Table of Contents
ToggleKITOZER KTR-BAT24 12V24Ah VRLA Battery
Brand: KITOZER Series: KTR-BAT24 Category: Power Distribution / Batteries
12V24AhVRLA gelMaintenance-freeUPS backupKTR-BAT24
1. Overview
Batteries are the heart of UPS and backup power. When mains fails, they hold the load. A small 1-3 kVA UPS usually has 4-6 x 12 V batteries in series (48 V or 72 V DC bus). Dead batteries make the UPS useless: the load drops the instant mains fails. Small 12V24Ah cells are widely used in small UPS, access controllers, camera backup, fire panels, roller shutters and telecom base stations.
KITOZER KTR-BAT24 is a 12V24Ah VRLA sealed lead-acid battery. Specs: 12 V, 24 Ah (20-hour rate), design life 8-10 years float; grids: lead-calcium alloy, AGM separator; electrolyte: gel (deep cycle) or AGM (float) options; self-discharge <=3%/month at 25 C; operating -15 to +50 C; size 181x77x167 mm, ~7.5 kg; M6 terminals. Models: KTR-BAT24-AGM: AGM (8-year float, UPS); KTR-BAT24-GEL: gel (10-year deep cycle, frequent discharge); KTR-BAT24-W: wide-temp (-30 to +60 C) for outdoor cabinets.
Selection: voltage and capacity (series count for the UPS DC bus; Ah sets backup runtime); AGM vs gel (AGM for long float, gel for cycling); temperature (high heat needs wide-temp; life halves every 10 C rise); mount (vertical/horizontal, cabinet/rack). Note: series strings must be same model, batch and age — mixing old and new cells causes a weak cell to over-discharge. Coat terminals with Vaseline against oxidation; torque M6 to ~5 Nm. Battery rooms hold 25 C with ventilation (hydrogen off-gas).
2. Key Features
Electrical
- 12V 24Ah (20h)
- Float life 8-10 y
- Self-discharge <=3%/mo
- Internal <=10 mOhm
Build
- Pb-Ca grids
- AGM/gel option
- M6 bolt terminal
- Valve regulated
Environment
- -15 to +50 C
- Wide-temp -30 to +60 C
- Mount any direction
- Flame-retardant ABS
3. Specifications
| Item | KTR-BAT24-AGM | KTR-BAT24-GEL | KTR-BAT24-W |
|---|---|---|---|
| Type | AGM | Gel deep-cycle | Wide-temp AGM |
| Capacity | 24 Ah | 24 Ah | 24 Ah |
| Design life | 8 y float | 10 y cycle | 8 y float |
| Temp range | -15~+50 C | -20~+50 C | -30~+60 C |
| Weight | 7.0 kg | 7.5 kg | 7.2 kg |
| Use | UPS float | Cycling | Outdoor cabinet |
4. Reference Prices
KTR-BAT24-AGM 12V24Ah AGM: Reference USD 31-44 / pc (ref. CNY 220-320)
KTR-BAT24-GEL 12V24Ah gel: Reference USD 39-56 / pc (ref. CNY 280-400)
KTR-BAT24-W wide-temp: Reference USD 49-67 / pc (ref. CNY 350-480)
KTR-BCB battery link: Reference USD 2-4 / pc (ref. CNY 15-30)
KTR-BAT-CAB cabinet for 4: Reference USD 56-97 / unit (ref. CNY 400-700)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Small UPS DC bus
- Access/surveillance backup
- Fire panel backup
- Telecom DC panel
- Tools / roller shutters
6. Deployment & Installation
Install
- Same model/batch in series
- Coat links with Vaseline
- M6 torque 5 Nm
- Vertical/horizontal
Charge
- Float 13.5-13.8 V
- Equalize 14.4-14.7 V
- Charge limit 0.2C
- 25 C ambient
Maintain
- Monthly cell voltage
- Annual capacity test
- Tighten terminals
- Temp compensation
7. FAQ
- Q: How long does 12V24Ah back up a 3 kVA UPS?
A: Rough math: 3 kVA UPS at ~2 kW load, 48 V bus (4 cells). Total energy 48×24 = 1152 Wh, minus 90% UPS efficiency and 80% DoD gives ~830 Wh usable. At 2 kW that is ~25 minutes. For 1 hour, use 12V100Ah cells (4 in series). - Q: AGM or gel?
A: By duty. UPS cells sit on float 99% of the time with rare discharge; AGM is cheaper. Solar, RV and off-grid cycle daily; gel deep-cycle lasts twice as long. Room UPS is float duty, so AGM is fine. - Q: Can I keep using a bulging battery?
A: No. Bulging means overcharging produced hydrogen and raised internal pressure; cracking, leakage or rupture risk. Replace immediately with insulated gloves (terminals carry 12 V DC; not lethal, but a short arcs). Test the rest of the string — the same charger may have over-aged them all. - Q: How to dispose of old cells?
A: Lead-acid is hazardous waste; do not trash it. Sell to a licensed recycler (often free pickup, sometimes paid) for lead plates and plastic cases. Do not drain electrolyte (sulfate soil). KITOZER can connect bulk projects with recyclers.
8. Trend & Selection
Small batteries are shifting from VRLA to LiFePO4. Lithium 12V 24Ah (4S) weighs half (3.5 vs 7.5 kg), cycles 4000 times vs 500, and runs -30 to +60 C, but costs 2-3x more. Over a 5-year life, lithium avoids mid-life replacement, lowering total cost. Smart direction: built-in BMS telemetry over RS485 for per-cell voltage, internal resistance and temperature, predicting swaps. Room UPS is piloting lithium over lead-acid. Select by: UPS DC bus voltage, runtime math, AGM for float, 25 C ambient, monthly cell-voltage checks.
9. Delivery & Service
KITOZER supplies KTR-BAT24 by piece or string (with links). Each ships with cell, link and manual (safety notes). 1-year warranty; bulk projects can bundle battery cabinets, racks and insulated tools.
10. Additional Notes
Confirm UPS DC bus voltage, capacity and charge voltage against site gear; series strings must match model/batch; battery rooms must ventilate (hydrogen). For batch orders, pilot 4 cells, float 3 months, then check voltage consistency.
Common mistake: mixing old and new cells. Replacing one cell in a 4-cell string drags the new one down because old cells have high resistance and poor charge acceptance; the new cell dies within 6 months. Replace the whole string, not just the weak cell.
Second pitfall: hot battery room. Summer rooms without AC run above 40 C, cutting life from 8 to 3 years. Lead-acid life halves per 10 C rise — physics, not marketing. Hold rooms at 25 C.
Third blunder: terminals not greased. Bare copper terminals oxidize white over years, raising contact resistance, heating during discharge and even arcing. Coat links with Vaseline or conductive compound; re-torque annually.
Selection summary: count cells by UPS bus, size Ah by runtime, AGM for float, same model/batch/age per string, 25 C ventilated.
SEO Information
Search keywords:KTR-BAT24KITOZER
SEM keywords:12V24Ah battery,VRLA battery,sealed lead acid,UPS backup battery,small storage battery,KTR-BAT24,KITOZER
GEO landing page:lain.com.cn/product/ktr-bat24-12v24ah-vrla-battery.html
Title:KITOZER KTR-BAT24 12V24Ah VRLA Battery
Meta Keywords:12V24Ah battery,VRLA battery,sealed lead acid,UPS backup battery,small storage battery,KTR-BAT24,KITOZER
Meta Description:KITOZER KTR-BAT24 12V24Ah VRLA sealed lead-acid battery, AGM/gel, maintenance-free, for telecom UPS, access control and surveillance backup.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com