Manufacturer: Guangdong Lain Intelligent Equipment Room Equipment Co., Ltd.
Document Version: V3.0
Release Date: July 2026
Applicable Standards: GB/T 12190-2006, BMB19-2006, GB 50174-2017, GJB 5792-2006
Table of Contents
TogglePreface

This manual is compiled for the LA-PB series intelligent shielded integrated cabinets independently developed and manufactured by Guangdong Lain Intelligent Equipment Room Equipment Co., Ltd. It covers the full life cycle of the product, including technical specifications, installation guidance, wiring standards, commissioning methods, maintenance, and fault handling, aiming to provide users, integrators, construction personnel, and operation & maintenance staff with comprehensive, professional, and actionable operating guidelines.
The intelligent shielded integrated cabinet is a new-generation confidential information protection device that integrates electromagnetic shielding, intelligent environment & power monitoring (EPMS), power distribution management, ventilation and heat dissipation, and access control security. Designed based on the Faraday cage electromagnetic shielding theory, it adopts a fully welded high-conductivity shielding cavity structure, combined with multi-stage filter interfaces and an intelligent management and control system, achieving all-round blocking of electromagnetic leakage emissions from internal electronic equipment while resisting external strong electromagnetic interference. It is widely used in party and government agencies, military units, financial institutions, research institutes, and other scenarios with high requirements for information security and electromagnetic compatibility.
The content of this manual strictly complies with relevant national standards and industry specifications, and all operating procedures have been validated through extensive engineering practice. Users must read the full document carefully before operation and strictly follow the specifications. Improper operation may result in reduced shielding effectiveness, equipment damage, or even safety accidents. The content of this manual will be continuously updated with product technology iterations. The final interpretation right belongs to Guangdong Lain Intelligent Equipment Room Equipment Co., Ltd.
Table of Contents

1. Product Introduction
2. Product Composition
3. Product List
4. Product Working Principles
5. Product Technical Parameters
6. Product Functions and Features
7. Product Application Scenarios
8. Product Installation Specifications
9. Product Wiring Specifications
10. Product Commissioning Process
11. Product Usage Precautions
12. Product Repair and Maintenance
13. Product Common Problems and Solutions
14. Product Q&A
15. Product Acceptance Standards
16. SEO Optimization System and Keywords
17. Copyright Statement and Contact Information
Chapter 1 Product Introduction

1.1 Development Background
With the rapid development of information technology, electronic equipment has become increasingly deeply applied in core fields such as government affairs, military, finance, and energy. Electromagnetic security has become a critical link that cannot be ignored in the information security system. On one hand, computers, servers, switches, and other electronic equipment generate electromagnetic leakage emissions during operation. These emission signals carry sensitive information processed by the equipment and can be received and restored by specialized equipment at distances of hundreds of meters or even several kilometers, causing information leakage. On the other hand, external strong electromagnetic interference, electromagnetic pulses, lightning surges, etc., can affect stable equipment operation and, in severe cases, cause equipment damage, system paralysis, and data loss.
Traditional ordinary server cabinets only provide physical load-bearing and basic protection functions and cannot solve electromagnetic leakage and interference problems. Traditional shielded cabinets have single functions and lack intelligent management and control capabilities, failing to meet the needs of modern equipment rooms for centralized management, remote monitoring, and intelligent operation and maintenance. Against this background, Guangdong Lain Intelligent Equipment Room Equipment Co., Ltd., combining more than ten years of R&D experience in electromagnetic shielding and equipment room equipment, has launched the LA-PB series intelligent shielded integrated cabinets, deeply integrating high-performance electromagnetic shielding technology with IoT intelligent monitoring technology to create a “security + intelligence” integrated electromagnetic protection solution.
1.2 Product Definition
The intelligent shielded integrated cabinet is an integrated cabinet device that uses high-conductivity, high-permeability metal materials to construct a fully enclosed shielding cavity. It achieves electromagnetic shielding functions through structural sealing, interface filtering, and reliable grounding, while integrating intelligent power distribution, temperature and humidity monitoring, access control management, smoke detection, water leakage detection, remote management and control, and other functions. It can effectively suppress the leakage of electromagnetic signals from internal equipment to the outside, preventing information theft, and also block external strong electromagnetic interference from entering the cabinet, ensuring stable equipment operation. Through the intelligent system, it achieves real-time perception and centralized management of cabinet operating status.
1.3 Design Philosophy
This product is designed around the core philosophy of “high security, high reliability, high intelligence, and easy maintenance”:
Security First: Using national confidential-grade shielding effectiveness as the baseline standard, shielding performance is controlled throughout the entire process from material selection, structural design, process manufacturing, to installation and commissioning, ensuring the electromagnetic security baseline.
Reliable and Durable: Industrial-grade components and mature structural design are adopted, passing stringent environmental reliability testing to adapt to various complex operating conditions and ensure long-term stable operation.
Intelligent Integration: Environment and power monitoring, power distribution management, security access control, and other functions are deeply integrated to avoid third-party device external mounting that could compromise shielding integrity, achieving integrated management and control.
Convenient Operation and Maintenance: Standardized modular design allows for quick replacement of key components, with comprehensive fault diagnosis and O&M guidance to reduce maintenance difficulty and cost.
1.4 Applicable Standards
The design, production, testing, and acceptance of this product strictly comply with the following national and industry standards:
- GB/T 12190-2006 “Measurement methods for shielding effectiveness of electromagnetic shielding enclosures”
- BMB19-2006 “Technical requirements and test methods for electromagnetic leakage emission shielded cabinets”
- GB 50174-2017 “Code for design of data centers”
- GJB 5792-2006 “General specification for military electromagnetic shielding enclosures”
- GB/T 2887-2011 “General specification for computer field”
- GB 7251.1-2013 “Low-voltage switchgear and controlgear assemblies – Part 1: General rules”
- GB/T 17626 “Electromagnetic compatibility – Testing and measurement techniques” series standards
- YD/T 2319-2011 “Technical requirements and test methods for electromagnetic shielding cabinets for communication equipment”
1.5 Product Series and Positioning
The LA-PB series intelligent shielded integrated cabinets are divided into multiple sub-series according to shielding level, functional configuration, and dimensional specifications, covering different scenario requirements:
- LA-PB-C Series: Confidential-grade Type C, meeting BMB19-2006 Class C standard, suitable for general classified information systems and internal office confidential scenarios.
- LA-PB-B Series: Confidential-grade Type B, meeting BMB19-2006 Class B standard, suitable for important classified departments, general military units, and financial core outlets.
- LA-PB-A Series: Military/top-secret grade, meeting GJB and higher shielding requirements, suitable for core military units, top-secret information processing scenarios, and electromagnetic pulse protection scenarios.
- LA-PB-INT Series: Industrial-grade shielded cabinets, optimized for industrial control scenarios, suitable for factory automation, rail transit, power dispatching, and other strong interference environments.
Chapter 2 Product Composition
The LA-PB series intelligent shielded integrated cabinets feature modular integrated design, consisting of six core systems: the shielded cabinet body system, intelligent management and control system, power distribution and filtering system, ventilation and heat dissipation system, access control and locking system, and internal load-bearing and auxiliary system. Each system operates independently while working collaboratively to form a complete shielding and intelligent management architecture.
2.1 Shielded Cabinet Body System
The shielded cabinet body system is the core entity that implements the electromagnetic shielding function. It is a six-sided fully enclosed metal cavity structure and serves as the foundation for load-bearing and shielding.
2.1.1 Cabinet Main Shell
The main shell is formed from high-quality cold-rolled steel plates using fully automated robotic argon arc welding. Different shielding grades use different plate thicknesses: Class C uses 1.5mm thick cold-rolled steel plates, Class B uses 2.0mm thick cold-rolled steel plates, and Class A uses a 2.5mm double-layer composite steel plate structure. Continuous full-penetration welding is employed with no weld interruptions, cold welds, or porosity. After welding, the surface is ground, shaped, and treated with conductive passivation to ensure overall electrical continuity of the shell, with surface resistance ≤ 2.5mΩ/m².
The shell structure uses a nine-fold (roll-formed) profile reinforced frame, welded as one piece with the shell, greatly enhancing structural strength. The static load-bearing capacity reaches 1500kg or more, meeting the load-bearing requirements of high-density servers, storage devices, and other heavy equipment, while providing seismic resistance up to Magnitude 8. The outer surface of the shell undergoes multiple anti-corrosion treatments including acid washing, phosphating, and electrostatic powder coating. The coating has strong adhesion, is resistant to acid and alkali corrosion, and has a smooth and aesthetically pleasing appearance. The inner surface is treated with conductive oxidation to ensure electrical continuity inside the cavity.
2.1.2 Shielded Door Assembly
The shielded door is the only openable component of the shielding cavity and is also one of the weakest points in shielding performance. Its sealing performance directly determines the overall shielding effectiveness. This product adopts a knife-edge insertion-type shielded door structure, consisting of the door body, door frame, conductive sealing components, hinge mechanism, and locking mechanism.
- Door Body: Formed by welding steel plates of the same thickness as the shell, with internal reinforcing ribs to prevent door deformation.
- Door Frame: Precision-machined, welded to the shell as one piece after installation, with flatness ≤ 0.3mm/m.
- Conductive Sealing Components: High-elasticity silver-plated beryllium copper contact fingers are embedded around the door frame. Stainless steel knife edges are provided at corresponding positions on the door body. When the door is closed, the knife edges insert into the contact finger grooves, forming a continuous circumferential conductive contact with contact resistance ≤ 10mΩ. The beryllium copper contact fingers have excellent elasticity and conductivity, with performance degradation ≤ 5% after 10,000 open/close cycles, and are resistant to oxidation and wear.
- Hinge Mechanism: Heavy-duty load-bearing hinges, with 3 sets of hinges per single door, providing strong load capacity, smooth opening and closing, and no sagging with long-term use.
- Locking Mechanism: Three-point locking structure. Rotating the handle drives the upper, lower, and side locking bolts to engage simultaneously, ensuring uniform pressure around the door perimeter and consistent compression of the contact fingers, avoiding local poor contact.
2.1.3 Ventilation Waveguide Windows
To meet the heat dissipation requirements of equipment inside the cabinet, ventilation openings are required. Ordinary openings would cause severe electromagnetic leakage; therefore, cutoff waveguide-type ventilation windows are used to achieve both ventilation and shielding.
The waveguide windows adopt a honeycomb structure composed of numerous hexagonal waveguide tubes welded together. Utilizing the waveguide cutoff principle, when the electromagnetic wave wavelength is greater than the waveguide cutoff wavelength, the wave cannot pass through the waveguide tubes. This blocks electromagnetic wave propagation while allowing air circulation. This product is standardly equipped with 304 stainless steel honeycomb waveguide windows. The cutoff frequency is designed according to the shielding grade, with ventilation rate ≥ 60%, low wind resistance, and no impact on heat dissipation efficiency.
The cabinet is typically equipped with two sets of waveguide windows: intake and exhaust. The intake window is located at the lower part of the cabinet, and the exhaust window is at the upper part, forming a natural convection air path. Models with intelligent cooling are equipped with axial fans on the exhaust side, forming a forced air-cooling system. The waveguide windows are connected to the cabinet body via flanges, with conductive gaskets filled at the contact surfaces to ensure electrical continuity at the connection and eliminate electromagnetic leakage gaps.
2.1.4 Shielding Interface Components
All wiring that penetrates the shielding shell can become an electromagnetic leakage path. Therefore, all power and signal interfaces must be connected through dedicated shielding interface devices, mainly including:
- Power Filters: Provide conducted interference filtering for power lines entering and exiting the cabinet, suppressing electromagnetic interference conduction on the lines.
- Signal Filters: Provide filtering and shielded transition for network cables, serial ports, fiber optics, and other signal lines. Types include RJ45 signal filters, RS232/485 signal filters, and fiber optic waveguides.
- Shielded Cable Entry Plates: Used for entry of a small number of non-standard cables, equipped with conductive sealing putty. After cable entry, the plate is sealed to ensure shielding performance.
- Grounding Terminals: Dedicated grounding copper busbar on the shell for connection to the cabinet grounding system.
2.1.5 Seam and Penetration Treatment
All assembly seams and component installation joints of the cabinet use conductive sealing treatment: fixed joints use conductive gaskets with compression or continuous welding; removable component joints use beryllium copper contact fingers, conductive foam, or conductive rubber seals. All shell penetration points use shielded sealing structures to ensure electrical continuity at the penetration point with no leakage points.
2.2 Intelligent Management and Control System
The intelligent management and control system is the “brain” of the intelligent shielded integrated cabinet, achieving comprehensive perception, analysis, control, and alarm of the cabinet operating status. It consists of the environment and power monitoring (EPMS) host, various sensors, human-machine interface, and remote communication modules.
2.2.1 EPMS Monitoring Host
An industrial-grade embedded host is used, featuring low power consumption and high reliability, equipped with dedicated monitoring software. It provides data acquisition, logic processing, alarm output, data storage, and remote communication functions. The host supports multiple analog and digital signal inputs and can simultaneously acquire data from various sensors including temperature/humidity, smoke, water leakage, door magnetic status, voltage, and current. Built-in storage can save no less than 1 year of historical operating data, supporting data query and export.
2.2.2 Environmental Monitoring Sensors
- Temperature and Humidity Sensors: High-precision digital temperature and humidity sensors installed at different positions (upper, middle, lower) inside the cabinet for real-time monitoring of internal temperature and relative humidity. Measurement accuracy: temperature ±0.5°C, humidity ±3%RH. Monitoring range: temperature -10°C to 80°C, humidity 0 to 100%RH.
- Smoke Detectors: Photoelectric smoke sensors installed at the top of the cabinet for real-time smoke detection. Response time ≤ 10s, with anti-false-alarm design. Upon smoke detection, an audible and visual alarm is immediately triggered and alarm information is uploaded.
- Water Leakage Sensors: Cable-type or point-type water leakage sensors deployed at the bottom of the cabinet and at air conditioner water inlet positions to monitor for liquid leakage. High detection sensitivity, immediate alarm upon water contact, preventing liquid damage to equipment.
- Access Control and Door Magnetic Sensors: Door magnetic sensors monitor the cabinet door opening/closing status in real time and record opening time and frequency. Combined with the access control system, they implement door opening permission management.
2.2.3 Human-Machine Interface Unit
The front door of the cabinet is equipped with a 7-inch color touchscreen display, located in the visible area at the upper part of the door. Cabinet operating status can be viewed without opening the door. The display uses an industrial-grade touchscreen with adjustable brightness and an intuitive interface. It can display real-time temperature/humidity, voltage/current, equipment operating status, alarm information, etc., and supports touch operation for parameter setting, historical data query, and system commissioning.
2.2.4 Communication and Alarm Module
- Wired Communication: Standard RJ45 Ethernet interface, supporting TCP/IP protocol, can be connected to the equipment room EPMS system for centralized management.
- Wireless Communication: Optional 4G/5G, WiFi, and other wireless communication modules for remote cloud monitoring.
- Alarm Output: Supports multiple alarm methods including audible/visual alarm, SMS alarm, email alarm, and platform alarm. Alarm thresholds are user-configurable, with graded alarm management and priority push for important alarms.
- Dry Contact Output: Multiple dry contact interfaces are reserved for linking with third-party fire protection and security systems.
2.3 Power Distribution and Filtering System
The power distribution and filtering system is responsible for power distribution, surge protection, and power filtering for equipment inside the cabinet. It ensures safe and reliable power supply while blocking electromagnetic conducted leakage through power lines.
2.3.1 Power Filters
The power filter is the core component for blocking electromagnetic conducted leakage through power lines. It uses a multi-stage filter circuit design, including common-mode filtering, differential-mode filtering, and surge suppression units, providing good suppression of conducted interference in the 14kHz to 10GHz frequency band. Insertion loss meets the requirements of the corresponding shielding grade.
Filters are divided into single-phase and three-phase types, selected according to the total cabinet power, with rated current coverage from 10A to 100A. The filter housing uses a metal shielding structure. During installation, the housing must be reliably connected to the cabinet shielding shell, and the grounding terminal is separately connected to the grounding copper busbar to ensure filtering effectiveness. The filter input side is located outside the shielding enclosure, and the output side is inside, with input and output lines physically isolated to avoid coupling interference.
2.3.2 Intelligent PDU Power Distribution Unit
A rack-mounted intelligent PDU (Power Distribution Unit) is configured inside the cabinet, using standard 19-inch mounting, providing multiple national standard (GB) or IEC power outlets for powering equipment in the cabinet. The intelligent PDU features voltage, current, power, and energy metering functions, can remotely monitor the power supply status of each outlet, and supports overload alarm and short-circuit protection. Some high-end models support remote on/off control for remote power-up/power-down management.
The PDU uses a flame-retardant housing with built-in overload protection switch and lightning/surge protection module. The input cable uses a flame-retardant shielded cable connected to the output terminal of the power filter.
2.3.3 Surge Protection and Electrical Protection
The power distribution system is equipped with two-stage surge protective devices (SPD). The first stage is at the main power entrance, and the second stage is at the front end of the PDU, effectively suppressing lightning surges and switching overvoltages to protect precision electronic equipment inside the cabinet. Multiple electrical protections are also configured, including air circuit breakers, residual current circuit breakers (RCD), and overload protectors, ensuring electrical safety.
2.4 Ventilation and Heat Dissipation System
The ventilation and heat dissipation system ensures that equipment inside the cabinet operates in a suitable temperature and humidity environment, preventing equipment from thermal throttling or damage due to overheating. It is divided into two types: natural heat dissipation and intelligent forced-air cooling.
2.4.1 Natural Heat Dissipation System
Relies on the natural air path formed by the upper and lower waveguide windows, using the principle of hot air rising to achieve natural convection heat dissipation. Suitable for scenarios with low equipment heat generation and low power density. A dust filter screen is configured at the lower part of the intake window to block dust from entering the cabinet. The dust filter screen can be pulled out for cleaning.
2.4.2 Intelligent Forced-Air Cooling System
Consists of axial fan units, temperature control module, and air path structure. The fans are low-noise industrial axial fans installed on the inner side of the top exhaust waveguide window, with exhaust direction upward. The temperature control module automatically adjusts fan speed or on/off status based on the internal temperature of the cabinet, achieving intelligent temperature control that ensures heat dissipation effectiveness while reducing energy consumption and noise.
The fans use vibration-dampening mounting to avoid noise generation and structural loosening from vibration. The air path is optimized to form an orderly bottom-to-top airflow to reduce local hot spots. Fan power is provided by the intelligent PDU, and operating status is connected to the EPMS system with automatic alarm upon fan failure.
2.4.3 Air Conditioning Cooling System (Optional)
For high power density scenarios, a rack-mounted precision air conditioner is optional, installed inside or beside the cabinet for precise temperature control. The air conditioning system also undergoes shielding adaptation treatment, with refrigerant lines and drain pipes passing through the cabinet through dedicated waveguides or shielded sealing components, without compromising shielding performance.
2.5 Access Control and Locking System
The access control and locking system ensures physical access security of the cabinet, preventing unauthorized personnel from opening the cabinet door, while recording door opening logs for traceability of access.
2.5.1 Mechanical Lock
Standard configuration includes a high-security mechanical anti-theft lock with dedicated keys. The lock body has a robust structure, resistant to picking and technical opening. It serves as the basic access control and emergency opening method—when power is off or the electronic access control fails, the door can be opened with the mechanical key.
2.5.2 Electronic Access Control System (Standard/Optional)
Standard configuration includes fingerprint + password access control, with optional card swipe or facial recognition access control. The access controller is installed inside the cabinet, the card reader is installed outside the door, and wiring passes through shielding interfaces. The access control system supports multi-user management, allows setting different permission levels, and records all door opening events including personnel, time, and opening method. Data can be queried and exported. The access control system has tamper-proof alarm functionality, triggering an alarm upon forced disassembly.
2.5.3 Electromagnetic Lock and Door Magnetic Sensor
An electromagnetic lock is configured as auxiliary locking, automatically engaging after door closure, working with the access control system for electrically controlled door opening/closing. Door magnetic sensors detect the door open/closed status in real time, and an alarm is immediately triggered upon abnormal door opening.
2.6 Internal Load-Bearing and Auxiliary System
2.6.1 Mounting Rails
The cabinet is equipped with four standard 19-inch mounting rails made of high-quality steel plate formed by bending, with galvanized surface treatment for good conductivity. The rails feature U-shaped mounting holes with hole spacing conforming to standard U-position dimensions, allowing flexible adjustment of equipment mounting height. The front and rear positions of the rails are adjustable to accommodate equipment of different depths.
2.6.2 Load-Bearing Shelves
Standard configuration includes fixed shelves and sliding shelves, formed by stamping 1.2mm thick cold-rolled steel plates with powder coating surface treatment. Single shelf load capacity ≥ 150kg. Shelves can be flexibly adjusted in mounting position as needed, used for placing servers, switches, displays, and other equipment. Sliding shelves are equipped with silent slide rails for smooth drawer-like operation, used for placing keyboards, mice, and other operation equipment.
2.6.3 Cable Management and Wiring Accessories
- Vertical Cable Managers: Installed on both sides of the mounting rails for organizing cables inside the cabinet, keeping wiring neat and orderly.
- Horizontal Cable Management Rings: Installed above and below equipment to guide cable routing.
- Cable Ties and Cable Clips: Used for cable fixation.
- Grounding Copper Busbar: A dedicated grounding copper busbar is provided inside the cabinet for grounding connections of equipment enclosures, shielding layers, filters, etc.
2.6.4 Other Accessories
- Cabinet Feet and Casters: Adjustable heavy-duty support feet at the bottom for leveling the cabinet and load-bearing. Heavy-duty casters are optional for cabinet mobility.
- Lighting System: LED lighting is installed at the top inside the cabinet, automatically turning on when the door opens and off when the door closes, facilitating operation and maintenance.
- Blank Panels: 1U/2U shielded blank panels for covering unused U-positions, optimizing airflow, and reducing electromagnetic leakage.
Chapter 3 Product List
3.1 Standard Configuration List
Taking the LA-PB-B-42U standard model as an example, the standard factory configuration is as follows:
| No. | Component Name | Specification/Model | Qty | Unit | Remarks |
|---|---|---|---|---|---|
| 1 | Shielded cabinet body | LA-PB-B-42U, 2000×700×900mm (H×W×D) | 1 | Set | Includes shielding shell and nine-fold profile frame |
| 2 | Shielded door assembly | Single-door knife-type shielded door with beryllium copper contact finger seal | 1 | Set | Includes door frame, door body, hinges, three-point locking mechanism |
| 3 | Intake waveguide window | 304 stainless steel honeycomb waveguide window, 300×300mm | 2 | Pcs | Lower left and right sides of cabinet |
| 4 | Exhaust waveguide window | 304 stainless steel honeycomb waveguide window, 300×300mm | 1 | Pcs | Top of cabinet |
| 5 | Single-phase power filter | 220V/32A, multi-stage filtering, Class B | 1 | Unit | Power input filtering |
| 6 | RJ45 signal filter | 8-port, gigabit network filtering | 1 | Unit | Network signal filtering |
| 7 | EPMS monitoring host | LA-MON-100, embedded industrial host | 1 | Unit | Includes data acquisition, storage, communication functions |
| 8 | Temperature/humidity sensor | High-precision digital type | 2 | Pcs | Upper and lower inside cabinet |
| 9 | Smoke detector | Photoelectric type, DC12V power supply | 1 | Pcs | Top of cabinet |
| 10 | Water leakage sensor | Point type, adjustable sensitivity | 1 | Pcs | Bottom of cabinet |
| 11 | 7-inch touchscreen display | Industrial-grade capacitive touch | 1 | Unit | Mounted on outside of front door |
| 12 | Intelligent PDU | 19-inch, 8-position 10A GB outlets, with metering | 1 | Unit | Vertical mounting |
| 13 | Intelligent forced-air cooling system | 4 axial fans, temperature-controlled speed regulation | 1 | Set | Top mounting |
| 14 | Access control system | Fingerprint + password + mechanical lock, three-in-one | 1 | Set | Includes card reader, controller, electromagnetic lock |
| 15 | 19-inch mounting rails | 42U, front/rear adjustable | 4 | Pcs | Galvanized |
| 16 | Fixed shelf | 19-inch, load capacity 150kg | 3 | Pcs | Standard configuration |
| 17 | Sliding keyboard shelf | 19-inch, with slide rails | 1 | Pcs | Standard configuration |
| 18 | Cable manager | Vertical cable manager | 2 | Pcs | One on each left/right rail |
| 19 | Grounding copper busbar | 30×3mm copper, tin-plated | 1 | Pcs | Bottom inside cabinet |
| 20 | LED lighting | DC12V, with door-operated switch | 2 | Lamps | Top inside cabinet |
| 21 | Adjustable support feet | M16 heavy-duty adjustable feet | 4 | Pcs | Bottom of cabinet |
| 22 | Shielded blank panels | 1U shielded type | 10 | Pcs | Cover unused U-positions |
| 23 | Dedicated keys | Mechanical lock keys | 3 | Pcs | 2 in regular use, 1 spare |
3.2 Optional Configuration List
| No. | Component Name | Specification Description | Applicable Scenario |
|---|---|---|---|
| 1 | Three-phase power filter | 380V/63A/100A | High-power equipment configuration |
| 2 | Fiber optic waveguide | Single-mode/multi-mode, 6-channel/12-channel | Fiber optic access scenarios |
| 3 | Serial port signal filter | RS232/RS485, multi-channel | Industrial control signal access |
| 4 | Video signal filter | BNC/VGA/HDMI | Video signal access |
| 5 | Rack-mounted UPS | 1kVA/3kVA/6kVA | Backup power supply requirements |
| 6 | Rack-mounted precision air conditioner | 3kW/5kW cooling capacity | High power density heat dissipation |
| 7 | Heptafluoropropane gas fire suppression module | Cabinet-type automatic fire suppression | High-level fire protection requirements |
| 8 | Facial recognition access control | Face recognition door opening, liveness detection | High security level scenarios |
| 9 | 4G wireless communication module | Full network compatible, remote alarm | Scenarios without wired network |
| 10 | Heavy-duty casters | 4 swivel casters, 2 with brakes | Scenarios requiring mobility |
| 11 | Shielded cable entry plate | 100×100mm, with sealing putty | Non-standard cable entry |
| 12 | Vibration-damping base | Spring shock absorbers, isolation efficiency ≥ 80% | Strong vibration environments |
3.3 Accompanying Documents and Tools
| No. | Name | Qty | Remarks |
|---|---|---|---|
| 1 | This installation and commissioning manual | 1 copy | Paper version |
| 2 | Product certificate of conformity | 1 copy | Includes factory inspection records |
| 3 | Third-party shielding effectiveness test report | 1 copy | Photocopy; original shipped with goods or separately |
| 4 | Product warranty card | 1 copy | Effective after completion |
| 5 | Electrical schematic and wiring diagrams | 1 set | Paper version |
| 6 | Dedicated hex wrench set | 1 set | For installation and commissioning |
| 7 | Conductive cleaning cloth | 2 pcs | For cleaning contact fingers |
| 8 | Spare conductive gasket | 1 meter | For emergency repair |
| 9 | Grounding terminals and bolt kit | 1 set | For grounding installation |
3.4 Acceptance and Verification Notes
1. Upon product arrival, please check item by item against the above lists, verifying quantity, model, and appearance integrity of components, and checking for any transportation damage.
2. If shortages, wrong items, or damage are found, please retain the packaging and contact our after-sales personnel within 24 hours.
3. Optional configurations are based on actual order selection, subject to the contract configuration list.
4. Please keep the accompanying documents properly as the basis for subsequent acceptance, warranty, and O&M.
Chapter 4 Product Working Principles
4.1 Core Theoretical Basis of Electromagnetic Shielding
The shielding function of the intelligent shielded integrated cabinet is based on classical electromagnetic theory, with the Faraday cage principle at its core, combined with the attenuation mechanisms of electromagnetic wave reflection, absorption, and multiple reflections, as well as auxiliary technologies such as cutoff waveguides, filtering, and grounding, together achieving full-band electromagnetic shielding.
4.1.1 Faraday Cage Principle
The Faraday cage principle is the core theory of electromagnetic shielding: for a closed shell made of conductive material, when placed in an external electromagnetic field, induced charges and induced currents are generated on the shell surface. The secondary electromagnetic field generated by these induced charges and currents cancels the external electric field component inside the shell, thereby making the internal space of the shell unaffected by external electromagnetic fields. Similarly, electromagnetic fields generated by internal equipment are also blocked by the shell and cannot leak to the outside.
The fully welded metal shell of this product is essentially a high-performance Faraday cage. By ensuring electrical continuity of the shell, minimizing gap leakage, and treating cable penetrations, shielding effectiveness close to that of an ideal Faraday cage is achieved.
4.1.2 Three Mechanisms of Electromagnetic Wave Shielding
When an electromagnetic wave is incident on a metal shielding body, its energy attenuation consists of three components: reflection loss, absorption loss, and multiple reflection loss. The total shielding effectiveness is the sum of these three.
- Reflection Loss:
When an electromagnetic wave is incident from air onto a metal surface, due to the enormous difference in wave impedance between air and metal, most of the electromagnetic wave energy is reflected back at the interface and cannot enter the metal interior. Reflection loss is the primary attenuation method for low-frequency electric fields and high-frequency electromagnetic waves. The higher the metal conductivity, the greater the reflection loss. The cold-rolled steel plates, copper contact fingers, and other materials used in this product are all high-conductivity materials with excellent reflection loss capability.
Reflection loss is related to electromagnetic wave frequency: in the low-frequency band, the magnetic field wave impedance is low, resulting in small reflection loss; in the high-frequency band, the electric field and plane wave impedance is high, resulting in large reflection loss. Therefore, low-frequency magnetic field shielding requires higher material permeability to supplement absorption loss.
- Absorption Loss:
Electromagnetic waves that are not reflected and enter the metal interior generate Joule heat through eddy current effects during propagation, converting electromagnetic energy into heat energy that is dissipated. This process is called absorption loss. Absorption loss increases with metal thickness, conductivity, permeability, and electromagnetic wave frequency.
For low-frequency magnetic fields, ordinary conductive materials have insufficient absorption loss. Therefore, high-grade shielding products use high-permeability materials (such as permalloy and silicon steel) for composite shielding, guiding the magnetic circuit through high-permeability materials to increase absorption loss. The composite steel plate structure used in the Class A model of this product includes a high-permeability layer to enhance low-frequency magnetic shielding effectiveness.
- Multiple Reflection Loss:
When the shielding body is thin, electromagnetic waves entering the metal reflect again when reaching the second interface. Part of the energy reflects back to the first interface, forming multiple reflections and absorptions. For thick shielding bodies, electromagnetic waves are essentially absorbed before reaching the second interface, and multiple reflection loss is negligible. For thin shielding bodies and gap structures, multiple reflection loss is an important supplement.
4.1.3 Gap Leakage Principle
An ideal seamless and aperture-free metal shell has extremely high shielding effectiveness. However, actual cabinets have gaps and apertures such as cabinet door seams, ventilation openings, and cable entry points, which are the main causes of reduced shielding effectiveness.
Leakage rules for electromagnetic waves through gaps: When the gap length is greater than 1/20 of the electromagnetic wave wavelength, significant electromagnetic leakage occurs. The longer and wider the gap, the more severe the leakage. For the same area, the greater the number of apertures and the smaller the individual size, the less the leakage. Therefore, one of the core aspects of shielding design is controlling the size and number of all gaps, converting gaps into continuous conductive contact surfaces through conductive sealing components to eliminate leakage paths.
The shielded door of this product uses circumferential continuous beryllium copper contact fingers, dividing the door seam into numerous microscopic contact gaps far smaller than 1/20 of the wavelength in the operating frequency band, effectively suppressing leakage. Ventilation openings use honeycomb waveguide structures, where the cutoff wavelength of each hexagonal aperture is greater than the operating wavelength, preventing electromagnetic waves from passing through.
4.2 Conducted Interference Suppression Principle
Electromagnetic interference not only propagates through spatial radiation but also through cables such as power lines and signal lines, known as conducted interference. If only spatial shielding is performed without treating cable conduction, the shielding effectiveness will be greatly compromised.
4.2.1 Power Filtering Principle
The power filter is a passive low-pass network that allows DC or 50Hz power frequency current to pass through while presenting high impedance to high-frequency electromagnetic interference signals, thereby suppressing conducted interference in power lines. The power filter of this product uses a multi-stage LC filter structure, including common-mode chokes, differential-mode inductors, X capacitors, and Y capacitors:
- Common-mode choke: Suppresses common-mode interference between phase wire, neutral wire, and ground wire.
- Differential-mode inductors and X capacitors: Suppress differential-mode interference between phase wire and neutral wire.
- Y capacitors: Connected between phase/neutral wire and ground, filtering common-mode interference.
The filter must be reliably grounded to achieve optimal performance. The lower the grounding impedance, the better the filtering effect. At the same time, the filter input and output must be physically isolated to avoid input-output line coupling that could render the filtering ineffective.
4.2.2 Signal Filtering Principle
Signal filters are designed for different types of signals. Under the premise of ensuring normal transmission of useful signals, they suppress high-frequency electromagnetic interference on signal lines. Taking the RJ45 network filter as an example, it integrates an isolation transformer and common-mode filtering network internally, with minimal attenuation for network signals below gigabit speeds, while effectively suppressing high-frequency common-mode interference and blocking the electromagnetic leakage path of signal lines.
For fiber optic signals, since optical signals do not conduct electromagnetic interference, fiber optic waveguides are sufficient. The waveguide utilizes the cutoff principle to block electromagnetic waves while allowing optical signals to pass through.
4.3 Grounding System Working Principle
Grounding is an indispensable component of the electromagnetic shielding system. Its functions are mainly reflected in:
- Discharging induced charges: Induced charges and currents on the shielding shell are rapidly conducted to earth through the grounding system, maintaining the shell at zero potential and enhancing shielding effectiveness.
- Ensuring filtering effectiveness: The filter capacitors of the filter require a grounding path; poor grounding will cause a significant drop in filtering performance.
- Electrical safety protection: Equipment metal enclosures are grounded to prevent electric shock accidents from leakage.
- Lightning and surge discharge: Surge protective devices discharge lightning currents and surge currents to earth through grounding.
This product requires grounding resistance ≤ 1Ω, using a combination of single-point grounding and equipotential bonding to avoid grounding loop interference. The cabinet shielding shell, filter grounding terminals, equipment enclosures, and PDU grounding terminals are all connected to the cabinet’s internal grounding copper busbar, which is then connected via a single point to the equipment room grounding system.
4.4 Intelligent Management and Control System Working Principle
The intelligent management and control system adopts a four-layer architecture of “Perception Layer – Transmission Layer – Processing Layer – Application Layer”:
- Perception Layer: Various sensors collect physical quantities such as temperature, humidity, smoke, water leakage, voltage, current, and door status inside the cabinet in real time, converting them into electrical signals for upload.
- Transmission Layer: Sensor data is transmitted to the monitoring host through the internal bus, and externally communicated with host computers and cloud platforms via Ethernet or wireless networks.
- Processing Layer: The monitoring host performs computation and processing on the collected data, compares it with preset thresholds, determines whether anomalies exist, generates alarm information, and executes control logic (such as temperature-controlled fan speed regulation).
- Application Layer: Operating data is displayed to users through the local touchscreen, client software, cloud platform, and other interfaces, providing functions such as parameter setting, data query, and remote control.
The system adopts a modular design where each functional unit operates independently. A single sensor failure does not affect the overall system operation, providing high reliability and scalability.
4.5 Ventilation and Heat Dissipation System Working Principle
The intelligent forced-air cooling system uses the negative pressure air induction principle: top fans exhaust air outward, creating negative pressure inside the cabinet. External air is drawn into the cabinet from the lower intake waveguide windows, flows across equipment surfaces to absorb heat, and is then discharged from the top, forming a bottom-to-top vertical air path.
The temperature control module collects internal temperature data in real time. When the temperature is below the set lower limit, the fans operate at low speed or stop. When the temperature exceeds the set value, the fan speed increases linearly with rising temperature until full speed. When the temperature exceeds the alarm threshold, a high-temperature alarm is triggered. Through intelligent temperature control, heat dissipation is ensured while achieving energy savings and noise reduction, extending fan service life.
Chapter 5 Product Technical Parameters
This chapter takes the mainstream models of the LA-PB series as the baseline and lists detailed technical parameters. Different models may have slightly different parameters; the contract configuration list shall prevail.
5.1 Shielding Performance Parameters
Shielding performance is the core indicator of this product, strictly tested in accordance with BMB19-2006 and GB/T 12190 standards.
| Shielding Grade | Test Frequency Band | Shielding Effectiveness Requirement | Typical Measured Value | Applicable Standard |
|---|---|---|---|---|
| Class C | 14kHz~150kHz (Magnetic field) | ≥60dB | 65~75dB | BMB19-2006 Class C |
| Class C | 150kHz~1GHz (Plane wave) | ≥80dB | 85~95dB | BMB19-2006 Class C |
| Class C | 1GHz~10GHz (Microwave) | ≥70dB | 75~85dB | BMB19-2006 Class C |
| Class B | 14kHz~150kHz (Magnetic field) | ≥70dB | 75~85dB | BMB19-2006 Class B |
| Class B | 150kHz~1GHz (Plane wave) | ≥90dB | 95~105dB | BMB19-2006 Class B |
| Class B | 1GHz~10GHz (Microwave) | ≥80dB | 85~95dB | BMB19-2006 Class B |
| Class A | 10kHz~150kHz (Magnetic field) | ≥80dB | 85~95dB | GJB 5792 Class A |
| Class A | 150kHz~1GHz (Plane wave) | ≥100dB | 105~115dB | GJB 5792 Class A |
| Class A | 1GHz~18GHz (Microwave) | ≥90dB | 95~105dB | GJB 5792 Class A |
Note: Shielding effectiveness tests are conducted in an empty cabinet state. After equipment installation, actual effectiveness may vary due to factors such as cables and equipment grounding, requiring on-site commissioning and optimization.
5.2 Structural and Dimensional Parameters
5.2.1 Standard Model Dimensions
| Model | External Dimensions (H×W×D) mm | Internal Usable Height | Standard U-positions | Internal Usable Width | Internal Usable Depth |
|---|---|---|---|---|---|
| 22U | 1200×700×700 | 977mm | 22U | 483mm (19-inch) | 550mm |
| 32U | 1600×700×800 | 1422mm | 32U | 483mm | 650mm |
| 37U | 1800×700×900 | 1644mm | 37U | 483mm | 750mm |
| 42U | 2000×700×900 | 1866mm | 42U | 483mm | 750mm |
| 47U | 2200×800×1000 | 2089mm | 47U | 483mm | 850mm |
5.2.2 Structural Parameters
- Main body plate thickness: Class C 1.5mm cold-rolled steel plate, Class B 2.0mm cold-rolled steel plate, Class A 2.5mm composite steel plate
- Frame structure: Nine-fold roll-formed profile reinforced frame
- Static load capacity: ≥1500kg (42U model)
- Cabinet door opening angle: ≥110°
- Surface treatment: Electrostatic powder coating on exterior, conductive oxidation on interior
- Protection rating: IP50 (closed state)
- Seismic rating: Magnitude 8 intensity
- Total weight: 42U model approximately 280~350kg (depending on configuration)
5.3 Electrical Performance Parameters
5.3.1 Input/Output Parameters
- Rated input voltage: Single-phase AC 220V±15%, 50Hz; optional three-phase AC 380V±15%, 50Hz
- Rated input current: 10A/16A/32A/63A/100A selectable
- Output outlet specifications: GB standard 10A, GB standard 16A, IEC C13, IEC C19 selectable
- Number of output outlets: 8-position/12-position/16-position/24-position selectable
- Number of power distribution circuits: 1~4 circuits selectable
5.3.2 Filter Parameters
- Power filter insertion loss: Common mode ≥60dB, differential mode ≥40dB in the 14kHz~10GHz range (Class B)
- Signal filter insertion loss: ≤1dB in the corresponding operating frequency band, stopband ≥40dB
- Surge protection level: Class II, maximum discharge current 40kA (8/20μs)
- Insulation resistance: Power circuit ≥10MΩ (DC500V)
- Dielectric withstand voltage: AC 1500V/1min, no breakdown, no flashover
5.3.3 Grounding Parameters
- Grounding terminal specification: M8/M10 grounding bolts
- Grounding copper busbar specification: 30×3mm tin-plated copper
- Required grounding resistance: ≤1Ω
- Shell contact resistance: ≤2.5mΩ between any two points
5.4 Environmental and Cooling Parameters
Operating ambient temperature: -5℃~45℃
Storage ambient temperature: -20℃~60℃
Operating ambient humidity: 10%~90%RH (non-condensing)
Storage ambient humidity: 5%~95%RH (non-condensing)
Altitude: ≤2000m (derating required above 2000m)
Cooling method: Natural convection / Intelligent forced-air cooling / Rack-mount air conditioning (optional)
Forced-air cooling capacity: ≥3kW (42U standard forced-air cooling model)
Fan noise: ≤55dB (at 1m distance, full-speed operation)
Ventilation rate: ≥60% (net ventilation area of waveguide vent panel)
5.5 Intelligent Monitoring Parameters
5.5.1 Monitoring Accuracy
| Parameter | Range | Accuracy |
|---|---|---|
| Temperature measurement | -10℃~80℃ | ±0.5℃ |
| Humidity measurement | 0~100%RH | ±3%RH |
| Voltage measurement accuracy | — | ±1% |
| Current measurement accuracy | — | ±1% |
| Power measurement accuracy | — | ±2% |
5.5.2 System Parameters
Main control unit: ARM Cortex-A8 1GHz processor
Memory: 512MB DDR3
Storage: 8GB eMMC, SD card expansion supported
Display: 7-inch capacitive touchscreen, resolution 800×480
Data storage duration: ≥12 months
Data sampling interval: 1 second to 60 minutes (configurable)
Alarm response time: ≤1 second
5.5.3 Communication Interfaces
Ethernet: 1× RJ45, 10/100/1000Mbps auto-negotiation
RS485: 2 ports, Modbus-RTU protocol supported
Dry contact inputs: 4 channels
Dry contact outputs: 2 channels
USB interface: 2 ports, for data export and commissioning
5.6 Access Control and Security Parameters
Access control method: Fingerprint + PIN + mechanical key (standard); card swipe, facial recognition (optional)
Fingerprint capacity: 1,000 fingerprints
PIN capacity: 1,000 PIN codes
Card capacity: 10,000 cards (card-swipe model)
Door opening record storage: ≥10,000 records
Electromagnetic lock holding force: ≥280kg
Door sensor type: Normally open / normally closed (selectable)
Alarm methods: Local audible/visual, remote SMS/email/platform notification
5.7 Reliability and Service Life Parameters
Mean time between failures (MTBF): ≥50,000 hours
Shielding door mechanical life: ≥10,000 open/close cycles
Fan service life: ≥50,000 hours (at 25℃ ambient)
Beryllium copper finger strip life: performance degradation ≤5% after ≥10,000 open/close cycles
Overall equipment design life: ≥15 years
6.1 Core Shielding Safety Functions
6.1.1 Full-Band Bidirectional Electromagnetic Shielding
Provides bidirectional shielding capability: internally, it suppresses equipment electromagnetic leakage emissions, preventing information leakage through electromagnetic pathways; externally, it withstands strong external electromagnetic interference, electromagnetic pulses, and electrostatic discharge, ensuring stable operation of internal equipment. Covers the wide frequency band of 14kHz~18GHz, with different grades meeting various protection requirements from commercial confidentiality to military top-secret levels.
6.1.2 Full-Path Leakage Blocking
Not only does the cabinet body itself provide high shielding effectiveness, but all penetration paths are also specially treated: power and signal circuits all pass through dedicated filters; ventilation openings use cutoff waveguide vent panels; cabinet doors use multi-stage conductive sealing; the grounding system is designed to specification, achieving 360° leak-proof blocking with no blind spots, avoiding the “barrel effect” that would degrade overall shielding performance.
6.1.3 High-Reliability Structural Sealing
Fully welded main shell structure, eliminating leakage risk from seams; knife-blade insertion-type shielding door paired with continuous silver-plated beryllium copper finger strips, providing uniform contact pressure, good electrical continuity, and resistance to deformation over long-term use. All removable components are fitted with conductive gaskets, and shielding performance is not affected after disassembly and reassembly.
6.1.4 Compliance Certification Assurance
The product has been tested by the National Secrecy Science and Technology Testing Center, complies with the corresponding grade requirements of the BMB19-2006 standard, and can be used in classified information systems; it has also passed military electromagnetic compatibility testing, meeting military application requirements, with complete testing and certification qualifications.
6.2 Intelligent Management Functions
6.2.1 Comprehensive Environmental Monitoring
Real-time monitoring of temperature, humidity, smoke, water leakage, access control, and other environmental and security parameters inside the cabinet. Abnormal conditions trigger immediate alarms, allowing early identification of hidden hazards and preventing accidents such as equipment overheating, fire, or water immersion. Multi-point temperature and humidity monitoring can accurately identify local hot spots and provide visibility into temperature distribution within the cabinet.
6.2.2 Intelligent Power Distribution Management
The intelligent PDU monitors voltage, current, power, and energy consumption in real time, provides equipment energy statistics, and automatically alarms on overload, undervoltage, and overvoltage conditions. Supports remote on/off control, enabling remote equipment reboots, scheduled power-on/off, and other functions. The energy metering function can be used for energy consumption statistics and PUE analysis.
6.2.3 Intelligent Temperature-Controlled Cooling
Fan speed is automatically adjusted based on internal cabinet temperature, achieving on-demand cooling. Compared with traditional constant-speed fans, this saves more than 30% energy while reducing operating noise and extending fan service life. High-temperature conditions trigger automatic alarms, and fan faults are automatically indicated, preventing equipment overheating due to cooling failure.
6.2.4 Multi-Level Alarm and Notification
Supports multiple alarm methods including local audible/visual alarms, SMS alarms, email alarms, and platform pop-up alarms. Alarm levels are configurable, and important alarms are pushed through multiple channels to ensure operations and maintenance personnel are notified promptly. Alarm information includes time, location, type, and value, facilitating rapid problem identification.
6.2.5 Data Recording and Analysis
Automatically records all operational data and alarm events, with a storage duration of over 1 year. Supports historical data query, curve display, and report export. Data analysis reveals equipment operating patterns, enabling optimized O&M strategies and predictive maintenance.
6.2.6 Centralized Management and Remote O&M
Supports integration with the centralized data center environment monitoring platform, unified management of multiple cabinets, remote viewing of operating status, parameter modification, and firmware upgrades. Most O&M tasks can be completed without on-site visits, significantly improving management efficiency and reducing O&M costs.
6.3 Structural and Process Features
6.3.1 High-Strength Nine-Fold Profile Frame
Utilizes nine-fold formed steel profiles as the main load-bearing frame, featuring a large sectional moment of inertia, high structural strength, and strong load-bearing capacity without deformation under full load. The frame is welded as one piece with the cabinet shell, providing excellent overall rigidity and seismic performance, suitable for vehicle-mounted, field, and other harsh environments.
6.3.2 Modular Integrated Design
All functional units adopt modular design with standardized mounting interfaces. Filters, monitoring modules, fans, PDUs, and other components can be quickly removed and replaced, facilitating maintenance without disassembling the entire cabinet. The modular design also supports flexible configuration, allowing functional modules to be added or removed as needed.
6.3.3 Precision Manufacturing Processes
Main body welding uses fully automated industrial robot welding, providing uniform weld seams and consistent weld quality, avoiding quality variations of manual welding. Sheet metal parts are manufactured using CNC punching and bending, ensuring high dimensional accuracy and interchangeability. Surface treatment uses automated production lines, providing uniform coating, strong adhesion, and corrosion resistance.
6.3.4 Ergonomic Structural Design
Both front and rear doors of the cabinet can be opened (some models have single door), with unobstructed access on both interior sides, facilitating equipment installation and maintenance.
U-position markings on mounting rails are clearly visible, making installation heights obvious at a glance.
The front door is equipped with a visual observation window (optional shielded glass), allowing viewing of internal equipment indicator status without opening the door.
Bottom leveling feet have a wide adjustment range, allowing easy leveling on uneven floors.
Sufficient cable management space with separate routing for power and signal cables, facilitating organization and maintenance.
6.4 Safety and Reliability Features
6.4.1 Multiple Electrical Safety Protections
The power distribution system features four levels of protection: overload, short circuit, earth leakage, and surge protection, with graded tripping to ensure equipment and personnel safety. All electrical components are 3C certified or carry equivalent qualifications, with insulation and withstand voltage performance meeting national standards.
6.4.2 High-Reliability Components
Core components are selected from industrial-grade branded products. Key parts including filters, monitoring hosts, sensors, fans, and locks undergo strict screening and burn-in testing, adapting to wide temperature and humidity ranges with long-term stable and reliable operation.
6.4.3 Complete Grounding System
A dedicated grounding copper busbar is installed inside the cabinet. All components requiring grounding are connected locally, providing good equipotential bonding and effectively avoiding interference and safety hazards caused by ground potential differences. The grounding path is short with low impedance, ensuring shielding and filtering effectiveness.
6.4.4 Fire-Resistant and Environmentally Friendly Design
The entire unit uses flame-retardant materials; all plastic components are V0 flame-retardant grade; cables are flame-retardant type; smoke detectors provide early fire warning; an optional automatic fire suppression module is available to enhance fire safety level. Production complies with RoHS environmental requirements with no hazardous substances.
6.5 Scenario Adaptation Features
6.5.1 Flexible Deployment
A single cabinet forms a complete system without requiring large-scale data center renovation — plug in and use. Suitable for distributed, small-scale classified equipment deployment. Can be used as a single unit or multiple cabinets can be joined to form a shielding cabinet group, flexibly adapting to different scale requirements.
6.5.2 Strong Environmental Adaptability
Wide temperature and humidity design allows normal operation in ambient temperatures from -5℃ to 45℃, adapting to different climate conditions including high temperature and humidity in the south and low temperature and dryness in the north. Dust-proof and corrosion-resistant design enables use in relatively harsh environments such as industrial plants and underground equipment rooms.
6.5.3 Strong Customization Capability
Supports non-standard size customization, special interface customization, and special function customization. Targeted design can be performed based on user site conditions and equipment requirements, meeting various personalized scenario needs.
The LA-PB series intelligent shielded integrated cabinet, with its excellent shielding performance and comprehensive intelligent functions, is widely used in various scenarios with high requirements for information security, electromagnetic compatibility, and stable equipment operation. Below are typical application fields and solution descriptions.
7.1 Party and Government Agency Classified Office Scenarios
7.1.1 Scenario Pain Points
Party and government agencies process large volumes of classified documents and sensitive information. Electromagnetic leakage from office computers, printers, scanners, and other equipment may lead to theft of classified information, presenting serious confidentiality risks. Traditional office environments lack electromagnetic protection measures, do not comply with confidentiality management regulations, and cannot pass confidentiality evaluations. Additionally, dispersed office equipment is difficult to manage with low O&M efficiency.
7.1.2 Solution
Deploy LA-PB-B/C series intelligent shielded integrated cabinets to centrally house classified computers, classified switches, storage devices, and other equipment inside the shielded cabinet. All cables enter through filters, effectively blocking electromagnetic leakage, meeting BMB19 standard requirements, and complying with confidentiality evaluation specifications.
The intelligent monitoring system provides real-time monitoring of the cabinet environment and equipment operating status. The access control system manages physical access with traceable door opening records, achieving dual protection of physical security and information security. Single cabinet deployment is flexible, suitable for distributed deployment across departments, or centralized deployment of multiple units in the central equipment room.
7.1.3 Application Value
Meets national confidentiality standards and passes confidentiality qualification reviews and routine inspections.
Blocks electromagnetic leakage pathways at the physical level, ensuring classified information security.
Intelligent management reduces O&M workload and improves office equipment management efficiency.
7.2 Military and National Defense Sector
7.2.1 Scenario Pain Points
Military units handle core confidential information involving weapons and equipment and national defense research. Information security requirements are extremely high — not only preventing electromagnetic leakage but also withstanding external electromagnetic interference and electromagnetic pulse weapon attacks, ensuring stable equipment operation. Military environments may also involve harsh conditions such as vibration and extreme temperatures, requiring high equipment reliability.
7.2.2 Solution
Deploy LA-PB-A series military-grade shielded cabinets that meet military shielding standards, with excellent low-frequency magnetic shielding effectiveness capable of withstanding strong electromagnetic pulse impacts. The cabinet uses reinforced construction and high-reliability components to adapt to military environments.
Special versions with vibration resistance, shock resistance, and wide temperature range can be customized as needed, paired with military filters and special signal interfaces to meet electromagnetic protection requirements for various military equipment testing, operation, and storage. The intelligent monitoring system supports military communication protocols for integration into military security management systems.
7.2.3 Application Value
Achieves military electromagnetic protection standards, safeguarding national defense core information and equipment security.
High-reliability construction adapts to complex military environments with low failure rates and reduced maintenance pressure.
Customized design matches special interfaces and installation requirements of different equipment.
7.3 Financial and Securities Industry
7.3.1 Scenario Pain Points
Core business systems of banks, securities, and insurance companies process large volumes of customer information and transaction data, making data security critically important. Financial branches are widely distributed with varying equipment room conditions. External electromagnetic interference may cause transaction system failures and data errors, resulting in economic losses and reputation damage. Dispersed branches also create O&M management difficulties.
7.3.2 Solution
Deploy LA-PB-B series shielded cabinets in core equipment rooms and branch equipment rooms to house core servers, trading terminals, encryption machines, and other equipment — preventing data electromagnetic leakage while withstanding external electromagnetic interference, ensuring stable transaction system operation.
Remote intelligent monitoring enables headquarters to centrally manage cabinet operations across all branches, with real-time visibility of operating status and remote fault alerts, reducing on-site maintenance visits and lowering O&M costs. Access control and operation records meet financial industry audit requirements.
7.3.3 Application Value
Protects financial core data security and prevents information leakage risks.
Enhances system anti-interference capability and reduces transaction system failure rates.
Centralized remote O&M improves management efficiency and reduces branch O&M costs.
7.4 Research Institutes and Laboratories
7.4.1 Scenario Pain Points
Precision test instruments and experimental equipment in research institutes have high electromagnetic environment requirements. External electromagnetic interference affects test accuracy, leading to inaccurate experimental data. Additionally, sensitive information such as research results and patent technologies requires strict confidentiality to prevent electromagnetic theft. Some laboratories have multiple high-frequency devices with severe mutual electromagnetic crosstalk.
7.4.2 Solution
Configure shielded cabinets of appropriate shielding grades based on the electromagnetic sensitivity and confidentiality level of different equipment, providing a clean electromagnetic environment for precision instruments, avoiding external interference, and improving test accuracy. Provide electromagnetic shielding protection for classified research equipment to prevent technical information leakage.
Multiple devices can be placed in independent shielded cabinets to avoid mutual electromagnetic crosstalk. Intelligent temperature and humidity control provides stable environmental conditions for precision equipment, ensuring equipment performance.
7.4.3 Application Value
Provides a clean electromagnetic environment for precision instruments, improving experimental data accuracy and equipment service life.
Protects research results and core technologies, preventing electromagnetic leakage.
Resolves electromagnetic crosstalk between multiple devices and improves laboratory space utilization.
7.5 Data Center and Cloud Computing Scenarios
7.5.1 Scenario Pain Points
Data centers have high-density servers and storage equipment with complex electromagnetic environments. Mutual interference between equipment affects system stability. Some managed hosting customers handle sensitive data with special electromagnetic security requirements. Data centers also have high requirements for energy efficiency and O&M efficiency, requiring refined management.
7.5.2 Solution
Deploy LA-PB series shielded cabinets as independent security zones for highly sensitive customer operations, providing dedicated electromagnetic protection and meeting customer information security compliance requirements. Intelligent power distribution and temperature control functions enable cabinet-level energy management, supporting PUE optimization.
The environment monitoring system integrates with the data center infrastructure management platform (DCIM), achieving unified management and control with transparent operational data, improving O&M refinement.
7.5.3 Application Value
Provides value-added security services for high-value, highly sensitive operations, enhancing data center competitiveness.
Cabinet-level refined management optimizes energy consumption and reduces operating costs.
Comprehensive monitoring and alarms improve availability and service levels.
7.6 Industrial Control and Intelligent Manufacturing Scenarios
7.6.1 Scenario Pain Points
Factory workshops contain numerous strong electromagnetic interference sources such as variable frequency drives, motors, and welding equipment, which interfere with PLCs, industrial computers, servo controllers, and other industrial control equipment, causing control failures and data errors that affect production stability. Factory environments also have high dust, vibration, and significant temperature/humidity variations, creating harsh operating conditions for equipment.
7.6.2 Solution
Deploy LA-PB-INT industrial-grade shielded cabinets to house core control equipment, effectively isolating strong workshop electromagnetic interference and ensuring stable control system operation. The cabinet features enhanced dust-proof and vibration-resistant design suitable for harsh industrial site environments.
Wide-temperature cooling design adapts to high workshop temperatures, and industrial-grade components ensure long-term stable operation. Supports industrial bus protocol integration for incorporation into factory automation control systems.
7.6.3 Application Value
Significantly reduces electromagnetic interference failures in industrial control systems, improving production stability.
Adapts to harsh industrial environments, extending control equipment service life.
Reduces downtime losses, improving production efficiency and product yield rates.
7.7 Power and Energy Industry
7.7.1 Scenario Pain Points
Substations, power plants, and oil/gas stations have complex electromagnetic environments. High-voltage equipment generates strong electromagnetic fields that easily interfere with relay protection devices, measurement and control devices, and communication equipment, causing protection misoperation or failure to operate, potentially triggering power accidents. Sites are also remotely located with difficult O&M access, placing extremely high demands on equipment reliability.
7.7.2 Solution
Deploy LA-PB series power-dedicated shielded cabinets to house secondary equipment such as relay protection, measurement and control, and communication devices, shielding high-voltage electromagnetic field interference and ensuring safe and stable operation of the power secondary system. The product complies with power industry electromagnetic compatibility standards and has passed relevant EMC testing.
Remote monitoring enables unattended station remote O&M with proactive alarms for abnormal conditions, promptly identifying hidden hazards and ensuring power system safety. The cabinet features moisture-proof and salt-spray-resistant characteristics suitable for outdoor site environments.
7.7.3 Application Value
Protects power secondary equipment from strong electromagnetic interference, preventing protection misoperation that could trigger power accidents.
Remote intelligent monitoring reduces O&M difficulty at remote sites and improves O&M efficiency.
High-reliability design meets high-availability requirements of power systems.
7.8 Medical and Biological Research Scenarios
7.8.1 Scenario Pain Points
Medical equipment such as MRI and X-ray machines generate strong electromagnetic radiation that interferes with nearby computers, patient monitors, laboratory equipment, and other devices, affecting normal equipment operation and detection accuracy. Some medical data involves patient privacy and requires information security protection.
7.8.2 Solution
Place interference-susceptible medical information equipment inside shielded cabinets, isolating strong electromagnetic equipment interference and ensuring stable equipment operation and accurate test data. Provide electromagnetic shielding protection for servers storing patient privacy data, complying with medical data security regulations.
7.8.3 Application Value
Avoids electromagnetic interference between medical equipment, improving diagnostic accuracy and equipment reliability.
Protects patient privacy data, complying with medical information security regulatory requirements.
7.9 Communication and Broadcasting Scenarios
7.9.1 Scenario Pain Points
Sites such as base stations and broadcasting transmission stations have high-power transmission equipment generating strong electromagnetic fields that interfere with transmission equipment and monitoring equipment, affecting communication quality. Communication core equipment also involves user data and network security, requiring electromagnetic leakage protection.
7.9.2 Solution
Deploy shielded cabinets to house core transmission and control equipment, withstanding strong RF interference and ensuring stable communication equipment operation. Shielding performance covers the full communication frequency band, effectively blocking electromagnetic leakage and interference.
7.9.3 Application Value
Enhances communication equipment anti-interference capability, reduces failure rates, and ensures network stability.
Protects core network equipment from electromagnetic leakage, safeguarding communication network security.
8.1 Pre-Installation Preparation
8.1.1 Personnel Preparation
Installation personnel must possess relevant qualifications and experience in electrical installation and low-voltage system construction, and be familiar with electromagnetic shielding equipment installation requirements.
At least 2 installation personnel are required on site; additional personnel are needed for large or heavy cabinets.
Read this manual carefully before construction to understand product structure, installation steps, and safety precautions.
Designate an on-site supervisor and a safety officer, and implement construction safety responsibilities.
8.1.2 Tool Preparation
The following tools must be prepared before installation, ensuring they are in good working condition:
| Category | Tools |
|---|---|
| Measuring tools | Laser level, tape measure, feeler gauge, ground resistance tester, multimeter, torque wrench |
| Installation tools | Hex key set, adjustable wrench, socket wrench set, screwdriver set, electric drill, rotary hammer drill, utility knife, wire stripper, crimping tool |
| Auxiliary tools | Forklift or hydraulic pallet truck, pry bar, rubber mallet, gloves, safety harness, cleaning cloth |
| Testing tools | Surface resistance tester (optional, for checking conductive contact) |
8.1.3 On-Site Environment Inspection
Floor conditions: The installation floor must be flat, solid, and dry, with a load-bearing capacity greater than the total weight of the cabinet at full load. Floor flatness ≤2mm/m. If the floor is significantly uneven, leveling treatment is required.
Space conditions: ≥800mm of operating space must be reserved in front of the cabinet, ≥600mm of maintenance space at the rear and sides, and ≥300mm of heat dissipation space above.
Environmental conditions: No corrosive gases or flammable/explosive materials on site. Ambient temperature between 0℃~40℃, relative humidity ≤80%RH, non-condensing.
Electromagnetic environment: Maintain a distance of at least 1 meter from strong electromagnetic interference sources such as large power transformers, motors, and transmitting antennas.
Power and grounding: A compliant AC power supply and independent grounding system must be available on site, with ground resistance ≤1Ω.
8.1.4 Goods Receiving Inspection
After the cabinet arrives, check whether the outer packaging is intact, with no signs of collision or water damage.
After unpacking, verify the quantity and models of components against the product list, inspect the cabinet body for deformation, paint damage, or scratches, and check the shielding door, glass, and other components for damage.
Check that all accompanying documents and accessories are complete.
After acceptance, complete the incoming inspection record. Contact the manufacturer promptly if any abnormalities are found.
8.2 Cabinet Handling and Positioning
8.2.1 Handling Precautions
The cabinet is heavy and must be moved using a forklift or hydraulic pallet truck. Manual lifting is strictly prohibited to prevent personal injury and equipment damage.
Keep the cabinet upright during handling. Tilt must not exceed 15°. Overturning or laying the cabinet on its side is strictly prohibited to prevent internal component displacement or damage.
Avoid severe vibration and impact during handling. Protect the cabinet surface and shielding door from scratches and deformation.
Measure dimensions in advance when passing through elevators and doorways to avoid collisions.
Place the cabinet gently in position, avoiding impact on the floor and cabinet body.
8.2.2 Positioning and Leveling
Determine the cabinet installation position according to the design drawings and mark the positioning lines.
Move the cabinet to the designated position and adjust the adjustable leveling feet at the bottom.
Use a laser level to measure the levelness and verticality of the cabinet top and sides. Adjust the height by rotating the leveling feet until the cabinet levelness deviation is ≤2mm/m and verticality deviation is ≤3mm/m.
All four leveling feet must bear load evenly with no floating feet, ensuring the cabinet is stable and does not wobble.
If casters are fitted, lock the brake wheels after leveling to prevent cabinet movement.
When installing multiple cabinets side by side, level each unit individually to ensure cabinets are aligned, gaps are uniform, and top surfaces are at the same height.
8.2.3 Floor Fixing (Optional)
For scenarios requiring seismic resistance or where the floor is smooth and prone to sliding, the cabinet must be fixed to the floor.
Drill holes in the floor at the positions of the mounting holes in the cabinet base and install expansion anchors.
Use M10 expansion anchors to securely fix the cabinet base to the floor, with bolt torque meeting requirements.
Re-check levelness and verticality after fixing.
8.3 Cabinet Component Installation
8.3.1 Shielding Door Inspection and Adjustment
The shielding door was pre-installed and adjusted at the factory. After transportation, check whether the door frame is deformed and whether hinges are loose.
Open and close the door several times to check smooth operation, with no sticking or abnormal noise.
Check that the door lock operates smoothly and the three-point locking bolts move synchronously.
Use a feeler gauge to check the clearance around the door perimeter. The gap should be uniform with a difference of ≤0.5mm. If the gap is uneven, adjust the hinge positions and locking points.
Check that the beryllium copper finger strips are intact, with no deformation, detachment, or oxidation, and that the knife-blade insertion depth is correct.
8.3.2 Waveguide Vent Panel Inspection
Check that the inlet and outlet waveguide vent panels are securely installed and that flange connection bolts are not loose.
Check that the honeycomb cells of the waveguide panels are not deformed or blocked. Clean off any dust or debris.
Check that the dust filter is properly installed and intact.
8.3.3 Internal Mounting Rails and Shelf Installation
Determine the front-rear position of the mounting rails according to the equipment installation plan. Loosen the rail fixing bolts, adjust the rail depth, and then retighten.
Install fixed shelves and sliding shelves according to the U-position markings. Shelves must remain level with fixing bolts fully tightened.
Shelf mounting intervals are determined by equipment height, reserving heat dissipation space and cable routing space.
Install vertical cable managers and cable management rings, ensuring they are securely fixed.
8.3.4 Grounding Copper Busbar Installation
The internal grounding copper busbar is pre-installed at the factory. Check that it is securely mounted and free from oxidation.
Confirm the position of the grounding lead-out terminal for subsequent grounding work.
Clean the busbar surface to ensure good electrical conductivity.
8.4 Grounding System Installation
The grounding system is critical to ensuring shielding effectiveness and electrical safety and must be installed strictly in accordance with specifications.
8.4.1 Grounding Requirements
The cabinet must be connected to an independent, qualified grounding system. Connection to non-dedicated ground points such as water pipes, lightning protection strips, or the power supply neutral conductor is strictly prohibited.
Ground resistance requirements: Confidential-grade cabinet ≤1Ω, military-grade ≤0.5Ω.
Grounding conductor: stranded copper insulated cable with cross-sectional area ≥16mm², kept as short as possible to reduce grounding impedance.
Grounding connections must use bolted compression joints. Contact surfaces must be ground clean and coated with conductive grease to ensure low contact resistance.
For multiple cabinets installed side by side, connect the grounding busbars of each cabinet with equipotential copper straps, then connect to the equipment room grounding busbar at a single point to avoid ground loops.
8.4.2 Grounding Installation Procedure
Measure the ground resistance of the equipment room grounding busbar and confirm it meets requirements.
Cut the grounding cable to the appropriate length and crimp copper lug terminals at both ends. The crimping must be secure with insulation treatment applied.
Connect one end to the grounding bolt of the cabinet grounding busbar. Tighten the bolt with torque ≥20N·m.
Connect the other end to the equipment room grounding busbar with a secure connection.
After connection, measure the resistance between the cabinet shell and the grounding busbar, which should be ≤0.1Ω.
Measure the overall ground resistance and confirm it meets specifications.
Route the grounding cable along the cabinet side, secure it neatly, and label it.
8.4.3 Grounding Precautions
The grounding conductor must not have intermediate splices or be connected in series with other equipment.
The grounding cable should be routed away from power cables to avoid coupling interference.
Grounding bolts must have anti-loosening measures to prevent loosening from long-term vibration.
The cabinet ground must not be directly shared with the lightning protection ground; they should be connected through equipotential bonding.
8.5 Auxiliary System Installation
8.5.1 Intelligent Monitoring System Installation
The monitoring host is pre-installed and fixed at the designated position inside the cabinet at the factory. Check that it is securely mounted.
Check that all sensors are correctly positioned and cable connections are secure.
Check the front door touchscreen wiring connections and inspect the screen for damage.
The audible/visual alarm is installed in a prominent position on top of the cabinet with correct wiring.
8.5.2 Forced-Air Cooling System Installation
The fan assembly is pre-installed on top at the factory. Check that fans are securely fixed and shock-absorbing pads are intact.
Manually rotate the fan blades to verify smooth rotation without sticking or rubbing.
Fan wiring must be connected to the temperature control module and PDU, with secure connections and correct polarity.
Check the air duct for obstructions to ensure smooth airflow.
8.5.3 Access Control System Installation
The access control controller is installed inside the cabinet. The card reader is installed at the designated position on the outside of the door and must be securely fixed.
The electromagnetic lock and strike plate must be accurately aligned, making firm contact with sufficient holding force.
The door sensor is installed in place, providing correct door open/closed signals.
Wiring connects to the access control controller and monitoring host, with cables organized and secured.
8.5.4 PDU Installation
Install the intelligent PDU on the rear mounting rail of the cabinet at an appropriate height for convenient plugging and unplugging of power cables.
Tighten the fixing bolts; the PDU must remain vertical without tilting.
Leave appropriate cable length at the input end for subsequent connection.
8.6 Precautions During Installation
Drilling, welding, cutting, or otherwise compromising the integrity of the shielding shell is strictly prohibited. If openings are required, dedicated shielded interface components must be used.
During installation, protect sealing components such as beryllium copper finger strips and conductive gaskets from collision, deformation, oil contamination, and dust.
All fasteners must be tightened to specification. Components requiring anti-loosening protection must be fitted with spring washers or lock nuts.
Electrical installation must be performed with power disconnected, following electrical safety regulations to prevent electric shock.
When working at heights, wear a safety harness and take appropriate safety precautions.
Metal shavings and debris generated during installation must be cleaned up promptly to avoid short circuits from leaving debris inside the cabinet.
At the end of each workday, close the cabinet door and lock it to prevent unauthorized access.
8.7 Initial Inspection after Installation Completion
After installation is complete, perform the initial inspection according to the following items. Only after passing may the wiring and commissioning phase proceed:
- Cabinet position is correct; levelness and verticality meet requirements; cabinet is stable.
- Cabinet exterior is intact with no obvious deformation, paint damage, or scratches.
- Shielding door opens and closes smoothly with reliable locking; finger strips are in good contact with no deformation or detachment.
- Waveguide vent panels, filters, and other components are securely installed with no damage.
- Internal shelves and mounting rails are securely installed in the correct positions.
- Grounding system connections are reliable; ground resistance meets requirements.
- All installation accessories are complete with none missing.
- Cabinet interior is clean with no debris or metal shavings.
After passing the initial inspection, complete the installation process acceptance record and proceed to the next phase.
Wiring work directly affects the product’s shielding performance, electrical safety, and system functionality. It must be performed strictly in accordance with the electrical schematic diagram and these specifications, and only by certified electricians.
9.1 General Wiring Principles
Safety first: All wiring operations must be performed with power disconnected, with warning signs posted to prevent accidental switch-on.
Standardized routing: Separate power and signal cables, separate AC and DC, to reduce mutual interference. Route cables neatly and secure them firmly.
Shielding continuity: Shielded cable shield layers must be grounded to specification. All cables passing through the shielding enclosure must pass through filters or shielded interfaces.
Clear identification: All cables must be labeled with wire numbers at both ends, with clear terminal numbers for ease of future maintenance.
Reliable contact: Terminals must be crimped securely, bolt tightening torque must meet specifications, with no loose connections, poor contacts, or burrs.
9.2 Power System Wiring
9.2.1 Power Input Wiring
Confirm that the on-site power supply voltage and frequency match the equipment rated parameters, and that the power capacity meets the total power requirements of the cabinet.
Route the power input cable through the power entry point at the bottom of the cabinet and connect it to the input side of the power filter. Note: The power filter input side is located outside the shielding enclosure and the output side is inside the shielding enclosure. Reversing the connection is strictly prohibited.
Input cable cross-section is selected according to total current: 4mm² copper conductor for 32A and below, 10mm² copper conductor for 63A, 16mm² copper conductor for 100A.
Connection sequence: connect the ground (PE) terminal first, then the neutral (N) conductor, and finally the phase conductor(s) (L/L1/L2/L3).
Tighten terminal bolts to the specified torque. Stranded conductors must be crimped with ferrules before connection. Direct connection of bare stranded conductors is strictly prohibited.
A waterproof sealed cable gland must be installed at the power input point, with the cable securely fixed to prevent pulling force from transferring to the terminals.
9.2.2 Filter Output Wiring
Connect the power filter output to the intelligent PDU input using flame-retardant stranded copper cable.
Filter output cables and input cables must be routed separately with a spacing of ≥20cm. Parallel bundling is strictly prohibited to prevent input-output coupling that could render the filter ineffective.
The filter ground terminal must be connected individually to the internal grounding copper busbar using copper cable of at least 4mm², with the connection as short and direct as possible.
The filter housing must have good contact with the cabinet body to ensure equipotential shell grounding.
9.2.3 PDU Output Wiring
Connect equipment power cables inside the cabinet to the PDU output sockets, ensuring full insertion and locking of anti-disconnection devices (if provided).
Neatly route equipment power cables along cable managers, with ties of appropriate tightness to avoid cable compression.
High-power equipment should be assigned to separate circuits to avoid overloading a single circuit.
Power cables and signal cables must be routed separately with a spacing of ≥10cm, crossing at right angles when necessary.
9.2.4 Surge Protector Wiring
The surge protector is connected in parallel at the power input end, with phase, neutral, and ground conductors connected correspondingly.
Connection cables should be as short and direct as possible, with length ≤0.5m, to reduce the effect of lead inductance on discharge performance.
The ground terminal must be connected directly to the grounding copper busbar with minimal impedance.
9.3 Signal Cable Wiring
9.3.1 Network Signal Wiring
External network cables connect to the input side of the RJ45 signal filter; internal network cables connect to the output side. Direct bypassing is strictly prohibited.
Use shielded Cat5e or Cat6 network cables with intact shield layers.
RJ45 connectors must be crimped to specification with correct wire ordering, and the shield layer must make reliable contact with the connector metal shell.
Filters are installed on the shielding enclosure wall, with the housing reliably connected to the cabinet body to ensure shielding continuity.
Internal network cables are routed along cable managers, separated from power cables, and secured neatly.
9.3.2 Fiber Optic Signal Wiring
Fiber optic cables pass through the shielding enclosure via dedicated fiber optic waveguide feedthroughs. Both ends of the feedthrough must be securely fixed with good contact with the cabinet body.
Fiber splicing must be performed to specification, with splice loss ≤0.3dB.
Fiber bend radius must be ≥30mm, avoiding bending stress.
Label both ends of the fiber and reserve appropriate slack length.
Fill feedthrough openings with sealing compound to prevent electromagnetic leakage.
9.3.3 Serial Port and Control Signal Wiring
Control signals such as RS232/RS485 must be connected through dedicated signal filters with correct pin connections.
Shielded cable shield layers must be grounded at a single end, with the grounding point on the cabinet side and the signal source side left floating.
Signal cables must be kept away from power cables and avoid parallel routing to reduce interference coupling.
Terminal connections must be secure with no cold solder joints or loose connections.
9.3.4 Sensor and Monitoring Wiring
Temperature/humidity, smoke, water leakage, and other sensor signal cables must use RVVP shielded cable with single-ended shield grounding.
Connect the positive/negative conductors and signal pins correctly, avoiding reversed connections that could damage sensors.
All sensor cables connect to the corresponding terminals on the monitoring host, with terminal numbers matching the drawings.
Route cables along the inner walls of the cabinet and secure them neatly, avoiding interference with equipment installation and door operation.
9.4 Shielded Cable Grounding Specifications
The grounding method of shielded cables directly affects shielding effectiveness. Different cable types require different grounding methods. Random grounding is strictly prohibited.
9.4.1 Low-Frequency Analog Signal Cables
For low-frequency signals below 1MHz, use the single-ended grounding method.
The shield layer is grounded at the cabinet side (receiving end) and left floating at the signal source side, avoiding ground loops.
The grounded end must have a reliable connection to the grounding copper busbar with low contact resistance.
9.4.2 High-Frequency Digital Signal Cables
For high-frequency signals above 1MHz, use the double-ended grounding method.
The shield layer is connected at both ends to the equipment chassis and the cabinet grounding copper busbar respectively, reducing high-frequency impedance.
Both ends must be at equal potential, with a ground potential difference not exceeding 1V; otherwise, circulating currents may occur.
9.4.3 Double-Shielded Cables
The outer shield layer is grounded at both ends, providing electric field shielding; the inner shield layer is grounded at a single end, providing magnetic field shielding.
The inner and outer shield layers must be insulated from each other and must not be shorted together.
9.4.4 Power Cable Shield Layers
Power cable shield layers must be grounded at both ends, connected to the power source ground and the cabinet ground respectively.
Armored cable steel tape must be grounded at both ends, with the armor layer and shield layer grounded separately.
9.4.5 Shield Layer Installation Key Points
When stripping cable ends, keep the shield layer intact, bundle it, and crimp a terminal for grounding.
Shield grounding length must be as short as possible to avoid the “antenna effect.”
The shield layer must not be interrupted in the middle; continuity must be maintained at splices.
The floating end of the shield layer must be insulated and must not contact metal surfaces.
9.5 Internal Wiring Process Requirements
Power-signal separation: AC power cables and DC signal/network cables must be routed separately, using separate cable managers on each side with a spacing of ≥100mm.
Neat routing: Cables must be routed neatly, horizontally and vertically aligned, with no twisting or tangling.
Proper bundling: Use nylon cable ties with uniform spacing and appropriate tightness, without damaging cable insulation. Trim tie ends flush, leaving no sharp burrs.
Clear identification: Each cable must have clear wire number labels at both ends, indicating circuit, number, and destination, with legible and durable lettering.
Slack allowance: Reserve 10~20cm of slack at equipment ends for easy plugging/unplugging and maintenance.
Heat source avoidance: Keep cables away from heat sources such as fans and heaters to prevent high-temperature aging.
Abrasion protection: Add protective grommets or corrugated conduit where cables pass through corners or openings to prevent insulation damage.
9.6 Post-Wiring Inspection
After wiring is complete, perform the following checks item by item. Only after passing may power-on commissioning proceed:
Wiring correctness check: Verify each circuit against the electrical schematic diagram, confirming no wrong, missing, or reversed connections.
Tightness check: Re-tighten all terminals and bolts individually, confirming no looseness or poor contacts.
Insulation resistance test: Disconnect all sensitive electronic equipment and measure the power circuit insulation resistance to ground using a 500V megger. ≥0.5MΩ is acceptable for power circuits; ≥1MΩ for control circuits.
Continuity test: Use a multimeter continuity mode to test each circuit for open/short circuits, confirming no shorts or breaks.
Ground continuity check: Measure the resistance between each metal component of the cabinet and the grounding copper busbar. ≤0.1Ω is acceptable.
Wiring process check: Verify that cable routing is neat, identification is clear, power/signal separation is maintained, and shield layer grounding is compliant.
Cleanliness check: Remove all leftover wire ends, cable ties, tools, and debris from inside the cabinet, keeping the interior clean.
After passing the inspection, complete the wiring process acceptance record and proceed to the commissioning phase.
9.7 Wiring Safety Precautions
Strictly adhere to the power-off work system. Confirm that power is disconnected and verify no voltage before beginning any work.
Operators must wear insulated gloves and use insulated tools to prevent electric shock.
Provide insulation protection for exposed live parts to prevent accidental contact.
Hot-plugging of active components such as filters and sensors is strictly prohibited, as this may damage equipment and cause electric shock.
When performing temporary power-on testing, arrange for dedicated personnel to supervise and cut power immediately upon detecting any abnormality.
After wiring is complete, all live parts must be properly protected with no exposed conductors.
Commissioning is a critical stage for verifying the quality of installation and wiring and validating all functions and performance. It must be carried out step by step in an orderly manner: check before power-on, no-load before loaded operation, and subsystems before the overall system.
10.1 Pre-Commissioning Preparation
10.1.1 Technical Preparation
Commissioning personnel must be familiar with the product principles, functions, and commissioning methods, and have mastered the contents of this manual.
Prepare technical documents including the electrical schematic diagram, wiring diagram, factory parameter tables, and other materials.
Clearly define commissioning items and acceptance criteria, and develop a commissioning plan.
10.1.2 Instruments and Tools Preparation
- Multimeter (digital type, accuracy class 0.5)
- Clamp-on ammeter
- Ground resistance tester
- Thermometer/hygrometer (calibrated)
- Tachometer/anemometer (optional)
- Laptop computer and commissioning cables
- Voltage tester, insulated gloves, and other safety tools
10.1.3 Safety Confirmation
Confirm that installation and wiring work are fully completed and have passed acceptance.
Confirm that there are no leftover tools or debris inside the cabinet and that the cabinet doors open and close normally.
Confirm that all air circuit breakers are in the OFF position and equipment power switches are OFF.
Confirm that the grounding system is reliably connected and ground resistance meets specifications.
Ensure fire extinguishing equipment is available on site with safety precautions in place.
10.2 Pre-Power-On Special Inspection
Before powering on, the following inspections must be completed. Only after all items are confirmed correct may power be applied:
Visual Inspection: Cabinet body, doors, and all components are intact, with no damage or looseness.
Wiring Inspection: All wiring is correct and secure, with no misconnections, short circuits, or exposed terminals.
Switch Status: The main power switch, branch switches, and PDU switches are all in the OFF position.
Load Inspection: Do not connect high-power equipment inside the cabinet at this stage; proceed with no-load commissioning first.
Grounding Inspection: Re-measure the ground resistance and confirm it meets the requirements.
Insulation Inspection: Re-measure the insulation resistance of the main circuit and confirm there are no short circuits or ground faults.
10.3 No-Load Power-On Commissioning
10.3.1 Main Power Supply Energization
Close the upstream main power switch of the cabinet. Use a multimeter to measure the voltage at the power input terminals and confirm the voltage is normal, with deviation within ±10% of the rated value.
Observe for any abnormal phenomena such as unusual noise, odor, or smoke. If any occur, cut off power immediately and investigate.
Measure the voltage at the input terminals of the power filter to confirm normal input.
10.3.2 Power Distribution System Testing
Close the air switch on the output side of the filter and measure the output voltage. The voltage should be normal with no abnormalities.
Close the PDU input switch and measure the PDU output voltage. The voltage at every outlet socket should be normal.
Test the PDU metering function: Verify that the voltage, current, and power displayed on the screen are accurate. Compare with multimeter readings; the error must be within the allowable range.
Test overcurrent protection: Simulate an overload condition and verify that the overcurrent protection activates (optional).
Test surge protection: Check that the surge protector status indicator is normal and the device is undamaged.
10.3.3 Monitoring System Power-On Commissioning
Power on the environmental monitoring (dynamic environment) host and observe the startup process. The system should start up normally with no error messages.
The touchscreen should illuminate and enter the main interface, displaying operational parameters.
Sensor Testing:
- Temperature/Humidity: Check the displayed temperature and humidity values against a standard thermometer/hygrometer. The error must meet accuracy requirements. Simulate changes using hot air or humidification; readings should change accordingly.
- Smoke: Press the test button on the smoke detector. A smoke alarm should trigger, audible and visual alarms should activate, and the alarm message should display on the interface.
- Water Leakage: Touch the water leakage sensor probe with a damp cotton swab. A water immersion alarm should trigger.
- Door Magnetic Contact: Open and close the cabinet door; the door status display should change accordingly, and the door-open alarm function should operate normally.
Alarm Function Testing:
- Manually set temperature/humidity thresholds and simulate exceeding the limits. Verify that audible/visual alarms and message push notifications function normally.
- Test alarm levels: different alarm levels should correspond to different notification methods.
Data Storage Testing: Review historical data to confirm records are being captured normally and sampling intervals are correct.
Communication Testing:
- Connect the network cable and test that the network connection is normal. The monitoring interface should be accessible from a computer.
- Test remote data upload and remote parameter configuration functions.
- Test SMS/email alarm functions and confirm alarm messages are sent correctly.
10.3.4 Air Cooling System Commissioning
Manually start the fan and observe that the rotation direction is correct, rotation is smooth, and there is no abnormal noise or vibration.
Measure the fan current; it should be within the rated range.
Test the temperature control function: set temperature thresholds, simulate temperature changes, and observe that fan start/stop and speed changes follow the configured logic.
Test the fan fault alarm: disconnect fan power and verify that the fault alarm triggers.
Measure the airflow velocity and air volume inside the cabinet to confirm that heat dissipation capacity meets design requirements.
10.3.5 Access Control System Commissioning
Test mechanical key locking/unlocking functions; they should operate smoothly and reliably.
Test password unlocking: enter a test password and verify normal unlocking. Incorrect passwords must not open the lock.
Test fingerprint unlocking: enroll a test fingerprint and verify recognition success rate and response speed.
Test the electromagnetic lock: the lock should engage firmly, respond promptly to unlocking, without sticking.
Test door-open records: review the access control log; door-open events should be recorded accurately and completely.
Test tamper alarm: simulate removal of the card reader and verify that the alarm triggers.
10.3.6 Lighting System Testing
The LED light should illuminate automatically when the door opens, with sufficient brightness.
The light should turn off automatically after the door closes, with a reasonable delay time.
Manual switch testing should function normally.
10.4 Loaded Operation Commissioning
After no-load commissioning passes, connect actual load equipment for loaded commissioning.
10.4.1 Equipment Power-On
Following the equipment operating procedures, power on the equipment inside the cabinet one by one, starting with peripheral equipment and then core equipment.
Observe the equipment startup process for any abnormalities. The PDU current and power readings should display normal values.
Monitor the temperature changes inside the cabinet; the temperature rise should remain within a reasonable range.
10.4.2 Loaded Heat Dissipation Testing
Run the equipment under full load for more than 1 hour. Monitor temperatures at various points inside the cabinet; the maximum temperature must not exceed the equipment’s allowable operating temperature.
Test the intelligent temperature control effect: the fan should automatically adjust according to temperature, and the temperature should remain stable within the set range.
Check for local hot spots. If any are found, optimize equipment layout and airflow paths.
10.4.3 Electromagnetic Compatibility Verification
During normal equipment operation, observe for any interference phenomena. Equipment should operate stably with no data errors, system crashes, or other issues.
Where conditions permit, test the electromagnetic environment inside the cabinet to confirm that interference levels are within equipment tolerance.
Verify there is no abnormal electromagnetic leakage to the outside and that nearby sensitive equipment is not affected.
10.4.4 Full-Load Stability Testing
Run the complete system under full load continuously for no less than 24 hours. Conduct periodic inspections during this period and record operational parameters.
There should be no alarms, no faults, and no abnormal temperature rise during the test period. All functions should operate normally.
During testing, simulate operations such as opening/closing the door and plugging/unplugging cables to verify that shielding performance and system stability are not affected.
10.5 Preliminary Shielding Effectiveness Testing
Formal acceptance testing shall be conducted by a third-party organization. During the commissioning phase, a simple shielding effectiveness test may be performed to preliminarily verify shielding performance.
10.5.1 Simple Test Methods
Place a mobile phone inside the cabinet, close and lock the door, then call the phone to see if it can connect. If it cannot connect, this indicates that the basic shielding effect is good.
Use a small signal source to transmit signals inside the cabinet, and use a field strength meter outside the cabinet to measure signal strength. Compare with the unshielded condition to estimate shielding effectiveness.
Check the door seams and interface areas for obvious signal leakage. Field strength at key locations should not show abnormal elevation.
10.5.2 Common Leakage Point Troubleshooting
If the preliminary shielding test shows poor performance, troubleshoot in the following order:
1. Check whether the cabinet door is fully closed and locked, whether the spring contacts are making good contact, and whether any foreign objects are caught in the door seam.
2. Check whether the waveguide window is blocked, deformed, or loosely installed.
3. Check whether the filter is connected in reverse and whether input/output are coupled.
4. Check whether any cables pass directly through the cabinet without going through the filter.
5. Check whether grounding is good and whether ground resistance exceeds the limit.
6. Check the enclosure for any unsealed holes or gaps.
After identifying and rectifying problems, retest until performance is satisfactory.
10.6 System Parameter Optimization and Configuration
After commissioning is complete, optimize system parameters based on the actual site conditions and set reasonable thresholds:
Temperature/Humidity Alarm Thresholds: Set high-temperature, low-temperature, high-humidity, and low-humidity alarm values according to equipment requirements. Typically, the high-temperature alarm is set to 35°C and the low-temperature alarm to 5°C.
Temperature Control Parameters: Set fan start temperature, stop temperature, and speed control curves to balance heat dissipation and energy efficiency.
Access Control Parameters: Enroll user fingerprints, passcodes, and cards. Set permissions and door-open time periods.
Alarm Parameters: Configure alarm notification methods, contacts, alarm levels, and delay times.
Communication Parameters: Configure network parameters such as IP address, port, platform address, etc.
Time Calibration: Calibrate the system time to ensure accurate records.
After all parameters are configured, save the settings and export a backup.
10.7 Commissioning Completion Confirmation
After all commissioning items are completed and have passed inspection, organize the commissioning records and fill out the commissioning report. The report shall include:
- Commissioning date, location, and personnel
- Test results for each function
- Actual measured performance parameter values
- Problems identified and rectification status
- Parameter configuration list
- Commissioning conclusion
After commissioning passes, proceed to the trial operation and final acceptance phase.
11.1 Daily Operation Specifications
Cabinet Door Operation: Open and close the shielding door smoothly, avoiding forceful impact. When closing, confirm the door is fully locked, with all three-point locks fully engaged. It is strictly forbidden to operate with the door ajar, as this will severely degrade shielding effectiveness.
Key Management: The mechanical key shall be kept by designated personnel and used only according to authorized permissions. Unauthorized key duplication is strictly prohibited. Spare keys shall be sealed and stored per regulations and may only be used in emergencies.
Equipment Installation/Removal: When installing or removing equipment inside the cabinet, handle with care to avoid impacting the cabinet interior walls and mounting rails, preventing damage to the shielding layer and conductive gaskets. Equipment must be securely mounted to prevent tipping.
Cable Plugging/Unplugging: When plugging or unplugging cables, hold the connector body. Pulling on the cable itself is strictly prohibited. All external cables must be routed through dedicated filters or shielded interfaces. Routing cables through door seams or unsealed holes is strictly prohibited.
Cleaning and Maintenance: For routine cleaning, use a dry cloth or neutral cleaning agent to wipe the cabinet exterior. The use of corrosive cleaners such as strong acids or alkalis is strictly prohibited. When cleaning conductive contact surfaces, use anhydrous ethanol and a dedicated cleaning cloth.
11.2 Shielding Performance Protection Precautions
Shielding performance is the core value of this product. Care must be taken during use to protect it and avoid human-induced degradation of shielding effectiveness.
No Unauthorized Drilling: Drilling, cutting, or welding on the shielding enclosure is strictly prohibited. Any action that compromises the integrity of the enclosure may cause electromagnetic leakage. If additional interfaces are required, contact the manufacturer to implement a dedicated shielding solution.
Keep Door Seams Clean: The beryllium copper spring contacts and knife-edge on the door seam are critical sealing components. Do not apply tape or paint to them, and avoid trapping paper, dust, or oil in the seam. Clean regularly to prevent oxidation and rust.
Avoid Hard Object Scratches: Scraping the interior surface of the enclosure or conductive contact surfaces with sharp or hard objects is prohibited, as scratches may compromise electrical continuity.
Filter Protection: Do not arbitrarily replace the filter model. Do not bind the filter input and output cables together. Do not overload the filter, as this may cause damage.
Waveguide Window Protection: Do not block the waveguide window with objects or insert foreign objects into it, to prevent deformation or damage to the honeycomb structure. Clean dust from the waveguide window regularly to maintain ventilation and shielding performance.
Proper Grounding: Disconnecting the grounding device is prohibited. Loose grounding connections are prohibited. Check grounding connections regularly to ensure reliable grounding.
Shielding Blank Panels: Unused mounting positions and cable pass-through holes must be sealed with shielding blank panels or sealing components. Leaving them open is prohibited.
11.3 Electrical Safety Precautions
Electrical Safety: The total load of the cabinet must not exceed the rated power. Overload operation is strictly prohibited to prevent overheating and fire hazards.
No Live-Working: Disassembling electrical components or servicing internal circuits while energized is strictly prohibited. Maintenance must be performed with power disconnected, with warning signs posted, and after verifying zero voltage.
Wet Hands Prohibition: Operating switches or plugging/unplugging power cables with wet hands is prohibited to prevent electric shock.
Liquid Protection: Placing water cups or liquid containers on top of the cabinet or on equipment is prohibited, to prevent liquid spills from entering the cabinet and causing short circuits.
Foreign Object Prohibition: Leaving metal tools, screws, or other debris inside the cabinet is prohibited, as these may cause short-circuit faults.
Abnormal Condition Handling: If abnormal conditions such as unusual noise, odor, smoke, or electrical leakage are detected during operation, immediately cut off power and contact qualified personnel for repair. Do not disassemble the equipment yourself.
11.4 Environmental Safety Precautions
Fire Safety: Flammable and explosive materials must not be stored near the cabinet. Open flames must be kept away. Do not store flammable debris inside the cabinet. Fire access routes must remain clear.
Temperature Environment: The operating environment temperature of the cabinet must not exceed 45°C. Avoid direct sunlight on the cabinet and keep it away from heat sources.
Humidity Environment: Keep the environment dry, with relative humidity not exceeding 90% RH, and avoid condensation. In high-humidity environments, dehumidification measures must be taken to prevent corrosion of metal parts and degradation of electrical insulation.
Dust Protection: Keep the environment clean and clean the dust filter regularly to prevent excessive dust from affecting heat dissipation and electrical contact integrity.
Vibration Protection: Avoid strong vibration and impact. Do not strike the cabinet with force. In vibrating environments, vibration isolation measures must be implemented.
11.5 Smart System Usage Precautions
Parameter Setting: System parameters shall only be configured by authorized administrators. Unauthorized personnel modifying parameters is strictly prohibited, as it may affect normal system operation.
Password Management: System administrator passwords must be kept secure and changed periodically to prevent unauthorized operations.
Data Backup: Regularly export and back up system configurations and historical data to prevent data loss due to system faults.
Firmware Upgrade: Firmware upgrades must be performed by qualified personnel. Back up data before upgrading. Power loss during the upgrade process may cause system damage.
Alarm Handling: Alarm messages must be addressed promptly. Ignoring alarms and continuing operation is prohibited, as this may lead to fault escalation.
11.6 Transportation and Storage Precautions
Transportation Requirements: Products must be transported using original packaging, secured firmly to prevent collision. Maintain upright orientation during transport, with a tilt angle not exceeding 15°. Avoid rain exposure and direct sunlight.
Lifting Requirements: Use dedicated lifting slings when hoisting. Lifting points are located at the lifting holes on the top of the cabinet. Never attach slings to the doors, handles, or other components. Lift smoothly to avoid swinging and impact.
Storage Environment: For long-term storage, place the cabinet in a dry, well-ventilated warehouse free of corrosive gases. Temperature range: -20°C to 60°C. Humidity range: 5% to 95% RH. Elevate the cabinet at least 10 cm off the ground to avoid moisture.
Storage Protection: Close and lock the cabinet doors during storage and cover with a dust cover. Inspect periodically to prevent rust and mold.
Storage Period: The shelf life of original packaging is 1 year. After more than 1 year, performance must be re-inspected.
11.7 Personnel Qualification and Responsibility
Cabinet operation and maintenance personnel must undergo professional training, be familiar with product performance and operating specifications, and pass qualification assessments before being permitted to work.
A designated manager shall be responsible for daily inspections, maintenance, and safety management.
An equipment operation log shall be established to record operation, maintenance, fault, and repair information.
Unauthorized personnel operating, disassembling, or modifying the equipment is strictly prohibited.
Good maintenance is key to ensuring long-term stable operation of the shielded cabinet, maintaining shielding effectiveness, and extending service life. A scheduled maintenance system must be established, with maintenance tasks performed according to the prescribed schedule.
12.1 General Maintenance Principles
Prevention First: Adhere to the principle of prevention first. Conduct regular inspections and maintenance, identify hidden hazards promptly, and prevent faults from occurring.
Professional Operation: Maintenance shall be performed by trained professionals who strictly follow operating procedures and safety regulations.
Complete Records: Maintain detailed records for each maintenance activity, including time, personnel, items, results, and problem resolution. Establish an equipment health file.
Spare Parts Support: Stock commonly used wear parts such as conductive spring contacts, filters, sensors, and fans to ensure rapid replacement in the event of failure.
12.2 Daily Inspection (Daily/Weekly)
Duty personnel shall conduct routine inspections daily or weekly, covering the following items:
Visual Inspection: Cabinet exterior is intact with no deformation, damage, or paint peeling. The surrounding environment is clean with no debris accumulation.
Door Inspection: The door is closed and locked properly. No foreign objects are caught in the sealing surfaces. The door lock operates normally.
Status Indication: Check the touchscreen operating status. There should be no alarm messages. Voltage, temperature, and humidity readings should display normal values.
Fan Operation: Listen to fan operation for abnormal noise or vibration. Temperature-controlled start/stop functions should operate normally.
Environment Inspection: The machine room temperature and humidity should be normal, with no water leakage or open flame hazards.
Access Control Inspection: The access control system operates normally. No abnormal door-open records.
Any abnormalities found during inspection shall be recorded and addressed promptly. Major issues must be reported immediately and the manufacturer contacted.
12.3 Monthly Maintenance
A comprehensive maintenance shall be performed monthly by operation and maintenance personnel.
12.3.1 Cleaning and Maintenance
Use a dry, soft cloth to wipe dust from the exterior surface of the cabinet to maintain a clean appearance. For stubborn stains, use a neutral cleaning agent and wipe dry afterward.
Clean the touchscreen surface with a dedicated screen cleaning cloth to avoid scratches.
Remove the intake dust filter, rinse with clean water, allow to dry, and reinstall. Replace promptly if severely clogged.
Clean dust inside the cabinet, particularly on top of equipment, fans, and waveguide windows. Use a vacuum cleaner or soft brush. Take care to prevent static damage to equipment.
Clean dust and debris from the door seams to maintain clean conductive contact surfaces.
12.3.2 Structural Inspection
Check door hinges for looseness and smooth opening/closing. Tighten hinge bolts if loose.
Check that the door lock mechanism operates flexibly, with smooth latch bolt extension/retraction. Apply a small amount of lubricating grease if necessary.
Check cabinet mounting bolts for looseness and the cabinet for stability.
Check internal trays and mounting rails for looseness, and confirm equipment is securely mounted.
Check cable management bars and cable securing for looseness or detachment.
12.3.3 Electrical Inspection
Check power distribution wiring for heating or aging. Check terminals for discoloration or looseness.
Measure main circuit voltage and current and confirm they are within normal ranges.
Check grounding connections for looseness or corrosion. Measure ground resistance and confirm it meets requirements.
Check the surge protector status indicator. Replace promptly if failed.
Check PDU outlets for looseness or burn marks. Confirm plug connections are secure.
12.3.4 Functional Testing
Test the audible/visual alarm function and confirm alarms operate correctly.
Test access control unlocking functions, verifying fingerprint and password recognition.
Manually start and stop the fan and check operating status.
Check that system time is accurate and data recording is normal.
12.4 Quarterly Maintenance
An in-depth maintenance shall be performed quarterly, focusing on shielding-performance-related components and core functions.
12.4.1 Shielding Seal Component Inspection
Open the cabinet door and comprehensively inspect the beryllium copper spring contacts on the door frame for deformation, fracture, detachment, or oxidation darkening.
Clean the contact surfaces of the spring contacts and knife-edge with anhydrous ethanol to remove oil and oxidation layers.
Check that spring contact pressure is uniform. Adjust the position of spring contacts where local pressure is insufficient.
Check the waveguide window honeycomb structure for deformation, rust, or blockage. Clean accumulated dust inside.
Check filter mounting bolts for looseness and confirm good housing contact.
Check conductive gaskets at all removable seams. Replace aged or detached gaskets promptly.
12.4.2 Cooling System Deep Maintenance
Remove the fan protective guard and clean dust from the fan blades and airflow ducts.
Check fan bearings for abnormal noise and apply dedicated lubricating oil.
Check the temperature control sensor calibration. Recalibrate if deviation is excessive.
Clear obstructions from cooling airflow paths to optimize airflow routing.
12.4.3 Monitoring System Maintenance
Restart the monitoring host, clear system cache, and check operating status.
Back up historical data and system configurations.
Check sensor wiring for looseness and measure supply voltages to confirm they are normal.
Calibrate temperature/humidity sensors to ensure measurement accuracy.
Check communication connection status to confirm network transmission is normal.
12.4.4 Grounding System Testing
Use a ground resistance tester to accurately measure the ground resistance. Record the value and compare with historical data.
Check grounding cables for damage or oxidation. Check connection terminals for corrosion.
Check the equipotential bonding inside the cabinet. All grounding points should be electrically continuous.
12.5 Annual Maintenance
A comprehensive maintenance and performance test shall be performed annually, which may be combined with the annual acceptance inspection.
12.5.1 Comprehensive Performance Testing
Shielding Effectiveness Testing: Commission a qualified third-party organization to conduct a comprehensive shielding effectiveness test. Obtain a test report and evaluate the degree of shielding performance degradation.
Electrical Performance Testing: Comprehensively test electrical safety indicators including insulation resistance, withstand voltage, ground resistance, and leakage current.
Fan Performance Testing: Test fan air volume, static pressure, speed, and noise. Evaluate performance degradation. Replace fans showing significant performance decline.
12.5.2 Wear Part Replacement
Conduct preventive replacement of wear parts that have reached their service life, such as fans, sensors, and dust filters.
Check the elasticity and conductivity of conductive spring contacts. Replace entirely after 3 years of service or when performance degrades.
Check seal gaskets and conductive foam. Replace those that have aged and hardened.
Check door locks and hinges for wear. Replace components with severe wear.
12.5.3 System Upgrade and Optimization
Upgrade the monitoring system firmware to the latest stable version to fix known issues and improve performance.
Optimize system parameter configurations. Adjust alarm thresholds and temperature control strategies based on operational data.
Clean up redundant system data to free up storage space.
12.5.4 Structural Anti-Corrosion Treatment
Inspect the cabinet surface coating. Perform touch-up painting and anti-corrosion treatment on areas with paint peeling or rust.
Inspect internal conductive surfaces. Perform conductive repair treatment on severely oxidized areas.
Inspect the ground copper busbar and terminals. Polish and tin-plate oxidized areas.
12.6 Common Wear Parts and Replacement Methods
12.6.1 Beryllium Copper Spring Contact Replacement
Replacement Reasons: Spring contact fracture, loss of elasticity, or severe oxidation that cannot be restored.
Replacement Procedure:
1. Disconnect power and open the cabinet door. Use a screwdriver to remove the fixing screws of the old spring contact.
2. Remove the old spring contact and clean the mounting surface, ensuring it is flat, clean, and free of oil.
3. Verify the new spring contact specification matches. Install the new spring contact sequentially along the door frame, tightening screws evenly.
4. After installation, check that spring contact heights are uniform and joints are aligned without gaps.
5. Close the door for testing. Contact should be uniform, with no localized excessive tightness or looseness.
6. Test the shielding effect and confirm performance is restored.
12.6.2 Fan Replacement
Replacement Reasons: Fan noise, insufficient speed, or burnout (not rotating).
Replacement Procedure:
1. Disconnect fan power. Disconnect the fan wiring and mark the wire sequence.
2. Remove the fan mounting bolts and take out the old fan.
3. Clean the mounting surface. Install vibration-damping pads on the new fan and align with the mounting holes.
4. Tighten the bolts. Reconnect the wiring according to the marks and verify correct polarity.
5. Power on for a test run. Check rotation direction, noise, and vibration.
6. Secure the protective guard and restore the airflow duct.
12.6.3 Sensor Replacement
Replacement Reasons: Sensor damage or measurement deviation too large to calibrate.
Replacement Procedure:
1. Access the system menu, disable the corresponding sensor, and disconnect sensor power.
2. Remove the old sensor, unplug the wiring terminals, and record the pin definitions.
3. Install the new sensor and connect the wiring according to the pin definitions.
4. Power on and test, verifying that readings display normally.
5. Perform calibration procedures according to the manual.
6. Restore system settings and confirm alarm functions operate normally.
12.6.4 Power Filter Replacement
Replacement Reasons: Filter damage or degraded filtering performance.
Replacement Procedure:
1. Disconnect the main power supply. Verify zero voltage with a voltage tester.
2. Mark the input and output wiring. Disconnect the filter wiring terminals.
3. Remove the filter mounting bolts and take out the old filter.
4. Clean the mounting surface, ensuring good contact with the enclosure. Apply conductive grease if necessary.
5. Install the new filter and tighten the bolts, ensuring good housing grounding.
6. Connect the input and output wiring according to the marks. Reverse connection is strictly prohibited.
7. After verifying the wiring is correct, power on and test functions and shielding effect.
12.7 Maintenance Safety Regulations
All maintenance operations must be performed with power disconnected, warning signs posted, and dedicated personnel supervising.
Maintenance personnel must wear anti-static wrist straps to prevent static damage to electronic components.
After replacing shielding components, the sealing performance must be checked to ensure shielding effectiveness is not compromised.
After replacing electrical components, check insulation and grounding to confirm electrical safety.
After completing maintenance, clean up the work area and account for all tools to prevent foreign objects from being left inside the cabinet.
After major fault repairs, trial operation testing shall be conducted. The equipment may only be put into formal service after passing.
12.8 Warranty Service Description
The complete product carries a 1-year free warranty, and core components carry a 3-year warranty, calculated from the date of acceptance.
Quality problems arising from normal use during the warranty period will be repaired or components replaced free of charge.
Damage caused by human factors, improper operation, or force majeure is not covered under the warranty.
After the warranty period, lifetime paid repair services are available at cost only.
Service response: Response within 2 hours of receiving a repair request. On-site service within 24 hours in the local urban area, and within 48 hours for out-of-province locations.
13.1 Shielding Effectiveness Degradation Faults
Fault 1: Overall shielding effectiveness degraded; mobile phone still receives signal inside the cabinet
Cause Analysis:
- Cabinet door not fully closed and locked, high door seam leakage.
- Beryllium copper spring contacts deformed, detached, or oxidized, causing poor contact.
- Cables pass directly through the cabinet without going through filters.
- Waveguide window deformed, blocked, or loosely installed.
- Unsealed holes or gaps in the enclosure.
- Poor grounding, ground resistance too high.
- Filter damaged or connected in reverse.
Troubleshooting and Solutions:
- Check the cabinet door, confirm it is fully closed and locked. Re-open and re-close once to ensure proper seating.
- Open the door and check the beryllium copper spring contacts. Clean dust and oil from contact surfaces. Reshape deformed contacts back into position. Re-secure detached contacts. Replace severely oxidized contacts.
- Check all incoming and outgoing cables, confirm all pass through dedicated filters or shielded interfaces. Direct cable routing is strictly prohibited. Immediately rectify any unauthorized cables.
- Check the waveguide window. Clear blockages. Correct deformation. Tighten loose bolts.
- Comprehensively inspect the enclosure. Seal any excess holes with metal plates and conductive gaskets. Weld-repair any cracked seams.
- Measure ground resistance. If it exceeds the limit, inspect the grounding circuit, treat corrosion and looseness, and upgrade the grounding system if necessary.
- Check filter wiring to confirm input/output are not reversed. Test filter performance and replace if damaged.
Fault 2: Obvious signal leakage at door seams
Cause Analysis:
- Foreign objects trapped in the door seam, preventing full closure.
- Door body deformed, local gap too large.
- Localized spring contact missing or damaged.
- Insufficient door lock clamping force, uneven pressure.
- Knife-edge deformed, poor contact with spring contacts.
Troubleshooting and Solutions:
- Remove foreign objects from the door seam and ensure the sealing surface is free of debris.
- Use a feeler gauge to measure the gap around the door perimeter. Adjust hinge and lock point positions to correct uneven gaps.
- Replace damaged or missing spring contacts to ensure circumferential continuity.
- Adjust the locking mechanism to increase clamping force and ensure even pressure around the perimeter.
- Correct the deformed knife-edge to ensure straightness and full contact with the spring contacts.
Fault 3: Power cable conducted leakage exceeds limits
Cause Analysis:
- Power filter damaged or failed.
- Poor filter grounding.
- Coupling between filter input and output wiring.
- Power cables connected directly without passing through the filter.
- Incorrect filter selection; rated current mismatch.
Troubleshooting and Solutions:
- Test filter insertion loss. Replace damaged filters with identical models.
- Check filter ground terminal connections, ensure good contact. Ground wire should be as short and thick as possible.
- Separate input and output cables by a spacing of ≥20 cm. Avoid parallel bundling.
- Standardize wiring. All power cables must be routed through the filter.
- Replace with a filter of matching rated current. Do not use an undersized filter for a larger load.
13.2 Electrical System Faults
Fault 4: Complete system power failure; display screen not lit
Cause Analysis:
- External power outage or upstream breaker tripped.
- Main power switch tripped or damaged.
- Power input line open circuit or loose terminal.
- Surge protector short-circuited (breakdown).
- Monitoring host power supply failed.
Troubleshooting and Solutions:
- Check upstream power supply, confirm mains power is normal. Reset tripped breakers.
- Check the cabinet main air switch. If tripped, first identify and clear the short-circuit cause, then reset. Replace the switch if damaged.
- Check input terminals. Tighten loose connections. Reconnect broken wires.
- Check the surge protector. Remove or replace if the status indicator shows failure.
- Measure the monitoring host input voltage. If voltage is normal, replace the power module or host.
Fault 5: Breaker trips after power-on; RCD (residual current device) activates
Cause Analysis:
- Leakage in cabinet wiring or equipment.
- Neutral and ground wires reversed.
- Leakage current from filter Y-capacitors accumulates, causing RCD nuisance tripping.
- Reduced insulation due to moisture.
- Cable sheath damaged, causing ground fault.
Troubleshooting and Solutions:
- Disconnect all loads. Energize each circuit one by one to identify the leaking circuit, then address the leak point.
- Check neutral and ground wiring, confirm correct connections.
- If tripping is caused by normal filter leakage current, replace with an RCD with a higher leakage current rating, or use a main switch without RCD protection.
- Dry out the system. Measure insulation resistance. Restore power only after values return to normal.
- Check cable insulation. Repair or replace damaged sections.
Fault 6: PDU has no output or some outlets have no power
Cause Analysis:
- PDU input switch tripped.
- Input wiring loose or open circuit.
- Loose or burned-out contact blades inside the outlet.
- Internal PDU circuit damage.
- Overload protection activated.
Troubleshooting and Solutions:
- Check the PDU switch. For overload trips, reduce the load and reset.
- Check input wiring. Tighten loose terminals and reconnect broken wires.
- If a single outlet has no power, check the internal contact blades. Reshape deformed blades. Replace burned outlets.
- If an entire row has no power and input is normal, replace the internal PDU module or the entire PDU.
- Calculate the total load and avoid overload operation.
Fault 7: Cabinet enclosure gives tingling sensation; electrical leakage felt
Cause Analysis:
- Poor grounding or disconnected ground wire.
- Equipment leakage, enclosure energized.
- Induced voltage, more noticeable when grounding is poor.
Troubleshooting and Solutions:
- Immediately disconnect power. Check the grounding system. Reconnect disconnected ground wires. Tighten loose terminals. Measure ground resistance to confirm acceptable values.
- Disconnect equipment one by one to identify the leaking device. Repair or replace as needed.
- After confirming reliable grounding, induced voltage should disappear.
13.3 Smart Monitoring System Faults
Fault 8: Abnormal temperature/humidity display; inaccurate readings or no change
Cause Analysis:
- Sensor wiring loose or reversed.
- Sensor damaged.
- Sensor blocked or positioned near heat/cold source.
- Monitoring host channel fault.
- Long-term lack of calibration, excessive drift.
Troubleshooting and Solutions:
- Check sensor wiring. Tighten terminals and confirm correct polarity.
- Replace with a spare sensor for testing to determine if the sensor is faulty. Replace if damaged.
- Adjust the sensor installation position, keeping it away from interference sources and in a location with good air circulation.
- Test by switching channels. If the host channel is faulty, repair or replace the host.
- Calibrate the sensor according to the manual procedures.
Fault 9: Alarm function failed; no alarm when abnormality occurs
Cause Analysis:
- Alarm threshold set too high or too low; condition not triggered.
- Alarm function disabled.
- Audible/visual alarm device damaged.
- Communication fault; remote alarms cannot be sent.
- Sensor fault; cannot detect abnormality.
Troubleshooting and Solutions:
- Check alarm threshold settings and adjust to appropriate values.
- Enable the corresponding alarm switches to activate alarm functions.
- Manually test the alarm device and replace if damaged.
- Check network connections and SMS/email configurations to confirm communications are normal.
- Troubleshoot sensor faults using the methods in Fault 8.
Fault 10: Monitoring system generates frequent false alarms
Cause Analysis:
- Alarm thresholds set too strictly.
- Sensor interference causing large reading fluctuations.
- Large environmental fluctuations, e.g., frequent door opening or direct air conditioning airflow.
- System fault causing abnormal data.
Troubleshooting and Solutions:
- Appropriately relax alarm thresholds and increase alarm delay to prevent false alarms from transient fluctuations.
- Check sensor installation location. Move away from vents and doorways. Add shielding to reduce interference.
- Optimize the environment to avoid severe temperature/humidity fluctuations. Reduce frequent door opening.
- Restart the system. Restore factory settings and reconfigure.
Fault 11: Unable to access remotely; data not uploading
Cause Analysis:
- Network line disconnected or IP address conflict.
- Network parameter configuration error.
- Firewall or router blocking.
- Platform server fault.
- Monitoring host network port damaged.
Troubleshooting and Solutions:
- Check the network cable connection and test network connectivity. Resolve IP conflicts.
- Verify IP address, subnet mask, gateway, and DNS settings. Ensure they are correct.
- Open the corresponding ports. Check firewall rules.
- Confirm the platform service is running normally. Contact the platform administrator.
- If the network port is physically damaged, repair or replace the host.
13.4 Cooling and Fan Faults
Fault 12: Fan not rotating
Cause Analysis:
- Fan power supply disconnected.
- Fan motor burned out.
- Temperature controller fault; no start signal output.
- Fan bearing seized.
- Wiring loose or reversed.
Troubleshooting and Solutions:
- Check the fan power circuit and switch. Restore power.
- Measure fan resistance. If infinite, the motor is burned out. Replace the fan.
- Test the temperature controller output. Replace the temperature control module if there is no output.
- Manually turn the fan blades. If stuck, clean the bearings and add lubricating oil. Replace the fan if severely damaged.
- Check wiring. Tighten loose terminals and correct reversed wiring.
14.3 Installation & Construction
Q9: Are there load-bearing requirements for the floor where a shielding cabinet is installed?
A: Yes. A standard 42U shielding cabinet weighs approximately 300 kg by itself, and with full equipment loading, the total weight can reach 1000–1500 kg. Therefore, the floor load-bearing capacity must exceed the total weight. Typically, the floor load-bearing requirement is ≥500 kg/m². For raised-floor (access floor) scenarios, the floor load-bearing capacity must be verified, and load-bearing supports must be added if necessary.
Q10: Can I install it myself, or is on-site installation by the manufacturer mandatory?
A: If you have experience in electrical installation and shielding equipment construction, you may install and commission the unit yourself following this manual. However, for first-time installations or higher-grade shielding models, it is recommended that professional engineers from the manufacturer perform the on-site installation and commissioning to ensure shielding performance and system functions meet the required standards. The manufacturer provides one-stop services including on-site installation, commissioning, and training.
Q11: Can shielding cabinets be installed side-by-side? Will side-by-side installation affect shielding performance?
A: Multiple cabinets can be installed side-by-side. Side-by-side installation itself does not affect the shielding performance of individual cabinets, as each cabinet is an independent shielding enclosure. When installing cabinets side-by-side, ensure the cabinets are securely fastened to each other and proper equipotential bonding is established for grounding.
Q12: What if the computer room has no dedicated grounding? Can the power supply ground wire be used?
A: No. The power outlet ground wire cannot be used directly, as the power ground typically has high impedance and may carry interference, which does not meet the grounding requirements of a shielding cabinet. A dedicated grounding system must be constructed separately, using grounding electrodes or a grounding grid, ensuring the grounding resistance is ≤1 Ω. You may contact a professional grounding construction company, or consult our company for grounding solutions.
14.4 Operation & Maintenance
Q13: What should be noted in daily use of the shielding cabinet? What is most easily overlooked?
A: The most critical aspect of daily use is protecting shielding performance. The most easily overlooked points are:
- The door must be locked securely when closed; leaving it ajar will cause shielding failure.
- It is forbidden to drill holes or run unapproved wiring through the cabinet body without authorization.
- Regularly clean the door-seal contact strips (beryllium copper fingers); dust and oil contamination can cause poor contact.
- Ensure reliable grounding; the ground wire must not be disconnected.
- All cables must be routed through filters for entry; do not bypass filters for convenience by running cables directly.
Q14: How often should the beryllium copper contact strips be replaced? What happens if they are not replaced?
A: Under normal operating conditions, the service life of silver-plated beryllium copper contact strips is approximately 3–5 years. The specific replacement interval depends on the operating environment and frequency of door opening/closing. In high-humidity or high-salt-fog environments, the service life will be shortened. Degraded spring tension and severe oxidation of the contact strips will result in increased contact resistance, reduced shielding effectiveness, and may even cause localized leakage exceeding limits. It is recommended to test shielding performance annually and replace the strips when a significant decline is observed.
Q15: Can the shielding cabinet door be opened and closed frequently? Will frequent opening and closing affect shielding?
A: Normal opening and closing does not affect shielding. The shielding door is designed with a mechanical life of ≥10,000 opening/closing cycles. The frequency of door operations during routine maintenance is far below the design life. As long as the door is operated properly without rough handling, the shielding performance will not significantly degrade over long-term use. Simply check the condition of the contact strips periodically.
Q16: Can an ordinary power strip be placed inside the cabinet? Will it affect shielding?
A: Ordinary PDUs or power strips can be used inside the cabinet, but the power supply must be taken from the output side of the filter — direct introduction from outside is strictly prohibited. As long as the power cable passes through the filter, power distribution inside the cabinet will not affect shielding performance. However, it is recommended to use shielded smart PDUs for better performance and manageability.
14.5 Performance Testing
Q17: How can the shielding effectiveness of the shielding cabinet be verified?
A: A simple method is the mobile phone test: place a mobile phone inside the cabinet, close and lock the door, then call the phone number. If the call cannot connect, the basic shielding effectiveness is good. If the call connects, the shielding effectiveness is inadequate. For professional testing, a qualified third-party testing institution must be engaged to test in accordance with the GB/T 12190 standard, using professional field strength meters to test at multiple frequency points and issue an official test report. This is also the formal basis for confidentiality acceptance.
Q18: Will shielding effectiveness decrease after equipment is installed? Why?
A: After equipment installation, the actual shielding effectiveness will typically be slightly lower than the empty-cabinet test result, which is a normal phenomenon. The reasons include: conducted leakage from equipment cables, gaps formed by contact between equipment metal parts and the enclosure, and resonance effects of the equipment itself. However, as long as wiring is standard and grounding is proper, the degradation is limited and the corresponding grade requirements can still be met. Optimization is performed during construction and commissioning to ensure the final performance meets the required standards.
Q19: Is it necessary to test shielding effectiveness every year?
A: Confidentiality management requirements typically mandate an annual shielding effectiveness test to detect performance degradation in a timely manner. During daily use, if the cabinet body is not modified and components are not replaced, performance will not suddenly decline. The annual test can be combined with the annual maintenance schedule. If modifications or repairs to shielding components have been performed, retesting is required after the work is completed.
14.6 Troubleshooting
Q20: If paper is caught in the shielding door causing shielding degradation, will the shielding recover once the paper is removed?
A: After removing the foreign object, if the contact strips and knife-edge show no damage and no deformation from clamping marks, the shielding performance can recover after closing the door. If a hard object has caused deformation of the contact strips or denting of the knife-edge, reshaping and repair are required before performance can be restored. It is recommended to regularly inspect the door gap to prevent foreign objects from being caught.
Q21: Can an ordinary filter be used as a replacement if the filter fails?
A: No. Ordinary power filters are not optimized for electromagnetic shielding, have insufficient insertion loss, and their housing shielding structure does not meet requirements. Using an ordinary filter will cause conducted leakage to exceed limits and significantly degrade overall shielding performance. Only the original manufacturer’s special shielding filter of the same specification, or a professional filter that meets the corresponding shielding grade requirements, must be used as a replacement.
Q22: What can be done if the grounding resistance cannot be reduced?
A: The following measures can be taken when grounding resistance exceeds the standard:
- Increase the number of grounding electrodes and expand the grounding grid area.
- Relocate the grounding electrodes to areas with moist soil and low resistivity.
- Use resistance-reducing agents to improve soil resistivity.
- Adopt the deep-well grounding method to reach low-resistivity strata.
- Inspect grounding connection points, polish and de-rust them to reduce contact resistance.
It is recommended that a professional grounding construction company conduct an on-site survey and develop a solution.
Chapter 15 Product Acceptance Standards
Product acceptance is divided into three stages: incoming acceptance, installation process acceptance, and final completion acceptance. The acceptance work shall be jointly carried out by the construction unit, the construction contractor, and the supervision unit (if any), strictly in accordance with these standards and contractual requirements.
15.1 Incoming Acceptance
After equipment arrives on site, incoming acceptance shall be performed prior to installation to confirm the products meet the procurement requirements.
15.1.1 Acceptance Contents
- Packaging and Appearance Inspection: Packaging is intact, with no damage, water immersion, or impact marks; after unpacking, the cabinet body shows no deformation, paint peeling, scratches, corrosion, or other defects; glass, door panels, displays, and other fragile components are intact.
- Specification and Model Verification: The product model, specification, and dimensions are consistent with the contract and order, and the grade meets the requirements.
- Configuration List Verification: Check against the contract configuration list and the product packing list, item by item, to verify the quantity and model of the main unit, accessories, auxiliary materials, and accompanying documents, confirming completeness and correctness.
- Qualification Document Inspection: Product certificates of conformity, factory inspection reports, third-party shielding effectiveness test reports, qualification certificates, and other documents are complete and valid.
- Functional Pre-check: Where conditions permit, energize for preliminary functional testing to confirm the product has no factory defects.
15.1.2 Acceptance Standards
- No obvious damage to appearance; dimensions and model meet contract requirements.
- Configuration matches the packing list with no missing or incorrect items.
- Qualification documents are authentic and valid, and the test report corresponds to the product model.
- All factory inspection items pass.
15.1.3 Acceptance Records
Complete the *Equipment Incoming Acceptance Form*, with signatures from all participating parties for confirmation. Items that fail acceptance shall be returned or exchanged until they pass.
15.2 Installation Process Acceptance
During the installation and construction process, staged acceptance of key procedures shall be performed. Non-conforming procedures must not proceed to the next stage.
15.2.1 Cabinet Positioning and Installation Acceptance
- Installation position meets design drawing requirements, deviation ≤10 mm.
- Cabinet levelness ≤2 mm/m, verticality ≤3 mm/m.
- Cabinet is stable, with the four feet evenly loaded and no rocking.
- Floor fixing (where applicable) is secure, and bolt specifications meet requirements.
- Side-by-side cabinets have uniform seams and are properly aligned.
15.2.2 Grounding System Acceptance
- Grounding cable specifications meet requirements, cross-sectional area ≥16mm².
- Connections are secure with good contact, free from oxidation and corrosion.
- Measured grounding resistance: Grade C ≤1Ω, Grade B ≤1Ω, Grade A ≤0.5Ω.
- Grounding path is clearly defined, with no series connections, and clearly labeled.
- Equipotential bonding is properly implemented with no ground loops.
15.2.3 Wiring Procedure Acceptance
- Wiring is correct and consistent with drawings, with no wrong or missing connections.
- Terminals are tightened with torque meeting requirements, with no loose connections.
- Wiring is neat, with separation of power and signal cables, and clear labeling.
- Shielding cable grounding method is correct with continuous shielding.
- Insulation resistance test passes, power circuits ≥0.5MΩ.
- Filter input/output wiring is correct with no coupling.
15.2.4 Acceptance Method
After each procedure is completed, the construction contractor performs self-inspection. Upon passing self-inspection, the supervisor or construction unit is notified for acceptance. Only after acceptance and signature may the next procedure proceed. Concealed works must be inspected before covering.
15.3 Final Completion Acceptance
After all installation and commissioning work is completed and the trial operation passes, the final completion acceptance shall be conducted.
15.3.1 Preconditions for Acceptance
- Installation, wiring, and commissioning are all completed with self-inspection passed.
- Continuous trial operation of no less than 72 hours with stable operation and no faults.
- Completion documents are complete, including construction records, commissioning records, test reports, etc.
- The site is cleaned up and the environment is tidy.
15.3.2 Functional Acceptance Items
- Shielding Door Function: Smooth opening/closing, reliable locking, synchronized three-point lock, no jamming or abnormal noise.
- Access Control System: Fingerprint, password, and mechanical key unlocking operate normally; door opening records are accurate; anti-tamper alarm operates normally.
- Power Distribution System: Circuit breakers at all levels operate normally, PDU metering is accurate, protection functions are reliable, and voltage/current readings are normal.
- Monitoring System: Temperature/humidity, smoke, water leak, door magnetic, and other sensors monitor accurately with normal data display.
- Alarm Function: All types of alarms trigger correctly; audible/visual alarms, SMS, and email notification methods are effective.
- Cooling System: Fans run smoothly, temperature control logic is correct, and temperature remains stable under load.
- Lighting System: Door-controlled lighting operates normally with sufficient brightness.
- Remote Communication: Network connection is normal, and remote monitoring, data upload, and remote configuration functions operate normally.
15.3.3 Performance Acceptance Items
Electrical Safety Performance
- Insulation resistance: Main circuit to ground ≥0.5MΩ, control circuit ≥1MΩ.
- Dielectric withstand voltage: AC 1500V/1min, no breakdown, no flashover.
- Grounding resistance: Meets the requirements of the corresponding grade.
- Leakage current: ≤3.5mA (per safety code requirements).
Shielding Effectiveness Special Acceptance
- Testing shall be performed by a third-party testing institution with CMA/CNAS qualifications.
- Test standards: GB/T 12190-2006, BMB19-2006.
- Test frequency points: At minimum, cover typical frequency points including 14kHz, 100kHz, 1MHz, 10MHz, 100MHz, 1GHz, and 10GHz.
- Acceptance criteria: Shielding effectiveness at all frequency points meets the grade requirements specified in the contract.
- An official test report shall be issued as the acceptance basis.
Cooling Performance
- At full load operation, the maximum temperature inside the cabinet ≤35°C (at an ambient temperature of 25°C).
- Equipment inlet air temperature meets the equipment operating temperature requirements.
- Fan noise ≤55dB (at 1 meter distance).
15.3.4 Documentation Acceptance
The completion and delivery documents shall include the following, complete and comprehensive:
- Product manual, certificate of conformity, warranty card
- Third-party shielding effectiveness test report
- Electrical schematic diagrams, wiring diagrams, installation drawings
- Incoming acceptance records
- Installation construction records
- Commissioning records and test reports
- Grounding resistance test records
- Insulation resistance test records
- Trial operation records
- Spare parts list
- Operation and maintenance manual
15.3.5 Acceptance Conclusion
When all acceptance items pass and all documentation is complete, the completion acceptance report shall be signed and the product formally delivered for use. If general issues exist, a deadline shall be set for rectification, followed by re-inspection after rectification. If major quality issues exist, acceptance shall be withheld, and the construction contractor and manufacturer shall be directed to rectify the problems.
15.4 Acceptance-Related Notes
- If the contract specifies higher acceptance standards, the contract shall prevail.
- The party responsible for third-party testing costs shall be determined per the contract.
- In case of disputes over results between parties during acceptance, an authoritative institution may be commissioned for arbitration testing.
- After acceptance passes, the warranty period commences.
Chapter 16 SEO Optimization System and Keywords
16.1 Keyword System
16.1.1 Core Primary Keywords
Smart shielded integrated cabinet, electromagnetic shielding cabinet, shielding cabinet, classified shielding cabinet, smart shielding cabinet
16.1.2 High-Conversion Long-Tail Keywords
Smart shielded integrated cabinet manufacturer, electromagnetic shielding cabinet manufacturer, classified-grade shielding cabinet price, Grade B shielding cabinet installation, classified information system shielding cabinet, data center electromagnetic shielding cabinet, 42U shielding cabinet, military-grade electromagnetic shielding cabinet, shielding cabinet installation and commissioning, custom smart shielding cabinet
16.1.3 Industry Traffic Keywords
Electromagnetic shielding equipment, information security shielding equipment, Faraday cage cabinet, server shielding cabinet, network shielding cabinet, electromagnetic leakage protection cabinet, anti-EMI cabinet, classified room shielding cabinet, shielded data center cabinet, EMC cabinet
16.1.4 Brand-Specific Keywords
Lain shielding cabinet, Guangdong Lain smart shielded integrated cabinet, LA-PB shielding cabinet, Lain smart data center shielding equipment, Guangzhou shielding cabinet manufacturer, Lain electromagnetic shielding cabinet
16.1.5 Dropdown/Related Search Keywords
Shielding cabinet working principle, shielding cabinet grounding requirements, shielding cabinet shielding effectiveness standards, shielding cabinet installation specifications, how to wire a shielding cabinet, shielding cabinet commissioning methods, shielding cabinet maintenance, common shielding cabinet faults, shielding cabinet acceptance standards, difference between shielding cabinet and ordinary cabinet
16.2 SEO Optimization Tag System
16.2.1 Page Core Optimization Tags
- Page Topic: Smart Shielded Integrated Cabinet Installation, Wiring, and Commissioning Manual — Guangdong Lain Smart Data Center Equipment Co., Ltd.
- Core Keyword Placement: Core keywords naturally integrated into the title’s opening paragraph, the beginning and end of the body, and chapter titles throughout, with a density controlled at 2%–3%.
- Semantic Related Words: Industry terms such as electromagnetic shielding, shielding effectiveness, Faraday cage, beryllium copper contact strips, power filter, waveguide vent, grounding resistance, and BMB19 standard are naturally distributed to enhance topical relevance.
16.2.2 Title Tag
Smart Shielded Integrated Cabinet Installation, Wiring, and Commissioning Manual_Electromagnetic Shielding Cabinet Manufacturer – Guangdong Lain Smart Data Center Equipment Co., Ltd.
16.2.3 Meta Keywords
Smart shielded integrated cabinet, electromagnetic shielding cabinet, shielding cabinet installation and commissioning, classified shielding cabinet, smart shielding cabinet manufacturer, Guangdong Lain shielding cabinet, shielding cabinet wiring specifications, shielding cabinet acceptance standards
16.2.4 Meta Description
Guangdong Lain Smart Data Center Equipment Co., Ltd. professionally manufactures smart shielded integrated cabinets and provides a complete electromagnetic shielding cabinet installation, wiring, and commissioning manual covering product principles, technical parameters, installation specifications, troubleshooting, acceptance standards, and more. Products comply with the BMB19 confidentiality standard and are suitable for government, military, financial, and other classified applications. Service hotline: +86 13538869979.
16.2.5 H1 Tag
Smart Shielded Integrated Cabinet Installation, Wiring, and Commissioning Manual
16.2.6 H2 Tags
Product Introduction, Product Composition, Product List, Product Working Principle, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation Specifications, Product Wiring Specifications, Product Commissioning Process, Product Usage Precautions, Product Repair and Maintenance, Product Common Problems and Solutions, Product Q&A, Product Acceptance Standards
16.3 Internal Link Optimization Tags (Natural Anchor Text Integration)
16.3.1 Core Anchor Texts
- Smart shielded integrated cabinet (linking to the product homepage)
- Electromagnetic shielding cabinet (linking to the product category page)
- Shielding cabinet manufacturer (linking to the About Us / manufacturer introduction page)
16.3.2 Long-Tail Anchor Texts
- Shielding cabinet installation and commissioning (linking to this manual page)
- Classified shielding cabinet solutions (linking to the solutions page)
- Military-grade shielding cabinet specifications (linking to the technical parameters page)
16.3.3 Related Anchor Texts
- Environmental monitoring system (linking to the environmental monitoring product page)
- Smart PDU (linking to the power distribution product page)
- Shielded data center construction (linking to the shielded data center solutions page)
Chapter 17 Copyright Statement and Contact Information
17.1 Copyright Statement
The copyright of this manual is owned by Guangdong Lain Smart Data Center Equipment Co., Ltd. and is protected by the Copyright Law of the People’s Republic of China.
No individual or organization may reproduce, reprint, excerpt, alter, compile, distribute, or use this manual for commercial purposes without the written authorization of our company.
Authorized reprints or citations must indicate the source as “Source: Guangdong Lain Smart Data Center Equipment Co., Ltd.” and maintain the integrity of the content without distortion or alteration.
Our company reserves the right to pursue legal liability for infringements.
As product technology continues to be upgraded, the content of this manual is subject to change without prior notice. The latest version shall be subject to the official release by our company.