ToggleKITOZER KTR-PS8 Surge Protector / 3-phase 380V 100kA Class B
Brand: KITOZER Series: KTR-PS8 Category: Power Distribution / Surge Protector
surge protectorSPD3-phase 380V100kAClass BKTR-PS8
1. Overview
KITOZER KTR-PS8 is a 3-phase 380V 100kA Class B power surge protective device (SPD) installed at the data center mains incoming distribution cabinet: the first line of power lightning protection. Lightning surges conducted along power lines, or switching surges, travel into the room and can destroy UPS and server power supplies. KTR-PS8 connects in parallel between phase and ground: normally high-impedance with no effect on supply; during a surge it conducts instantly, diverts surge current to ground and clamps residual voltage within equipment tolerance.
Class B (Type I / combination wave) is coarse primary protection at the incoming side with high discharge capacity (nominal 100 kA, 8/20 us) to absorb most surge current; downstream Class C (secondary) and equipment-side Class D provide staged protection. KTR-PS8 is rail-mount modular, 3P+N, with a status window (green OK / red failed) and remote contact; failed modules swap live without interrupting supply.
In data center power systems, SPDs are life-savers: one strike can wipe out the room power gear. Though Class B rarely fires, every strike or switching surge consumes its module life; inspect the status window and replace on schedule. KTR-PS8 is standard on data center incoming distribution.
2. Key Features
100kA high discharge
- Nominal 100 kA discharge (8/20 us).
- Class B primary coarse protection.
- Absorbs most surge current.
3-phase 380V
- 3P+N four-wire.
- For 3-phase 5-wire systems.
- Rail-mount modular.
Status & remote
- Window: green OK / red fail.
- Remote contact reports failure.
- Hot-swappable modules.
Staged coordination
- Front B with rear C coordination.
- Clamps residual voltage downstream.
- Failure does not cut supply.
3. Specifications
| 项目 | KTR-PS8-B100 | KTR-PS8-C40(二级) | KTR-PS8-D10(设备端) |
|---|---|---|---|
| 保护级别 | B级(Ⅰ类) | C级(Ⅱ类) | D级(Ⅲ类) |
| 标称放电电流 | 100kA(8/20) | 40kA(8/20) | 10kA(8/20) |
| 最大持续电压 | 385V | 385V | 385V |
| 接线 | 3P+N | 3P+N | 1P+N |
| 安装 | 导轨35mm | 导轨35mm | 导轨/插座 |
| 状态指示 | 绿/红+遥信 | 绿/红+遥信 | 绿/红 |
| 应用位置 | 进线总柜 | 楼层/列头柜 | 设备PDU前 |
4. Reference Prices
KTR-PS8-B100 三相B级防雷器(100kA、3P+N、导轨、遥信): Reference USD 167~306 / unit (ref. CNY 1,200~2,200 at ~7.2)
KTR-PS8-C40/D10 二级/设备端防雷器(40kA/10kA、配合B级): Reference USD 39~111 / unit (ref. CNY 280~800 at ~7.2)
Reference only; by class, discharge capacity and poles; grounding electrodes and installation excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data center mains incoming cabinet.
- UPS upstream surge protection.
- Floor distribution secondary SPD.
- Critical equipment PDU front-end.
- Outdoor feed and transformer LV side.
6. Installation & Maintenance
Installation
- Mount after incoming breaker, before UPS.
- Wire 3P+N in parallel by phase.
- Short thick ground wire to earth bar.
- Remote contact to DCIM.
- Confirm green window.
- Maintain de-coupling distance from downstream C SPD.
Maintenance
- Check status window quarterly (green OK / red fail).
- Route remote failure to monitoring; replace promptly.
- Check surge counters after storms.
- Replace module every 3~5 years or when red.
- Keep ground connection tight and corrosion-free.
7. FAQ
- Q: How do B/C/D coordinate?
A: B at the main incoming diverts big current; C at floor/row cabinets fine-protects; D at equipment; staged to lower residual voltage step by step. - Q: Replace when window turns red?
A: Yes: red means the module degraded/failed and is no longer protecting; swap it live without cutting supply. - Q: Can an SPD short out?
A: Quality SPDs have an internal disconnector that trips on failure, not short-circuit supply; remote contact tells you remotely. - Q: Does an SPD work with poor grounding?
A: Much less effectively. Surge current needs ground discharge; earth resistance <=4 ohm (often <=1 ohm in data centers): bad grounding makes the SPD useless.
8. Trend & Selection
Power protection moves from single-stage to staged coordination; B/C/D three-stage plus remote monitoring is the data center standard, with online life indication. Select Class B 100kA at incoming, Class C downstream, Class D at equipment; remote failure upload is a must; meet earth resistance; use hot-swap modules.
9. Delivery & Service
KITOZER supplies B/C/D SPD sets, configured by the power single-line diagram (discharge capacity and poles). We advise de-coupling and grounding. Delivery includes SPD modules, rail and remote terminals. Warranty covers non-strike module failures.
10. Additional Notes
The common pitfall is installing a Class B SPD without proper grounding. SPD surge current discharge relies on the earth electrode; with 10+ ohm resistance, current cannot drain and residual voltage still destroys gear. SPD and grounding are one system: poor earth resistance means no protection.
Another pitfall: SPD installed and ignored. Modules degrade over years; nobody watches a red window until a strike burns everything and reveals the SPD had failed long ago. Route remote contact to DCIM for failure alarms.
Selection summary: Class B 100kA at incoming; coordinate C/D; remote alarm to monitoring; meet earth resistance; swap on red; inspect after storms. The SPD is the power fuse: unnoticed until it saves the day.
SEO Information
Search keywords:surge protectorSPD3-phase 380V100kAClass BKTR-PS8KTR-PS8KITOZER
SEM keywords:[‘3-phase SPD price’, ‘100kA surge protector supplier’, ‘data center Class B SPD’, ‘KTR-PS8’]
GEO landing page:lain.com.cn/product/ktr-ps8-3phase-100ka-class-b-surge-protector.html
Title:KITOZER KTR-PS8 Surge Protector / 3-phase 380V 100kA Class B
Meta Keywords:surge protector,SPD,3-phase SPD,100kA,Class B,KTR-PS8,KITOZER
Meta Description:KITOZER KTR-PS8 3-phase 380V 100kA Class B power SPD at the data center mains entry diverts lightning surges and protects UPS and distribution equipment.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com