Table of Contents
ToggleKITOZER KTR-192V 192V Series Battery String for UPS
Brand: KITOZER Series: KTR-192V Category: Power Distribution / Batteries
192V string16x 12VVRLA10~12 yrKTR-192V

1. Overview
When mains fails, the UPS runs on the battery string — the string is the UPS’s fuel tank. Large UPS (20 kVA+) DC buses are commonly 192 V, 240 V or 384 V. A 192 V bus is built from 16 series-connected 12 V VRLA cells (16×12 V = 192 V). Series connection adds voltage, not capacity; one bad cell drops the whole string and the UPS either fails over or shuts down.
The KITOZER KTR-192V string consists of 16×12 V/100 Ah (or 65/120/200 Ah) VRLA cells on a rack or cabinet, with optional BMS monitoring per-cell voltage, current and temperature. Cells use AGM absorptive-glass-mat, valve-regulated, spill-proof, mountable in any orientation. Float life 10~12 years at 25C; deep-cycle life 300~500 cycles. Float 2.27 V/cell (~36.3 V per string), boost 2.40 V/cell (~38.4 V), end-of-discharge 1.80 V per 2 V cell (= 10.8 V per 12 V cell, ~172.8 V per string).
Selection: capacity by backup time — 100 Ah for 30 min, 200 Ah for 2 h, 300+ Ah for 4 h; type — VRLA AGM for general rooms, gel for high temperature or long-life needs; and rack/cabinet — 16×100 Ah cells weigh ~500 kg, so verify floor loading (battery room floor >=10 kN/m2). Batteries are consumables; after 5 years capacity drops below 80% and the whole string should be replaced — never mix old and new cells.
2. Key Features
Performance
- 16×12 V series = 192 V
- AGM starved-electrolyte
- Float life 10~12 yr
- 65~200 Ah options
Safety
- VRLA spill-proof
- Any orientation
- Built-in relief valve
- Flame-retardant ABS case
Monitoring
- Per-cell voltage
- Optional BMS
- Temperature-compensated charge
- Over-charge/discharge protection
3. Specifications
| Item | KTR-192V-S1 | KTR-192V-S2 | KTR-192V-S3 |
|---|---|---|---|
| 型号 | KTR-192V-65 | KTR-192V-100 | KTR-192V-200 |
| 单节容量 | 12V/65Ah | 12V/100Ah | 12V/200Ah |
| 串联节数 | 16节 | 16节 | 16节 |
| 组标称电压 | 192V | 192V | 192V |
| 后备时间(20kVA) | 约15分钟 | 约30分钟 | 约2小时 |
| 浮充电压 | 2.27V/节 | 2.27V/节 | 2.27V/节 |
| 放电终止 | 10.8V/节 | 10.8V/节 | 10.8V/节 |
| 单节重量 | 约20kg | 约30kg | 约60kg |
4. Reference Prices
KTR-192V-65 string 16x12V/65Ah (rack incl.): Reference USD 583~944 / set (ref. CNY 4200~6800 at ~7.2)
KTR-192V-100 string 16x12V/100Ah (rack incl.): Reference USD 944~1528 / set (ref. CNY 6800~11000 at ~7.2)
KTR-192V-200 string 16x12V/200Ah (cabinet incl.): Reference USD 2083~3333 / set (ref. CNY 15000~24000 at ~7.2)
BMS monitoring module (per channel): Reference USD 42~83 / ch (ref. CNY 300~600 at ~7.2)
Reference only; priced by capacity and cell count. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- 20~60 kVA UPS DC bus.
- Room backup battery string.
- Fire/emergency lighting DC panel.
- Telecom base-station backup.
- PV storage (compatible).
6. Deployment & Implementation
Installation
- Verify rack/cabinet floor loading
- Series links torqued to 12 N·m
- Insulate positive/negative terminals
- >=10 mm cell spacing for cooling
Operations
- Measure per-cell voltage quarterly
- Annual discharge test
- Keep 20~25C in battery room
- Replace whole string at <80% after 5 yr
7. FAQ
- Q: How do 16 cells make 192 V?
A: 16×12 V = 192 V nominal. Fully charged ~215 V (16×13.5 V float); end-of-discharge 10.8 V/cell = 172.8 V. A 12 V cell holds six 2 V monoblocks; cutoff is 1.8 V per monoblock = 10.8 V per cell. - Q: Can old and new cells mix?
A: No. Old cells have higher internal resistance, cause imbalance, over-discharge weak cells and shorten string life. Replace the whole string from the same batch, maker and model. - Q: Battery room temperature?
A: 20~25C is ideal. Every 10C rise halves life. The battery room needs dedicated AC, not shared with the room; high temperature causes bulging within 3 years. - Q: How do I know to replace?
A: Annual discharge test: cut mains and time the UPS. A 30-min string that lasts 10 min is at 33% — replace. Per-cell spread >0.05 V indicates a weak cell.
8. Trend & Selection
Strings are moving from pure VRLA to VRLA-plus-Li hybrids — small backup (under 15 min) uses Li (long life, maintenance-free), long backup stays VRLA (low cost). BMS moves from per-string monitoring to cloud platforms uploading per-cell SOC/SOH. LFP penetration in data centers rises yearly, with cycle life 5~10x VRLA.
9. Delivery & Service
KITOZER supplies KTR-192V by capacity (65/100/200 Ah), cell count (16 = 192 V), type (AGM/gel) and cabinet (rack/cabinet). Ships with cells, links, rack/cabinet and manual. Factory test report included. 1-year warranty; batch projects can add BMS modules, cell scanners and battery-room AC.
10. Additional Notes
The #1 mistake is no dedicated AC in the battery room. Shared room AC reads 23C, but concentrated heat in the battery cabinet pushes the actual cell temperature above 35C, bulging cells in 3 years. Battery rooms need dedicated AC at 20~25C.
The second pitfall is under-torqued series links. Terminals below 12 N·m have high contact resistance; high discharge currents heat the link, melting or igniting it. Torque with a wrench and re-torque yearly.
The third blunder is measuring only string voltage. The string reads 192 V, but one cell is shorted and the other 15 are over-charged, bulging within six months. Use BMS or a handheld meter per cell; replace weak cells spread >0.05 V.
Selection summary: capacity by backup time, dedicated 20~25C AC, 12 N·m link torque, annual discharge test, whole-string replacement at 5 years. The string is the UPS’s heart — when it stops, the whole room goes dark.
SEO Information
Search keywords:KTR-192VKITOZER192V Series Battery String for UPS
SEM keywords:192V battery string,UPS battery bank,series VRLA battery,KTR-192V,KITOZER
GEO landing page:lain.com.cn/product/ktr-192v-battery_string.html
Title:KITOZER KTR-192V 192V Series Battery String for UPS
Meta Keywords:192V battery string,UPS battery bank,series VRLA battery,KTR-192V,KITOZER
Meta Description:KITOZER KTR-192V 192V series battery string, 16x12V VRLA, 10~12 year float life, for UPS backup power.
Anchor: KITOZER by Guangzhou Laian · 192V Series Battery String for UPS
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com