When a server room loses utility power, two things must happen simultaneously: the IT equipment must keep running, and the heat it generates must be continuously removed. Traditional server rooms rely on a centralized AC unit, but once mains power fails, that AC shuts down. Servers continue producing heat inside an enclosed rack, and within minutes inlet temperatures can trigger thermal shutdown.
KITOZER’s 42U top-mounted air-conditioned rack integrates the enclosure, precision cooling, PDU, and temperature/humidity display into a single cabinet. Paired with an online double-conversion UPS and valve-regulated lead-acid battery banks, the system delivers “no interruption, no overheating” during outages. This article walks through the design logic for two typical room sizes—a larger room with roughly 4,000W IT load and a smaller room with roughly 1,700W.
Table of Contents
Toggle1. Which Scenarios Does This Solution Fit?
This package is suitable for retrofits or new builds where:
- Existing UPS battery capacity is too small for the required runtime
- Floor space cannot accommodate a separate cooling unit or battery room
- Continuous server operation under outage is a stated requirement
- Logistics warehouses, office IT closets, and small data nodes need reliable power
Existing servers, switches, and storage equipment are not part of this supply scope; they are re-racked according to the site layout.
2. System Architecture
The solution comprises two independent sub-systems:
Larger room (approx. 4,000W load)
- Reuse the existing online UPS; add one string of sixteen 12V/150Ah batteries (series-connected to 192V)
- Add one 42U top-mounted air-conditioned rack with cooling capacity ≥6.0kW
- Include a standalone battery cabinet, DC protection components, hot-air duct, and condensate drain line
Smaller room (approx. 1,700W load)
- Add one new 10kVA/9kW online double-conversion UPS
- Add two 192V battery strings (thirty-two 12V/150Ah batteries total), housed in a dual-string battery cabinet
- Add one 42U top-mounted air-conditioned rack with cooling capacity ≥3.5kW
- Include hot-air duct and condensate drain line
3. What Happens When Power Fails
Under normal mains: The UPS operates in online double-conversion mode—rectifying AC to DC, then inverting back to clean AC—feeding servers, switches, and the rack AC simultaneously. Batteries float-charge during this phase.
On outage: The UPS output transfers seamlessly to the battery string (near-zero transfer time). Servers and the rack AC do not reboot. The rack AC continues extracting heat through its top or side exhaust, while condensate drains by gravity. IT equipment can therefore keep running unattended for several hours.
Runtime verification: The design target is 12 hours, but actual runtime depends on measured IT load, rack AC input power, and battery state of health. If the larger room’s existing 16 batteries plus 16 new batteries cannot sustain a full 12 hours with the AC also on UPS, a third string of 16 batteries may be required. This must be confirmed on site using the UPS manufacturer’s discharge curve.
4. Key Equipment Specifications
42U Top-Mounted Air-Conditioned Rack (KITOZER-IC42-6K / KITOZER-IC42-3.5K)
- Form factor: Standard 19-inch 42U, approx. 600W × 1200D × 2000H mm
- Cooling: Larger room ≥6.0kW; smaller room ≥3.5kW
- Operation: 24/7 continuous duty
- Integrated: Rack-mount PDU, digital temp/humidity display, door-contact dry-contact alarm, cable management, blanking panels
- AC interfaces: Top or side hot-air exhaust, standard condensate drain connection
Online UPS (KITOZER-10KVA-2026)
- Rating: 10kVA / 9kW
- Topology: Online double-conversion, zero transfer time
- Battery bus: 192VDC external battery
- Protection: Auto bypass, overload, short-circuit, over-temperature
- Display/comm: LCD panel, remote monitoring interface
VRLA Maintenance-Free Battery (KITOZER-12V150AH-2026)
- Rating: 12V, 150Ah
- String configuration: 16 in series = 192V per string
- Larger room: 16 units (one string); smaller room: 32 units (two strings in parallel)
- Mounting: Floor-standing battery cabinet or rack; never share the IT rack’s load path
5. Configuration and Reference Pricing
| No. | Product | Model | Qty | Unit (RMB) | Total (RMB) |
|---|---|---|---|---|---|
| 1 | 42U AC rack, 6.0kW (larger room) | KITOZER-IC42-6K-2026 | 1 set | 63,600 | 63,600 |
| 2 | UPS battery 12V150Ah (larger room) | KITOZER-12V150AH-2026 | 16 ea | 2,560 | 40,960 |
| 3 | Battery cabinet + DC protection (larger room) | KITOZER-BCB-192V-2026 | 1 set | 13,600 | 13,600 |
| 4 | Hot-air duct + condensate drain kit (larger room) | KITOZER-DUCT-KIT-2026 | 1 set | 11,600 | 11,600 |
| 5 | 42U AC rack, 3.5kW (smaller room) | KITOZER-IC42-3.5K-2026 | 1 set | 51,600 | 51,600 |
| 6 | Online UPS 10kVA (smaller room) | KITOZER-10KVA-2026 | 1 unit | 39,600 | 39,600 |
| 7 | UPS battery 12V150Ah (smaller room) | KITOZER-12V150AH-2026 | 32 ea | 2,560 | 81,920 |
| 8 | Dual-string battery cabinet + DC protection | KITOZER-BCB-192V-DUAL-2026 | 1 set | 19,600 | 19,600 |
| 9 | Hot-air duct + condensate drain kit (smaller room) | KITOZER-DUCT-KIT-2026 | 1 set | 11,600 | 11,600 |
| 10 | Site survey, design, install & commission (two rooms) | KITOZER-SVC-2SITE-2026 | 1 lot | 33,600 | 33,600 |
| Total (tax excl., reference price) | 367,680 | ||||
Reference prices in RMB. USD equivalent (at 7.2) totals approximately USD 51,067. Prices exclude freight and off-site labor; VAT invoice adds 13%.
6. Frequently Asked Questions
Q1: Why must the rack AC be on UPS?
A: During an outage, the centralized AC has no mains power and stops. If only IT gear is on UPS but the AC is not, heat builds up inside the rack within minutes until server inlet temperatures trigger throttling or shutdown.
Q2: How is the 12-hour runtime calculated?
A: Rough formula: usable battery capacity (Ah) × nominal voltage (V) × discharge efficiency ÷ actual load (W) = runtime in hours. Verify on site with the UPS discharge curve.
Q3: Why do batteries need a separate cabinet?
A: A single 12V/150Ah cell weighs over 40kg; sixteen cells in series weigh more than 600kg. Placing this load on an IT rack’s frame exceeds its structural rating. A floor-standing battery cabinet is standard.
Q4: Can old and new batteries be mixed?
A: Not recommended. Different brands, models, and ages have different internal resistances. Mixing causes unbalanced charging and discharging over time.