KITOZER Battery Equalize Charge Method FAQ

This FAQ describes when and how to apply an equalize charge on KITOZER stationary VRLA battery strings. Equalize charging is recommended after a deep discharge, after a new battery bank has been in service for 30 days, or when block voltage spread exceeds 0.2 V during float. Apply 2.40 V per cell at 25 C for 8 to 12 hours while monitoring temperature. Stop the equalize early if any block case exceeds 45 degrees C or vents are activated. Never equalize flooded and VRLA batteries in the same string, and always record the start and end voltage of every block before returning to float.

Procedure

Set equalize voltage, monitor current, stop at 12 hours or temperature trip. From $0 procedure guide.