ToggleKITOZER KTR-BPDU Basic Rack PDU / 8-Outlet
Brand: KITOZER Series: KTR-BPDU Category: Power Distribution / Rack Power
rack PDUbasic PDU8 outletIEC C13KTR-BPDU

1. Overview
The KITOZER KTR-BPDU is the most ordinary yet essential power strip in a rack — a basic PDU (Power Distribution Unit). It looks like an office power strip, but it is designed for vertical rack mounting: a long metal bar with a row of outlets on top and an input cord at the bottom, fixed to a rack post to power servers, switches and storage. A rack normally holds two PDUs (A and B feeds); each dual-power server plugs power supply A into feed A and power supply B into feed B, so one feed failing leaves the other running.
“Basic” contrasts with “smart.” A basic PDU does one thing: splits one incoming feed into multiple outlets, with an over-current breaker in between. It does not measure, does not network, cannot switch outlets remotely. Its strengths are simplicity, low cost and reliability — no screen, no NIC, no battery; failure rate is very low, and a failed unit is swapped in minutes. A smart PDU (current/voltage metering, remote web control, per-outlet switching) costs 5–10× more and suits rooms needing fine power management; a basic PDU suits most small-to-mid racks where you just need power split out, not per-device wattage.
Key specs: input rating (16A/32A, i.e. 3.5 kW/7 kW at 220V), outlet types and count (GB 10A/16A, C13, C19; commonly 8 or 12), housing material (aluminium/steel), and whether it has over-current protection. Outlet type must match device plugs: servers/switches usually use C13 (kettle cord), high-power servers/storage use C19, and domestic gear may use GB plugs. Common practice is a mixed bar of C13 + GB, or custom-built to match device plugs.
2. Key Features
Electrical
- 16A/32A input, single-phase 220V.
- 8 or 12 outlets; mixed layout possible.
- Main breaker with over-current/short protection.
Outlets
- GB 10A (domestic gear).
- IEC C13 (generic servers/switches).
- IEC C19 (high-power servers/storage).
Structure & mounting
- Aluminium bar; vertical rack-post mount.
- 0U vertical (no rack units used) or 1U horizontal.
- Input cord 1.8–3m; terminated by industrial plug or UPS-end connector.
Safety
- Shutter outlets against shock.
- Flame-retardant housing.
- Reliable ground; low temperature rise.
3. Specifications
| Item | KTR-BPDU-8C13 | KTR-BPDU-8GB | KTR-BPDU-12C19 | KTR-BPDU-MIX |
|---|---|---|---|---|
| Input | 16A/220V | 16A/220V | 32A/220V | 16A/220V |
| Rating | 3.5 kW | 3.5 kW | 7 kW | 3.5 kW |
| Outlets | 8×C13 | 8×GB 10A | 12×C19 | 4×C13+4×GB |
| Mount | 0U vertical | 0U vertical | 0U vertical | 0U vertical |
| Breaker | 16A | 16A | 32A | 16A |
| Input cord | 3m+C14 | 3m+GB plug | 3m+32A industrial | 3m+industrial |
| Use | servers/switches | domestic gear | dense servers | mixed rack |
4. Reference Prices
KTR-BPDU-8C13 basic 8-outlet C13 PDU (16A, 0U, main breaker): Reference USD 17~39 / unit (ref. CNY 120~280 at ~7.2)
KTR-BPDU-12C19/32A high-power (12×C19, 32A input, industrial plug): Reference USD 49~97 / unit (ref. CNY 350~700 at ~7.2)
Reference only; final quote depends on outlet mix, input current, cord length and termination. Rack bulk (2 per rack, hundreds) discounted. Distinct from smart PDU (KTR-IPDU, with metering/remote, 5-10× price). Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Standard 42U/47U racks (A/B dual feeds per rack).
- Servers, switches, storage, firewalls.
- Weak-current rooms and network cabinets.
- Small / edge rooms with whole-rack distribution.
- Low-cost alternative to smart PDU when remote monitoring is not needed.
6. Installation & Maintenance
Installation
- Count devices, plug types and total load; size outlets and input current.
- Run A and B PDUs per rack from different UPS branches/transformers.
- Vertical-mount to rear posts, left and right (no U-space used).
- Route input cord from top/bottom to the row cabinet / UPS output.
- Dual-power servers: PSU-A to feed A, PSU-B to feed B.
- Balance load across outlets; don’t overdraw one bar.
- Before power-on: test insulation; verify phase (L/N/PE correct).
Maintenance
- IR-scan every half year: look for hot plugs/outlets.
- Main breaker should not trip or overheat.
- Clean plugs; replace loose contacts.
- Never daisy-chain another strip off the PDU (hazard).
- Keep 20% headroom; upgrade if above 90% loaded.
7. FAQ
- Q: Basic vs smart PDU?
A: If you don’t need remote current readout, remote outlet switching, or per-outlet metering, use basic (KTR-BPDU) — cheap and reliable. Choose smart only when doing PUE analysis, remote power-off, or tiered alarms. Many small rooms are fine with basic. - Q: Why A and B feeds?
A: Server dual-power is designed for redundancy. If everything plugs into one PDU, that PDU or its upstream UPS/breaker failure kills the whole rack. A/B feeds from separate UPS: one fails, the other continues. - Q: 16A or 32A?
A: Depends on rack total load. Typical 3–5 kW racks use 16A (3.5 kW); 5–8 kW use 32A (7 kW). Dense racks (10 kW+) need dual 32A or three-phase. Choose by actual load × 1.25. - Q: C13 vs C19?
A: C13 is 10A kettle, on switches and ordinary servers; C19 is 16A large, on blades, high-end storage and UPS. They are not interchangeable — order correctly.
8. Trend & Selection
The PDU market sees basic units getting cheaper at scale (an 8-outlet C13 bar is down to under USD 20) while smart PDUs move from optional to standard as rooms fine-tune power per rack and per device. But for many small rooms and edge nodes, basic remains the value choice. Selection: size input current (16A/32A) by rack kW; pick C13/C19/GB mix by device plugs; A/B dual feeds from different UPS; 0U vertical mount; keep breaker headroom; never daisy-chain strips. A basic PDU is simple, but it is the outlet every device depends on — wrong sizing, wrong phase, or single feed causes a whole-rack outage.
9. Delivery & Service
KITOZER selects the basic PDU from the rack device list (plug types, counts, rack kW), configuring outlet mix, cord length and termination. Rack bundles (A+B pair) are available, custom-terminated to row cabinet/UPS ends. Delivery includes the PDU, input cord, mounting bracket and manual. Housing, switch and outlet defects are replaced free in warranty.
10. Additional Notes
The common pitfall is “enough outlets but overloaded power.” Eight C13 outlets look like eight servers, but at 500 W each that is 4 kW, while a 16A PDU is rated 3.5 kW — long-term overloading heats the breaker and cord. Calculate total kW, not just outlet count.
The second pitfall is single-feed powering. People save wiring by plugging everything into one PDU (the other unused), wasting the dual-power redundancy; when that PDU dies, the whole rack dies. Even on a tight budget, run A/B feeds and split dual-power supplies.
Third: wrong outlet type. Buying 8×C13 when devices are all GB, then arriving with a bag of adapters — loose contacts, wasted space. Count device plug ends before ordering: kettle (C13) vs large (C19) vs GB flat pins.
Summary: size 16A/32A by kW; pick C13/C19/mix by plugs; A/B dual feeds from separate UPS; 0U vertical; calculate kW not outlets; no daisy-chain strips. The basic PDU is the “last meter” of rack power — if that meter is wrong, a bigger upstream UPS won’t help.
SEO Information
Search keywords:rack PDUbasic PDU8 outlet PDUIEC C13 PDUpower distribution unitKTR-BPDUKITOZER
SEM keywords:rack PDU price,basic PDU supplier,8 outlet C13 PDU,32A C19 PDU,rack power distribution unit,KTR-BPDU,KITOZER
GEO landing page:lain.com.cn/product/ktr-bpdu-basic-rack-pdu-8-outlet.html
Title:KITOZER KTR-BPDU Basic Rack PDU / 8-Outlet Power Distribution Unit
Meta Keywords:rack PDU,basic PDU,8 outlet power distribution unit,IEC C13 PDU,KTR-BPDU,KITOZER
Meta Description:KITOZER KTR-BPDU basic rack PDU, 8 outlets (GB/IEC C13/C19), 16A/32A input, vertical 0U mount, circuit breaker, low cost, for rack power distribution.