Table of Contents
ToggleKITOZER KTR-PS9 Surge Protector / 3-Phase 380V 120KA Class B+
Brand: KITOZER Series: KTR-PS9 Category: Power Distribution / Surge Protection
SPD3-phase 380V120KAClass B+KTR-PS9
1. Overview
KITOZER KTR-PS9 is a three-phase power surge protective device (SPD) installed at the data center PDB incoming line to suppress lightning surges and switching over-voltages. Lightning induction, grid switching and large motor starts produce transient kilovolt spikes on power lines that enter the room, breaking power modules and damaging servers and precision AC. KTR-PS9 parallels across the PDB busbars, clamping the surge to an equipment-safe level by diverting current.
KTR-PS9 is a Class B+ (Class II test) 380V three-phase SPD: nominal discharge In 60KA, max discharge Imax 120KA, voltage protection level Up ≤2.5 kV. It uses a plug-in module, so a failed module is swapped without powering down the cabinet. A remote-signaling contact reports degradation to BMS. Wired three-phase five-wire (L1/L2/L3/N/PE) for TN-S systems, installed between the mains incomer and UPS front end as a bridge between Class B and Class C protection.
In data center power distribution, surge protection is a safety baseline: external lightning rods and arresters protect the building, but the internal PDB still needs SPD for fine protection, clamping residual surges lower. KTR-PS9 pairs with Class B main SPD and Class C end SPD in a multi-stage chain.
2. Key Features
High-current diversion
- Imax 120KA (8/20μs).
- In 60KA, withstands repeated events.
- Up ≤2.5 kV clamping.
Plug-in module
- Swap failed modules live.
- No cabinet shutdown for service.
- Red/green status window.
Remote signaling
- Dry contact on degradation.
- Uploads to BMS remote.
- No on-site patrol needed.
Three-phase five-wire
- Full L1/L2/L3/N/PE wiring.
- For TN-S 380V systems.
- Mounts on PDB busbars.
3. Specifications
| Item | KTR-PS9-40 | KTR-PS9-60 | KTR-PS9-120 |
|---|---|---|---|
| Rated voltage (V) | 380 3-ph | 380 3-ph | 380 3-ph |
| Imax (KA) | 40 | 60 | 120 |
| In (KA) | 20 | 30 | 60 |
| Up (kV) | ≤1.8 | ≤2.0 | ≤2.5 |
| Class | C (Class III) | B+ (Class II) | B+ (Class II) |
| Wiring | 3P5W | 3P5W | 3P5W |
| Signaling | Optional | Standard | Standard |
| Mounting | 35mm rail | 35mm rail | 35mm rail |
4. Reference Prices
KTR-PS9-40 SPD (40KA, Class C, 3-phase): Reference USD 39~63 / unit (ref. CNY 280~450 at ~7.2)
KTR-PS9-60 SPD (60KA, Class B+, signaling): Reference USD 81~122 / unit (ref. CNY 580~880 at ~7.2)
KTR-PS9-120 SPD (120KA, Class B+, signaling): Reference USD 136~206 / unit (ref. CNY 980~1,480 at ~7.2)
Reference only; by discharge current, class and signaling. PDB installation and wiring excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Mains incomer main surge protection.
- UPS front-end PDB surge protection.
- Precision AC and PDB incoming lines.
- Low-voltage room and row cabinet Class C.
- Inter-stage in multi-stage SPD chains.
6. Installation & Maintenance
Installation
- Reserve rail space in the PDB.
- Fix SPD base on 35mm rail.
- Wire L1/L2/L3/N to phases and neutral.
- Run PE to nearest earth bar, short and thick.
- Wire signaling contact to BMS dry input.
- Insert module; window shows green.
- Tighten connections, insulation-test, energize.
Maintenance
- Check status window for red (degraded).
- Inspect after thunderstorms.
- Rely on BMS alarms to swap modules.
- Check earth wire for rust and looseness.
- Swap failed modules with same rating.
- Test earth resistance yearly, ≤4Ω.
7. FAQ
- Q: How do Class B and C SPD coordinate?
A: Class B at incomer (high current, high Up), Class C at row cabinet (low current, low Up); keep ≥10 m separation or add decoupling between stages. - Q: Must I replace when the window turns red?
A: Yes — red means degraded or failed; it no longer protects, so swap a same-rating module promptly. - Q: Does SPD affect power quality?
A: No — SPD is high-impedance and idle normally; it conducts only during a surge. - Q: Why must the earth wire be short and thick?
A: A long earth wire adds inductive drop that raises the actual clamping voltage; keep it short, cross-section ≥16mm².
8. Trend & Selection
Power protection moves from single-stage to coordinated multi-stage, modules from fixed to plug-in, and signaling becomes standard. Choose Class B high-current at the incomer, Class C low-Up at the end, keep decoupling distance between stages, use short thick earth wires, and wire signaling to BMS.
9. Delivery & Service
KITOZER selects SPD by distribution architecture, incoming position and multi-stage coordination, setting SPD class, current rating and location. We provide a surge-coordination diagram. Delivery includes SPD module, base, signaling lead and manual. Warranty covers earth testing and module swaps.
10. Additional Notes
The common pitfall is installing only one stage, assuming the incomer SPD is enough. After the Class B SPD diverts a large surge, residual voltage still sits above a kilovolt at the server power board — precision gear cannot withstand it. Add a Class C SPD at the row cabinet and UPS output to clamp below equipment tolerance; the two stages must work together.
Another pitfall is a thin, long earth wire. A loop from SPD to the earth bar with 4mm² wire adds inductive drop of hundreds of volts during a surge, leaving equipment over-volted. Run the earth wire to the nearest bar, keep it short, no thinner than 16mm² — this is the prerequisite for SPD to work.
Selection summary: Class B at incomer, Class C at end in coordination; plug-in modules for live swap; signaling to BMS; short thick earth ≥16mm²; replace on red window. The SPD is the indoor lightning rod — it keeps surges outside the door so equipment stays safe.
SEO Information
Search keywords:SPD3-phase 380V120KAClass B+KTR-PS9KITOZER
SEM keywords:surge protector price,three-phase SPD supplier,data center power SPD,KTR-PS9
GEO landing page:lain.com.cn/product/ktr-ps9-three-phase-380v-120ka-surge-protective-device.html
Title:KITOZER KTR-PS9 Surge Protector / 3-Phase 380V 120KA Class B+
Meta Keywords:surge protective device,SPD,three-phase 380V,120KA,Class B+,power distribution,KTR-PS9,KITOZER
Meta Description:KITOZER KTR-PS9 three-phase power SPD, 380V, 120KA, Class B+, plug-in module, for data center PDB surge protection.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com