ToggleProduct Overview
The KITOZER 60 kW chilled-water in-row air conditioner is a compressor-free rack-height terminal unit designed for data halls served by a central chiller plant. It uses a high-capacity cooling coil, a modulating control valve, EC plug fan array, and optional steam humidifier. Chilled water enters at 10 to 14 degrees Celsius and absorbs heat directly from hot aisle exhaust air. Because no refrigeration circuit lives inside the white space, the unit is quiet, reliable, and easy to service without refrigerant handling certification. The cabinet matches a standard rack bay, allowing installation between server rows without modifying the floor.
Technical Specifications
Rated sensible cooling is 60 kW at 27 degrees Celsius entering air, 50 percent relative humidity, and 10 degree Celsius entering water. Coil is 6-row copper tube with aluminum fins, rated to 1.6 MPa working pressure. Water flow is 2.6 liters per second at a design delta-T of 5 degrees. Supply airflow is 14,000 cubic meters per hour against 80 Pa. Electrical supply is three phase 400 V 50 Hz with fan power 2.2 kW and humidifier 6 kW. Dimensions are 600 mm wide by 1200 mm deep by 2000 mm high. Weight is 280 kg. Noise is 64 dBA at 3 meters. Communication supports BACnet IP, Modbus TCP, and SNMP.
Application Scenarios
This unit is deployed in colocation halls, enterprise data centers, and cloud zones where chilled water is already distributed. It suits rack densities of 10 to 20 kW per rack, GPU compute clusters, and storage arrays. It pairs naturally with hot-aisle containment and water-side economizers, allowing free cooling whenever outdoor temperatures permit the chiller to unload. The unit is also used in broadcast master control rooms, hospital IT suites, and university research data centers. Because the cabinet is rack-height, it can be rolled through standard doorways and installed without a crane, making it well suited to urban colocation buildings with limited service access.
Advantages and Features
The absence of compressors eliminates refrigerant leak risk inside the data hall and removes the dominant source of acoustic noise. The 0 to 10 V modulating valve adjusts water flow down to 10 percent, maintaining stable aisle temperatures under rapidly changing IT loads. EC fan arrays deliver high efficiency and redundancy: loss of one fan leaves the rest continuing to supply cooling. The controller integrates with DCIM platforms, providing per-unit kilowatt metering, filter loading alarms, and condensate overflow protection. A built-in web server exposes trends and setpoints to any browser on the local network. The unit also supports scheduled start-stop based on IT load patterns, avoiding unnecessary cooling during weekends or holiday periods.
Installation and Maintenance Recommendations
Piping must include isolation valves, Y-strainer, flexible connector, and balancing valve. A drain pan with float switch and lift pump protects against condensate overflow. Air filters are G4 and should be inspected quarterly. The coil should be chemically cleaned at commissioning and inspected annually. Valve actuators and temperature sensors require annual calibration. Water quality must be maintained to prevent fouling of the coil. Commissioning should include a balancing procedure that sets water flow to design delta-T and a 24-hour aisle temperature stability test. A thermal imaging walk-through after commissioning confirms that no rack inlet exceeds the design setpoint. Operators should be trained on reading the touchscreen, acknowledging alarms, and replacing filters before handover. A remote alarm forwarding module can send fault messages to a dedicated phone line or email address, so the site team is paged before a small issue becomes a room-temperature excursion. The controller also logs filter differential pressure trends, helping maintenance teams plan replacements during scheduled windows.
Energy and Environmental Performance
Because the unit contains no compressor, its only parasitic energy is fan power, which averages less than 4 percent of the heat it rejects. When paired with a water-side economizer, the central chiller can be bypassed for most of the year, pushing site PUE below 1.25. The cabinet uses CFC-free foam insulation and is fully recyclable at end of life. The modulating valve also reduces pump energy by avoiding over-flow at part load. Over a year, the energy savings compared with a compressor-based in-row unit can exceed 80 percent of the cooling-side electricity bill.
Configuration Options and Warranty
The unit is offered in multiple coil rows and fan sizes to match different rack densities. Optional extras include a steam humidifier, a BACnet routing module, a stainless-steel front for coastal sites, and a high-static fan option. The standard warranty covers the cabinet and controls for 1 year, with extended coverage up to 5 years available. Factory commissioning and operator training are recommended for multi-unit arrays. A preventive maintenance package with quarterly filter changes and valve calibration is available.
Price
From $11,800 per unit. Contact plus 86 13922289957 for chilled-water in-row pricing and hydraulic layout.