KITOZER
KITOZER

KITOZER 100 sqm Welded Electromagnetic Shielding Enclosure: C-Class 80dB Design Guide

In radar testing, EMC laboratories, classified equipment rooms and military electronics debugging, external electromagnetic interference directly degrades measurement accuracy. KITOZER delivers a 100 sqm welded electromagnetic shielding enclosure rated to C-class shielding effectiveness (80 dB across 10 kHz to 18 GHz).

Design Standards

This design follows GB/T 12190-2021 and GJB 5786-2006. The enclosure uses fully welded cold-rolled steel plate construction; unlike bolted modular rooms, welded joints do not loosen over decades of service.

Structure

Floor: 80×60 mm steel framing at 600 mm spacing, covered with 5 mm cold-rolled plate welded by CO2 arc welding. Walls and ceiling: 2 mm steel plate on 40×60 mm framing, all welds continuously sealed. Anti-corrosion: two coats of epoxy zinc-rich primer (60 um dry film).

Flooring: 10 mm EPDM insulating rubber mat (volume resistivity >1e9 Ohm-cm) over the floor plate, topped with 600x600x35 mm all-steel anti-static ceramic access flooring (system resistance 1e6-1e9 Ohm, load >1200 kg/m2).

Shield Door and Waveguide

One motorized KITOZER KZ-ED-920C shield door (900×2000 mm) with beryllium-copper finger gaskets, access control and emergency egress. All cable penetrations use waveguide tubes and line filters: mains filter KZ-PF-380100 (380V/100A, insertion loss >60 dB), HVAC filter KZ-PF-38032, network filters, fire signal filter RS-485 (>50 dB), and 600×600 mm aluminum ventilation waveguide vents.

Reference Pricing

Shell structure (door, framing, plates, welding): approximately $50,000. Waveguide and filters: approximately $8,500. Power distribution and interior: approximately $6,600. Total reference price: approximately $65,100 (market range $62,000-$90,000). Reference price only; final pricing confirmed after site survey. Source: KITOZER project library.

Acceptance Criteria

Shielding effectiveness >=80 dB (third-party tested per GB/T 12190); grounding resistance <=1 Ohm; insulation resistance >=1e9 Ohm.

FAQ

Welded vs modular? Choose welded for permanent installations requiring >=80 dB. Modular suits temporary deployments but finger gaskets oxidize after 3-5 years.

HVAC sizing? Two 5-tonne AC units in N+1 redundancy; power cords through line filters, condensate through waveguide tubes.