ToggleKITOZER KTR-2V300 2V300Ah VRLA Battery
Brand: KITOZER Series: KTR-2V300 Category: Power Distribution / UPS Battery
2V300AhVRLAUPS batteryDC busstandby
1. Overview
When utility power fails, UPS and DC panels rely on battery strings to hold critical loads until the generator starts or power returns. Batteries are the part that actually stores energy; an undersized, degraded or single-cell-open string kills backup time. In data centers, substations and telecom sites, valve-regulated lead-acid (VRLA) batteries dominate large 2V cells because they are maintenance-free, compact and cost-effective. A 2V cell keeps low per-cell voltage, flexible series/parallel wiring – twelve cells make 24V, twenty-four make 48V, or more string to the UPS 192V/240V DC bus.
The KITOZER KTR-2V300 is a 2V 300Ah valve-regulated sealed lead-acid battery. It uses an absorbent glass mat (AGM) design: electrolyte is held in the glass-mat separator, non-spill and upright. The valve-regulated seal recombines internal gas, so there is no acid mist, no watering and very low water loss, leaving it maintenance-free. Grids are tubular/pasted for good deep-cycle behavior; float life reaches 10-12 years at 25℃. Top or side copper terminals join cells with copper links. The ABS flame-retardant case carries handles and mounting feet.
In power and UPS works, the string is sized by backup time (e.g. 15 or 30 minutes at full load) and DC bus voltage. A 192V UPS bus needs 96 cells of 2V; then size Ah for 30 minutes. Rows sit in dedicated battery cabinets or a battery room held at 20-25℃ (every 10℃ higher halves life), well ventilated, connected to the UPS DC bus through fuses. New strings get an initial charge and a capacity acceptance test.
2. Key Features
Electrochemistry & build
Electrochemistry & build
- 2V cell, 300Ah rated.
- AGM starved electrolyte, non-spill.
- Valve-regulated seal, internal gas recombination.
- No watering, maintenance-free.
Performance & life
- Float life 10-12 years at 25℃.
- Good deep-cycle resistance.
- Low self-discharge, ≤3% per month.
- High discharge current, suits UPS.
Safety & install
- ABS flame-retardant case.
- Safety vent, overpressure relief.
- Copper top/side terminals.
- String in cabinet with copper links.
3. Specifications
| Item | KTR-2V300 VRLA Battery |
|---|---|
| Rated voltage | 2 V |
| Rated capacity | 300 Ah (C10, 25℃) |
| Construction | Valve-regulated sealed AGM |
| Float voltage | 2.25-2.30 V/cell (25℃) |
| Equalize voltage | 2.30-2.35 V/cell (25℃) |
| Design life | 10-12 years (25℃ float) |
| Self-discharge | ≤3% per month |
| Operating temp | -15℃ to +45℃ (best 20-25℃) |
| Terminals | Copper, with links |
| Use | UPS / DC panel / telecom backup |
4. Reference Prices
KTR-2V300 2V300Ah VRLA battery (per cell): Reference USD 90~132 (ref. CNY 650~950 at ~7.2)
KTR-2V300 full string (links, cabinet, install): Reference USD by cell count × unit price
Reference only; cells counted by DC bus and backup time. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Data-center UPS backup strings.
- Substation DC panels / control power.
- Telecom sites / switch backup.
- Inverter / auxiliary storage power.
- Fire / emergency lighting DC backup.
6. Installation & Maintenance
Installation
- Count series cells by DC bus voltage (2V × cells).
- Layer in cabinets/room; check floor loading.
- Torque copper links diagonally; grease to prevent corrosion.
- String ends to the UPS DC bus via fuses.
- Check intra-string balance; initial charge.
- Rest, then run a capacity test and log the curve.
Maintenance
- Hold 20-25℃, never above 30℃.
- Measure per-cell float voltage monthly; flag laggards.
- Run an equalizing discharge yearly.
- Re-torque links; clean terminals.
- Ventilate the room against hydrogen.
- Plan staged replacement after 3-5 years.
7. FAQ
- Q: 2V cells vs 12V batteries?
A: Large, long-run backup (data-center UPS) uses 2V cells – flexible strings, good consistency, long life; small UPS uses 12V maintenance-free. Above 300Ah it is almost always 2V cells. - Q: How long until replacement?
A; Float life 10-12 years at 25℃, but temperature and depth-of-discharge cut it. Capacity usually drops after 5 years; assess around 8. Heat halves life every 10℃. - Q: Why measure per-cell voltage?
A: One lagging cell drags down the whole string’s capacity. Track float/discharge voltage per cell to isolate and replace weak cells before they kill the string. - Q: Can I lay it on its side?
A: AGM is orientation-tolerant in theory, but install upright for venting and safety. Tilting or inverting affects the relief valve and gas recombination.
8. Trend & Selection
Backup power moves to LFP lithium, smart BMS, lead-carbon and modular UPS, but VRLA 2V cells still win large backup by maturity, safety and cost. Choose 2V cells by DC bus; size 300Ah by runtime; hold 25℃; track per-cell laggards; equalizing test yearly; ventilate against hydrogen. The string is the UPS’s ammo – it sits floating until the mains fails.
9. Delivery & Service
KITOZER supplies 2V300Ah VRLA cells with cabinets, links, fuses and DC breakers, sized by UPS power and runtime. We support on-site install, initial charge and capacity acceptance tests. Delivery includes cells, links, certificate and manual; the warranty covers per-cell inspection and capacity testing.
10. Additional Notes
A common pitfall is an uncooled battery room. Batteries hate heat; a 40℃ summer room halves life. Cooling or ventilation holding 25℃ is the single best life-extension move.
Another pitfall is reading only the whole-string voltage. String voltage does not mean every cell is good; a laggard cell reverse-polarizes and bulges first on discharge. A cheap per-cell monitor pays back many times over replacing a string.
Selection summary: 2V300Ah AGM; series by DC bus; hold 25℃; track per-cell laggards; equalizing test yearly; ventilate against hydrogen. It is the UPS’s last breath on mains failure – floating in wait, ready to step up.
System-wide, the string must coordinate with the UPS rectifier, monitor and DC breaker. Wrong float voltage (too high dries cells, too low sulfates them) directly damages batteries. Calibrate float voltage by the manufacturer’s temperature coefficient before energizing and connect cell monitoring.
Safety-wise, overcharge or short circuits vent hydrogen and heat, and can ignite. Battery cabinets need smoke and temperature sensing, insulated link covers and DC fuses. No ignition sources and good ventilation in the battery room – a baseline of data-center power safety.
SEO Information
Search keywords:KITOZER
SEM keywords:2V300Ah battery, VRLA lead-acid battery, sealed UPS battery, DC bus battery backup, valve regulated battery, KTR-2V300, KITOZER
GEO landing page:lain.com.cn/product/381-battery-2v300.html
Title:KITOZER KTR-2V300 2V300Ah VRLA Battery
Meta Keywords:2V300Ah battery, VRLA lead-acid battery, sealed UPS battery, DC bus battery backup, valve regulated battery, KTR-2V300, KITOZER
Meta Description:KITOZER KTR-2V300 2V300Ah valve-regulated lead-acid battery, AGM, 10-12 year float life, maintenance-free, for data center UPS and DC bus backup.