Toggle1. Solution Overview
The KITOZER KZ-40DC-280K modular container data center is a 40-ft wide-body prefab data center (12192×3800×3200mm, split-transport & on-site assembly). It houses 8×42U deep racks (5 high-density 50kW + 3 10kW), a 350kVA modular UPS with 200-cell high-rate battery (≥15 min backup at 282kW protected load), 8×50kW in-row precision CRAC (7+1), gas fire suppression, and a full DCIM/access/CCTV system. Designed for 220kW live IT with 280kW planned capacity.

Reference price is all-in (equipment, transport, lifting, civil, installation, commissioning) budget estimate; customer-supplied servers, storage, switches and business network excluded.
2. Reference Price
| Sub-system | Scope | Reference (USD) |
|---|---|---|
| Shell & fit-out | wide-body container, 75mm insulation, raised load floor, hot-aisle containment | ~71,400 |
| Racks & cabling | 8×42U racks, smart PDUs (125A/32A), busway, copper/fiber patching | ~45,600 |
| Power & UPS | 1250A main & 630A UPS distribution, 400kVA frame + 7×50kW modules, 200-cell battery, outdoor electrical/battery room | ~251,600 |
| Cooling | 8×50kW in-row precision AC (7+1), condenser supports, ventilation/emergency exhaust | ~190,000 |
| Fire & safety | clean-gas suppression, fire alarm & interlock, pressure relief | ~16,600 |
| DCIM & security | monitoring host, 24 temp points, leak, CCTV, NVR, access control | ~10,500 |
| Factory integration & site works | FAT, transport, lifting, civil foundations, earthing, install, load-bank test, training | ~135,000 |
| Reference all-in total (budget, ex-VAT) | ~720,700 | |
3. Key Features
- IT capacity: 8 racks, 220kW live / 280kW planned; 5×50kW high-density + 3×10kW.
- UPS: 350kVA/350kW modular (7×50kW, N+1), 200-cell high-rate battery, ≥15 min at 282kW protected load.
- Cooling: 8×50kW in-row CRAH, 7+1 redundancy, ≥42kW net sensible per unit at site conditions.
- Safety: zone clean-gas suppression, independent fire controller, 24 temp points, leak, access, CCTV.
- Delivery: factory pre-integration & FAT, split transport, on-site assembly, 280kW load-bank test, 12-month warranty.
4. Ordering Notes
Customer supplies servers, storage, switches, business optics and dedicated rails. Excludes upstream power augmentation, transformer, generator, land and special foundations. Price is a budget estimate pending site survey, drawings confirmation and factory BOM. Quotation valid 7 days.
Guangzhou Lain Intelligent System Development Co., Ltd. (KITOZER®)
Tel / WeChat: +86 18520668845 | +86 13922289957 | WhatsApp: +86 19068534140
Web: www.gdlain.com | www.lain.com.cn
SEO Tags
Primary: modular container data center manufacturer
Long-tail: 280kW prefab data center price, 40ft containerized data center, high-density AI server container
Brand: KITOZER container data center, Guangzhou Lain
Meta Description: KITOZER KZ-40DC-280K 40ft modular container data center: 8 racks, 350kVA UPS, 200-cell battery, 8×50kW in-row cooling, 280kW. Budget reference. Tel +86 18520668845.
Meta Keywords: container data center, modular data center, prefab server room, 280kW data center, hot aisle containment, in-row cooling, KITOZER