 sets of ultra-early aspirating detectors + 4 manual alarm call points +