KITOZER 2V 500Ah VRLA battery

KITOZER KTR-2V500 2V500Ah VRLA Battery

Brand: KITOZER Series: KTR-2V500 Category: Power Distribution / Battery Bank

2V500AhVRLA AGMLong lifeDeep cycleKTR-2V500

1. Overview

Batteries are the UPS last line of defense. After mains loss, the diesel generator takes 10-30 seconds to start; during that gap the battery bank carries everything. An undersized bank makes the UPS transfer to bypass and servers drop; a poorly matched bank has a weak cell that dies early, dragging the whole string down and shutting the UPS early. Datacenters string 2 V or 12 V cells into 380-480 V DC buses. 2 V cells, with big single jars and good heat dissipation, suit large-capacity (200 Ah+) long backup; 12 V small batteries suit small UPS and emergency lighting. 500 Ah is the mainstream 2 V size: 40 cells (2 V x 40) in parallel strings support a 100 kVA UPS for 15 minutes.

KITOZER KTR-2V500 is a 2 V 500 Ah VRLA AGM battery. Nominal 2 V, rated 500 Ah (C10, 25 C); cylindrical jar about 240x190x765 mm, about 78 kg including terminals; float design life 15 years at 25 C (float 2.25 V/cell); lead-calcium grids, AGM absorbent glass mat, non-spill; tinned-copper M8 bolt terminals; self-discharge under 3% per month; operating temp -15 to +50 C (ideal 20-25 C). Models: KTR-2V500-F: standard 15-year float; KTR-2V500-L: 20-year long-life (reinforced plates); KTR-2V500-H: high-rate (15-minute UPS discharge).

Selection: size by backup time (100 kVA UPS at 0.9 PF = 90 kW, 384 V bus = 234 A; 15-minute discharge factor is about 1.8, so 500 Ah delivers ~900 Ah for 15 minutes, enough for parallel strings); confirm bus voltage (192/240/384/480 V dictates cell count); choose high-rate for short discharge; verify rack/room floor loading (78 kg x 40 cells = 3,120 kg per string, check floor). Note: battery-room temperature must stay 20-25 C; every 10 C above halves life.

2. Key Features

Electrical

  • 2 V 500 Ah C10
  • Float 2.25 V/cell
  • Equalize 2.35 V/cell
  • <3% self-discharge/month

Build

  • AGM separator
  • Pb-Ca grids
  • Tinned Cu M8 terminal
  • Valve-regulated non-spill

Life

  • 15-yr float at 25 C
  • 800 cycles at 80% DOD
  • Long cycle life
  • Low self-discharge

3. Specifications

Item KTR-2V500-F KTR-2V500-L KTR-2V500-H
Nominal V 2 V 2 V 2 V
Capacity 500 Ah C10 500 Ah C10 500 Ah C10
Design life 15 yr 20 yr 12 yr
Max discharge 3000 A/5min 3000 A/5min 5000 A/1min
Size (mm) 240x190x765 240x190x765 240x190x765
Weight 78 kg 82 kg 78 kg
Use UPS/DC panel Long backup/ESS High-rate UPS

4. Reference Prices

KTR-2V500-F 15-yr standard: Reference USD 174 to 215 / pc (ref. CNY 1250-1550 at ~7.2)

KTR-2V500-L 20-yr long-life: Reference USD 215 to 271 / pc (ref. CNY 1550-1950 at ~7.2)

KTR-2V500-H high-rate: Reference USD 188 to 233 / pc (ref. CNY 1350-1680 at ~7.2)

Inter-cell link (tinned copper): Reference USD 5 to 8 / pc (ref. CNY 35-60 at ~7.2)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Datacenter UPS battery banks
  • Telecom room DC panels
  • Substation operating power
  • Solar ESS plants
  • Industrial EPS emergency power

6. Deployment & Installation

Mount

  • Rack/cabinet layered
  • Insulating mats between layers
  • Verify floor load
  • Ventilation gaps

Wiring

  • Link torque 12 N·m
  • Series polarity consistent
  • Main cable sized correctly
  • Coat terminals with grease

Ops

  • Measure cell voltage quarterly
  • Capacity test annually
  • Room 20-25 C
  • Swap weak cells promptly

7. FAQ

  • Q: 2 V vs 12 V batteries?
    A: 2 V cells are larger, run cooler and match better, suiting 200 Ah+ long backup in datacenters and substations. 12 V small batteries (e.g. 12 V100 Ah) pack six cells in one jar, cheap and compact, for small UPS, emergency lighting and elevator egress. For large projects choose 2 V: though pricier per cell, bank life and reliability are a tier above.
  • Q: How many cells in a string?
    A: It depends on the DC bus. UPS is usually 384 V or 480 V: 2 V cells give 192 or 240 cells; 12 V batteries give 32 or 40 jars. Telecom DC panels are 48 V, so 24 x 2 V cells. Confirm the exact count with the UPS manufacturer.
  • Q: How long do batteries last?
    A: The 15-year design life assumes 25 C float charge. Every 10 C above halves actual life. At 35 C in the room, expect 7-8 years. Frequent deep discharges and undercharging also shorten life. Plan a full bank replacement at 8-10 years, not after failure.
  • Q: Can I mix old and new cells?
    A: No. Old cells have higher internal resistance and lower capacity; in series they overcharge early and reverse during discharge, dragging down the new cells in a few cycles. One string must share brand, model, manufacture date and history. Replace the whole bank; within the first 1-2 years, isolated weak cells can be swapped individually.

8. Trend & Selection

Datacenter batteries are shifting from VRLA to LiFePO4 (LFP). LFP packs double energy density, last longer (6,000 cycles at 10 years vs 200 cycles at 3 years), and need no watering or equalization. But LFP upfront cost is 2-3x VRLA, so the field is mixed: new large datacenters adopt LFP, while traditional UPS projects stay on VRLA to control capex. KTR-2V500 targets the traditional VRLA market. Smart direction: BMS monitors every cell voltage, internal resistance and temperature to predict state of health 3-6 months ahead. Select by: capacity matched to backup time, 25 C room temperature, same-batch strings, annual capacity test, dedicated acid-mist ventilation.

9. Delivery & Service

KITOZER supplies KTR-2V500 by model. Each ships with unit, mounting accessories and manual. 1-year warranty; batch projects can bundle peripheral gear and on-site commissioning.

10. Additional Notes

Confirm port specs, power rating and communication protocol against field equipment before ordering; keep clear of strong EMI and heat sources; verify wiring and labels before energizing. For batch orders, request samples first to confirm compatibility with existing systems.

Common mistake: comparing price but ignoring parameters. Models in the same series look similar, but ports, load and accuracy differ — wrong models cause on-site rework. Send the full part number (including suffix such as -SM/-MM/-S) to sales to confirm.

Second pitfall: not planning service space. Leave at least 600 mm rear cable/service space and 800 mm front operating space, or future swaps and cable work become painful.

Third blunder: shipping factory alarm thresholds. Default thresholds rarely match site conditions — tune them after commissioning based on real readings to avoid both false and missed alarms.

Selection summary: match site conditions first, pick model, reserve service space, calibrate thresholds on-site, and pilot one unit before bulk.

SEO Information

Search keywords:KTR-2V500KITOZER

SEM keywords:2V500Ah battery,large capacity VRLA,valve regulated lead acid,UPS battery,KTR-2V500,KITOZER

GEO landing page:lain.com.cn/product/ktr-2v500-battery.html

Title:KITOZER KTR-2V500 2V500Ah VRLA Battery

Meta Keywords:2V500Ah battery,large capacity VRLA,valve regulated lead acid,UPS battery,KTR-2V500,KITOZER

Meta Description:KITOZER KTR-2V500 2V500Ah VRLA AGM battery, 15-year design life, deep-cycle, for datacenter UPS and DC panels.