ToggleKITOZER 20ft Container Data Center KITOZER-CDC-20F: Outdoor Prefabricated Modular Server Room — Configuration & Price
1. Product Overview
The KITOZER-CDC-20F is a 20-foot ISO containerized prefabricated modular data center produced by Guangzhou Lain Intelligent System Development Co., Ltd. It is designed for outdoor ground installation. The enclosure structure, cooling, power distribution, UPS, fire suppression, environmental monitoring, access control and IT racks are fully pre-assembled and pre-tested at the factory. On site, the unit only needs lifting into position, mains power connection and fiber link before it can be put into operation.
The outer dimensions follow the standard ISO 20ft container (approximately 6058 × 2438 × 2591 mm), so it can be transported on a standard flatbed trailer without road modification. The enclosure carries an IP55 protection rating with a 25-year design life and operates reliably in ambient temperatures from -30 °C to +55 °C at 5%–95% relative humidity. Typical use cases include campus edge rooms, mining / oilfield remote sites, field pump stations, temporary command centers and disaster recovery nodes.

2. Enclosure & Structure
The enclosure is built on a weathering-steel welded frame; the exterior surface is sand-blasted, coated with zinc-rich primer and finished with outdoor-grade powder coating to resist salt spray and UV. The enclosure fire resistance rating is ≥120 min and the door rating is ≥90 min. Doors use double-layer fire-steel panels with ceramic-fiber insulation, three-point locking rods and watertight gaskets.
Internally, a 30 mm raised anti-static floor covers the room (system resistance 10⁶–10⁹ Ω), with the plenum underneath acting as the underfloor supply air chamber. Galvanized cable trays run on both sides, with strong-current and weak-current circuits routed in separate trays. Ceiling LED panels are dual-fed (normal + emergency). Equipotential grounding bars are installed at the four corners, with grounding resistance ≤1 Ω.
3. Cooling System
Five KITOZER-PAC-05K backpack precision air conditioners are installed inside the container in a 4+1 redundancy arrangement. Each unit provides ≥5 kW of cooling and uses top supply / bottom return airflow matched to the underfloor plenum to form a closed cold aisle. The AC units are mounted on the side wall as backpacks and do not consume internal IT space; on site only refrigerant piping and condensate lines (integrated lift pump, 900 mm max lift) need to be connected.
- Refrigerant: R410A, environmentally friendly
- Fans: EC direct-drive, speed modulated by load
- Operating ambient: -30 °C to +55 °C
- Redundancy logic: if any single unit fails, the remaining four share the load automatically; internal temperature rise is held within 3 °C

4. Power Distribution & UPS
Mains power enters through the KITOZER-PDC-100 main distribution cabinet, supplied as three-phase four-wire + PE, 380/400/415 VAC, 50 Hz. The cabinet includes the incoming breaker, class-C SPD (In 20 kA), branch metering meters and UPS input / output switches.
The IT load is backed by one KITOZER-UPS-10K online double-conversion UPS rated 10 kVA / 9 kW, output PF 0.9, efficiency ≥95% in the 50%–75% load band, with an SNMP card included for direct connection to the environmental monitoring platform. Two KITOZER-BAT-12100 VRLA strings (12 V / 100 Ah each) are housed in a dedicated battery cabinet with interconnect bars and a DC breaker; float design life is 5 years at 25 °C.
5. IT Rack Layout
Four KITOZER-NET-42U standard server racks are arranged in a row inside the container, each 600 × 1200 × 2000 mm with 42U of usable space. Every rack comes with dual PDU (A/B feeds), two fixed shelves, vertical cable managers, a top fan tray and a grounding bar. Racks are arranged face-to-face to form a cold aisle, with a hot aisle at the rear, matched to the backpack AC underfloor supply and top return.
Estimated at 4 kW per rack, the designed IT load of the unit is about 16 kW, leaving roughly 1.5× margin against the 5 × 5 kW redundant cooling capacity.

6. Fire Suppression
Fire protection uses the KITOZER-FIRE-012 Novec FK-5-1-12 clean-agent system — residue-free, non-conductive and non-corrosive to IT equipment. The system includes:
- Detection: heat + smoke dual detectors above each rack row, with cross-zone logic
- Suppression: cylinder group + piping + nozzles, designed discharge time ≤10 s
- Alarm: sounder / strobe, discharge indicator, manual abort / release buttons
- Linkage: integrates with environmental monitoring, access control and AC — before discharge, AC is shut down and door locks released
7. Environmental Monitoring & Access Control
The KITOZER-ENV-DH10 monitoring host is mounted inside the container door, with a 10-inch touchscreen for local visibility of UPS, AC, temperature/humidity, water leak, fire and access status. Outbound, it supports SNMP v3, Modbus TCP and dry-contact interfaces to the customer’s DCIM or third-party NMS, and also comes with a Guangzhou Lain cloud remote account for mobile-app alarm push.
Access control uses a KITOZER-ACS-02 IC-card solution with controller, reader, magnetic lock, exit button and emergency release button; door events are logged to the monitoring host. On fire linkage, locks release automatically to support fast evacuation along with emergency lighting and exit signs.

8. Optional Energy Storage
For sites without reliable mains power or requiring longer backup, one KITOZER-ESS-50K commercial & industrial ESS cabinet (outdoor IP55, about 50 kWh, with integrated AC, fire protection and remote monitoring) can be paralleled next to the main container, providing roughly 10 hours of backup at a 5 kW IT load. The ESS sits side-by-side with the main container and connects by cable tray on the ground. This ESS is an optional add-on, priced separately and not included in the main quotation below.
9. Key Technical Parameters
| Item | Parameter |
|---|---|
| Overall size (L×W×H) | Approx. 6058 × 2438 × 2591 mm (ISO 20ft) |
| Protection rating | IP55 |
| Design life | 25 years |
| Enclosure / door fire rating | ≥120 min / ≥90 min |
| Operating ambient | -30 °C to +55 °C |
| Relative humidity | 5%–95% (non-condensing) |
| Power supply | 3-phase 4-wire + PE, 380/400/415 VAC, 50 Hz |
| Designed IT load | Approx. 16 kW (4 racks × 4 kW) |
| Cooling | 5 × 5 kW backpack precision AC, 4+1 redundancy |
| UPS | 10 kVA / 9 kW online double-conversion |
| Batteries | 2 × 12 V / 100 Ah VRLA |
| IT racks | 4 × 42U, 600 × 1200 mm |
| Fire suppression | Novec FK-5-1-12 clean agent |
| Monitoring | 10″ touchscreen + SNMP/Modbus + cloud |
10. KITOZER Quotation (USD, Ex-Tax)
| No. | Model | Item | Spec summary | Qty | Unit | Unit Price (USD) | Amount (USD) |
|---|---|---|---|---|---|---|---|
| 1 | KITOZER-CDC-20F | 20ft Container Enclosure | IP55, fire ≥120 min, insulation/floor/tray/light/grounding | 1 | set | 77,083 | 77,083 |
| 2 | KITOZER-PAC-05K | Backpack Precision Air Conditioner | ≥5 kW/unit, 4+1 redundancy, -30 to +55 °C | 5 | unit | 7,708 | 38,540 |
| 3 | KITOZER-FIRE-012 | Clean-Gas Fire Suppression | Novec FK-5-1-12, dual detection + linkage | 1 | set | 28,333 | 28,333 |
| 4 | KITOZER-ENV-DH10 | Environmental Monitoring Host | 10″ touchscreen, SNMP/Modbus, cloud platform | 1 | set | 13,333 | 13,333 |
| 5 | KITOZER-ACS-02 | Card Access Control | IC card + magnetic lock + emergency release | 1 | set | 3,542 | 3,542 |
| 6 | KITOZER-PDC-100 | Main Distribution Cabinet & UPS Circuit | 3-phase 4-wire + PE, 380/400/415 VAC, SPD + metering | 1 | set | 17,500 | 17,500 |
| 7 | KITOZER-UPS-10K | Online Double-Conversion UPS | 10 kVA / 9 kW, 3-in 1-out, SNMP included | 1 | unit | 11,667 | 11,667 |
| 8 | KITOZER-BAT-12100 | VRLA Battery String | 12 V / 100 Ah, cabinet + interconnect bars | 2 | string | 5,000 | 10,000 |
| 9 | KITOZER-NET-42U | 42U IT Rack | 600 × 1200 mm, dual PDU/shelves/cable mgmt/fan | 4 | unit | 2,708 | 10,832 |
| — | — | KITOZER Quotation Total (ex-tax) | 9 standard line items | — | — | — | 210,830 |
Optional add-on (priced separately, not included in the main total):
| Model | Item | Spec | Qty | Unit | Unit Price (USD) | Amount (USD) |
|---|---|---|---|---|---|---|
| KITOZER-ESS-50K | C&I ESS Cabinet | Outdoor IP55, ~50 kWh, ~10 h backup at 5 kW | 1 | unit | 70,000 | 70,000 |
11. Quotation Notes
- Prices above are equipment-only, ex-tax, excluding freight and on-site installation; VAT special invoice at 13%, ordinary invoice at 6%.
- Installation is preliminarily estimated at around 15% of the ex-tax equipment value; complex lifts or remote sites are quoted separately. Freight depends on distance and shipping method.
- Lead time: 15–30 working days after full payment and technical confirmation.
- Warranty: enclosure & structure 5 years; cooling, fire, monitoring, power distribution, UPS and access control 2 years.
- Default payment is full payment in advance before production; other terms are negotiable.
- If the customer adjusts quantity, cooling capacity, rack count or site interface conditions, the quotation is revised accordingly; the configuration can be further optimized to control cost while meeting the main technical requirements.
KITOZER by Guangzhou Lain Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | Web: lain.com.cn, gdlain.com | Add: Zhongrun Industrial Park Chaotian Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China.