ToggleI. System Overview
解决方案10-1024x575.jpg)
The 19-inch rack-mount UPS (Uninterruptible Power Supply) is a power protection device specially designed for standard 19-inch server cabinets, adopting a rack-mount installation method with height measured in “U” (1U=44.45mm). It can be installed in the same cabinet with servers, network equipment and other IT infrastructure, saving computer room space and improving the utilization rate of the computer room. The KITOZER rack-mount UPS system adopts a double-conversion online topology, realizing zero-millisecond switching between mains power and battery power supply. It provides continuous, stable and pure power protection for critical loads, and effectively prevents damage to IT equipment caused by power problems such as mains power outages, voltage fluctuations, frequency drifts and harmonic interference.
Integrated with advanced DSP (Digital Signal Processing) technology, an intelligent Battery Management System (BMS) and network monitoring functions, the system supports remote management and operation, and is widely used in scenarios with high requirements for power quality and reliability such as data centers, server rooms, communication base stations, financial institutions, medical equipment and industrial automation.
II. System Composition
解决方案8-1024x575.jpg)
The KITOZER 19-inch rack-mount UPS system consists of the following core components:
| Component Name | Function Description |
|---|---|
| Rectifier/Charger | Converts AC mains power to DC, provides stable DC power for the inverter, and charges the battery pack at the same time |
| Inverter | Converts DC to pure sine wave AC output to ensure high-quality power supply for loads |
| Static Switch | Implements fast switching between mains power and inverter output to ensure zero-millisecond conversion |
| Battery Pack | Energy storage device that provides DC power for the inverter when mains power is abnormal to ensure continuous power supply |
| Battery Management System (BMS) | Monitors battery status in real time, including voltage, current, temperature, internal resistance, etc., prevents overcharging and over-discharging, and extends battery life |
| DSP Digital Controller | Core control unit that realizes full digital control of the system, optimizes operation efficiency and provides a variety of protection functions |
| Input/Output Distribution Unit | Implements distribution and protection of power input and output, including circuit breakers, lightning protection modules, etc. |
| Monitoring and Communication Module | Provides communication interfaces such as RS232, USB and SNMP, supporting local and remote monitoring |
| Human-Machine Interface | LCD display + buttons, displays system operating parameters and fault information, and supports parameter setting |
| Cooling System | Intelligent temperature-controlled fan that automatically adjusts speed according to load and temperature, reducing noise and improving efficiency |
III. System Classification
解决方案6-1024x575.jpg)
1. Classification by Power Capacity
| Power Rating | Dimension Specification | Applicable Scenario |
|---|---|---|
| Low-power Type | 1-3kVA, 1U/2U height | Small computer rooms, network cabinets, edge computing nodes |
| Medium-power Type | 5-10kVA, 2U/3U height | Medium computer rooms, server clusters, storage devices |
| High-power Type | 15-40kVA, 3U/6U height | Large data centers, high-density server cabinets, critical business systems |
2. Classification by Topology
| Topology Type | Working Principle | Advantages | Applicable Scenario |
|---|---|---|---|
| Double-conversion Online Type | Mains → Rectification → Inversion → Load, full-process voltage and frequency stabilization | Zero switching time, perfect isolation of mains interference | Core business, critical equipment, medical systems |
| Line-interactive Type | Direct power supply with voltage stabilization when mains is normal; switching to inversion when mains is abnormal | High efficiency, moderate cost | Non-core business, general servers |
| Standby Type | Bypass power supply when mains is normal; inverter starts when mains is abnormal | Low cost, small size | Personal computers, small network equipment |
All series of KITOZER rack-mount UPS adopt double-conversion online topology to ensure the highest level of power protection.
3. Classification by Battery Configuration
解决方案5-1024x575.jpg)
| Configuration Type | Features | Applicable Scenario |
|---|---|---|
| Built-in Battery Type | Battery pack is built into the UPS chassis, no additional space required | Small computer rooms with limited space, rapid deployment scenarios |
| External Battery Type | Battery pack is installed independently in cabinets or battery cabinets, with flexible expandability | Critical business requiring long-delay power supply, large data centers |
| Modular Expandable Type | Battery modules support hot swap and online capacity expansion | Scenarios with dynamically changing loads, computer rooms requiring flexible expansion |
IV. System Configuration List (KITOZER Brand)
Standard Configuration List (10kVA as an example)
| Serial Number | Equipment Name | Model | Specifications | Quantity |
|---|---|---|---|---|
| 1 | 19-inch Rack-mount UPS Host | KITOZER-R10K | 10kVA/9kW, 2U height, double-conversion online type, input 220V/380V, output 220V | 1 unit |
| 2 | Built-in Battery Pack | KITOZER-BATT-10K | 12V/9Ah × 8 pcs, valve-regulated lead-acid battery | 1 set |
| 3 | Input Distribution Module | KITOZER-PDU-IN | 32A circuit breaker, surge protection, input terminal block | 1 piece |
| 4 | Output Distribution Module | KITOZER-PDU-OUT | 8 channels 16A C13 sockets + 2 channels 32A C19 sockets | 1 piece |
| 5 | Monitoring and Communication Card | KITOZER-SNMP-01 | Supports SNMP/HTTP/HTTPS, remote monitoring | 1 piece |
| 6 | Network Management Software | KITOZER-NMS-01 | Supports centralized management of multiple devices, alarm notification, data statistics | 1 set |
| 7 | Rack Mounting Kit | KITOZER-RMK-02 | Adapted to 19-inch standard cabinets, including guide rails and screws | 1 set |
| 8 | Operation Manual and CD-ROM | KITOZER-DOC-01 | Including user manual, installation guide, software CD-ROM | 1 set |
| 9 | Warranty Card and Certificate of Conformity | KITOZER-WTY-01 | Including 3-year warranty certificate, product certificate of conformity | 1 set |
Optional Configuration List
| Serial Number | Equipment Name | Model | Specifications | Remarks |
|---|---|---|---|---|
| 1 | External Battery Cabinet | KITOZER-BC-16 | Can hold 16 pcs 12V batteries, 19-inch 3U height | Selected for long-delay power supply |
| 2 | Battery Inspection Module | KITOZER-BIM-08 | Monitors single battery voltage and temperature for 8 pcs batteries | Improves battery management accuracy |
| 3 | Environment Monitoring Module | KITOZER-EM-01 | Monitors temperature, humidity, smoke detection, access control | Comprehensive computer room environment monitoring |
| 4 | Remote Maintenance Module | KITOZER-RMM-01 | Supports 4G/5G remote access, fault diagnosis | Unattended computer rooms |
| 5 | Parallel Module | KITOZER-PAR-01 | Supports parallel operation of multiple UPS units, improves reliability | Large data centers |
| 6 | Isolation Transformer | KITOZER-IT-10K | 10kVA, isolated output, suppresses common-mode interference | Medical equipment, precision instruments |
V. System Schematic Diagram
解决方案4-副本-1024x575.jpg)
Mains Input → Input Distribution Unit (Lightning Protection/Circuit Breaker) → Rectifier → DC Bus → Inverter → Output Distribution Unit → Load
└─────────── Static Switch ────────────┘
Battery Pack (Managed by BMS)
Monitoring and Communication Module (RS232/USB/SNMP)
Human-Machine Interface (LCD/Buttons)
Working Process Description
- Normal Mains Power: Mains power enters the rectifier through the input distribution unit and is converted into DC power, part of which supplies power to the inverter and the other part charges the battery pack; the inverter converts DC power into pure sine wave AC power and supplies it to the load through the output distribution unit; the static switch is on the inverter side.
- Abnormal Mains Power: The rectifier stops working, and the battery pack supplies power to the inverter through the DC bus to ensure the continuous operation of the load; the static switch remains on the inverter side to achieve zero-millisecond switching.
- Mains Power Recovery: The rectifier restarts and first charges the battery pack, then switches back to the normal working mode after the voltage is stable.
- Fault Protection: When the inverter fails, the static switch quickly switches to the mains bypass to ensure uninterrupted power supply to the load and send an alarm signal at the same time.
VI. Product Technical Parameters
解决方案3-副本-1024x575.jpg)
Technical Parameter Table of KITOZER-R Series 19-inch Rack-mount UPS (10kVA as an example)
| Item | Specifications |
|---|---|
| Basic Parameters | |
| Model | KITOZER-R10K |
| Type | Double-conversion online rack-mount UPS |
| Rated Capacity | 10kVA/9kW (power factor 0.9) |
| Dimension Specification | 19-inch standard rack, 2U height (88.9mm), depth 650mm |
| Weight | 35kg (including built-in battery) |
| Input Parameters | |
| Input Voltage | 220V/380V (optional), three-phase/single-phase (optional) |
| Input Voltage Range | 120V~275V (wide input range) |
| Input Frequency | 50/60Hz, automatic identification |
| Input Frequency Range | 40Hz~70Hz |
| Input Power Factor | ≥0.99 (full load) |
| Input Harmonic Distortion | ≤3% (full load) |
| Output Parameters | |
| Output Voltage | 220V/380V (optional), three-phase/single-phase (optional) |
| Output Voltage Accuracy | ±1% (steady state), ±3% (dynamic state) |
| Output Frequency | 50/60Hz, synchronized with input (mains mode), ±0.1Hz (battery mode) |
| Output Waveform | Pure sine wave, THD≤3% (linear load), ≤5% (non-linear load) |
| Switching Time | 0ms (mains/battery) |
| Overload Capacity | 125% load for 10 minutes; 150% load for 1 minute; 1000% load for 200ms |
| Battery Parameters | |
| Battery Type | Valve-Regulated Lead-Acid (VRLA) battery |
| Battery Voltage | 96V (8 built-in 12V batteries) |
| Charging Method | Intelligent three-stage charging, temperature compensation |
| Battery Management | Built-in BMS, monitoring voltage, current, temperature, internal resistance |
| Efficiency and Protection | |
| Conversion Efficiency | ≥95% at full load, ≥94% at half load, ≥98% in ECO mode |
| Protection Functions | Input overvoltage/undervoltage protection, output overvoltage/undervoltage protection, overcurrent protection, short circuit protection, overtemperature protection, battery overcharge/overdischarge protection |
| Communication and Monitoring | |
| Communication Interfaces | RS232, USB, SNMP, dry contact alarm |
| Monitoring Software | KITOZER-NMS network management system, supporting Web and APP remote monitoring |
| Environmental Parameters | |
| Operating Temperature | 0℃~40℃ |
| Storage Temperature | -25℃~55℃ |
| Relative Humidity | 0%~95% (no condensation) |
| Altitude | ≤1000m (derating required if exceeded) |
| Noise Level | ≤55dB (1-meter distance) |
VII. Product Application Scope
The KITOZER 19-inch rack-mount UPS system is applicable to the following scenarios:
1. Data Centers and Server Rooms
解决方案2-副本-1024x575.jpg)
- Enterprise-level data centers, colocation rooms, cloud computing centers
- High-density server cabinets, blade servers, storage arrays
- Edge computing nodes, micro data centers
2. Communication and Network Systems
- Communication base stations, core network computer rooms, transmission equipment
- Network core equipment, routers, switches, firewalls
- Data communication equipment, optical transmission equipment, satellite communication systems
3. Financial and Commercial Systems
- Bank data centers, ATMs, POS systems
- Securities trading systems, insurance business systems
- Commercial POS networks, payment and settlement systems
4. Medical and Scientific Research Institutions
解决方案1-1024x575.jpg)
- Operating room equipment, ICU life support systems
- Medical imaging equipment (CT, MRI, ultrasound)
- Laboratory precision instruments, analysis equipment
5. Industry and Automation
- Industrial control systems (PLC, DCS)
- Production line automation equipment, robot systems
- Precision processing equipment, semiconductor manufacturing equipment
6. Government and Public Services
- Government cloud platforms, e-government systems
- Emergency command centers, public security systems
- Traffic dispatching systems, air traffic control equipment
7. Education and Scientific Research
- Campus network centers, library servers
- Scientific research computing clusters, supercomputers
- Distance education platforms, multimedia teaching systems
VIII. Product Advantages
1. Space-Optimized Design
- Standard 19-inch rack-mount installation with 1U/2U/3U height, installed in the same cabinet with IT equipment to save computer room space
- High-density power design, 10kVA only requires 2U space to improve cabinet utilization
- Front and rear ventilation design, adapted to the hot and cold aisle layout of cabinets to improve heat dissipation efficiency
2. Excellent Power Protection
- Double-conversion online topology, zero-millisecond switching, complete isolation of mains interference
- Pure sine wave output with THD≤3% to meet the power supply requirements of precision equipment
- Wide input voltage range (120V~275V) to adapt to harsh power grid environments
- Comprehensive protection functions including overvoltage, undervoltage, overcurrent, short circuit, overtemperature and battery protection
3. High Energy Efficiency and Energy-Saving Features
- Conversion efficiency ≥95% at full load and ≥98% in ECO mode to reduce operating costs
- Intelligent fan control that automatically adjusts speed according to load and temperature to reduce noise and energy consumption
- Power Factor Correction (PFC) technology with input PF≥0.99 to reduce power grid harmonic pollution
- Complies with national first-class energy efficiency standards to support the construction of green data centers
4. Intelligent Management Functions
- DSP full digital control with fast response speed and high control precision
- Advanced Battery Management System (BMS) that extends battery life by more than 30%
- A variety of communication interfaces (RS232, USB, SNMP) supporting remote monitoring and management
- Compatible with mainstream network management platforms, supporting centralized monitoring and alarm notification
- LCD Chinese and English display for easy operation and real-time mastery of system status
5. High Reliability Design
- Redundant design with redundant configuration of key components (fans, capacitors) to improve system availability
- Supports N+1 parallel redundancy, with multiple UPS units operating in parallel to improve system reliability
- Hot-swappable battery modules support online replacement to reduce maintenance difficulty
- Industrial-grade components with MTBF≥200,000 hours to ensure long-term stable operation
6. Flexible Expandability
- Modular design supporting online capacity expansion of power modules and battery modules
- Compatible with external battery cabinets, flexible configuration of backup time according to requirements
- Supports a variety of output socket configurations to adapt to power interfaces of different equipment
- Expandable environment monitoring module to realize comprehensive monitoring of computer room temperature, humidity, smoke detection, etc.
IX. Product Bid Control Parameters
Core Bid Control Parameters (* indicates mandatory compliance items)
| Serial Number | Parameter Name | Bid Control Requirement |
|---|---|---|
| 1 | *Product Type | 19-inch rack-mount UPS, double-conversion online topology, zero-millisecond switching |
| 2 | *Rated Capacity | Not less than 10kVA/9kW, power factor 0.9 |
| 3 | *Dimension Specification | Standard 19-inch rack-mount installation, height ≤2U (88.9mm) |
| 4 | *Conversion Efficiency | ≥95% at full load, ≥94% at half load, ≥98% in ECO mode |
| 5 | *Input Parameters | Voltage range 120V275V, frequency range 40Hz70Hz, input PF≥0.99 |
| 6 | *Output Parameters | Pure sine wave output, THD≤3% (linear load), voltage accuracy ±1% |
| 7 | *Battery Management | Built-in intelligent BMS, monitoring single battery voltage, temperature, internal resistance, supporting battery charge and discharge management |
| 8 | *Communication Function | Supports RS232, USB, SNMP communication, provides network management software |
| 9 | *Protection Function | With input overvoltage/undervoltage, output overvoltage/undervoltage, overcurrent, short circuit, overtemperature, battery protection and other functions |
| 10 | *Reliability Index | MTBF≥200,000 hours, supports N+1 parallel redundancy |
| 11 | Operating Temperature | 0℃~40℃, adaptable to various environmental conditions |
| 12 | Noise Level | ≤55dB (1-meter distance), in line with computer room environmental requirements |
| 13 | Certification Requirements | With CE, UL, ISO9001 certifications, complying with relevant national standards |
| 14 | Warranty Period | Whole machine warranty ≥3 years, battery warranty ≥2 years |
| 15 | Brand Requirement | The bid product must be of KITOZER brand, with original factory authorization certificate provided |
Technical Deviation Table (Example)
| Serial Number | Bid Control Parameter | Bidding Product Parameter | Deviation Status | Explanation |
|---|---|---|---|---|
| 1 | Full load efficiency ≥95% | 95.5% | Positive deviation | Efficiency is higher than the standard requirement |
| 2 | Output THD ≤3% | 2.8% | Positive deviation | Harmonic distortion is lower than the standard requirement |
| 3 | MTBF ≥200,000 hours | 250,000 hours | Positive deviation | Reliability is higher than the standard requirement |
X. Product Solutions
Solution 1: Single Cabinet Protection Solution for Small Computer Rooms (1-3kVA)
Applicable Scenarios
- Small enterprise computer rooms, network cabinets, edge computing nodes
- Load power ≤3kVA, requiring independent single cabinet protection
- Limited space, moderate budget
Solution Configuration
- KITOZER-R3K (3kVA/2.7kW, 1U height) built-in battery type UPS host
- Standard 19-inch cabinet with guide rail mounting kit
- Basic monitoring module (RS232+USB)
- Input and output distribution unit (4 channels C13 sockets)
Solution Features
- Integrated design, easy installation, plug and play
- Built-in battery, no additional space required
- Suitable for rapid deployment, meeting basic power protection needs
Solution 2: Multi-Cabinet Parallel Solution for Medium Computer Rooms (5-10kVA)
Applicable Scenarios
- Medium enterprise data centers, server clusters
- Load power 5-10kVA, requiring high reliability guarantee
- Critical business systems with no power outage allowed
Solution Configuration
- 2 units of KITOZER-R10K (10kVA/9kW, 2U height) UPS hosts with N+1 parallel connection
- External battery cabinet KITOZER-BC-16 providing 1-hour backup time
- Centralized monitoring system supporting Web remote management
- Input and output distribution system with ATS automatic transfer switch
- Environment monitoring module (temperature, humidity, smoke detection, access control)
Solution Features
- Parallel redundancy design with system availability ≥99.999%
- Long-delay power supply to meet the continuous operation requirements of critical business
- Centralized monitoring for convenient unified management and maintenance
Solution 3: Modular Solution for Large Data Centers (15-40kVA)
Applicable Scenarios
- Large enterprise data centers, cloud computing centers
- High-density server cabinets with load power 15-40kVA
- Requiring phased capacity expansion and flexible configuration
Solution Configuration
- KITOZER-R series modular UPS, 3U height, 10kVA per module
- 4 power modules (3+1 redundancy) with total capacity 30kVA
- External battery array providing 2-hour backup time
- Intelligent battery management system supporting hot-swappable replacement
- Centralized monitoring platform supporting SNMP and Modbus protocols
- Input and output distribution cabinets with precision distribution monitoring
Solution Features
- Modular design supporting online capacity expansion to maximize return on investment
- Hot swap technology reduces maintenance difficulty and improves system availability
- Intelligent monitoring for real-time mastery of system operating status and early warning
- High energy efficiency to reduce the PUE value of data centers
XI. Product Application Cases
Case 1: Renovation Project of a Financial Institution’s Data Center
Project Background
The client is a large domestic bank. The existing UPS system of its data center is aging with the risk of single point of failure, requiring upgrading and renovation to ensure the 7×24-hour uninterrupted operation of core business systems.
Solution
- Adopt 4 units of KITOZER-R20K (20kVA/18kW, 3U height) UPS hosts with 2+2 parallel redundancy
- Configure external battery packs to provide 2-hour backup time
- Deploy a centralized monitoring system connected with the bank’s existing IT management platform
- Adopt closed hot and cold aisle design to improve heat dissipation efficiency
Implementation Effect
- System availability increased to 99.999%, eliminating single point of failure
- Conversion efficiency increased from the original 88% to 95.5%, saving about 200,000 RMB in electricity bills annually
- Realize remote monitoring and management, reducing operation and maintenance personnel by 50%
- Meet the Class A requirements of the China Banking and Insurance Regulatory Commission for power protection of financial institution data centers
Case 2: New Operating Room Project of a Grade III Class A Hospital
Project Background
The client is a Grade III Class A hospital with 10 new operating rooms. It needs to provide reliable power protection for life support systems and medical imaging equipment, requiring zero-interruption power supply and pure power output.
Solution
- Configure 1 unit of KITOZER-R5K (5kVA/4.5kW, 2U height) UPS host for each operating room
- Adopt isolated transformer output to suppress common-mode interference and meet the requirements of medical equipment
- Configure long-delay battery packs to provide 4-hour backup time
- Connect with the hospital’s HIS system to realize automatic fault alarm
Implementation Effect
- Zero-millisecond switching to ensure uninterrupted surgical procedures
- Pure sine wave output with THD≤2.8% to meet the requirements of precision medical equipment
- Long-delay power supply to cope with sudden power outages
- Comply with national electrical safety standards for medical equipment
Case 3: Automation Project of a Manufacturing Production Line
Project Background
The client is an auto parts manufacturer with a high degree of production line automation. The PLC control system and robot equipment have strict requirements for power quality. Frequent power outages lead to production line shutdowns and heavy losses.
Solution
- Configure 1 unit of KITOZER-R15K (15kVA/13.5kW, 3U height) UPS host for each production line
- Adopt wide input voltage design to adapt to factory power grid fluctuations
- Configure an intelligent battery management system to extend battery service life
- Integrate with the MES system to realize correlation analysis of power events and production data
Implementation Effect
- Eliminate the impact of power grid fluctuations on the production line, reducing downtime by 90%
- Improve equipment operation stability and increase product qualification rate by 2%
- Intelligent battery management extends the battery replacement cycle to 5 years
- Reduce maintenance costs and improve production efficiency
XII. System Schematic Diagram (Detailed Version)
┌─────────────────────────────────────────────────────────────────┐
│ Mains Input (220V/380V) │
└───────────────────────┬─────────────────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ Input Distribution Unit (Lightning Protection Module + │
│ Circuit Breaker + EMI Filter) │
└───────────────────────┬─────────────────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ Rectifier (PFC+IGBT) │
│ Function: AC→DC conversion, power factor correction, provides │
│ stable DC power for the inverter and charges the battery │
└───────────────────────┬─────────────────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ DC Bus (Capacitor Energy Storage + │
│ Voltage Detection) │
└───────────────────────┬─────────────────────────────────────────┘
┌───────────────┴───────────────┐
│ │
▼ ▼
┌─────────────────┐ ┌─────────────────────────────┐
│ Battery Pack │ │ Inverter │
│ (Managed by │ │ Function: DC→AC conversion, │
│ BMS) │ │ pure sine wave output │
└─────────────────┘ └─────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ Static Switch (IGBT+SCR) │
│ Function: Fast switching between mains and inverter output, │
│ zero-millisecond conversion │
└───────────────────────┬─────────────────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ Output Distribution Unit (Circuit Breaker + Surge Protection │
│ + Sockets/Terminal Block) │
└───────────────────────┬─────────────────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ Load (Servers/Network Equipment/Precision Instruments) │
└─────────────────────────────────────────────────────────────────┘
┌─────────────────────────────────────────────────────────────────┐
│ Monitoring and Control System │
│ 1. DSP Digital Controller: Core control unit, realizing full │
│ digital control of the system │
│ 2. Human-Machine Interface: LCD display + buttons, displaying │
│ operating status │
│ 3. Communication Module: RS232/USB/SNMP, supporting local and │
│ remote monitoring │
│ 4. Protection System: Overvoltage/undervoltage/overcurrent/short │
│ circuit/overtemperature/battery protection │
└─────────────────────────────────────────────────────────────────┘
XIII. Search Keywords, SEO and Tags
Search Keywords
- 19-inch rack-mount UPS
- Cabinet-specific UPS
- KITOZER UPS
- Double-conversion online UPS
- Data center UPS solution
- Rack-mount UPS system configuration
- Uninterruptible Power Supply system
- Computer room power protection solution
- Modular UPS
- Long-delay UPS power supply
SEO Optimization Keywords
- 19-inch rack-mount UPS brand recommendation
- Cabinet-specific UPS system composition
- Data center UPS solution design
- Detailed explanation of rack-mount UPS technical parameters
- UPS system schematic diagram
- KITOZER UPS application cases
- Computer room UPS power supply selection guide
- Advantages of double-conversion online UPS
- Uninterruptible Power Supply system bid control parameters
- Green data center UPS solution
Tags
- #19inchRackMountUPS
- #CabinetSpecificUPS
- #KITOZER
- #DoubleConversionOnline
- #DataCenterUPS
- #UninterruptiblePowerSupply
- #PowerProtection
- #ComputerRoomSolution
- #ModularUPS
- #IntelligentMonitoringUPS
- #LongDelayUPS
- #GreenEnergySavingUPS
- #IndustrialUPS
- #MedicalUPS
- #FinancialUPS