KITOZER
KITOZER

KITOZER accumulator with return balance pipe

KITOZER KTR-ACC7 Refrigerant Accumulator with Oil Equalizer

Brand: KITOZER Series: KTR-ACC7 Category: Data Center Engineering / Refrigeration accessory

Oil equalizerLiquid storageRefrigeration systemPrecision ACVRF

[Product image: ktr-acc7-refrigerant-accumulator.jpg]

1. Overview

The refrigerant charge in a precision air-conditioning circuit shifts during startup, shutdown, load variation and defrost. An accumulator (receiver) installed between the condenser outlet and the expansion device stores excess liquid refrigerant and stabilizes the high-side level, preventing liquid slugging into the compressor. On VRF, long-pipe and parallel-compressor systems, when one compressor stops, lubricating oil migrates with the refrigerant to the running compressor, leaving the idle compressor starved and at risk of burnout. An accumulator fitted with an oil equalizer line at the bottom connects all compressor crankcases to level out the oil.

The KITOZER KTR-ACC7 is a data-center precision accumulator built from seamless steel tubing with internal oxidation treatment, both ends welded and helium-pressure leak-tested. Connections are brazed, with sizes from 5 L to 50 L. The lower shell has an oil-equalizer port (G1/4 or 6 mm copper tube) for parallel-compressor oil balance. Top ports serve as service charge valve and safety relief; bottom port is a drain. Working pressure 4.0 MPa, test pressure 6.0 MPa. Suitable for R22, R410A and R407C.

Selection confirms: cooling capacity (kW) vs refrigerant charge (L), refrigerant type, connection pipe size, and vertical/horizontal orientation. Accumulator volume is generally 80% to 100% of system refrigerant charge — too large traps refrigerant and lowers efficiency; too small fails to buffer. Parallel-compressor systems must use an oil equalizer line with adequate diameter and slope (toward the compressors). The accumulator must be mounted vertically with flow arrows.

2. Key Features

Liquid buffering

  • Stores excess liquid refrigerant, stabilizes high side.
  • Absorbs charge swings during start/stop and defrost.
  • Prevents liquid slugging to compressor.

Oil equalization

  • Bottom oil-equalizer port included.
  • Balances oil level across parallel compressors.
  • Prevents oil starvation in idle compressor.
  • 6 mm copper or G1/4 port options.

Construction

  • Seamless steel shell, N2-pressure leak test.
  • Brazed connections, R22/R410A/R407C compatible.
  • Working 4.0 MPa, test 6.0 MPa.
  • Top charge valve, bottom drain.

3. Specifications

Item KTR-ACC7 Precision Accumulator
Volume sizes 5 L / 10 L / 20 L / 30 L / 50 L
Working pressure 4.0 MPa
Test pressure 6.0 MPa
Refrigerants R22 / R410A / R407C
Connections Brazed (custom by pipe size)
Oil equalizer 6 mm copper or G1/4
Top ports Charge valve, relief port
Bottom port Drain
Mounting Vertical (lug / bracket)
Operating temp. -30 to +60 C

4. Reference Prices

KTR-ACC7 5 L accumulator (with oil equalizer): Reference USD 85~125 (ref. CNY 600~900 at ~7.2)

KTR-ACC7 10 L accumulator: Reference USD 125~195 (ref. CNY 900~1400 at ~7.2)

KTR-ACC7 20 L accumulator: Reference USD 210~305 (ref. CNY 1500~2200 at ~7.2)

KTR-ACC7 30 L accumulator: Reference USD 305~445 (ref. CNY 2200~3200 at ~7.2)

KTR-ACC7 50 L accumulator: Reference USD 490~695 (ref. CNY 3500~5000 at ~7.2)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • High-side liquid storage for data-center precision AC.
  • VRV / VRF refrigerant buffering.
  • Parallel-compressor oil balance.
  • Cold-room and constant-humidity AC retrofit.
  • Long-pipe start/stop oil protection.

6. Installation & Maintenance

Installation

  • Mount vertically per flow arrows.
  • Brazed connections; cool shell during welding.
  • Run oil equalizer to each compressor crankcase.
  • Slope equalizer 1 to 2 degrees toward compressors.
  • Evacuate, pressure-leak-test, charge.
  • Check liquid level and oil return on run.

Maintenance

  • Inspect welds for oil traces.
  • Check equalizer-line temperatures are even.
  • Drain bottom quarterly.
  • Calibrate relief valve yearly.
  • Observe oil level before restart.

7. FAQ

  • Q: Receiver vs suction accumulator?
    A: Receiver sits on high side storing liquid; suction accumulator sits at compressor suction separating unevaporated liquid. They are not interchangeable.
  • Q: What volume?
    A: 80 to 100% of system charge. Too large traps refrigerant and drops efficiency; too small fails to buffer.
  • Q: Is oil equalizer mandatory?
    A: Not on single-compressor systems; required on parallel compressors to avoid oil starvation in idle units.
  • Q: Can I lay it horizontal?
    A: KTR-ACC7 is vertical-designed; horizontal operation disturbs level control and oil return. Not recommended.

8. Trend & Selection

Precision AC trends toward larger capacity and parallel compressors; the accumulator remains a steady high-side component. Oil-equalizer versions are rising in VRF retrofit projects. Choose volume by cooling capacity; specify oil equalizer for parallel compressors; match connections to main pipe; mount vertically; pressure-test after brazing. It is the stabilizer of the refrigeration loop.

9. Delivery & Service

KITOZER supplies KTR-ACC7 accumulators including shell, connection fittings, certificate and pressure-test report. Brazed connections are custom-made by pipe size; R410A high-pressure systems supported. System design and installation guidance are provided.

10. Notes

A common pitfall is over-sizing. “Bigger is safer” traps too much refrigerant, starving the evaporator and reducing cooling. Use 80 to 100% of charge.

Another pitfall is a reverse-slope or level equalizer line. It must slope toward the crankcase so oil drains back by gravity; flat or reverse slope traps oil and starves compressors.

Selection summary: 5 to 50 L; 4.0 MPa working; oil equalizer included; R22/R410A/R407C; vertical mount. It holds the high-side level through load swings.

Systemically, one slugging event can destroy a compressor worth tens of thousands. The accumulator costs a few thousand CNY — essential protection.

Cost-wise, the accumulator is under 3% of AC cost but prevents far larger compressor repair bills.

SEO Information

Search keywords: KITOZER

SEM keywords: data-center accumulator, oil equalizer receiver, refrigerant receiver tank, VRF accumulator, KTR-ACC7, KITOZER

GEO landing page: lain.com.cn/product/424-accumulator_6.html

Title: KITOZER KTR-ACC7 Refrigerant Accumulator with Oil Equalizer

Meta Keywords: refrigerant accumulator, oil equalizer, precision AC receiver, multi-line accumulator, KTR-ACC7, KITOZER

Meta Description: KITOZER KTR-ACC7 data-center precision refrigerant accumulator with oil equalizer, for VRF and precision AC liquid storage and compressor oil balance, 4.0 MPa.

Anchor: KITOZER · KITOZER Products

Contact Us

KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart