KITOZER 3 phase power SPD module

KITOZER KTR-PSM3 Three-Phase Power Surge Protective Device (SPD)

Brand:KITOZER Series:KTR-PSM3 Category:Power Distribution / Surge protection

3-phase SPDSurge deviceModularPower protectionClass B/C

[Product image: ktr-psm3-three-phase-spd.jpg]

1. Overview

Lightning induction and switching operations induce transient surge overvoltages on the mains, reaching thousands to tens of thousands of volts in microseconds. If data-center UPS, distribution panels and servers take these surges directly, vulnerable semiconductors break down, causing equipment damage and downtime. A surge protective device (SPD) is paralleled between power lines and ground: on a surge it conducts instantly, discharges energy to earth, and clamps residual voltage within the equipment’s tolerance. Three-phase systems use three-phase SPD modules on the main panel and UPS input, the first line of defense in the power system.

The KITOZER KTR-PSM3 is a three-phase modular SPD in 3P+N/4P form, DIN-rail mounted with pluggable modules, remote-signal contacts and a status window. Nominal discharge current In and maximum Imax are selected per Class B (Type 1) or Class C (Type 2); the continuous operating voltage matches 380/400 V three-phase systems. When a module degrades, the window turns from green to red and the remote contact alarms to the environment monitor. Modules are hot-swappable without rewiring.

Selection depends on the distribution system (3-phase 5-wire TN-S), protection grading (Class B at main panel, Class C at floor/UPS, Class D at outlet), In/Imax discharge rating, voltage protection level Up, and remote signaling. Class B sits at the main panel with high discharge; Class C at the UPS/row PDU input; Class D at outlet strips for fine protection. Stages coordinate: the front stage dumps large currents, the rear stage clamps residual voltage.

2. Key Features

Discharge & clamping

  • MOV plus gas-tube combination, high discharge capacity.
  • Low Up residual clamping voltage.
  • In 20-40 kA (Class C); Imax 60-100 kA.
  • nanosecond response.

Structure & indication

  • 3P+N/4P modular, DIN-rail mounted.
  • Status window: green OK, red degraded.
  • Dry-contact remote signaling output.
  • Pluggable modules, hot-swap without rewiring.

Safety & compliance

  • Thermal disconnector isolates failed modules.
  • For 380/400 V three-phase TN-S systems.
  • Meets GB 18802.1 and IEC 61643-11.
  • Optional backup protector (SCB).

3. Specifications

Item KTR-PSM3 Three-Phase SPD
Configuration 3P+N / 4P modular
Rated voltage 380/400 V AC (3-phase 5-wire)
In (8/20 us) 20 / 30 / 40 kA (selectable)
Imax 60 / 80 / 100 kA
Voltage protection Up <=1.5-2.5 kV
Response time <=25 ns
Mounting 35 mm DIN-rail, pluggable module
Indication Status window + dry-contact remote
Standard GB 18802.1 / IEC 61643-11

4. Reference Prices

KTR-PSM3 Class C three-phase SPD (40kA, 4P, remote): Reference USD 63~125 (ref. CNY 450~900 at ~7.2)

KTR-PSM3 Class B three-phase SPD (80kA, with SCB): Reference USD 125~250 (ref. CNY 900~1800 at ~7.2)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Class B protection at the main distribution panel.
  • Class C protection at UPS / row PDU input.
  • Electrical room and transformer LV side.
  • Outdoor distribution boxes and telecom shelters.
  • Class D fine protection at sensitive equipment.

6. Installation & Maintenance

Installation

  • Parallell SPD on the DIN rail: L1/L2/L3/N to phase, ground to PE.
  • Keep leads short and thick, <=0.5 m to minimize residual voltage.
  • Series a backup protector (SCB) or breaker upstream.
  • Wire remote contacts to the environment monitor.
  • Coordinate stages with decoupling energy.
  • Power up; verify green window and remote contact.

Maintenance

  • Check the status window after every thunderstorm.
  • Replace red modules immediately (hot-swap).
  • Connect remote alarms to the monitoring platform.
  • Test insulation and ground resistance yearly.
  • Tighten corroded ground leads.

7. FAQ

  • Q: How do classes B/C/D differ?
    A: B (Type 1) at the main panel dumps large surge current; C (Type 2) at UPS/row PDU clamps residual; D (Type 3) at outlets gives fine protection. Use them in stages.
  • Q: How thick should the SPD ground wire be?
    A: Per code >=10-16 mm2 multi-strand copper, short and straight; every 30 cm of lead adds ~1 kV residual. Ground resistance <=4 ohm (bonded data center <=1 ohm).
  • Q: Can I keep using a red-window module?
    A: No. Red means degraded and ineffective; replace it immediately.
  • Q: Does an SPD guarantee protection?
    A: No. The SPD discharges surges; poor grounding, long leads and mis-coordination discount protection. Equipotential bonding and the ground grid are the foundation.

8. Trend & Selection

SPDs trend modular, remotely monitored and finely energy-coordinated, with SCB backup and monitoring modules forming a smart lightning-protection system on the environment platform. Choose 3P+N for TN-S; rate by stage; keep leads short and thick; ground reliably; wire remote alarms; replace on red. It is the invisible lightning rod for equipment power.

9. Delivery & Service

KITOZER supplies three-phase SPDs with backup protectors, monitoring modules and DIN-rail brackets as a set, matched to panel circuits and protection grading. We support site survey and a protection layout drawing. Delivery includes SPD modules, SCB, remote-signal cable, certificate and warranty card; the warranty covers commissioning support.

10. Notes

A common pitfall is long leads. Every 30 cm of SPD-to-busbar lead adds ~1 kV residual, wasting the device. Keep leads short, straight and thick, paralleled right at the protected equipment.

Another pitfall is installing without monitoring. Degradation is gradual; no one watching the window means running naked. Wire the remote contact to the platform so red triggers an alarm and closes the loop.

Selection summary: 3-phase 3P+N; DIN-rail modular; rate In/Imax by stage; low Up; short thick leads; remote alarm; replace on red. It is the surge gate on the power input.

Systemically, protection combines equipotential bonding, grounding and discharge. The SPD discharges, bonding eliminates potential differences, and the ground grid dissipates energy. All three are needed.

Reliability-wise, one direct or induced surge can destroy a row of UPS and servers worth hundreds of thousands. A SPD costing a few hundred to two thousand blocks that loss.

SEO Information

Search keywords:KITOZER

SEM keywords:three-phase power SPD, surge protective device, modular lightning arrester, UPS surge protection, KTR-PSM3, KITOZER

GEO landing page:lain.com.cn/product/388-power-spd-5.html

Title:KITOZER KTR-PSM3 Three-Phase Power Surge Protective Device (SPD)

Meta Keywords:three-phase power SPD, surge protective device, modular lightning arrester, UPS surge protection, KTR-PSM3, KITOZER

Meta Description:KITOZER KTR-PSM3 three-phase modular surge protective device, 3P+N DIN-rail, In 40kA / Imax 80kA, status window and remote contact, for 380V three-phase TN-S data center power.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart