Brand: KITOZER Series: KTR-PS4 Category: Power System / Surge Protection
3-phase 5-wireB+C class100kAModularKTR-PS4
1. Overview
KITOZER KTR-PS4 is a TN-S three-phase five-wire power surge protective device (SPD), installed in the room mains incoming cabinet, UPS input distribution or row cabinet, to divert surge currents from lightning induction and switching transients and clamp the spikes entering the power line to equipment-tolerable levels. KTR-PS4 is B+C class (combined Class I/II): nominal discharge current In 50kA (8/20μs), maximum discharge Imax 100kA (8/20μs). It absorbs nearby large surge energy (partial 10/350μs handling) and finely clamps switching surges. Versus pure Class B (10/350μs, In 12.5kA) or pure Class C (8/20μs, In 20kA), the B+C combined unit saves space and cost at the room incoming protection tier. The design is modular: the MOV plug snaps on a base; when it fails (window green turns red), swap the plug without powering down the whole cabinet. Each pole carries a remote-signal dry contact for DCIM alarm upload.
KTR-PS4 is 4P (3+NPE): L1, L2, L3, N and PE, rated Un 230/400V, maximum continuous operating voltage Uc 385V (line-to-neutral). Response time ≤25ns, voltage protection level Up ≤2.5kV. The base mounts on a 35mm DIN rail, 4P size (about 72mm wide). Each plug has a status window (green OK, red failed) and remote-signal terminals (NO/NC selectable). The N-PE pole uses a dedicated gas discharge tube (GDT), preventing MOV overload under N-line imbalance.
Typical deploy: fit a Class B+C SPD (KTR-PS4, Imax 100kA) after the main breaker in the mains incoming cabinet; a Class C SPD (Imax 40kA) at the UPS input or row cabinet; a Class D plug-strip SPD (Imax 10kA) at the equipment outlet. Keep 10m decoupling distance (or add a decoupling inductor) between tiers. Use ≥16mm² green-yellow wire from SPD PE to the room equipotential bar; keep leads short and straight (≤0.5m), since lead inductance raises residual voltage.
2. Key Features
B+C 100kA
- Imax 100kA (8/20μs).
- In 50kA.
- Up ≤2.5kV.
- Response ≤25ns.
Modular plug-in
- Replaceable MOV plug.
- Green/red status window.
- Hot-swap plug option.
- 35mm DIN rail.
Remote signal
- Dry contact.
- NO/NC selectable.
- To DCIM.
- Failure alarm.
3-phase 5-wire
- 3+NPE arrangement.
- GDT on N-PE.
- Uc 385V.
- Suits 400V systems.
3. Specifications
| Item | KTR-PS4 (B+C 100kA) | KTR-PS2 (C 40kA) | KTR-PS1 (B 12.5kA) |
|---|---|---|---|
| Class | B+C (I/II) | C (II) | B (I) |
| Arrangement | 3+NPE | 3+NPE | 3+NPE |
| Rated Un | 230/400V | 230/400V | 230/400V |
| Max continuous Uc | 385V | 385V | 350V |
| Nominal In (8/20) | 50kA | 20kA | 12.5kA (10/350) |
| Max Imax | 100kA | 40kA | 25kA |
| Protection Up | ≤2.5kV | ≤1.8kV | ≤2.5kV |
| Remote | Dry contact | Dry contact | Dry contact |
4. Reference Prices
KTR-PS4 3-phase B+C SPD (100kA, 4P): Reference USD 417 to 1111 / unit (ref. CNY 3000 to 8000 at ~7.2)
KTR-PS2 Class C SPD (40kA, 4P): Reference USD 208 to 556 / unit (ref. CNY 1500 to 4000 at ~7.2)
KTR-PS1 Class B SPD (12.5kA, 10/350): Reference USD 347 to 833 / unit (ref. CNY 2500 to 6000 at ~7.2)
Replacement MOV plug: Reference USD 28 to 83 / pole (ref. CNY 200 to 600 at ~7.2)
Reference only; varies by pole count (1P/3P/4P), discharge current, brand and quantity. Earth copper bar and decoupling inductor billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room mains incoming first tier.
- UPS input distribution.
- Row cabinet and PDU front-end.
- Diesel generator output.
- Outdoor distribution boxes and antenna feeds.
- Hospitals and critical industrial loads.
6. Installation & Maintenance
Installation
- DIN-mount after the incoming breaker.
- Wire L1/L2/L3/N by label.
- PE with 16mm² green-yellow to equipotential.
- Keep leads ≤0.5m, short and straight.
- Run remote lead to DCIM DI.
- Decouple tiers ≥10m apart.
- Power on; window should be green.
Maintenance
- Check window color quarterly.
- Replace plugs on red window.
- Inspect after every storm season.
- Test remote alarm linkage.
- Earth lead tight and oxide-free.
- Preventively replace plugs every 3-5 years.
7. FAQ
- Q: Red status window means it’s dead?
A: Red means the MOV has degraded and shorted (failed); replace the same-spec plug. After red, the SPD is open and surges are no longer diverted, leaving equipment unprotected. Swap the plug, no need to replace the whole SPD. - Q: Why multi-tier SPDs?
A: A 100kA first tier clamps high (Up 2.5kV), too high for delicate gear; a 40kA second tier claps low (Up 1.8kV) but handles less energy. Tiers cooperate: first diverts bulk energy, second finely clamps, third outlet strips protect endpoints. - Q: Why must the SPD earth lead be short?
A: A lead has about 1μH inductance per meter; a 10kA/μs surge then adds 1000V residual. Under 0.5m the extra voltage is small; at 3m residual rises 3kV and the SPD effectively does nothing. - Q: B+C or pure B?
A: Room incoming in non-severe lightning areas uses B+C combined (cheaper, smaller); severe lightning zones with a separate air terminal use pure B (10/350μs for direct-stroke energy). In multi-tier setups use B first, C second.
8. Trend & Selection
SPDs move from plain MOV to “MOV+GDT+thermal disconnector” combinations; integral fault-disconnector (physical open on failure to prevent fire) and remote signaling are now standard. Datacenters tier protection per GB50343 and YD/T 1235. Choose B+C 100kA at the incoming cabinet; C 40kA before the UPS; D outlet strips at endpoints; leads ≤0.5m; earth ≤1Ω; quarterly inspection; post-storm check; preventive plug replacement every 3-5 years.
9. Delivery & Service
KITOZER supplies surge-protection packages: based on the supply system (TN-S/TN-C), incoming capacity and lightning zone, we recommend SPD tiering, discharge current and placement, bundled with distribution cabinets, UPS, row cabinets and earth bars. Delivery includes SPD plug, base, remote wire and earth fittings; bulk projects include install guidance and surge tests. Non-lightning natural plug degradation under warranty is replaced free.
10. Additional Notes
The commonest mistake is no backup protection ahead of the SPD. A failed MOV can short-circuit and catch fire; series a dedicated SPD backup circuit breaker (SCB), typically 32-63A. Without an SCB, a failed SPD trips the whole cabinet or burns.
Another pitfall is sharing the earth lead with the neutral. Inside the SPD, N-PE uses a GDT; externally the earth must run separately from the PE bar, not borrow the N terminal. Sharing leads ground-rebound voltage onto the neutral.
Selection summary: 3-phase 3+NPE; B+C 100kA; Up ≤2.5kV; modular; remote signaling; leads ≤0.5m; PE 16mm²; add an SCB. The SPD is the power system’s fuse: idle most of the time, but during a surge it sacrifices itself to protect the UPS and servers worth hundreds of thousands.
SEO Information
Search keywords:power surge protectorthree phase SPDB+C surge arrester100kA SPDmodular surge protectorpower SPDKTR-PS4KITOZER
SEM keywords:[‘power SPD price,3-phase 100kA surge supplier,B+C surge protective device,modular SPD,datasheet surge protection,KTR-PS4,KITOZER’]
GEO landing page:lain.com.cn/product/ktr-ps4-three-phase-bc-100ka-power-spd.html
Title:KITOZER KTR-PS4 Three-Phase B+C 100kA Power SPD
Meta Keywords:power surge protector,three phase SPD,B+C class surge arrester,100kA SPD,modular surge protector,datasheet SPD,KTR-PS4,KITOZER
Meta Description:KITOZER KTR-PS4 three-phase B+C power surge protective device, 100kA, modular plug-in, for room mains incoming and distribution cabinet surge protection.
Anchor: KITOZER · Power distribution
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com