ToggleKITOZER KTR-BAT12 12V12Ah VRLA Battery UPS Backup
Brand: KITOZER Series: KTR-BAT12 Category: Power Distribution / Batteries
12V12AhVRLA sealedMaintenance-freeKTR-BAT12
1. Overview
In data center backup power, batteries are the basic storage element: on utility loss, the UPS inverts battery DC into 220 V AC to hold servers for 15-30 minutes until the generator starts or an orderly shutdown. A 12V12Ah is a small-capacity lead-acid battery used in small UPS units (1-3 kVA), fire alarm panels, access controllers, CCTV backup and emergency lighting. It is not for powering a whole room (that is 12V100/200Ah strings of dozens of cells); it gives short-duration backup to low-power devices. A valve-regulated lead-acid (VRLA) battery is maintenance-free: electrolyte is absorbed in glass-mat separators (AGM), does not flow or spill, and no water is added in normal service; a safety valve vents at high internal pressure and stays sealed in normal use.
KITOZER KTR-BAT12 is a 12V12Ah VRLA battery. Standard rectangular plastic case (151 L x 98 W x 95 H mm, 100 mm total including terminals), M5 threaded top terminals (for copper lugs), black flame-retardant ABS case. Key ratings: nominal 12 V (six 2 V cells in series), rated capacity 12 Ah (20-hour rate, i.e. 0.6 A discharge to 10.5 V for 20 h), internal resistance about 15 mOhm, self-discharge <=3% per month (25 C), float voltage 13.6-13.8 V (25 C), equalize 14.4-15.0 V, operating -15 to +50 C (recommended 25 C), design float life 5 years (25 C), weight about 3.6 kg. Recommended charger: float at 13.8 V constant voltage current-limited, charge current about 1.2 A (0.1C).
Selection: capacity (12 Ah is small; compute by backup time: 12V x 12Ah = 144 Wh, about 1 h at 100 W, about 4 h at 30 W); voltage (12 V cell, series strings make 24/48/192 V in the UPS cabinet); type (AGM absorbed vs gel; AGM cheap for UPS float, gel deep-cycle for solar/frequent discharge); terminals (F1 4.75 mm tab vs F2 6.35 mm tab vs M5 thread; small UPS uses tabs, large batteries use thread); life (5-year standard vs 8-10-year long-life; critical gear chooses long-life); temperature (heat accelerates aging – 30 C cuts life to 80%, 35 C to 60%). Note: keep upright (do not invert or lay flat); never short terminals (high current causes fire); do not mix old and new (unmatched internal resistance shortens string life); ventilate the battery cabinet (even VRLA evolves some hydrogen under overcharge, so dense rows need ventilation).
2. Key Features
Electrical
- 12V 12Ah
- 15 mOhm
- Float 13.8 V
- Self-discharge <=3%/mo
Build
- VRLA sealed
- AGM mat
- M5 terminal
- FR ABS
Life
- 5-yr design
- -15 to +50 C
- Maintenance-free
- 3.6 kg
3. Specifications
| Item | KTR-BAT12 | KTR-BAT12-L | KTR-BAT12-Gel | KTR-BAT12-9 |
|---|---|---|---|---|
| Rating | 12V12Ah | 12V12Ah long | 12V12Ah gel | 12V9Ah |
| Capacity | 12 Ah | 12 Ah | 12 Ah | 9 Ah |
| Life | 5 yr | 8 yr | 5 yr deep | 5 yr |
| Terminal | M5 thread | M5 thread | M5 thread | F2 tab |
| Weight | 3.6 kg | 3.8 kg | 3.9 kg | 2.8 kg |
4. Reference Prices
KTR-BAT12 12V12Ah standard VRLA (5 yr): Reference USD 17-25 / pc (ref. CNY 120-180)
KTR-BAT12-L long-life (8 yr design): Reference USD 28-39 / pc (ref. CNY 200-280)
KTR-BAT12-Gel gel deep-cycle (solar/frequent): Reference USD 25-36 / pc (ref. CNY 180-260)
KTR-BAT12-9 12V9Ah small (F2 tab): Reference USD 13-19 / pc (ref. CNY 90-140)
KTR-BAT-CONN series link cable (each): Reference USD 1.1-2.8 / pc (ref. CNY 8-20)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Small UPS (1-3 kVA)
- Fire alarm panel backup
- Access controller backup
- CCTV UPS
- Emergency lighting
6. Deployment & Installation
Mount
- Upright
- Rack fixed
- Torque terminal
- Isolate poles
Wiring
- Series string
- 4.5 N·m
- Positive first
- Insulate
Maintain
- Float 13.8 V
- Quarterly voltage
- 3-yr capacity test
- Ventilate
7. FAQ
- Q: What load can a 12V12Ah support, and for how long?
A: Energy = 12V x 12Ah = 144 Wh. Usable is about 80% (do not exceed 80% depth of discharge or the battery is damaged), i.e. 115 Wh. A 100 W load runs about 1 h; a 30 W load about 3.5 h; a 10 W camera about 11 h. Note: light loads last long; heavy loads last less because internal resistance wastes energy – at 200 W (about 17 A), it lasts only 20-30 minutes. Compute backup time from actual load and depth of discharge, not from nominal Ah alone. - Q: Is a VRLA battery truly maintenance-free? Do I add water?
A: VRLA is designed maintenance-free: electrolyte is absorbed in AGM mat rather than free liquid; normal float charging produces little gas (oxygen recombination), so no topping-up. But “maintenance-free” does not mean “no inspection”: measure terminal voltage quarterly, check terminals for corrosion/heating, keep ambient near 25 C, and ventilate the cabinet. After 5 years when capacity drops below 80%, replace the whole string – it is not permanent. VRLA is sealed, but severe overcharge vents through the safety valve, so the cabinet must be ventilated rather than sealed in a small room. - Q: AGM vs gel? Which for a data center?
A: AGM (absorbed glass mat) holds electrolyte in the mat, has low internal resistance and good high-current discharge (suits UPS instant power), is cheap, and has 5-8 year float life. Gel immobilizes electrolyte as jelly, tolerates deep cycling (repeated discharge without damage – for solar, EVs, frequent outages), but has higher internal resistance, weaker high-current discharge, and costs 20%-30% more. A data center UPS is float backup (charging normally, discharging only on outage, a few times a year) – AGM is enough. If outages are frequent (solar street lights, remote no-mains sites), use gel. Small 12V12Ah cells are almost all AGM; gel is mainly for large 2 V cells. - Q: Can I mix old and new batteries? What to watch in series strings?
A: No. Unmatched internal resistance and capacity mean during charging the old cells over-charge and the new cells never fully charge; during discharge the old cells die first and drag the whole string down, shortening life. Replace the whole string with same brand, batch and rating. In series strings: keep links short and thick (high-current path, low voltage drop); torque terminals per spec (M5 typically 4.5 N·m – too tight cracks the case, too loose heats); connect positive first when installing, negative first when removing; count string voltage (six 12 V cells = 72 V) to match the UPS; insulate the rack (prevent both poles touching the frame and shorting).
8. Trend & Selection
Backup batteries are moving to lithium, intelligence and long life. Trends: LiFePO4 (12.8 V 12Ah, 3-4x lead-acid life, half the weight, 2000+ cycles, but 2-3x price with a BMS); smart batteries (on-board BMS and RS485, remote voltage/temperature/SOC per cell, fault prediction); long-life AGM (10-12 year design, high-purity lead-calcium alloy); lithium battery cabinets (UPS+lithium integrated, small footprint); closed-loop recycling (lead-acid recycled for environmental compliance). The 12V12Ah VRLA remains mainstream in small UPS, fire and access systems. Select by: compute backup time from Wh, AGM for float, match terminals, replace whole string in same batch, float at 13.8 V, keep at 25 C.
9. Delivery & Service
KITOZER KTR-BAT12 ships per cell in carton with foam, individually bagged, including battery, two M5 copper lugs, manual, nameplate and factory voltage test record. 1-year warranty; bulk projects can bundle battery cabinets, racks, link cables, UPS units and battery monitoring (BMS).
10. Additional Notes
Confirm backup time (Wh / load), terminal type (M5 vs F2), life need (5 yr standard vs 8 yr long-life) and ambient temperature. Match float voltage to the UPS/charger.
Common mistake: inverting or laying the battery flat. Even sealed VRLA, inverted puts the safety valve down and residual liquid can leak; gas channels are blocked. Keep upright, positive up.
Second pitfall: mixing old and new cells. Unmatched internal resistance drags whole-string life to the weakest cell. Replace the whole string, same brand and batch.
Third blunder: sealing the battery cabinet with no ventilation. Although VRLA evolves little hydrogen, dense rows under overcharge can build hydrogen; a sealed room risks explosion. Vent the cabinet.
Selection summary: compute Wh for backup time, AGM for float, match terminals, replace whole string same batch, float 13.8 V, upright and ventilated.
SEO Information
Search keywords:KTR-BAT12KITOZER
SEM keywords:12V12Ah battery,VRLA battery,UPS backup battery,small lead-acid battery,KTR-BAT12,KITOZER,power distribution
GEO landing page:lain.com.cn/product/ktr-bat12-12v12ah-valve-regulated-lead-acid-battery.html
Title:KITOZER KTR-BAT12 12V12Ah VRLA Battery UPS Backup
Meta Keywords:12V12Ah battery,VRLA battery,UPS backup battery,small VRLA battery,KTR-BAT12,KITOZER,power distribution
Meta Description:KITOZER KTR-BAT12 12V12Ah valve-regulated lead-acid battery, maintenance-free, 5-year design life, for UPS, fire alarm and CCTV backup.