Table of Contents
Toggle5.2 Medium Configuration List (Intelligent Type, 100A–630A, Dual Input)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | AC PDU Cabinet | KITOZER‑AC‑M2200 | Floor-standing, IP30 protection, dimensions 600×800×2200mm, cold-rolled steel plate with anti-corrosion coating | 1 | Set | KITOZER | Independent floor installation |
| 2 | Dual Input Circuit Breaker | KITOZER‑M630‑3P | 3P, rated current 630A, breaking capacity 30kA, overload/short-circuit/phase-loss protection | 2 | Pcs | KITOZER | Dual mains power input |
| 3 | ATS Automatic Transfer Switch | KITOZER‑ATS‑630 | 3P, rated current 630A, dual mechanical & electrical interlock, switching time ≤100ms, voltage range 180–480VAC | 1 | Set | KITOZER | Automatic transfer of dual power sources |
| 4 | Branch Circuit Breaker | KITOZER‑M250‑3P (3P, 250A, breaking capacity 20kA, 6 circuits); KITOZER‑M100‑1P (1P, 100A, 12 circuits) | — | 18 | Pcs | KITOZER | Mixed circuit configuration |
| 5 | Class B+C Surge Protection Device | KITOZER‑SPD‑B80+C40 | Class B: 80kA; Class C:40kA, 3P+N, residual voltage ≤800V, remote alarm contact | 1 | Set | KITOZER | Two-stage lightning protection |
| 6 | Intelligent Electricity Meter | KITOZER‑EM‑3000 | Three-phase, measuring voltage/current/power/frequency/electric energy, 0.5S accuracy class, RS485 communication | 1 | Pcs | KITOZER | Parameter metering and collection |
| 7 | Intelligent Monitoring Module | KITOZER‑SC‑200 | Monitors voltage/current/SPD status/switch status, local LCD display, RS485 communication, sound-light alarm | 1 | Set | KITOZER | Local monitoring and fault alert |
| 8 | AC Copper Bar | KITOZER‑CB‑630 | Three-phase copper bar, cross-section 30mm², tinned treatment, current carrying ≥800A | 1 | Set | KITOZER | Main circuit conduction |
| 9 | Flame-retardant Connecting Wire | KITOZER‑WL‑16 | 16mm² flame-retardant RV wire, withstand voltage ≥500V, heat-resistant up to 105℃ | 1 | Batch | KITOZER | Internal wiring |
| 10 | Alarm Buzzer | KITOZER‑BZ‑220 | AC220V, 85dB, fault sound alert | 1 | Pcs | KITOZER | Abnormal sound prompt |
| 11 | Earthing System | KITOZER‑GS‑M | Earthing copper bar + earthing cable, earthing resistance ≤0.1Ω, separated protective & working earth | 1 | Set | KITOZER | Safety earthing protection |
5.3 High Configuration List (IoT Type, ≥630A, Multi-source Integrated)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | AC PDU Cabinet | KITOZER‑AC‑H2200 | Floor-standing, IP54 protection, dimensions 800×1000×2200mm, 304 stainless steel for anti-corrosion & rust prevention | 1 | Set | KITOZER | Outdoor/harsh industrial environments |
| 2 | Multi-source Input Circuit Breaker | KITOZER‑M1250‑3P | 3P, rated current 1250A, breaking capacity 50kA, overload/short-circuit/phase-leakage protection | 3 | Pcs | KITOZER | Mains + Generator + New Energy Input |
| 3 | Intelligent ATS Transfer Switch | KITOZER‑ATS‑1250 | 3P, rated current 1250A, dual power + new energy grid-connected control, switching time ≤50ms, phase sequence identification, harmonic suppression | 1 | Set | KITOZER | Intelligent multi-source transfer & grid connection |
| 4 | Branch Circuit Breaker | KITOZER‑M630‑3P (3P,630A,35kA breaking capacity,4 circuits); KITOZER‑M250‑3P (3P,250A,8 circuits); KITOZER‑M100‑1P (1P,100A,16 circuits) | — | 28 | Pcs | KITOZER | Multi-loop precise power distribution |
| 5 | Class B+C+D Surge Protection Device | KITOZER‑SPD‑B100+C60+D20 | Class B 100kA, Class C 60kA, Class D 20kA, 3P+N, residual voltage ≤600V, remote monitoring & alarm | 1 | Set | KITOZER | Three-stage refined lightning protection |
| 6 | Multi-function Intelligent Electricity Meter | KITOZER‑EM‑5000 | Three-phase full electric energy measurement, 0.2S accuracy class, harmonic analysis, demand statistics, RS485/Ethernet communication | 1 | Pcs | KITOZER | High-precision metering & power quality analysis |
| 7 | IoT Monitoring Module | KITOZER‑SC‑500 | 7-inch touch screen, real-time parameter display, switch status monitoring, fault waveform recording, Ethernet/Wi-Fi communication, cloud access, APP remote control | 1 | Set | KITOZER | Intelligent operation & remote management |
| 8 | AC Copper Bar | KITOZER‑CB‑1250 | Three-phase copper bar, cross-section 50mm², tinned treatment, current carrying ≥1500A with insulating sheath | 1 | Set | KITOZER | High-current load bearing |
| 9 | Flame-retardant & Fire-resistant Connecting Wire | KITOZER‑WL‑25 | 25mm² low-smoke zero-halogen flame-retardant fire-resistant RV wire, withstand voltage ≥1000V, heat-resistant up to 125℃ | 1 | Batch | KITOZER | Fire-proof safe wiring |
| 10 | Sound-light Alarm | KITOZER‑AS‑220 | AC220V, 110dB, three-color red/yellow/green light for graded fault alert | 1 | Set | KITOZER | Classified fault notification |
| 11 | Temperature Monitoring Sensor | KITOZER‑TS‑100 | Measuring range -40℃~+125℃, accuracy ±0.5℃, monitors copper bar/circuit breaker temperature with over-temperature alarm | 6 | Pcs | KITOZER | Overheat protection to prevent fire hazards |
| 12 | Intelligent Earthing System | KITOZER‑GS‑H | Earthing copper bar + lightning protection cable + earthing resistance monitoring module, earthing resistance ≤0.05Ω with real-time alarm | 1 | Set | KITOZER | Advanced safety earthing |
| 13 | Cloud Monitoring Platform | KITOZER‑CP‑Cloud | Data storage, analysis, visualization, remote control, alarm push, report generation, multi-device access support | 1 | Set | KITOZER | IoT remote operation & maintenance |
6. Full Product Technical Specifications

Cabinet Wiring Drawing
6.1 AC PDU Cabinet
- Material: Cold-rolled steel plate (Basic/Medium Configuration); 304 stainless steel (High Configuration)
- Protection Rating: IP20 (Basic), IP30 (Medium), IP54 (High)
- Dimensions: 440×460×177mm (4U Rack-mounted); 600×800×2200mm (Medium Floor-standing); 800×1000×2200mm (High Floor-standing)
- Operating Temperature: -20℃~+70℃
- Relative Humidity: ≤95% (Non-condensing)
- Altitude Adaptation: ≤4000m
6.2 Circuit Breaker (MCCB/MCB)
- Rated Voltage: AC380V/400V (Three-phase), AC220V (Single-phase)
- Rated Frequency: 50Hz/60Hz
- Rated Current: Optional from 10A–1250A
- Breaking Capacity: Optional from 6kA–50kA
- Protection Functions: Overload, short-circuit, phase loss, leakage (High Configuration)
- Mechanical Service Life: ≥10,000 operations
- Electrical Service Life: ≥5,000 operations
6.3 ATS Automatic Transfer Switch

On-site Cabinet Installation
- Protection Class: Class B (80kA–100kA), Class C (40kA–60kA), Class D (20kA)
- Nominal Discharge Current: 20kA–100kA (8/20μs waveform)
- Maximum Discharge Current: 40kA–200kA (8/20μs waveform)
- Residual Voltage: ≤1000V (Basic), ≤800V (Medium), ≤600V (High)
- Operating Voltage: AC380V/400V
- Status Indication: Window color (Green=Normal / Red=Fault), remote alarm contact
6.5 Intelligent Electricity Meter
- Measurable Parameters: Voltage, current, power, power factor, frequency, electric energy, harmonic (High Configuration)
- Accuracy Class: 0.5S (Medium), 0.2S (High)
- Communication Interfaces: RS485 (Medium), RS485/Ethernet (High)
- Operating Voltage: AC85V–265V
- Output: Pulse output, data upload
6.6 Intelligent Monitoring Module
- Display: LED indicator lights (Basic), LCD screen (Medium), 7-inch touch screen (High)
- Monitored Parameters: Voltage, current, SPD status, switch status, temperature (High)
- Communication Interfaces: RS485 (Medium), Ethernet/Wi-Fi (High)
- Alarm Modes: Indicator light + buzzer (Medium), Sound-light + APP push notification (High)
- Operating Voltage: DC12V/24V, AC220V
6.7 Copper Bars & Connecting Wires
- Copper Bar Material: Pure copper with tinned surface treatment
- Copper Bar Cross-section: Optional from 10mm²–50mm²
- Wire Material: Flame-retardant RV wire (Basic/Medium); Flame-retardant & fire-resistant RV wire (High)
- Wire Cross-section: Optional from 6mm²–25mm²
- Withstand Voltage: ≥500V (Basic/Medium), ≥1000V (High)
- Maximum Operating Temperature: ≤105℃ (Basic/Medium), ≤125℃ (High)
6.8 Temperature Sensor
- Measuring Range: -40℃~+125℃
- Accuracy: ±0.5℃
- Output Signal: RS485
- Operating Voltage: DC24V
7. Product Application Scope
7.1 Telecommunications Industry
- Communication Base Stations: AC power distribution for outdoor cabinets and indoor integrated cabinets of 4G/5G base stations to stabilize power supply for base station equipment.
- Data Centers: Column head cabinet power distribution for small & medium-sized data center computer rooms, compatible with IT equipment including servers and switches.
- Supporting Computer Room Equipment: Power distribution for UPS input, rectifier module input, air conditioning and lighting loads in communication computer rooms.
7.2 New Energy Industry
- Photovoltaic Power Stations: AC bus collection and inverter input power distribution for distributed & centralized photovoltaic plants, adapting to PV grid-connected scenarios.
- Wind Power Stations: Low-voltage AC power distribution for wind farm box transformers and booster stations to guarantee power supply for fan control and auxiliary equipment.
- Energy Storage Power Stations: AC input and grid-connected power distribution for energy storage system PCS, matching energy storage charge-discharge control.
7.3 Industrial Sector
- Industrial Plants: Power, lighting and equipment control power distribution for electronics manufacturing, machining, chemical and other workshops.
- Rail Transit: Low-voltage AC power distribution for metro and light rail stations, supporting ventilation, lighting and signal equipment.
- Power Industry: Low-voltage AC power distribution for substations and switching stations to supply secondary equipment (protection, monitoring, communication).
7.4 Construction & Municipal Engineering

Central Monitoring Control Room
- Commercial Buildings: Low-voltage power distribution for office buildings, shopping malls and hotels, compatible with air conditioners, elevators, lighting and office equipment.
- Residential Buildings: AC power distribution for power distribution rooms of high-rise residential buildings and communities to secure domestic power consumption.
- Municipal Projects: Power distribution for road lighting, bridges and tunnels, adapted to harsh outdoor environments.
7.5 Other Scenarios
- Medical Industry: Power distribution for hospital operating rooms, ICUs and medical equipment computer rooms to ensure uninterrupted power supply for critical medical devices.
- Education Industry: Power distribution for school computer rooms, laboratories and teaching buildings, supporting teaching equipment and lighting.
- Outdoor Scenarios: Power distribution for field operation stations, meteorological stations and monitoring stations, adapting to wide temperature, dust-proof and waterproof environments.
8. Product Advantages
8.1 Core Functional Advantages
- High Reliability: Modular redundant design with N+1 redundancy for key components (ATS, monitoring modules); core components adopt world-renowned first-tier brands with strict aging tests, achieving system availability ≥99.99%.
- High Safety: Integrated multi-layer safety mechanisms including three-stage lightning protection, graded protection, leakage protection, over-temperature protection and earthing protection; insulated cabinet design with maximum IP54 protection rating to eliminate risks of electric shock, short circuit and fire.
- High Intelligence: Supports local intelligent monitoring, remote management, cloud access, APP control and fault early warning & data analysis; high-end models feature harmonic analysis, demand statistics and fault waveform recording for smart power distribution operation & maintenance.
- Strong Compatibility: Compatible with single/dual mains power, mains + generator, photovoltaic/wind multi-source input; compliant with international standard voltage & frequency of 380V/400V, 50Hz/60Hz; supports multiple communication protocols including RS485, Ethernet and Wi-Fi to connect mainstream monitoring platforms.
8.2 Customization & Service Advantages

On-site Outdoor Distribution Cabinet
10.1 AC Power Distribution Solution for Communication Base Stations
- Pain Points: Limited space in base stations, harsh outdoor environments (extreme temperature, humidity, lightning), high power supply stability requirements and difficulties in unattended operation & maintenance.
- Solution Configuration: Basic 4U rack-mounted AC PDU with single 100A input, 8-channel 63A output, Class C SPD and basic monitoring; IP20 cabinet with wide temperature design (-20℃~+70℃) compatible with outdoor cabinet installation.
- Solution Advantages: Compact size for flexible installation and low cost; wide temperature & dust-proof design adapts to outdoor environments; basic lightning protection safeguards power safety with maintenance-free unattended operation to cut O&M costs.
10.2 AC Power Distribution Solution for Data Centers
- Pain Points: High load power, ultra-high power supply continuity requirements, strict power quality standards, demand for intelligent remote O&M and precise multi-loop power distribution.
- Solution Configuration: High-end floor-standing AC PDU with dual mains + generator input, seamless ATS transfer, three-stage B+C+D SPD, IoT monitoring module, multi-function electricity meter and temperature sensors; supports cloud access, APP remote control and fault early warning.
- Solution Advantages: Multi-source redundant power supply with switching time ≤50ms to achieve zero power interruption; three-stage lightning protection & multi-layer safeguards eliminate lightning and short-circuit faults; intelligent remote monitoring reduces labor costs; harmonic stabilization ensures power quality for IT equipment.
10.3 AC Power Distribution Solution for Photovoltaic Power Stations
- Pain Points: Unstable PV output, grid connection impact, harsh outdoor operating environments, demand for new energy grid-connected control and accurate energy metering.
- Solution Configuration: Medium floor-standing AC PDU with dual mains + PV input, intelligent ATS transfer, Class B+C SPD, multi-function electricity meter and RS485 communication; supports PV grid-connected control and energy data upload to PV monitoring platforms.
- Solution Advantages: Compatible with multi-source new energy input with intelligent transfer to stabilize grid connection; two-stage lightning protection safeguards inverters and PV modules; precise metering simplifies power generation statistics and settlement; outdoor protection design adapts to harsh mountain environments with service life up to 20 years.
10.4 AC Power Distribution Solution for Industrial Plants
- Pain Points: Diverse load types (power/lighting/equipment), large power fluctuation, dusty & humid environments, demand for graded protection and convenient maintenance.
- Solution Configuration: Medium floor-standing AC PDU with single/dual mains input, mixed circuit layout (separate power & lighting loops), Class B+C SPD, intelligent monitoring module and sound-light alarm; IP30 dust-proof & moisture-proof cabinet.
- Solution Advantages: Mixed circuit layout matches multiple load types; graded protection prevents fault propagation; real-time intelligent monitoring and sound-light alarms accelerate fault location; dust & moisture resistance stabilizes operation in industrial environments.
10.5 AC Power Distribution Solution for Rail Transit
- Pain Points: High power supply reliability requirements, humid & vibration-prone environments, wide temperature variation for underground/ground stations, demand for centralized remote monitoring.
- Solution Configuration: High-end floor-standing AC PDU with dual mains + backup power input, seamless ATS transfer, three-stage B+C+D SPD, IoT monitoring module and vibration-reinforced structure; supports centralized remote monitoring, fault waveform recording and data analysis.
- Solution Advantages: High-reliability design resists vibration and humidity; three-stage lightning protection secures critical equipment; intelligent monitoring adapts to unattended rail transit operation; wide temperature design fits temperature differences between underground and ground stations.
11. Product Application Cases
11.1 5G Base Station Power Distribution Project of a Provincial Mobile Operator
- Project Overview: Covers 1,200 provincial 5G base stations, requiring outdoor AC PDUs installed in base station outdoor cabinets to stabilize power supply for RRU and BBU equipment.
- Product Configuration: KITOZER‑AC‑S4U Basic rack-mounted AC PDU with single 100A input, 8-channel 63A output, Class C SPD, IP20 protection and wide temperature design.
- Project Outcome: Easy installation matching narrow base station space; wide temperature & dust-proof design adapts to outdoor -20℃~+65℃ environments; lightning protection cuts base station power supply failure rate by 90%; maintenance-free unattended operation reduces O&M costs by 30%.
11.2 Small & Medium-sized Data Center Project of an Internet Enterprise
- Project Overview: Construction of a 2,000-rack medium data center, requiring column head AC PDUs with dual mains + generator power supply to guarantee uninterrupted power for servers, switches and other IT equipment.
- Product Configuration: KITOZER‑AC‑H2200 High-end floor-standing AC PDU with dual 1250A mains + generator input, seamless ATS transfer, three-stage B+C+D SPD, IoT monitoring module, multi-function electricity meter and temperature sensors.
- Project Outcome: Multi-source redundant power supply with ≤50ms switching time achieves zero data center power interruption; three-stage lightning protection & multi-layer safeguards eliminate lightning and short-circuit accidents; remote intelligent monitoring boosts O&M efficiency by 80%; harmonic stabilization reduces IT equipment failure rate by 40%.
11.3 10MW Distributed Photovoltaic Power Station Project
- Project Overview: Construction of a 10MW distributed PV station, requiring AC bus collection PDUs for inverter output to realize power collection, grid-connected control and energy metering.
- Product Configuration: KITOZER‑AC‑M2200 Medium floor-standing AC PDU with dual mains + PV input, 630A ATS transfer, Class B+C SPD and multi-function electricity meter with RS485 communication.
- Project Outcome: Adapts to intermittent PV output with intelligent transfer for stable grid connection; two-stage lightning protection reduces inverter failure rate by 50%; precise metering streamlines power generation statistics and settlement efficiency; outdoor protection design fits harsh mountain environments with projected service life of 20 years.
11.4 Power Distribution Project for an Automobile Manufacturing Workshop
- Project Overview: Automobile welding workshop loaded with high-power welding machines, fans and lighting, featuring heavy dust and high humidity, requiring AC PDUs for power distribution and graded fault protection.
- Product Configuration: KITOZER‑AC‑M2200 Medium floor-standing AC PDU with dual 630A mains input, mixed circuit layout (6×250A power loops + 12×100A lighting loops), Class B+C SPD and intelligent monitoring module with sound-light alarm.
- Project Outcome: Mixed circuit layout matches high-power loads including welding machines and fans; graded protection avoids full workshop shutdown from single equipment faults; dust & moisture resistance stabilizes equipment operation in workshop environments; intelligent monitoring shortens fault repair time by 60% and improves production efficiency.
12. Product Common Faults & Maintenance
12.1 Common Faults & Troubleshooting Methods
12.1.1 SPD Failure
- Fault Phenomenon: Monitoring system triggers SPD alarm, SPD indicator window turns red.
- Root Causes: Damage from lightning strikes, aging failure, poor contact.
- Solutions:
- Red indicator window: Directly replace SPD module with identical model;
- Green window with persistent alarm: Unplug and reinsert module, clean contact terminals if loose connection exists;
- Frequent damage: Test earthing resistance and optimize earthing system if resistance exceeds standard.
12.1.2 AC Input Phase Loss
- Fault Phenomenon: Phase loss alarm triggered by monitoring system, unbalanced three-phase voltage.
- Root Causes: Open-circuit input cable, poor contact of circuit breaker, faulty voltage/current transmitter.
- Solutions:
- Inspect input lines: Measure three-phase voltage with multimeter to confirm actual phase loss;
- Circuit breaker fault: Check oxidized/loose breaker contacts, fasten or replace breaker;
- Transmitter fault: Replace transmitter if no DC3V output, mark wiring before replacement.
12.1.3 Circuit Breaker Tripping
- Fault Phenomenon: Main or branch breaker trips with load power cut off.
- Root Causes: Load short circuit, overload, leakage, aging breaker.
- Solutions:
- Short-circuit trip: Disconnect all loads, close breakers one by one to locate short-circuit point, repair cable/load before resetting;
- Overload trip: Reduce load power to match breaker rated current;
- Leakage trip: Repair insulation of faulty load/cable before resetting;
- Frequent tripping: Replace breaker with identical specification.
12.1.4 ATS Transfer Failure
- Fault Phenomenon: Dual power sources operate normally but ATS fails to transfer or vibrates frequently after switching.
- Root Causes: Faulty control power supply, stuck interlock mechanism, oxidized contactor contacts, incorrect phase sequence.
- Solutions:
- Control power supply: Inspect control loop power and blown fuses;
- Mechanical jamming: Power off, clean interlock mechanism and apply lubricant;
- Oxidized contacts: Polish contactor contacts or replace contactor if severely burnt;
- Incorrect phase sequence: Adjust input power phase sequence to match ATS standard.
12.1.5 Monitoring Module Black Screen / Communication Abnormality
- Fault Phenomenon: Blank monitoring screen, unupdated parameters, inaccessible remote monitoring.
- Root Causes: Power supply failure, damaged module, loose communication cable, incorrect address code.
- Solutions:
- Power supply fault: Inspect module input power and blown fuses, replace power adapter;
- Damaged module: Restart module, replace with new unit if no response;
- Communication fault: Fasten RS485/Ethernet wiring terminals, verify communication address code and baud rate.
12.2 Maintenance Schedule
12.2.1 Daily Routine Inspection
- Check cabinet appearance for deformation, rust or damage; intact door locks.
- Inspect indicator lights & display screen for normal power and alarm status with no abnormal parameters.
- Check SPD windows remain green with no damage or red indication.
- Verify circuit breakers and ATS stay in correct position without accidental tripping.
- Clear debris around cabinet, ensure good ventilation and normal temperature & humidity.
12.2.2 Monthly Maintenance
- Internal cabinet cleaning: Cut off power, remove dust from circuit breakers, cooling fans and monitoring modules with vacuum cleaner or brush.
- Tighten wiring terminals: Secure loose joints of input/output cables, copper bars and breaker terminals to prevent heat generation from poor contact.
- ATS/contactor test: Manually simulate transfer function to ensure smooth operation without jamming; inspect contacts for oxidation or burning.
- Alarm function test: Simulate phase loss, overvoltage and SPD faults to verify sound-light alarm triggering.
12.2.3 Quarterly Maintenance
- Insulation test: Measure insulation resistance between cabinet ground and each circuit with megohmmeter after power cut; qualified value ≥1MΩ.
- Voltage & current calibration: Calibrate intelligent meters and monitoring modules with standard instruments; adjust or replace equipment if error exceeds threshold.
- Earthing resistance test: Measure cabinet earthing resistance; optimize earthing system if resistance exceeds standard (≤0.1Ω for Basic/Medium, ≤0.05Ω for High).
- Cable inspection: Check wires and copper bars for aging, damage or discoloration; replace severely degraded components.
12.2.4 Annual Maintenance
- Full disassembly inspection: Power off and disassemble cabinet to inspect all components (breakers, contactors, SPDs, monitoring modules); replace all aged or damaged parts in batch.
- Full load test: Operate under rated load for 2 hours, monitor temperature rise, voltage and current of all components to eliminate abnormal heat or parameter drift.
- Firmware upgrade: Update IoT module firmware for high-end models to optimize functions and patch vulnerabilities.
- Maintenance record filing: Sort full-year inspection, maintenance and fault handling records to build equipment maintenance archives for future reference.
12.3 Maintenance Precautions
- Safety Priority: All maintenance operations must be performed under power-off status; hang “No Closing” warning signs and confirm zero voltage via electroscope before operation. High-voltage work requires certified professional personnel.
- Matching Spare Parts: Replace components only with identical brand, model and specification; mixing mismatched brands or parameters is prohibited.
- Environmental Protection: Avoid dust and moisture entering equipment during maintenance; conduct outdoor maintenance on sunny days to prevent short-circuit from rain.
- Forbidden Operations: Do not arbitrarily rewire, remove protective devices or overload equipment; never touch live components with wet hands.
13. Factory Strength & After-sales Service
13.1 Factory Strength
- Production Scale: KITOZER owns a 20,000㎡ modern manufacturing base equipped with CNC stamping machines, laser cutters, automatic spraying lines and aging test benches; annual output reaches 50,000 AC PDUs to meet mass delivery demands of large-scale projects.
- R&D Team: Core R&D team consists of over 30 senior electrical, structural and software engineers with average industry experience exceeding 10 years; independent R&D and customized design capacity with more than 20 patents covering lightning protection, intelligent monitoring and ATS control technologies.
- Quality Control: Strictly complies with ISO 9001 Quality Management System, ISO 14001 Environmental Management System and ISO 45001 Occupational Health & Safety Management System certification; products conform to IEC 61439‑1/2 and GB 7251 national & international standards; full-process quality inspection covers raw material warehousing, production and finished product delivery with 100% factory pass rate.
- Supply Chain Advantages: Long-term strategic cooperation with world-renowned first-tier component brands including Schneider, ABB, Siemens and Phoenix Contact; direct supply of core components ensures stable quality and delivery cycle.
- Industry Qualifications: Possesses power facility installation (repair & test) license, energy management system certification and work safety license; products pass CE, RoHS and CCC certification for global export.
13.2 After-sales Service
Pre-sales Service
Free technical consultation, scheme design, on-site survey and product selection services; customized exclusive solutions, detailed configuration lists and technical drawings according to project requirements (load power, power supply level, environmental conditions).
In-sales Service
Free technical training, installation guidance and commissioning support; professional technical team tracks the whole project to assist equipment wiring, installation and commissioning for normal operation; theoretical & practical training for client operators to ensure independent operation.
After-sales Service
- Warranty Commitment: 3-year free warranty (5-year warranty for core components); free spare parts replacement and maintenance labor fees within warranty period.
- 7×24 Hour Support: Over 20 service outlets nationwide covering all provinces & cities; 7×24 technical hotline, response within 1 hour, solution provided within 4 hours, on-site service within 24 hours (48 hours for remote areas).
- Lifetime Maintenance: Discounted maintenance service after warranty expiration, spare parts supplied at cost price, regular return visits and inspections, technical upgrade & optimization suggestions.
- Remote Operation & Maintenance: High-end models support remote fault diagnosis, firmware upgrade and parameter adjustment; most faults resolved remotely without on-site visits to cut O&M costs.
Service Tenet: Customer First, Quality Priority, Service-oriented. We provide full-lifecycle services to guarantee long-term stable equipment operation and support client project success.
14. Conclusion
As core equipment of low-voltage power distribution systems, KITOZER AC Power Distribution Units integrate four major advantages: high reliability, high safety, high intelligence and strong compatibility, covering full-scenario power distribution demands across telecommunications, new energy, industry, construction and municipal sectors. Adopting modular design, advanced production technology and strict quality control, the products support customized configuration and OEM/ODM processing with a complete after-sales service system.
In the future, KITOZER will deepen layout in the power distribution industry, increase R&D investment, continuously optimize product performance and upgrade intelligence to match emerging power distribution demands of new energy, data centers and industrial internet. Driven by technological innovation, we will upgrade products and empower client success with premium services, striving to become a world-leading supplier of power distribution equipment solutions and contribute to safe, stable and efficient operation of power systems.
15. Search Keywords, SEO & Tags
15.1 Core Search Keywords
AC Power Distribution Unit, Low-voltage AC PDU, Intelligent AC PDU, Rack-mounted AC PDU, Floor-standing AC PDU, Dual-input AC PDU, ATS AC PDU, Communication Base Station AC PDU, Data Center AC PDU, Photovoltaic Power Station AC PDU, Industrial Plant AC PDU
15.2 Long-tail Search Keywords
KITOZER AC Power Distribution Unit, AC PDU Solution, AC PDU Technical Parameters, AC PDU Application Scope, AC PDU Fault Maintenance, Custom AC PDU, IoT AC PDU, Three-stage Lightning Protection AC PDU, Multi-source Integrated AC PDU, Outdoor AC PDU
15.3 SEO Tags
#ACPowerDistributionUnit #LowVoltageDistributionEquipment #IntelligentPowerDistribution #ATSPDU #TelecomPowerDistribution #DataCenterPowerDistribution #NewEnergyPowerDistribution #IndustrialPowerDistribution #KITOZER #CustomPowerDistribution
15.4 Website Meta Keywords
AC Power Distribution Unit, Low-voltage AC PDU, Intelligent AC PDU, ATS PDU, Communication Base Station Power Distribution, Data Center Power Distribution, Photovoltaic Power Station Power Distribution, Industrial Plant Power Distribution, KITOZER, Custom Power Distribution Solution