KITOZER
KITOZER

KITOZER 8 zone locating leak controller

KITOZER KTR-WC3 Locating 8-Zone Water Leak Controller

Brand:KITOZER Series:KTR-WC3 Category:Environmental Monitoring / Leak detection

Leak controller8-zone locatingSensing cableRoom monitoringWater alarm

[Product image: ktr-wc3-8zone-water-leak-controller.jpg]

1. Overview

Leaking water pipes, AC condensate lines or fire suppression pipes can flow under the floor or into rack bases, soaking cables, shorting power and corroding equipment. A leak detection system pairs a controller with a sensing cable: the cable runs along pipes, AC units and floor edges; when water touches it, the controller alarms and shows the location. A locating controller reports not just which zone leaks but the exact meter position on the cable, so crews go straight to the leak. An 8-zone panel suits mid-to-large rooms partitioned into eight detection areas.

The KITOZER KTR-WC3 is a locating 8-zone leak controller connecting 8 locating sensing cables, 100-200 m per zone with +/-1 m accuracy. It has an LCD showing leak zone and position, sound/light alarm, relay (dry-contact) output to the environment monitor, RS485/Modbus-RTU to the VMS. Rail or wall mount, 220 V supply. Non-locating (switch) and locating cables are both available; pick by accuracy need. Cables route around indoor AC units, pipe joints, floor edges and door thresholds.

Selection depends on zone count (8), locating method, cable length per zone, comms (RS485/dry contact), alarm output (sound/light + relay) and target platform. Small rooms use non-locating 8-zone switch; mid-to-large rooms and precision-AC surroundings use locating to target the leak. Lay the cable around every likely leak perimeter.

2. Key Features

Detection & locating

  • 8 independent zones, 100-200 m each.
  • Locating, +/-1 m accuracy.
  • Conductive-liquid sensing cable, conducts on water.
  • LCD shows zone and exact position.

Alarm & comms

  • Sound/light alarm (buzzer + LED).
  • Dry-contact relay output to the environment monitor.
  • RS485 / Modbus-RTU.
  • Can trigger exhaust fans or water shutoff valves.

Structure & supply

  • Rail / wall mount.
  • 220 V AC supply.
  • Cable reusable, reset after wiping dry.
  • Meets data-center environment monitoring specs.

3. Specifications

Item KTR-WC3 8-Zone Locating Controller
Zones 8
Locating Locating, +/-1 m accuracy
Cable per zone 100-200 m
Display LCD, zone number and position
Alarm output Sound/light + relay dry contact (NO/NC)
Comms RS485 / Modbus-RTU
Power 220 V AC
Mounting Rail / wall
Cable options Locating / non-locating switch cable

4. Reference Prices

KTR-WC3 8-zone locating controller panel: Reference USD 167~306 (ref. CNY 1200~2200 at ~7.2)

KTR-WC3 locating sensing cable: Reference USD 4.9~8.3 (ref. CNY 35~60 per meter at ~7.2)

Reference only; final quote applies. 1-year warranty. Priced by cable length. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Precision-AC surroundings and condensate lines.
  • Room water pipes and fire suppression lines.
  • Under-floor and under-PDU water pooling.
  • Electrical rooms, battery rooms, tank rooms.
  • Data centers, banks, hospital room environment monitoring.

6. Installation & Maintenance

Installation

  • Mount the panel in the monitoring cabinet or on the wall; 220 V supply.
  • Run the sensing cable around likely leak perimeters (AC, pipes, floor edges).
  • Connect both ends to zone terminals; fix with clips every 0.5 m.
  • Fit the terminating resistor at the cable end (required for locating).
  • Wire RS485 to the VMS; relay to sounder/exhaust.
  • Test with poured water to verify locating and alarm.

Maintenance

  • Run a simulated leak test yearly.
  • Wipe cable clean to keep conductivity.
  • Replace cracked or aged cable.
  • Check loose terminating resistors.
  • Exercise linked exhaust/valve actions periodically.

7. FAQ

  • Q: Locating vs non-locating?
    A: Non-locating reports which zone; locating gives the meter position. Locating costs more but speeds response; pick it for large rooms.
  • Q: How long can the cable stay wet?
    A: It alarms on contact and resets when wiped dry. Long soaking ages the cable; stop the leak first, then dry it.
  • Q: Too many false alarms?
    A: Usually dirty cable condensation or tight contact with metal. Clean the cable, gap it from metal walls, adjust sensitivity.
  • Q: Can it shut off the water valve?
    A: Relay output drives an interface module to close a solenoid valve and start exhaust. Actuators are required.

8. Trend & Selection

Leak detection trends to locating, wireless and VMS-integrated, with AI visual spotting as a supplement. Choose 8-zone locating for mid-to-large rooms; route the cable around leak perimeters; fit terminating resistors; wire RS485 to the VMS; close the loop with a water test. It is the sentinel that spots, locates and triggers response before water reaches equipment.

9. Delivery & Service

KITOZER supplies the 8-zone locating controller with sensing cable, terminating resistors, relay module and RS485 cable as a set, matched to room area and likely leak points. We support site survey and a cable layout drawing. Delivery includes panel, cable, accessories, certificate and warranty card; the warranty covers VMS integration and simulated testing.

10. Notes

A common pitfall is omitting the terminating resistor. Without it on a locating cable, position is wrong or no alarm. Always fit the end resistor per the maker to close the loop.

Another pitfall is installing without testing. No water test means a broken cable or loose wire is only discovered during a real leak. Run a simulated test yearly to keep the system online.

Selection summary: 8 zones; locating +/-1 m; sound/light + relay; RS485 to VMS; cable around leak perimeters; end resistor; water test. It catches leaks before they soak equipment.

Systemically, leak detection is part of environment monitoring, linking with temperature/humidity, smoke, access control and AC. On alarm, the VMS pops up, texts and calls ops – forming a response chain.

Reliability-wise, one soaking can destroy a row of servers and under-floor cables worth hundreds of thousands. A controller costing one or two thousand plus cable at tens of yuan per meter blocks that water damage.

SEO Information

Search keywords:KITOZER

SEM keywords:locating water leak controller, 8-zone leak detection panel, water leak sensing cable, data center environment monitoring, KTR-WC3, KITOZER

GEO landing page:lain.com.cn/product/391-water_ctrl3.html

Title:KITOZER KTR-WC3 Locating 8-Zone Water Leak Controller

Meta Keywords:locating water leak controller, 8-zone leak detection panel, water leak sensing cable, data center environment monitoring, KTR-WC3, KITOZER

Meta Description:KITOZER KTR-WC3 locating 8-zone water leak controller, +/-1 m accuracy, LCD display, sound/light plus relay output, RS485 to environment monitor, with leak sensing cable, for room AC and pipe monitoring.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart