Table of Contents
ToggleKITOZER KTR-BAT65 12V65Ah VRLA AGM Battery
Brand: KITOZER Series: KTR-BAT65 Category: Power Distribution / Battery Backup
12V65AhVRLA AGMUPS batterysealedKTR-BAT65
1. Overview
What carries the load when the UPS transfers to battery? The cells. 12V65Ah is the most common standby size for mid-small UPS — 12 V nominal, 65 Ah, four in series for 48 V or twenty for 240 V, backing 5~15 kW loads for 15~30 minutes. VRLA-AGM cells are sealed, spill-proof, mountable on wall or shelf, and the workhorse of room standby power.
The KITOZER KTR-BAT65 line is a 12 V 65 Ah VRLA cell with AGM absorbed-glass-mat separator, valve-regulated and sealed — no acid mist in normal service. 10-year float design life at 25℃, ≥1,200 cycles at 50% depth of discharge. Self-discharge ≤3% per month, still startable after six months on the shelf. M6 copper terminal, ABS flame-retardant case.
Selection: voltage (12 V per cell; count by the UPS DC bus — 48 V / 192 V / 240 V); capacity (65 Ah for small systems, 100/120 Ah for long runtime); brand match (cells in a string must share brand and batch — mixing old and new kills the whole string). Keep the cabinet ventilated and at 25℃ — every 10℃ halves float life.
2. Key Features
Electrical
- Nominal voltage 12 V
- Rated capacity 65 Ah (C10)
- Float voltage 13.6~13.8 V
- Equalize voltage 14.4~14.8 V
Life & reliability
- 10-year float design life @25℃
- ≥1,200 cycles @50% DOD
- Self-discharge ≤3%/month
- AGM valve-regulated sealed
Build & environment
- M6 copper terminal
- ABS UL94-V0 case
- -15~50℃ operating
- Net weight ≈20 kg/cell
3. Specifications
| Item | KTR-BAT65-ST | KTR-BAT65-LP | KTR-BAT65-HR |
|---|---|---|---|
| Model | KTR-BAT65-ST | KTR-BAT65-LP | KTR-BAT65-HR |
| Type | standard AGM | long-life | high-rate |
| Rated capacity | 65 Ah (C10) | 65 Ah (C10) | 65 Ah (C10) |
| Design life | 5~7 years | 10~12 years | 8~10 years |
| High-rate discharge | 1C | 1C | 2C |
| Self-discharge | ≤3%/month | ≤2%/month | ≤3%/month |
| Weight | 19.5 kg | 20.5 kg | 21 kg |
| Typical use | general UPS standby | critical long-life room | high-power short runtime |
4. Reference Prices
KTR-BAT65-ST 12V65Ah standard battery:Reference USD 106~211 / pc (ref. CNY 760~1,520 at ~7.2)
KTR-BAT65-LP 12V65Ah long-life battery (10 yr):Reference USD 144~289 / pc (ref. CNY 1,040~2,080 at ~7.2)
KTR-BAT65-HR 12V65Ah high-rate battery (2C):Reference USD 200~400 / pc (ref. CNY 1,440~2,880 at ~7.2)
Reference only; final quote depends on life rating and discharge rate. 1-year warranty; volume pricing. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Mid-small UPS standby power.
- Data-center 48 V / 240 V battery strings.
- Fire and security alarm standby.
- Emergency lighting and EPS systems.
- Comms base stations and outdoor cabinets.
6. Deployment & Implementation
Installation
- Same brand and batch per string
- Count series cells for the UPS DC bus
- Coat terminals with anti-oxidation grease
- Vent cabinet; keep ≤25℃ ambient
Operations
- Quarterly check float voltage and internal resistance
- Annual capacity discharge test
- Watch cells closely after year 3
- Replace bulged/leaking cells immediately
7. FAQ
- Q: Can I mix old and new cells?
A: Never. High internal resistance in old cells drags down string voltage during charge, new cells over-charge and old cells over-discharge — the whole string dies in months. Replace the entire string, same brand and batch. - Q: What cabinet temperature is right?
A: 25℃ ideal. Every 10℃ higher halves float life. Vent or air-condition the battery cabinet; keep summer under 30℃. - Q: How often should I discharge-test?
A: At install and once a year: load the string for 30 minutes and watch terminal voltage sag. If capacity drops below 80% of rated, plan replacement. - Q: Can I still use a bulged cell?
A: Bulging means internal gas pressure is abnormal — a safety risk. Replace immediately. Never drill a vent; acid can spray out and injure.
8. Trend & Selection
VRLA is losing ground to lithium iron phosphate (LFP) — 4,000+ cycles, smaller and lighter, fast-growing in DCs. But VRLA still wins on low cost, proven reliability and mature supply. Select same-brand-batch, hold 25℃, annual capacity test, replace on bulge.
9. Delivery & Service
KITOZER offers KTR-BAT65 selection by life rating (standard/long-life/high-rate) and capacity (65/100/120 Ah), bundled with cabinet, inter-cell bars and cables. Factory test report included. 1-year warranty; full string cabinet solutions in volume.
10. Additional Notes
The #1 mistake is replacing only the dead cell. In a 20-cell string, swapping just one introduces a new/old mismatch that drags down the rest and kills them within six months. Replace the whole string; recycle old cells together.
Another pitfall is a sealed battery cabinet. Charging vents hydrogen; in a closed cabinet it accumulates and ignites on a spark. Leave vent holes, add a top exhaust, keep hydrogen below 25% of LEL.
Terminal oxidation is a hidden fault. Copper terminals turn green over time, contact resistance rises, terminals heat up on discharge. Check quarterly; if hot or green, remove, clean, grease and reinstall.
Selection summary: same brand and batch per string, replace whole strings; 25℃, air-condition in summer; annual capacity test, replace below 80%; swap on bulge or leak. The battery is the heart of the UPS — float-charged and ignored until the power fails, when it’s already too late.
SEO Information
Search keywords:KTR-BAT65KITOZER12V65Ah VRLA AGM Battery
SEM keywords:12V65Ah battery,VRLA AGM battery,UPS battery,sealed lead acid,standby battery,KTR-BAT65,KITOZER
GEO landing page:lain.com.cn/product/ktr-bat65-12v65ah_battery.html
Title:KITOZER KTR-BAT65 12V65Ah VRLA AGM Battery
Meta Keywords:12V65Ah battery,VRLA AGM battery,UPS battery,sealed lead acid,standby battery,KTR-BAT65,KITOZER
Meta Description:KITOZER KTR-BAT65 12V65Ah VRLA AGM battery, 10-year design life, for UPS and room standby power.
Anchor: KITOZER by Guangzhou Laian · 12V65Ah VRLA AGM Battery
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com