Table of Contents
ToggleProduct Overview
The KITOZER 2500kVA box type substation is a purpose built skid mounted unit for large scale solar photovoltaic and wind farm collector networks. It integrates a 35kV vacuum circuit breaker switchgear, a 2500kVA step up or step down transformer, and a 0.4kV LV distribution compartment in a weatherproof enclosure. KITOZER designs each unit to match the PV inverter output voltage and the 35kV collector grid, with protection relays metering and SCADA communication for remote farm management. The compact skid base allows rapid shipment and crane placement in remote sites.
Technical Specifications
Transformer 2500kVA, 0.4kV to 35kV (step up for PV) or 35kV to 0.4kV. Vector group Dyn11. Impedance 6.5 percent. Cooling ONAN with optional ONAF. HV switchgear: 35kV vacuum circuit breaker, 1250A bus, 25kA short time withstand, protection relay with overcurrent, earth fault, and trip output. LV: 3200A main breaker, inverter feeder breakers, surge protection, power quality meter. Enclosure IP54, cold rolled steel with outdoor powder coat, anti condensation heater. Weight approximately 16000kg, dimensions 5000mm by 2400mm by 2800mm. Standards IEC 62271, IEC 60076, IEEE C57, GB/T 17467, CE.
Application Scenarios
This substation is deployed in 10MW to 100MW utility scale solar farms, wind farm collector stations, and rural microgrid projects. It also serves as a mobile substation for temporary construction power and grid reinforcement. The 35kV class is typical for large PV plants where inverter clusters feed a common booster station.
Advantages and Features
Skid mounted design eliminates on site civil foundation work. Integrated protection relay and meter provide full visibility to the farm SCADA. IP54 enclosure tolerates dust, sand, and rain in remote desert or rural sites. KITOZER offers options including a 35kV SF6 RMU, an on load tap changer, reactive power compensation, and fiber optic communication. The unit is factory tested with full power frequency and impulse tests before shipment.
Installation and Maintenance
Place on a level compacted gravel or concrete pad with a ground rod system. Connect 35kV cable from the collector line and 0.4kV cables from inverter combiner boxes. Bond all compartments to the station ground grid. Annual maintenance includes HV breaker mechanical test, relay secondary injection test, transformer oil DGA, and enclosure gasket inspection. KITOZER recommends remote monitoring via SCADA to reduce site visits.
Price
From $58,800/pc. Contact +86 13922289957 for solar farm substation quote.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com