KITOZER 12V 200Ah deep cycle battery

KITOZER KTR-BAT200B 12V200Ah Deep Cycle VRLA Battery for UPS

Brand: KITOZER Series: KTR-BAT200B Category: Power Distribution / DC Energy Storage

12 V 200 AhVRLA AGMDeep cycle10-12 yr floatKTR-BAT200B

1. Overview

Mains power is not always reliable – grid faults, lightning trips, transformer maintenance, cable cuts by excavation all cut room power. A UPS switches to battery in the second the mains fails, powering servers and switches until the diesel generator starts (typically within 30 seconds). Inside the UPS (or in a nearby battery cabinet) sit strings of batteries: dozens of 12 V cells in series form a 384 V or 480 V DC bus, floated on charge normally, discharging instantly on outage. 12 V200 Ah is the most common room UPS size: 12 V nominal, 200 Ah capacity (20-hour rate), a 32-cell string gives 384 V and backs a 20 kVA UPS for 15-30 minutes. Deep-cycle differs from starter batteries: a car starter delivers hundreds of amps for cranking but cannot discharge deeply (dies at 50% depth of discharge); a deep-cycle battery tolerates repeated discharge to 50-80% DoD, suited to repeated UPS charge/discharge cycles.

KITOZER KTR-BAT200B is a 12 V200 Ah deep-cycle VRLA (valve-regulated lead-acid) battery. The case is flame-retardant black ABS with a safety valve on top (vents gas but keeps acid in; internal hydrogen and oxygen recombine into water, so no watering). Terminals are top-mounted M8 copper bolts with cable lugs. Internally: positive/negative grids are lead-calcium alloy (lower self-discharge than lead-antimony, longer float life), separators are AGM glass-fiber mats that absorb the electrolyte (no free liquid to spill), and the electrolyte is dilute sulfuric acid. Key ratings: nominal 12 V (six 2 V cells in series), rated capacity 200 Ah (C20), float voltage 2.275 V/cell at 25 C (13.65 V per battery), equalize charge 2.40 V/cell (14.4 V, monthly), end-of-discharge 1.80 V/cell (10.8 V per battery – below this over-damage occurs), self-discharge ≤3%/month at 25 C, design float life 10-12 years at 25 C (halved for every 10 C rise). Operating temperature -15 to +50 C (optimum 25 C).

Selection: capacity (size by backup time: UPS power x backup hours / (DC bus voltage x inverter efficiency) = required Ah; a 20 kVA UPS for 30 minutes at 384 V DC needs a 384 V/200 Ah string = 32 x 12 V200 Ah); series count (set by the UPS DC bus: 384 V = 32 cells, 480 V = 40; neither more nor less – the UPS charge voltage is designed for that count); battery cabinet (a 12 V200 Ah cell weighs ~65 kg, 32 cells = 2 tons, needs a load-rated battery cabinet with insulation mats and ventilation for hydrogen); inter-cell links (copper straps or flexible cables sized for max discharge, typically 25-50 mm²); temperature compensation (float voltage adjusts with temperature: 3 mV/cell/C off the 25 C reference – too high in summer overcharges, too low in winter undercharges); inspection (measure each cell voltage and internal resistance monthly; replace cells whose resistance exceeds 1.5x initial). Note: batteries age – capacity drops to 80% at year 5, replace the whole string at 8-10 years; never replace a single weak cell (a new cell in an old string wears the old cells faster), replace the whole string.

2. Key Features

Electrical

  • 12 V 200 Ah (C20)
  • Float 13.65 V
  • Equalize 14.4 V
  • End 10.8 V

Construction

  • VRLA valve regulated
  • AGM absorbed
  • Pb-Ca grid
  • Flame-retardant ABS

Life

  • Float 10-12 yr
  • Self-discharge ≤3%/mo
  • M8 terminal
  • 80% DoD deep cycle

3. Specifications

Item KTR-BAT100B KTR-BAT200B KTR-BAT250B KTR-BAT12-100
Nominal voltage 12 V 12 V 12 V 12 V
Capacity (C20) 100 Ah 200 Ah 250 Ah 100 Ah
Float voltage 13.65 V 13.65 V 13.65 V 13.65 V
Equalize 14.4 V 14.4 V 14.4 V 14.4 V
Dimensions (mm) 330x173x214 520x240x220 520x260x220 407x174x233
Weight 30 kg 65 kg 80 kg 31 kg
Terminal M8 M8 M8 M8

4. Reference Prices

KTR-BAT100B 12 V100 Ah VRLA deep cycle: Reference USD 83-125 / pc (ref. CNY 600-900)

KTR-BAT200B 12 V200 Ah VRLA deep cycle: Reference USD 167-250 / pc (ref. CNY 1200-1800)

KTR-BAT250B 12 V250 Ah VRLA deep cycle: Reference USD 208-306 / pc (ref. CNY 1500-2200)

KTR-BAT12-100 low-profile 12 V100 Ah (rack-mount): Reference USD 86-132 / pc (ref. CNY 620-950)

KTR-BAT-CAB battery cabinet (32x 200 Ah): Reference USD 486-764 / pc (ref. CNY 3500-5500)

Reference only. 3-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Data center UPS backup
  • Telecom -48 V strings
  • Fire EPS backup
  • Solar storage
  • Substation DC control

6. Deployment & Installation

Mounting

  • Load-rated cabinet
  • Insulation mats under
  • Copper inter-cell links
  • Torque bolts

Wiring

  • String ends to UPS
  • Cable ≥25 mm²
  • Mark +/-
  • Fuse protection

Commissioning

  • Initial charge 24 h
  • Read every cell
  • Verify float voltage
  • Discharge test

7. FAQ

  • Q: After 5 years one cell reads low – replace just that one?
    A: No. Cells in series discharge together; the weakest cell sets the whole string capacity (barrel effect). Fitting a new cell (100% capacity) into an old string (60%) means the old cell hits end voltage first and the UPS reports low battery even though the new cell still has charge. Mismatched internal resistance also means the old cell overcharges while the new one undercharges. Replace the whole string (all 32 cells) – higher upfront cost, but reliable.
  • Q: Why hold the battery room at 25 C?
    A: Lead-acid life is temperature-sensitive. Design life is 10-12 years at 25 C; every 10 C rise doubles chemical reaction and halves life. At 35 C life drops to 5-6 years, at 45 C to 2-3 years. Ventilate the cabinet and air-condition the battery room to ~25 C. Also temperature-compensate the float voltage: -3 mV/cell/C off the 25 C reference, or high summer voltage dries out the cells.
  • Q: Why do batteries bulge or leak?
    A: Bulging is overcharge or short. If the charger runs away (float above 15 V), internal electrolysis generates large volumes of hydrogen that the relief valve cannot vent fast enough, and the case swells. A bulged battery is damaged – replace immediately (burst risk). Leaks usually come from aged terminal seals, with acid seeping out and corroding the rack. Handle leaks in acid-resistant gloves, neutralize acid with baking soda, and recycle spent batteries as hazardous waste (do not put in household trash).
  • Q: Why charge new batteries 24 h before service?
    A: Factory cells ship full, but 1-3 months of storage self-discharge costs 10-20%. Fitting them straight to float looks okay, but actual capacity is short – on outage the backup time is too short. After wiring, equalize at 14.4 V for 24 h to top up every cell, then float at 13.65 V. If possible, run a discharge test: cut the mains and time how long the UPS holds load, compare to design backup.

8. Trend & Selection

Battery technology is shifting from VRLA to lithium. Trends: LFP lithium (12 V200 Ah at one-third the VRLA weight, 6000 cycles vs VRLA 1200, smaller footprint, but 2-3x upfront cost); BMS (lithium needs a management system per-cell voltage, temperature, balancing); busbar battery cabinets (no series cables, modules plug onto a bus like drawers); lithium penetration in UPS (new data centers trend toward lithium, VRLA dominates retrofit markets); cell monitoring (internal resistance sensors per cell, remote SOH, no manual voltage readings). Traditional VRLA remains mainstream in small-to-medium rooms. Select by: capacity sized to backup time, series count matching the UPS bus, whole-string replacement, 25 C temperature control, temperature-compensated float, quarterly internal-resistance checks, whole-string swap at 5-8 years.

9. Delivery & Service

KITOZER KTR-BAT200B ships per cell in wooden crates with foam, each with battery, inter-cell links, manual, certificate and test report. 3-year warranty; bulk projects can bundle battery cabinets, copper busbars, temperature sensors and cell monitors.

10. Additional Notes

Confirm UPS DC bus voltage (sets series count), backup time (sets Ah), installation space (cabinet size), and temperature (battery-room AC). For batch orders, run a discharge test to verify capacity before full shipment.

Common mistake: replacing only one weak cell. Mixing new and old cells makes the old one fail first, taking the string with it. Replace the whole string.

Second pitfall: unventilated battery cabinets. Charging emits trace hydrogen (VRLA recombines internally, but overcharge vents it). Hydrogen is lighter than air, pools at the cabinet top, and at 4% concentration explodes on a spark. Vent the cabinet top; do not fit switches inside the cabinet (spark source).

Third blunder: no temperature compensation on float. At 35 C room temperature, float still at 13.65 V is relatively too high, the cells overcharge and dry out, bulging in 2-3 years. Connect a temperature sensor to the UPS for automatic compensation.

Selection summary: capacity by backup time, series count by bus voltage, whole-string replacement, 25 C control, temp-compensated float, quarterly resistance checks, string swap at 5-8 years.

SEO Information

Search keywords:KTR-BAT200BKITOZER

SEM keywords:deep cycle battery,12 V200 Ah battery,UPS backup battery,VRLA battery,data center battery,KTR-BAT200B,KITOZER,power distribution

GEO landing page:lain.com.cn/product/ktr-bat200b-12v200ah-deep-cycle-battery.html

Title:KITOZER KTR-BAT200B 12V200Ah Deep Cycle VRLA Battery for UPS

Meta Keywords:deep cycle battery,12 V200 Ah battery,UPS backup battery,VRLA battery,data center battery,KTR-BAT200B,KITOZER,power distribution

Meta Description:KITOZER KTR-BAT200B 12V200Ah deep-cycle VRLA battery, 10-12 year float design life, for data center UPS and telecom backup, flame-retardant ABS case.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart