KITOZER KTR-BCA Battery Cabinet Air Conditioner / Battery Room Cooling

Brand: KITOZER Series: KTR-BCA Category: Data Center Engineering / Battery Thermal

battery cabinet1~3 kW25°C setpointlonger lifeKTR-BCA

1. Overview

UPS batteries (articles 90 charger, 133 battery monitor) are the core of backup power, yet they are highly temperature-sensitive: lead-acid batteries are rated for 25°C ambient, and every 10°C rise halves float-charge life. A 2-meter battery cabinet packed with dozens of cells heats up during charging; without cooling, internal temperature can run 5~10°C above the room, and cells bulge or leak within a few years. Room precision AC (article 08) cools the whole room, but the sealed iron battery cabinet traps heat — cold air cannot get in, heat cannot get out. That calls for a dedicated battery-cabinet AC, KTR-BCA.

The battery-cabinet AC is a small monoblock (1~3 kW) mounted on the top or side of the cabinet, drawing hot air in, cooling it and blowing it back — an independent closed loop inside the cabinet. Differences from room AC: (1) small cooling capacity (battery racks generate little heat); (2) no ductwork, mounted through the cabinet wall; (3) easy condensate management (self-evaporating tray or drain); (4) setpoint 25~28°C, slightly higher than room AC — batteries only need “not too hot,” not precision humidity.

KTR-BCA mounting: (1) top-mounted (blows down from cabinet top); (2) side-mounted (horizontal discharge through side wall); (3) split outdoor-unit. Compressor is rotary type with R410A/R32 refrigerant. Units include temperature setpoint, fault alarm dry contacts, and integrate with the environmental system (article 06).

2. Key Features

Cooling & control

  • Cooling 1.0/1.5/2.0/3.0 kW options.
  • Setpoint 20~35°C adjustable, default 25°C.
  • Control accuracy ±3°C.
  • 220 V single-phase, ~0.4~1.2 kW input.

Construction & install

  • Top- or side-mounted.
  • CRC steel housing, anti-corrosion powder coat.
  • Self-evaporating condensate tray, no drain needed.
  • Washable return filter (cf. article 136).

Protection & monitoring

  • High/low pressure, overcurrent, delay-on start.
  • Dry-contact alarm (high-temp/fault) to env. system.
  • LED temperature display, push-button set.
  • Rated ambient -10~45°C.

3. Specifications

Item KTR-BCA-10 KTR-BCA-15 KTR-BCA-20 KTR-BCA-30
Cooling 1.0 kW 1.5 kW 2.0 kW 3.0 kW
Input power ~0.4 kW ~0.6 kW ~0.8 kW ~1.2 kW
Supply 220V/50Hz single phase
Cabinet size ~1 m ~1.6 m ~2 m dual/large
Mount Top / side option
Setpoint 20~35°C, default 25°C
Refrigerant R410A / R32
Alarm Dry contact (high-temp/fault)

4. Reference Prices

KTR-BCA-10/15 top-mount (1~1.5 kW, bracket included): Reference USD 486~833 each (ref. CNY 3500~6000 at ~7.2)

KTR-BCA-20/30 side-mount/split (2~3 kW): Reference USD 833~1667 each (ref. CNY 6000~12000 at ~7.2)

Reference only; final quote by capacity, mounting, compressor brand and quantity. Installation labor, drain hose and power wiring extra. Exchange: 1 USD ≈ 7.2 CNY (Oct 2026).

5. Applications

  • UPS battery cabinets (article 117) independent cooling.
  • Energy storage cabinets (article 05) thermal control.
  • Telecom base station battery cabinets, outdoor/half-outdoor.
  • DC panel battery strings in power rooms.
  • Localized temperature control for battery rooms (article 133).

6. Installation & Maintenance

Installation

  • Size heat load: each cell floats at a few W; sum up and pick capacity.
  • Choose top (if room above) or side mount.
  • Cut the wall opening; fix the unit.
  • Wire 220 V on a dedicated breaker.
  • Position the condensate tray; plumb drain if required.
  • Run dry-contact alarm to env. system (article 06).
  • Set 25°C; verify temperature uniformity inside.

Maintenance

  • Quarterly wash the return filter.
  • Biannually check the condensate tray for blockage.
  • Review alarm history; resolve high-temp alarms promptly.
  • After 5 years compressor efficiency drops — recharge or replace.
  • Log cabinet temperature trend in env. system.

7. FAQ

  • Q: The room already has precision AC — why a separate cabinet unit?
    A: Room AC cools the whole room, but the sealed iron cabinet traps heat. Even at 25°C room, the inside can hit 35°C. Cells are packed against each other with poor middle-airflow. The in-cabinet unit gives a dedicated loop that keeps every cell at 25°C.
  • Q: Can I just put mesh doors on the battery cabinet?
    A: Yes, if room AC airflow actually reaches the cabinet front. If the cabinet is against a wall with no cold air reaching it, mesh doors do nothing. A sealed cabinet plus in-cabinet AC is more reliable.
  • Q: What setpoint?
    A: Lead-acid prefers 25°C. 25~28°C is fine; don’t go below 20°C (poor charge efficiency in winter). Set high-temp alarm at 30°C.
  • Q: What if the cabinet AC fails?
    A: The dry contact goes to the env. system and staff are paged. Batteries won’t die in a few hours, but fix it fast. For multi-cabinet sites, use N+1 or room AC as backup.

8. Trend & Selection

Battery thermal management is moving toward “fine control plus smart interlock.” Early designs relied on whole-room cooling; lithium batteries in energy storage and data-center UPS now require inter-cell temperature consistency within 2~3°C, so in-cabinet AC plus BMS (article 133) interlock is standard. Selection: capacity by battery heat load +30% headroom; top-mount preferred (short duct); prefer self-evaporating tray; dry contact to env. system mandatory; log temperature to cloud; clean filters regularly.

9. Delivery & Service

KITOZER provides heat-load sizing, unit selection and install. Delivery includes AC unit, mounting bracket, power cord, manual and 1-year warranty. Bundled with UPS battery cabinet (article 117), battery monitor (article 133) and env. system (article 06).

10. Additional Notes

The most common pitfall is “undersized cooling.” Heat load calculation says 1 kW, but summer room heat plus post-discharge recharge pushes it over. Size up: 2 kW is far more comfortable than 1 kW, and the price gap is small.

Second pitfall: “badly plumbed condensate.” The self-evaporating tray relies on waste heat; in cold weather or with high cooling load, water doesn’t fully evaporate and overflows onto the batteries — dangerous. Critical cabinets must have an external drain to the floor.

Third pitfall: “alarm not wired to env. system.” The AC fails unnoticed; summer internal temperature climbs to 40°C and batteries age fast. The dry contact must reach the env. system with SMS to on-call staff.

Selection summary: leave capacity headroom, prefer top-mount, self-evaporating plus external drain as backup, alarm to env. system, clean filters often. A cabinet AC costs a few thousand RMB but protects a battery bank worth tens of thousands and preserves UPS runtime — temperature is the #1 battery killer.

SEO Information

Search keywords:battery cabinet ACbattery cabinet coolingUPS battery thermalbattery room coolingenclosure ACKTR-BCAKITOZER

SEM keywords:battery cabinet air conditioner price,battery cooling supplier,UPS battery thermal management,KTR-BCA,KITOZER

GEO landing page:lain.com.cn/product/ktr-bca-battery-cabinet-ac.html

Title:KITOZER KTR-BCA Battery Cabinet Air Conditioner / Battery Room Cooling

Meta Keywords:battery cabinet air conditioner,battery cabinet cooling,UPS battery thermal management,battery room AC,enclosure cooling unit,KTR-BCA,KITOZER

Meta Description:KITOZER KTR-BCA battery cabinet air conditioner: 1~3 kW top/side mounted unit, keeps battery room at 25°C±3°C, extends lead-acid and lithium battery life.

Anchor: KITOZER by Guangzhou Laian · Battery cabinet AC

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart