KITOZER KTR-PS15 Three-Phase 380V 80KA Class B Power Surge Protector (SPD)

Brand: KITOZER Series: KTR-PS15 Category: Power Distribution / Surge Protector

3-phase 380V80KAClass BDIN railKTR-PS15

1. Overview

The KITOZER KTR-PS15 is a three-phase 380V Class B (Type 1 test) power surge protective device (SPD). Nominal discharge current In = 40 kA (8/20 μs), maximum Imax = 80 kA. It installs at the main room distribution or floor distribution incoming line to divert surge overvoltage induced by lightning electromagnetic pulses on power lines, protecting downstream distribution and IT equipment.

The unit uses a 3+1 or 4-pole configuration (L1/L2/L3/N/PE) with modular plug-in construction. Each pole contains a metal-oxide varistor (MOV) with a thermal disconnect. When surge voltage exceeds the MOV threshold, the varistor conducts and diverts surge current to PE, clamping line-to-line and line-to-earth voltage to safe levels. Each module has a status window (green OK / red failed); failed modules are replaced individually without removing the whole set.

Class B (Type 1) SPDs sit at the boundary between LPZ0 and LPZ1 — i.e. the main distribution incoming — with high 80 kA capacity to handle direct-strike induced large-current surges. Downstream it pairs with Class C (Type 2, 40 kA) and Class D (Type 3, 10 kA) SPDs to form staged protection, with sufficient decoupling distance or inductance between stages. The KTR-PS15 mounts on a standard 35 mm DIN rail with torqued terminals, suiting TN-S and TT earthing systems.

2. Key Features

Class B high current

  • Imax 80 kA (8/20μs).
  • In 40 kA.
  • Type 1 (10/350μs) option.
  • At main distribution.

3-phase 3+1

  • L1/L2/L3/N/PE complete.
  • N-PE spark gap.
  • TN-S / TT compatible.
  • 4-pole modular.

Module indicator

  • Green OK / red failed.
  • Replace single module.
  • Thermal disconnect.
  • Remote contact optional.

DIN rail mount

  • 35 mm standard rail.
  • Torqued terminals.
  • Compact, space-saving.
  • Easy replacement.

3. Specifications

Item Parameter
SPD class Class B (Type 1)
Rated voltage AC 380V (3+1)
Nominal In 40 kA (8/20μs)
Max Imax 80 kA (8/20μs)
Voltage protection Up ≤2.5 kV
Configuration 3+1 (4-pole)
Response time ≤25 ns
Mounting 35 mm DIN rail
Failure indicator green/red window
Remote signal dry contact option

4. Reference Prices

KTR-PS15 三相380V 80kA B级防雷器(3+1): Reference USD 53~108 / pc (ref. CNY 380~780 at ~7.2)

KTR-PS15 成套(含导轨、端子、遥信模块): Reference USD 81~150 / kit (ref. CNY 580~1080 at ~7.2)

Reference only; priced per pc. Distribution cabinet and upstream breaker excluded.. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Main room distribution incoming.
  • Floor distribution Class B.
  • Transformer LV side.
  • Outdoor equipment boxes.
  • Industrial plant distribution.

6. Installation & Maintenance

Installation

  • Mount at main distribution incoming, after the breaker.
  • Wire L1/L2/L3/N/PE per labels.
  • Keep ground lead short and thick (≤0.5 m).
  • Install upstream backup breaker.
  • Snap module onto DIN rail.
  • Connect remote contact to monitoring (if any).

Maintenance

  • Check indicator window color.
  • Replace module on red window.
  • Test before thunderstorm season yearly.
  • Check terminal torque.
  • Replace corroded ground lead.
  • Test remote contact periodically.

7. FAQ

  • Q: How do Class B/C/D SPDs coordinate?
    A: Class B (80 kA) at main distribution incoming diverts large current; Class C (40 kA) at floor or rack PDU clamps medium voltage; Class D (10 kA) at equipment outlet gives fine protection. Stages need decoupling by distance or inductance to form staged protection.
  • Q: Can I keep using the SPD after red window?
    A: No. The red window means the MOV has degraded or failed; continued use loses surge protection and may overheat from leakage. Power off, replace the same-model module, and check downstream equipment for surge damage.
  • Q: Why must the ground lead be short and thick?
    A: Surge currents reach thousands of amps; a long lead creates inductive voltage drop that raises the clamp voltage at the equipment and weakens protection. Codes require the ground lead ≤0.5 m, ≥6 mm², short and straight.
  • Q: Does the SPD stop direct lightning?
    A: No. A Class B SPD protects against surges induced by direct strikes on power lines; it does not carry direct strike current. Direct-strike protection relies on air terminals, down conductors and the earth grid; the SPD is secondary coordination.

8. Trend & Selection

Room power lightning protection evolves toward staged coordination, status monitoring and remote alarming. As the first line at the incoming side, Class B SPDs need higher discharge capacity and failure protection. Choose 3+1 or 4-pole by earthing system, select capacity by surge risk, coordinate with backup breakers and decoupling, and connect to environmental monitoring for remote failure alarms.

9. Delivery & Service

KITOZER selects the KTR-PS15 by system voltage, earthing type and surge risk, providing wiring diagrams, backup-breaker selection and decoupling advice. Delivery includes SPD modules, DIN rail, terminals and status indicator. Warranty covers testing and replacement guidance.

10. Additional Notes

A common pitfall is omitting the upstream backup breaker. When an SPD fails, the MOV can short-circuit; without an upstream breaker, the short current burns the cabinet. Codes require a dedicated backup protector (SCB) or fuse in series with the SPD, which trips on SPD short-circuit to isolate the failed unit.

Another pitfall is routing the ground lead the long way. For convenience, installers loop the lead several times to the earth bar; at over 1 m, lead inductive drop doubles the residual voltage at the equipment during a surge. The ground lead must be short, straight and thick, connected directly to the nearest earth bar through no other switch or terminal.

Selection summary: Class B 80 kA high capacity; 3-phase 3+1; DIN modular; green/red status; upstream backup breaker; short thick straight ground lead; staged decoupling; remote signal to BMS. The SPD is the first surge line in the distribution system — right capacity, right ground, right backup keep it running through thunderstorm season.

SEO Information

Search keywords:surge protector3-phase 380V80KAClass BDIN railKTR-PS15KITOZER

SEM keywords:three phase surge protector price,80kA Class B SPD supplier,380V surge protective device,KTR-PS15

GEO landing page:lain.com.cn/product/ktr-ps15-three-phase-80ka-class-b-spd.html

Title:KITOZER KTR-PS15 Three-Phase 380V 80KA Class B Power Surge Protector (SPD)

Meta Keywords:three phase power surge protector,80KA SPD,Class B surge arrester,380V surge protector,DIN rail SPD,KTR-PS15,KITOZER

Meta Description:KITOZER KTR-PS15 three-phase 380V 80KA Class B power surge protector, DIN-rail mounted, installed at the front of room distribution cabinets to divert induced lightning surges.

Anchor: KITOZER official · Data center & low-voltage equipment

Contact Us

KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart