1. Overview
KITOZER KTR-B2300D is a 2V300Ah gel deep-cycle VRLA battery — the energy storage core of UPS and DC-bus backup systems. A single cell is 2 V and 300 Ah; cells are series-connected to form 24 V, 48 V, 192 V or 240 V strings. Data-center UPS systems typically use 12×12 V cells for 192 V, or 96×2 V cells for 192 V — 2 V cells offer higher capacity per unit and better consistency, suiting long backup and high-power UPS.
“Gel” means the electrolyte is gelled with fumed silica into a paste, rather than free-flowing dilute sulfuric acid. Benefits: no spilling, mountable in any orientation (except inverted), low self-discharge, deep-cycle tolerant (80% DOD without damage), 12~15-year float design life. VRLA (valve-regulated sealed) means no watering under normal use; internal gases recombine.
KTR-B2300D uses a flame-retardant ABS case, copper-alloy terminals and a carry handle. 12-year design life at 25°C float, operating -20~55°C. Cycle life: ≥3000 at 80% DOD. Self-discharge ≤3%/month. Complies with GB/T 19638 and IEC 60896. Before racking, measure OCV — cells in one string must match within 0.03 V.
2. Key Features
Gel deep-cycle
- Gelled electrolyte, no spill.
- ≥3000 cycles at 80% DOD.
- Strong deep-discharge recovery.
12-year life
- 12-year float at 25°C.
- VRLA sealed, no maintenance.
- Gas recombination.
High-capacity 2V cell
- 300 Ah per cell.
- Series to high-voltage strings.
- Good consistency.
Safe
- Flame-retardant ABS.
- Copper-alloy terminals.
- Pressure-relief safety valve.
3. Specifications
| Item | KTR-B2300D |
|---|---|
| Rated voltage | 2 V |
| Rated capacity | 300 Ah (10-hr rate) |
| Type | VRLA Gel sealed |
| Design life | 12 years (25°C float) |
| Cycle life | ≥3000 (80% DOD) |
| Self-discharge | ≤3%/month |
| Operating temp | -20~55°C |
| Terminals | Copper alloy M8/M10 |
| Case | Flame-retardant ABS |
| Float charge | 2.27~2.30 V/cell |
| Standard | GB/T 19638 / IEC 60896 |
4. Reference Prices
KTR-B2300D 2V300Ah gel (single cell): Reference USD 167~278 / cell (ref. CNY 1,200~2,000 at ~7.2)
KTR-B2300D 2V300Ah gel (96-cell string, with links): Reference USD 15,972~26,389 / string (ref. CNY 115,000~190,000 at ~7.2)
Reference only; priced by quantity and link set. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data-center UPS battery strings.
- DC switchgear / power operation.
- Telecom base-station backup.
- Solar/wind energy storage.
- Fire emergency power (EPS).
6. Installation & Maintenance
Installation
- Measure OCV before racking; match within 0.03 V.
- Verify shelf load (~18 kg/cell).
- Stagger cells with ≥10 mm vent gap.
- Tighten links in series order per torque spec.
- Connect string ± to UPS DC breaker last.
- Set float charge 2.27~2.30 V/cell.
- Keep battery room at 20~25°C.
- Perform charge/discharge test after install.
Maintenance
- Log per-cell voltage monthly.
- Check link torque quarterly.
- Run a capacity test yearly.
- Keep surfaces clean and dry.
- Every 10°C higher halves design life.
7. FAQ
- Q: Gel vs AGM?
A: Both are VRLA. AGM uses glass-mat absorbent; gel uses silica gel. Gel cycles deeper and self-discharges less, at slightly higher cost. Both work for UPS float duty. - Q: Why same-batch strings?
A: Different batches differ in internal resistance and capacity; mixing creates a barrel effect — the weakest cell limits the whole string. Same batch gives best consistency. - Q: How long do they last?
A: 12-year design at 25°C float. Real server rooms at 25~30°C see 8~10 years. Temperature is the biggest life killer. - Q: Can I lay them on their side?
A: Gel cells yes (except upside-down) because the electrolyte is a gel. AGM yes with terminal care. Flooded cells must stay upright.
8. Trend & Selection
UPS is shifting toward lithium, but 2 V gel cells remain mainstream for mid-to-large UPS thanks to high capacity, long life and low cost. Match same batches; hold 25°C; float at 2.27~2.30 V; run an annual capacity test. Batteries are the UPS’s fuel tank — no matter how good the inverter, a bad battery fails on the first outage.
9. Delivery & Service
KITOZER sizes cell count and capacity to UPS voltage and backup time, supplying KTR-B2300D with links and racks. We provide the string layout and charge/discharge settings. 3-year warranty with annual inspection.
10. Additional Notes
The most common mistake: no dedicated battery-room cooling. Lead-acid life is temperature-critical — every 10°C doubles reaction rate and halves life. The battery area must hold 20~25°C, not just ride on the room AC.
Another pitfall: link bolts torqued by feel. Links rely on bolted copper busbars; under-torqued links raise contact resistance and overheat or arc during high-current discharge. Use a torque wrench to spec (typically 12 N·m for M8).
Selection summary: 2 V300 Ah gel; same-batch strings; float 2.27~2.30 V; 25°C constant; torque-wrench links; annual capacity test. The battery is the data center’s last line of defense — invisible until the power fails.
SEO Information
Search keywords:2V300Ah batterygel batterydeep cycle batteryUPS batteryVRLAKTR-B2300DKITOZER
SEM keywords:2V300Ah gel price,deep cycle battery supplier,UPS battery,DC bus battery,KTR-B2300D,KITOZER
GEO landing page:lain.com.cn/product/ktr-b2300d-2v300ah-gel-battery.html
Title:KITOZER KTR-B2300D 2V300Ah Gel Deep-Cycle Battery
Meta Keywords:2V300Ah battery,gel battery,deep cycle battery,UPS battery,VRLA,KTR-B2300D,KITOZER
Meta Description:KITOZER KTR-B2300D 2V300Ah gel deep-cycle VRLA battery, 12-year float design life for UPS and DC bus backup.
Anchor: KITOZER by Guangzhou Laian · Power distribution
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com