KITOZER -48V Telecom DC Distribution Unit DDU DDP Rectifier 90A Technical Parameters

Telecom room DC distribution equipment does not have the complex topologies or waveforms of a UPS; its spec sheet looks straightforward—input current, number of output branches, protection configuration—but every figure directly affects the safety of downstream telecom gear. This handbook explains the parameters of three product families: rack-top DC distribution units (DDU), rack-top DC distribution panels (DDP), and rectifier modules, clarifying what each number means and how it is used in engineering practice.

KITOZER -48V telecom DC power cabinet open with rectifier modules and battery breakers
KITOZER -48V telecom DC power cabinet — open view showing AC input breakers, rectifier modules, and DC distribution

1. System Basics: The -48V Standard

Telecom rooms use -48V DC as the industry standard. Nominal voltage is -48V, with a normal operating range of -38.4V to -57.6V. Output voltage is adjustable between -42V and -59.5V to accommodate different battery float and boost charge settings.

Why -48V and not +48V? Negative-potential output with positive grounded reduces electrochemical corrosion on cable sheaths and equipment racks. This historical convention explains why telecom power has long used -48V (positive grounded, -48V as the negative output rail).

2. Rack-Top DC Distribution Unit (DDU)

A DDU mounts on top of a standard 19-inch rack and delivers -48V branch outputs directly to telecom equipment inside the rack. It is the last stage in the DC power chain.

Input parameters: Input voltage -48V DC; input terminal rating 63A / 100A / 160A (selected by site load); input side uses a 2-pole DC breaker on both + and – rails; overcurrent, short-circuit, and overvoltage protection.

The input terminal rating must exceed the total current drawn by all equipment in the rack. Example: a 3kW rack load at -48V draws about 62.5A; a 100A input terminal leaves roughly 60% headroom.

Standard output branch configuration:

  • 6 × 63A — feeds main transmission gear
  • 6 × 32A — feeds service board power
  • 2 × 20A and 2 × 16A — auxiliary equipment and monitoring modules

Simplified configuration (smaller sites): 6 × 32A + 2 × 20A + 2 × 16A with 63A input.

Protection: Each output branch independently protected by a DC circuit breaker. DC breakers must be rated for DC arc interruption; AC breakers cannot be substituted.

KITOZER rack-mount -48V rectifier system with modular rectifier units
KITOZER rack-mount -48V rectifier system — modular rectifier units with cooling fans and DC distribution terminals

3. Rack-Top DC Distribution Panel (DDP)

The key difference between a DDP and a DDU is primary/backup redundancy. A DDU has a single input; a DDP provides redundant primary and backup inputs on both the input and output sides.

Output branches: 4 × 63A (2 primary, 2 backup) and 4 × 32A (2 primary, 2 backup). When a primary branch fails, the backup branch can be switched in manually or automatically.

Input redundancy configurations:

  • Config A: 2 × 100A inputs (1 primary, 1 backup) — for sites with two independent DC buses
  • Config B: 4 × 63A inputs (2P2B) + 4 × 32A inputs (2P2B) — for higher-current, more granular distribution

DDP is deployed in core rooms carrying critical loads—core switches and transmission equipment racks. Access-layer racks can use DDU.

KITOZER embedded -48V rectifier system with breaker panel and modular rectifier slots
KITOZER embedded -48V switching power system — breaker panel, SPD protection, and hot-swap rectifier modules

4. Rectifier Module

The rectifier converts 220V AC to -48V DC, feeding the DC bus and charging the battery bank.

Parameter Value
AC input 220V AC
DC output -48V DC
DC capacity ≥90A
Output branches DC ≥63A + 1×32A; AC ≥1×32A
System efficiency ≥91%
Protection Overcurrent, short-circuit, overvoltage

At 90A output / -48V, DC output power is roughly 4.3kW. Raising efficiency from 91% to 95% saves hundreds of kWh per year per unit. However, at small sites, cost and volume constraints make 91% a common entry-level efficiency figure.

Ripple (noise) voltage specifications:

Frequency Range Limit Meaning
0–300Hz ≤400mV peak Low-frequency ripple affects supply stability
300Hz–3.4kHz ≤2mV (weighted) Mid-frequency noise can introduce audio interference
3.4kHz–150kHz Single-tone ≤5mV RMS High-frequency switching noise affects digital circuits
KITOZER VRLA battery bank racked in battery cabinet for -48V telecom backup
VRLA battery bank in floor-standing cabinet — provides -48V backup during mains outage

5. Configuration and Reference Pricing

No. Product Model Qty Unit (RMB)
1 Rack-top DDU (standard, 100A input) KITOZER-DDU-100A-2026 1 2,400
2 Rack-top DDU (63A input) KITOZER-DDU-63A-2026 1 2,200
3 Rack-top DDU (160A input) KITOZER-DDU-160A-2026 1 2,600
4 Rack-top DDU (simplified, 63A input) KITOZER-DDU-LITE-63A-2026 1 1,960
5 Rack-top DDP (Config A, 2×100A) KITOZER-DDP-2X100A-2026 1 3,600
6 Rack-top DDP (Config B, 4×63A) KITOZER-DDP-4X63A-2026 1 4,400
7 Rectifier module (220V AC / -48V 90A) KITOZER-RECT-220V-90A-2026 1 7,000

A typical site combination (2× DDU + 1× DDP) costs approximately RMB 8,400 per site (USD 1,167). Sites including a rectifier add RMB 7,000. Reference prices are doubled from the original quote; excludes freight, installation, and tax.

6. Frequently Asked Questions

Q1: What is the difference between DDU and DDP?
A: A DDU is a single-input distribution unit—simpler and lower cost, for access and general service racks. A DDP provides redundant primary/backup inputs and output branches, with higher reliability, for core switches and transmission gear.

Q2: How do I choose between 63A, 100A, and 160A input terminals?
A: Convert total rack load to current: current (A) = total rack power (W) ÷ 48V. Reserve at least 30%–50% headroom. Example: 3kW ≈ 62.5A → choose 100A input.

Q3: Why use a 2-pole breaker on the input?
A: In a -48V system, the positive pole is grounded. If only the negative pole (-48V) is disconnected, the positive (0V) remains connected to ground, leaving chassis and wiring at a potential that poses a shock risk during maintenance.

Q4: Is 91% rectifier efficiency considered low?
A: Small-site entry-level rectifiers typically range from 90% to 93%. High-efficiency modules in large rooms reach 96%+, but at significantly higher cost. For small sites with space and budget constraints, 91% is reasonable.