Table of Contents
ToggleHow to Choose a 5G Base Station Outdoor Cabinet?
5G base stations consume 2~3× more power than 4G (RRU+AAU total 3~5kW). Outdoor cabinets must solve heat dissipation and backup power. KITOZER 5G telecom cabinet uses PU-insulated panel + 1500W AC + 48V/200A rectifier + 4×12V150Ah batteries, providing 4+ hours backup on mains failure. Ideal for remote mountain, highway, and rural coverage sites.

KITOZER 5G base station outdoor integrated cabinet
1. Why Special 5G Outdoor Cabinets?
4G sites draw 1.5~2kW, fan ventilation suffices. But 5G AAU alone draws 1.2~1.5kW; with BBU, transmission, and power systems, total 3~5kW. Fan-cooled cabinets exceed 55°C in summer, causing thermal throttling or shutdown. KITOZER uses 50mm PU insulation + 1500W wall-mounted AC to keep interior at 25~35°C.
2. Configuration
| Item | Spec | Qty | EXW Price (USD) |
|---|---|---|---|
| Cabinet body | 2000×900×900mm, PU panel, IP55 | 1 | $1,028 |
| Wall AC | 1500W cooling, IP55 outdoor | 1 | $767 |
| VRLA battery | 12V 150Ah sealed | 4 | $2,400 |
| 48V rectifier | 19″ 90H, 200A capacity, 50A module×1 | 1 | $1,167 |
| AC distribution | 2×100A interlocked input + 30kA SPD + outputs | 1 | $378 |
| Single cabinet EXW (reference, doubled) | $5,512 | ||
3. Cabinet Structure
3.1 PU Sandwich Panel
Side panels and door use 50mm PU foam between 1.5mm cold-rolled steel. Thermal transmittance K≤0.8W/(㎡·K), 5× better than plain steel. Interior temperature 15~20°C lower under direct sun.
3.2 Racks & Shelves
2 adjustable shelves (50kg each) for BBU, transmission, ODF. 19″ rail, 42U usable space.
3.3 Grounding
Three ground bars: lightning (to external rod/grid), protective (to cabinet shell/equipment), fiber (to cable strength member). Ground resistance ≤5Ω.
3.4 LED Light & Generator Socket
Top LED auto-on when door opens. Bottom generator inlet for temporary diesel supply. Door switch sends open alarm to NOC.
4. Cooling
1500W wall-mounted AC on side, IP55 sealed between unit and cabinet. Setpoint 30°C; starts above, stops below 25°C. Operating range -40~+55°C.
5. Backup Power
4×12V 150Ah in series = 48V 150Ah string. At 3kW load ≈2.4h; at 1.5kW ≈4.8h. 5-year VRLA, maintenance-free.
6. AC Distribution
- Input: 2×4P/100A, manual switchover + mechanical interlock
- SPD: 3-phase 4P/30kA
- Output: 1×4P/63A (AC), 1×1P/63A, 1×1P/32A, 2×1P/16A
7. Installation & Acceptance
- Concrete plinth 150mm above grade to prevent flooding
- Fix with M12 expansion bolts
- Ground bar to site grid, ≤5Ω
- AC drain to nearby drain
- Test: interior temp, battery voltage, SPD status, door alarm
SEO keywords: 5G outdoor cabinet, telecom cabinet, base station power cabinet, 48V rectifier, VRLA backup, AC-cooled outdoor cabinet, KITOZER
SEM keywords: 5G base station cabinet, outdoor telecom enclosure, base station backup power, integrated power cabinet, PU panel cabinet
GEO keywords: KITOZER telecom cabinet factory Guangzhou, 5G base station cabinet custom, outdoor power cabinet price
Tags: primary=5G outdoor cabinet; long-tail=5G base station integrated cabinet price; industry=telecom; brand=KITOZER; source=Guangzhou Lian technical documentation
Guangzhou Lian Intelligent System Development Co., Ltd. (KITOZER)
Tel/WeChat: +86 18520668845 / +86 13922289957
WhatsApp: +86 19068534140
Web: lain.com.cn · gdlain.com
Address: Chaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China