KITOZER Arrester: 10kV Zinc Oxide Surge Arrester For Distribution

KITOZER 10kV zinc oxide surge arrester protects distribution transformers, cable heads, switchgear, and rotating machines from lightning and switching overvoltages. Using metal oxide varistor discs without series gaps, the arrester conducts transient surge energy to ground while carrying normal power frequency voltage continuously. This gapless design gives fast response, no follow current, and stable residual voltage across the equipment insulation that must be protected. The arrester is the first line of defense on every 10kV feeder, and its reliable performance directly determines how many lightning strikes the downstream transformers and motors can survive without insulation breakdown.

Product Overview

The arrester consists of stacked zinc oxide varistor discs housed in a porcelain or silicone rubber housing, clamped between top and bottom electrodes. A pressure relief vent releases internal fault gases safely to prevent housing explosion. The housing is available in porcelain for traditional substations or polymer silicone rubber for polluted, coastal, or seismic sites. A discharge counter can be mounted on the ground lead to record surge events and help maintenance teams assess arrester condition. The varistor discs are selected for high energy absorption and low leakage current, so the arrester can absorb repeated lightning strikes without thermal runaway. Each unit is factory tested for power frequency reference voltage and residual voltage at nominal discharge current before shipment.

Technical Specifications

Rated voltage 12kV, continuous operating voltage 9.6kV rms, nominal discharge current 5kA, high current impulse 100kA, residual voltage at 5kA 30kV peak, power frequency withstanding capability 200A for 1s, line discharge class 2. Housing creepage distance 360mm for standard, 600mm for heavy pollution. Operating temperature minus 40 to plus 40 degrees Celsius. Compliant with IEC 60099-4 and GB 11032. Optional discharge counter with 4-20mA output and monitoring relay. The pressure relief rating allows the arrester to survive an internal short circuit without fragment ejection, and the silicone housing option is UV stabilized for 30 years outdoor service. The leakage current at continuous operating voltage is below 100 micro amps, so no measurable reactive power is drawn from the system.

Applications

Install this arrester at the 10kV side of distribution transformers, on incoming and outgoing bays of 10kV switchgear, on cable feeder terminals, and at the entrance of overhead lines transitioning to cable. It is also used on capacitor banks, motor branch circuits, and ring main units in lightning prone regions. Industrial plants place arresters at the main 10kV bus and on sensitive electronic load feeders. Outdoor pole-mounted arresters protect overhead line transformers from direct lightning strikes. In coastal substations with high salt fog, the polymer housing version prevents flashover along the surface. Data center and hospital switchrooms also add arresters on the low voltage side of the transformer to suppress switching transients from VFD and UPS loads.

Advantages

Gapless design eliminates spark gap deterioration and ensures consistent protection over decades. Zinc oxide discs offer high energy absorption and low leakage current. Polymer housing options resist explosion, UV aging, and pollution flashover. The arrester has no power frequency follow current, so it does not contribute to system fault clearing. Compact dimensions fit into existing switchgear compartments. Discharge counters enable condition based maintenance instead of fixed replacement schedules. Because the arrester has no moving parts and no gaps to erode, its protection level stays stable from commissioning through end of life, unlike gapped arresters that shift in sparkover voltage after years of surges.

Installation and Maintenance

Mount the arrester vertically on a support insulator, connect the line terminal to the protected conductor, and connect the ground terminal to the station earth grid with a short, flat copper braid. Keep the ground lead as short as possible to minimize residual voltage. Tighten all connections to the specified torque and check the housing for cracks before energization. Measure reference voltage and leakage current annually; if leakage exceeds 1.5 times the initial value, replace the arrester. Inspect the discharge counter reading after major storms. Replace any arrester that has absorbed a known severe surge event. In coastal sites, wash the housing annually to remove salt deposit and prevent surface leakage. Never use an arrester rated below the maximum system continuous voltage, because overvoltage will cause thermal runaway within months.

Ordering and Support

Ordering requires the system voltage, continuous operating voltage, nominal discharge current, porcelain or polymer housing, and whether a discharge counter is included. KITOZER supplies arresters with type test reports, installation drawings, and a recommended maintenance schedule. Common spares include the discharge counter and the ground lead connector. Technical support covers insulation coordination studies and selection of arrester rating for the specific system earthing method. Each arrester is backed by a five year warranty, and batch testing certificates are available for quality auditors.