KITOZER Battery Float Voltage Setting FAQ

This FAQ explains the correct float voltage setting for KITOZER VRLA battery cabinets. For 12 V AGM blocks operated at 25 degrees C ambient, the recommended float charge is 2.25 to 2.30 V per cell, equal to 13.50 to 13.80 V per block. Every 5 degrees C rise above 25 C reduces the recommended float voltage by roughly 3 mV per cell. Setting float voltage too high causes overcharging, dry-out, and shortened life; setting it too low leaves the string undercharged and accelerates sulfation. Always verify the charger output with a calibrated multimeter after installation or battery replacement.

Reference Values

Float 2.275 VPC, equalize 2.40 VPC at 25 C. Battery cabinets from $680.