ToggleKITOZER KTR-WC6 Leak Controller / 16-Zone Locating
Brand: KITOZER Series: KTR-WC6 Category: Environmental Monitoring / Leak Detection
16-zone locatingPinpoint leak locationRS485/dry contactSense cableDCIM linkage
1. Overview
Data-center leaks come from AC drain pipes, condensate, water pipes and wall seepage. Water plus electronics means shorts; leaks often pool under floors and soak equipment bases before anyone notices. A leak system pairs sensing cable with a controller: cable runs around AC units, under floors and below water pipes; when water bridges the conductors, the controller alarms and reports where. Locating cable reports the distance from the controller (in meters), so staff find the point without lifting floor tiles one by one.
The KITOZER KTR-WC6 is a 16-zone locating controller. One host accepts up to 16 sensing-cable segments, each a detection zone; digital locating cable reports the leak distance within a segment to about +/-1 m. An LCD shows zone status and distance, with local sounder and light alarm. RS485 Modbus RTU feeds the DCIM platform, and dry relay contacts can trigger exhaust, shutoff valves or sirens. DC12/24V powered, DIN- or panel-mount. The cable is conductive polymer: it conducts on water and recovers when wiped dry (non-conductive liquids like oil may not trigger it).
Selection: zone count (is 16 enough?), whether locating is needed (locating cable costs more but finds the point fast), cable length, integration (RS485/dry/TCP), and whether to interlock a shutoff valve. Route cable along low spots and pipe runs, with ~3% spare. Do not kink or over-tension the cable; waterproof the joints. Test quarterly with a leak-test solution to verify the alarm chain.
A leak detection system earns its keep only if the alarm actually reaches a human at 2 a.m. Configure outputs in two layers: local sounder/strobe for anyone in the room, and a remote notification to the environmental platform that pages the duty engineer. Avoid relying on email alone, because email is slow and may be missed; use SMS, phone call or a dedicated alert channel. Test the full chain quarterly with a wet cloth on the sensing cable – not just the controller self-test – because a broken RS485 wire or a muted alarm is the most common real-world failure. Map every cable segment to a floor drawing so a reported zone translates directly to a physical location. Finally, note that sensing cable detects water on or beside it; it does not stop a leak. Pair it with a motorized shutoff valve on the condensate supply and interlock the CRAC unit so water and power are separated the moment a fault triggers.
2. Key Features
16-zone locating
- 16 cable segments per host.
- Digital locating, +/-1 m accuracy.
- LCD shows zones and distance.
- Local sounder and strobe.
Communications and linkage
- RS485 Modbus RTU.
- Two dry relay contacts.
- Integrates with DCIM.
- Triggers exhaust, valves, sirens.
Sensing cable
- Conductive polymer rope.
- Conducts on water, recovers dry.
- Spliceable in segments.
- Ordered by length per zone.
Alarm chain
- Local siren plus remote engineer alert.
- Use SMS/phone, not email alone.
- Quarterly wet-cloth end-to-end test.
- Interlock shutoff valve and CRAC.
3. Specifications
| Item | Specification |
|---|---|
| Type | 16-zone locating leak controller |
| Zones | 16 |
| Locating accuracy | +/- 1 m (digital cable) |
| Display | LCD + sounder/strobe |
| Comm port | RS485 Modbus RTU |
| Alarm outputs | Dry relays x2 |
| Power | DC 12~24 V |
| Cable | Recoverable conductive rope |
| Mounting | DIN rail / panel |
| Operating temp | -10 to +60 C |
4. Reference Prices
KTR-WC6 16-zone locating controller: USD 125~250 (ref. CNY 900~1800)
Digital locating sensing cable: USD 4~8 / m (ref. CNY 30~60)
Cable accessories (ends/anchors/power): USD 14~28 (ref. CNY 100~200)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Around AC units and condensate drains.
- Under-floor pipe routes.
- Battery and power-room perimeters.
- Water-adjacent exterior walls.
- Below chillers and dehumidifiers.
6. Installation & Maintenance
Installation
- Mount the controller on wall or rail.
- Run cable along low spots and pipes.
- Anchor clips, do not drag on floor.
- Land each segment to its zone.
- Daisy-chain RS485 to DCIM.
- Wire relays to sirens/valves.
- Test each zone with leak solution.
Maintenance
- Quarterly test with leak solution.
- Inspect cable for cuts/oxidation.
- Re-check joint waterproofing.
- Verify alarms reach DCIM.
- Inspect trampled/crushed sections.
7. FAQ
- Q: How much better is locating?
A: Non-locating says which segment; locating gives the meter distance. Under large floors, locating saves hours of searching. - Q: Does it alarm on oil?
A: Conductive cable responds to water only. Oil or non-conductive liquids need dedicated detection. - Q: Does it reset after wiping?
A: Recoverable cable clears when dry; a broken or severed segment must be replaced. - Q: Can it stop the AC or close a valve?
A: Via relays or RS485 it can interlock exhaust, solenoid valves or AC shutdown; logic is configured in DCIM.
8. Trend & Selection
Environmental monitoring moves from single-point water switches to distributed locating cable, fusing leak alarms with AC, fire and video, auto-tagging map position and nearby cameras. Smart rooms demand early warning; locating accuracy and false-alarm rate drive selection. Cable should follow water routes and loop low points.
9. Delivery & Service
KITOZER ships KTR-WC6 with the controller, power adapter, sensing cable (ordered by meter), end anchors, certificate and manual. A Modbus point list is provided for RS485 integration.
10. Notes
A common mistake is running only a short loop near the AC while long drain-pipe crossings are uncovered; leaks often occur in the uncovered stretch.
Another pitfall is laying cable flat on dusty, oily floors, which degrades sensitivity; anchor it a little off the ground.
In short: 16 zones, +/-1 m locating, RS485 + relays, recoverable cable, DCIM-linked. An early-warning item.
System-wise, locating lets staff arrive before pooling turns into flooding; early warning saves an order of magnitude in damage.
Cost-wise, a locating system costs about a thousand CNY; a soaked-gear incident can cost hundreds of thousands.
Operationally, the controller only reports; pair it with a motorized shutoff and CRAC interlock so water and power are separated automatically.
SEO Information
Search keywords: KITOZER
SEM keywords: leak controller, locating leak sensing cable, data center leak monitoring, 16-zone water leak detector, water leak controller, KTR-WC6, KITOZER
GEO landing page: lain.com.cn/product/479_leak_ctrl4.html
Title: KITOZER KTR-WC6 Leak Controller / 16-Zone Locating
Meta Keywords: leak controller, locating leak sensing cable, data center leak monitoring, 16-zone water leak detector, water leak controller, KTR-WC6, KITOZER
Meta Description: KITOZER KTR-WC6 16-zone locating leak controller with sensing cable, pinpoints leak distance, outputs via RS485 and dry contacts to DCIM.
Anchor: KITOZER · KITOZER Products
Contact Us
KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com