ToggleProduct Overview
KITOZER 400A automatic transfer switch is a four-pole, double-throw mechanical switch designed to transfer critical loads between utility power and a standby diesel generator. Unlike static transfer switches, the ATS uses a motor-driven contactor mechanism that operates in 100 to 250 milliseconds, which is fully compatible with generator startup sequences that require several seconds to stabilize. The four-pole design switches the neutral conductor as well, preventing unintended neutral back-feed from the generator into the utility transformer during maintenance. The unit is built into a floor-standing cabinet and integrates a programmable controller that monitors source voltage, frequency, generator availability, and transfer inhibit signals.
The controller follows a programmed sequence: upon utility failure, it starts the generator, waits for generator voltage and frequency to stabilize, then transfers the load. When utility returns, it waits for a programmable stabilization period, transfers back to utility, and leaves the generator running for a cool-down interval before shutting it down. This sequence protects both the generator and the load, and it can be customized through the front panel without external relays. The mechanical interlock makes it impossible to close both sources simultaneously, protecting lineworkers from back-feed.
Technical Specifications
Rated current 400A, rated voltage 400V three phase four wire, four pole double throw, mechanical switching time 100ms to 250ms, utility-to-generator transfer with adjustable time delay 0s to 300s, generator cool-down run-on 0min to 30min. Contacts silver alloy, electrical endurance 10000 operations, mechanical endurance 1000000 operations. Controller displays source voltage, frequency, generator state, and transfer count. RS485 Modbus RTU and 4 dry-contact outputs. Interlock between utility and generator positions is both mechanical and electrical, preventing simultaneous closure. IP32 cabinet, dimensions 800mm wide by 600mm deep by 2000mm high, weight 220kg. CE, IEC 60947-6-1, KITOZER brand, five year warranty.
Application Scenarios
This ATS is the standard transfer device for generator-backed critical loads such as data center switchboards, hospital emergency systems, hotel life safety loads, water treatment plants, and broadcast transmission sites. It sits between the generator set and the main low-voltage switchboard, automatically starting the generator when utility fails and transferring the load once generator voltage and frequency are stable. When utility returns, the ATS waits for a stabilization period before transferring back and then runs the generator for a cool-down interval. The four-pole configuration is mandatory in installations where the generator neutral must be isolated from the utility neutral, which is common in IT power systems that already have a UPS-derived neutral.
Additional uses include retail distribution centers, cold storage warehouses, airport terminal emergency systems, and telecom base station power feeds. In cold storage, even a few minutes of interruption can allow temperature rise that damages perishable goods, making the ATS essential. In telecom sites, the ATS ensures that backup generators automatically take over when utility fails, keeping base stations on air. The unit is also suitable as a manual changeover switch for small construction sites, where the manual handle allows direct selection of utility or generator without the controller.
Advantages and Features
Motor-driven contacts are robust and tolerant of inrush currents from transformer and motor loads. The double interlock design makes it physically impossible for the utility and generator contacts to close together, which protects utility lineworkers during back-feed events. The controller supports engine start output, engine stop output, and remote emergency stop, so the ATS can command the generator without a separate PLC. Event logging retains the last 200 operations with reason and timestamp, supporting compliance audits. A manual operating handle allows mechanical transfer during controller failure, ensuring the load can always be fed from either source even when electronics are down.
The four-pole neutral switching avoids stray circulating currents between two separately grounded systems, which is a common nuisance in three-pole ATS installations. The silver-alloy contacts handle repeated motor-starting inrush without welding. The controller allows both time-delay and frequency-stabilized transfer, so the load never lands on an unstable generator. The RS485 Modbus connection feeds the building management system with source status, generator state, and transfer count. The cabinet is pre-wired, so site electricians only land the main cables.
Installation and Maintenance
Mount the ATS adjacent to the generator switchgear and run heavy busbars or cable lugs to the utility incomer, generator incomer, and load feeder. Verify that the generator neutral is bonded as required by local code and that the four-pole neutral path is correctly installed. Set the voltage and frequency pickup thresholds according to the generator specification. Maintenance consists of annual contact inspection, contact resistance measurement, and lubrication of the motor drive gear as described in the service manual. Test transfer under load at least once per year, and inspect the mechanical interlock for wear. Keep the cabinet interior free of dust and rodents, and ensure the manual handle is stored in its holder.
During commissioning, simulate a utility failure by opening the upstream breaker and confirm that the generator starts, stabilizes, and accepts the load. Then simulate utility return and confirm the reverse sequence. Set the generator cool-down timer according to the engine manufacturer recommendation. If the site includes a remote emergency stop station, wire it to the dedicated input. Keep a spare contactor coil and control fuse on site. The motor drive gear should be lubricated annually with the grease specified in the manual. Contact resistance should be measured every two years, and contacts should be replaced when resistance exceeds the manufacturer threshold.